>> HVX
Vacuum circuit-breaker
up to 36 kV
Medium-Voltage Switching Devices
X
HV
Selection List
AREVA T&D
Conditions of Delivery
The General Conditions of Delivery as amended shall apply.
Illustrations
The illustrations are not binding.
>>
Contents
DESIGN
Design 6
Modules 7
Drive unit 7
HVX pole section, drawing unit, drive equipment 8
Secondary equipment 9
Power consumption and tripping range of releases 10
Electric circuit diagram 11
Type designation 12
SWITCHING TASKS
Applications 13
Standards, tests 14
Insulating level, environmental conditions 15
Disposal concept 15
SELECTION TABLES
12 kV for drawing unit 16
17.5 kV for drawing unit 18
24 kV for drawing unit 20
36 kV for drawing unit and fixed-type models 22
12 kV for fixed-type models 24
17.5 kV for fixed-type models 28
24 kV for fixed-type models 30
MODELS / DIMENSIONS
Dimensions HVX-E 32
Dimensions HVX-F 36
ACCESSORIES 39
TRANSPORT
Transport 40
3
>> Vacuum circuit-breaker
The result of consistent further development for
application in modern air-insulated switchgear units
GENERAL DESCRIPTION
COMPACT AND FUNCTIONAL
4
ESSENTIAL FEATURES Fields of application:
> Overhead cables
> compact design > Cables
> good operator guidance thanks > Motors
to the functional arrangement of > Transformers
operating and signalling elements > Generators
> no free-standing pole column
> vacuum interrupter chamber sus-
pended free of external forces
> pole envelope with supporting
and insulating functions
> high mechanical protection
thanks to pole envelope
> flexible application options:
- for fixed installation
- for mounting on isolating truck
- for drawer-type use
> high reliability and availabili-
ty thanks to mature vacuum
switching technology and proven
single-shaft spring drive
> world-wide application for all
standards
> maintenance-free
Performance characteristics
Rated voltage Rated lightning Rated short-time Rated short- Rated short- Rated current
impulse power frequency circuit making circuit breaking
withstand withstand current current
voltage voltage
1)
kV kV kV kA kA A
12 75 28 40 16 630 - 1250
63 25 630 - 2500
63 25 630 - 2500
63 25 630 - 2500
80 31.5 630 - 2500
5
>> Design
DESIGN
X
HV
Drawing unit with vacuum circuit- Drawing unit with vacuum circuit-breaker HVX-E ≤ 2500 A with 64-pole
breaker HVX-E ≤ 1250 A with connector attachment
64-pole connector attachment
X
HV
HVX 36 kV fixed-type model Drawing unit with vacuum circuit-breaker HVX-E > 2500 A, 50 kA with
64-pole connector attachment
6
MODULE Description be tensioned further, storing the
Thanks to the use of modern energy for a complete automatic
Drive unit vacuum interrupter chambers, reclosing cycle.
vacuum circuit-breakers make for
Essential features an optimization of the entire drive The drive mechanism is available
> Single-shaft system with a single kinematics. in two basic models, i.e. as manual
spiral spring for ON and OFF spring mechanism FH 2-01 or the
> Optimum adaptation to the small Method of operation: motorized spring mechanism FK
contact travel of the vacuum The energy for a complete 2-01. Appropriate interlocks rule
interrupter chamber switching cycle can be stored in out faulty switching operations.
> Minimum energy requirement the spiral spring. The ON and OFF In addition to the mechanical
movement of the vacuum inter- actuation of the manual ON/OFF
rupter chamber is controlled via pushbuttons, the drives can be
the cam discs. Once closing (ON) remote-controlled electrically or
has been effected, the spring can actuated via primary relays.
