Alarm Description

Once drill has been enabled a 30 second timer will


activate. The lube pump will need to show a run status
Lube Pump Fail
or flow feedback to the PLC or alarm will be activated.
Drilling will be disabled.

Alarm will be activated if the HPU Tank RTD registers


HPU Temp High
176° F and above. The alarm will reset at 168° F.

Hydraulic Activated once Hydraulic return pressure transducer


Pressure registers 600 psi. and above. The alarm will reset at
Return High 500 psi.

Hydraulic System Activated once Hydraulic pressure transducer registers


Pressure Low 700 psi. And below. The alarm will reset at 1500 psi.

HPU Low Activated once HPU pressure transducer registers 700


Pressure psi. And below. The alarm will reset at 1500 psi.

Hydraulic Temp Alarm will be activated if the Hydraulic RTD registers


High 176° F and above. The alarm will reset at 168° F

Alarm will be activated if one of the Motor RTD’s


registers 250° F and above. The alarm will have to be
Motor RTD’s
reset manually on the drillers console or HMI. Drilling
will be disabled at 295°.

Alarm will be activated if the Brake Caliper RTD


Brake RTD registers 250° F and above. The alarm will have to be
reset manually on the drillers console or HMI.

Oil Lube Temp Alarm will be activated if the Lube Tank RTD registers
High 176° F and above. The alarm will reset at 168° F.

Activated once Lube Tank RTD Exceeds 120° F. Vent


Lube Tank Vent
will stay open for 5 Minutes every hour until
Open
temperature drops below 100°F.
Activated once Lube Pressure transducer after the filter
Lube Pressure
registers 10 psi. And below. The alarm will reset at
After Filter Low
12 psi.

Activated once Lube Pressure Before Filter and After


Lube Pressure
Filter transducer range exceeds 40 psi. The alarm will
Differential Alarm
reset once the range drops below 35 psi.

Activated once Low Lube Flow Meter registers .5 GPM


Low Lube Flow
and below. The Alarm will reset at 1 GPM.

Weight Proximity Activated once Weight Proximity Sensor is activated. Pipe


Sensor handler is disabled until weight has been removed.

Active if the handler lock sensor is not registering that


Pipe handler Lock
the handler is fully locked. Torque functions will be
Sensor
disabled unless the handler bypassed is activated.

Active if VFD power is off or Profibus connection is


VFD Signal Loss
interrupted. All Top Drive Functions will be disabled.

Active if SCR Status is Lost. All Top Drive Functions


SCR Signal Loss
will be disabled.

24V Power
Active if Power Supply 1 Fails
Supply 1 Fail

24V Power
Active if Power Supply 1 Fails
Supply 2 Fail

24V Power Active if both Power Supplies fail. All Top Drive
Supply 1&2 Fail Functions will be Disabled.