Main shaft
Basic equipment
Mechanical elements
OFF push-button • •
ON push-button • •
Switch position indicator • •
Mechanical operations counter • •
Switching spring position indicator • •
Electrical equipment
7
Pole section HVX ≤ 2500 A Drawing unit
The supporting component of the The drawing unit is the supporting
entire pole section is the multi- element for:
functional pole shell. Its functions > the drive unit to move the vacu-
comprise those of a mechanical um circuit-breaker HVX-E into its
supporting device for the top and operating / isolating position
bottom terminal contacts between > secondary terminals (64/36-pole)
which the vacuum interrupter > interface elements for
chamber is suspended free of - panel interlocks
mechanical constraints. In this - drawing unit position
case, there are no insulating brid- indications
ges between the phases. > drawing unit coding
Pole section HVX 12/24 kV > 1250 A Pole section HVX 36 kV Pole section HVX 12 kV > 2500 A
8
SECONDARY EQUIPMENT Auxiliary switches Relay
9
POWER CONSUMPTION AND TRIPPING RANGES OF THE RELEASES
Tripping ranges
Release Designation Rated current Tripping current
Ia in [A] at AC 50/60 Hz
0.5 90
Transformer-
operated F3 1 – at
release
5 100 % Ia
at 48 V DC, L/R = 10 ms 10 A
S11 8
at 125 V DC, L/R = 10 ms 3.8 A
15 A at 220 V DC, L/R = 10 ms 2 A
S12 8
at (110) 120/(220) 230 V AC 10 A
One NC contact and one NO contact of the auxiliary switch respectively are required for each closing or opening
coil respectively.
10
>> Electric circuit diagram
These circuit diagrams show the possible secondary equipment. Depending on the order volume, components shown may not be included.
Operating equipment which may be installed in the circuit- –S11, S12 Auxiliary switchgear
breaker -QO depending on the order specification –S2 Push switch actuated by energy-storing device
–F11, –F12 Shunt opening release (shunt release) –S41, S42 Push switch actuated by ON/OFF pushbutton
–F2 Shunt closing release (shunt release) –S43 Push switch actuated by OFF pushbutton
–F3 Secondary coil (transformer-operated release) –S6 Push switch actuated by drawing unit
–F4 Undervoltage release –X01 Terminal strip
–K01 Anti-pumping relay –Y1 Blocking coil
–M1 Motor to charge the energy storing device
11
TYPE DESIGNATION
HVX 12-25-06-E
Drawing unit
Type
F
Fixed type
Rated voltage
Rated current
Rated short-circuit
breaking current
Example:
OFF button
HVX 12-31-25-E
Made in Germany
Position indicator of
circuit breaker
99815
Position indicator of
closing spring
HVX Insertion opening for manual
charging of the closing spring
12
>> Switching tasks
and applications
0–3 min – CO – 3 min – CO without reclosing facility IEC 62271-100 see Selection Tables
0–0.3s – CO – 3 min – CO with reclosing facility IEC 62271-100 see Selection Tables
IEC 62271-100 see Selection Tables
CO – 15s – CO with reclosing facility
ANSI C37 column "with reclosing facility"
APPLICATIONS
> Auto-reclosing
13
>> Specifications
and tests
STANDARDS TESTS
SAFE AND RELIABLE
ENVIRONMENTAL AND
OPERATING CONDITIONS
Ambient temperatures
Temperature class:
"minus 5 indoors” 1)
Min./max. ambient
temperature -5 / 40 °C 1)
Maximum installation 1)
altitude above sea-level 1000 m
1)
higher values on request
14
INSULATING LEVEL (TES- Thus, the following applies to the ENVIRONMENTAL
TED ACCORDING TO IEC selection of devices and switch CONDITIONS
60 694 or EN 60 694) gear:
Vacuum circuit-breakers HVX com-
HVX vacuum circuit-breakers are Rated withstand voltage ply with the environmental condi-
suitable for installation at high alti- to be selected 1) tions defined in IEC 60 721-3-3,
tudes. They can be used in build ≥ 1990.
ings with low thermal insulation Required rated
or low thermal capacity, heated withstand voltage 1)
or cooled, without temperature ka DISPOSAL CONCEPT
monitoring. The heating or cooling
systems may fail to operate for a However, if the actual insulating A disposal manual is available on
period lasting several days. The level at the site of installation - the request.
values specified for the insulating withstand voltage – is to be deter-
level are referred to sea-level. mined, the reduction of the insulat
In case of installation at altitudes ing level starting at 0 m (sea-level)
above 1000 m, a reduction of the must be taken into consideration
insulation level must be considered as follows:
using an altitude correction factor
(ka = correction factor). Withstand voltage 2) = ka · Rated
withstand voltage 1)
of the selected device.
voltage
Power frequency withstand
voltage
15
>> Selection tables
HVX VACUUM CIRCUIT-BREAKER 12 kV WITH DRAWING UNIT FOR
AREVA SWITCHGEAR PANELS
out-of-phase conditions
Rated lightning impulse
Type
withstand voltage
Rated frequency
Rated voltage
voltage
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
2) in case of PMA 210 mm panel with motor-driven fan
16
Rated operating sequence Number of operating cycles Breaker operating times
without overhaul
Interrupter chamber
O-0.3 s-CO-15 s-CO
Drive mechanism
1)
1)
Opening time
Closing time
Arc duration
CO-15 s-CO
Break time
Weight
ms ms ms ms ms ms s
135
10000 30000 10000 100 35-53 45-63 55-62 2-12 20 4-12 135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
160
160
160
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 160
160
160
230
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
135
160
160
230
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 230
230
17
HVX VACUUM CIRCUIT-BREAKER 17.5 kV WITH DRAWING UNIT
FOR AREVA SWITCHGEAR PANELS
out-of-phase conditions
Rated lightning impulse
Rated power frequency
Type
withstand voltage
withstand voltage
Rated frequency
Rated voltage
CO-15 s-CO
component
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
2) in case of PMA 210 mm panel with motor-driven fan
18
Number of operating cycles Breaker operating times
without overhaul
1)
1)
Opening time
Closing time
Arc duration
Break time
Weight
ms ms ms ms ms ms s
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
160
160
160
135
135
160
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
160
160
230
135
160
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 160
160
230
19
HVX VACUUM CIRCUIT-BREAKER 24 kV WITH DRAWING UNIT
FOR AREVA SWITCHGEAR PANELS
out-of-phase conditions
Rated lightning impulse
Type
withstand voltage
Rated frequency
Rated voltage
CO-15 s-CO
voltage
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
2) in case of PMA 210 mm panel with motor-driven fan
20
Number of operating cycles Breaker operating times
without overhaul
1)
1)
Opening time
Closing time
Arc duration
Break time
Weight
ms ms ms ms ms ms s
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
160
160
230
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
160
160
21
VACUUM CIRCUIT-BREAKER HVX-E 36 kV WITH DRAWING UNIT
FOR AREVA SWITCHGEAR PANELS AND HVX-F 36 kV FIXED-TYPE MODEL
out-of-phase conditions
Rated lightning impulse
Type
withstand voltage
CO-15 s-CO
voltage
3s
mm kV kV kV Hz A kA kA kA % A A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
22
Number of operating cycles Breaker operating times
without overhaul
1)
1)
Opening time
Closing time
Arc duration
Break time
Weight
ms ms ms ms ms ms s
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
10000 30000 10000 100 40-53 45-63 47-65 7-12 20 4-9 155
23
VACUUM CIRCUIT-BREAKER HVX-F 12 kV, FIXED-TYPE MODEL
out-of-phase condition
Rated (normal) current
Type
withstand voltage
Rated frequency
Rated voltage
CO-15 s-CO
voltage
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
24
Number of operating cycles Breaker operating times
without overhaul
1)
1)
Opening time
Closing time
Arc duration
Break time
ms ms ms ms ms ms Weight
s
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
160
160
25
VACUUM CIRCUIT-BREAKER HVX-F 12 kV, FIXED-TYPE MODEL
out-of-phase conditions
Rated lightning impulse
Type
withstand voltage
Rated frequency
Rated voltage
CO-15 s-CO
voltage
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
26
Number of operating cycles Breaker operating times
without overhaul
1)
1)
Opening time
Closing time
Arc duration
Break time
ms ms ms ms ms ms Weight
s
135
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
160
160
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 230
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
160
160
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 230
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 230
27
VACUUM CIRCUIT-BREAKER HVX-F 17.5 kV, FIXED-TYPE MODEL
out-of-phase conditions
Rated lightning impulse
Type
withstand voltage
Rated frequency
Rated voltage
CO-15 s-CO
voltage
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
28
Number of operating cycles Breaker operating times
without overhaul
1)
1)
Opening time
Closing time
Arc duration
Break time
ms ms ms ms ms ms Weight
s
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
135
160
160
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
160
160
230
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
160
160
230
29
VACUUM CIRCUIT-BREAKER HVX-F 24 kV, FIXED-TYPE MODEL
out-of-phase conditions
Rated lightning impulse
Type
withstand voltage
Rated frequency
Rated voltage
CO-15 s-CO
voltage
3s
mm kV kV kV Hz A kA kA kA % A kA
1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report
30
Number of operating cycles Breaker operating times
without overhaul
1)
1)
Opening time
Closing time
Arc duration
Break time
Weight
ms ms ms ms ms ms s
135/260
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135/260
135/260
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12 135
135
135/260
135/260
135/260
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
135/260
160/260
160/260
135
135
135
10000 30000 10000 100 35-53 45-63 55-62 2-15 20 4-12
135
160
160
31
>> Models/dimensions
DIMENSIONS HVX-E / 25 kA 3s
A A
16
16
A
A
A
Ø 60
16
32
DIMENSIONS HVX-E ≤ 1250 A / 25 kA 3s
Ur (kV) 12 kV
Ir (A) ≥ 1250
A 653
B 195/126
C 185
D 507
E 527
F 466
G 498
Dimensions in mm
33
DIMENSIONS HVX-E > 1250 A
C C
137
H (for installation in PIX only)
340
697
220
G
416 B E
E
C C
A
22
Dimensions in mm
– PID105, PID106
– PIA106, PID106,
– PN104/106
For panel
PIN106
– PID104
– PN104
– PIX 12
– PIX 12
– PIX 17
– PIX 24
– PIX 12
– PIX 17
– PIX 24
– PI104
– PI104
– PI106
– PIX-C
– PIX-S
A 563 653 569 653 563 653 753 569 569 653 753 763 653 763 653 653 763
B 126 195 126 195 126 195 294 126 195 195 294 294 195 294 195 195 294
H 805 805 735 805 735 735 805 735 805
C 185 210 254
D 507 570 658
E 527 577 665
F 466 516 604
G 497.5 547.5 635.5
34
DIMENSIONS HVX-E 3150 A
A
349 178
807 (for PIX 12 kV only)
22
340
732
743
669
B
11
C 23
735
472
D D
849
kV kV Ir A B C D
12 75 1250 688 220 502 254
12 75 2000 688 220 502 254
12 75 2500 688 220 502 254
12 75 3150 688 220 502 254
12 95 1250 723 239 537 254
12 95 2000 723 239 537 254
12 95 2500 723 239 537 254
12 95 3150 723 239 537 254
17.5 95 1250 723 239 537 254
17.5 95 2000 723 239 537 254
17.5 95 2500 723 239 537 254
17.5 95 3150 723 239 537 254
Dimensions in mm
35
DIMENSIONS HVX-F ≤ 1250 A / 25 kA 3s
Ur (kV) 12 kV
Ir (A) ≤ 1250
A 150
B 440
C 450
Dimensions in mm
≤ 1250 A
Vacuum circuit-breaker
HVX-F ≤ 1250 A
36
DIMENSIONS HVX-F > 1250 A
327 176
25
458
18
B
310
E
176
C C
348
Ir ≤ 1600 A Ir ≥ 2000 A
Dimensions in mm
340
732
735
B
22
706
A
254 254
Ur (kV) Up (kV) A B
12 75 688 220
12 95 723 239
17.5 95 723 239
Dimensions in mm
38
>> Accessories
Transport trolley
The vacuum circuit-breaker HVX-E
can be transported by means of
the transport trolley.
Chassis frame
A floor chassis frame can be used
to transport the HVX.
39
>> Transport
TRANSPORT
Shipping unit
>50¡
40
Notes:
41
Notes:
42
AREVA Energietechnik GmbH · Sachsenwerk Mittelspannung · Rathenaustraße 2 · D-93055 Regensburg
Postfach 10 01 55 · D-93001 Regensburg · Phone +49 (0)9 41/46 20-0 · Fax +49 (0)9 41/46 20-4 18
www.areva-td.com
Tel.: +44 (0) 1785 250 070
AREVA T&D Worldwide Contact Centre:
http://www.areva-td.com/contactcentre/
SYSTEMS-L4-FACTS-1016-EN-2- © - AREVA - 2006. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
All trade names or trademarks mentioned herein, whether registered or not, are the property of their owners. - 389191982 RCS PARIS
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up-to-date literature, this brochure should only be regarded as a guide and is intended for information
purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions based on its contents without specific advice. AGSIE0634
Stand 0708