GENERAL NOTES:

1. DIGITAL KILOWATT METER WITH REMOTE READING FACILITY TO


TRANSFER DATA TO METER READING ROOM AT DMS CENTER.

2. ALL THE SIGNALS FROM THE SWITCHGEAR SHALL BE TAKEN UP


TO DMS INTERFACE CUBICLE.

3. ALL THE SIGNALS / WIRING FROM THE TRANSFORMER


MARSHALLING BOX SHALL BE TAKEN TO SWITCHGEAR AND DMS
INTERFACE CUBICLE.

4. THE CONTRACTOR TO PROVIDE CT'S ON TRANSFORMER


NEUTRAL POINTS TO OPERATE SBEF RELAY.

5. CAPACITIVE VOLTAGE DETECTORS SHALL BE PROVIDED.

6. FACTORY ACCEPTANCE TEST (FAT) AND MATERIALS SHALL BE


WITNESSED AND INSPECTED BY ADDC / ASSET MANAGEMENT
LEGEND DIRECTORATE PRIOR TO DELIVERY WITH THREE WEEKS
ADVANCE IN FORMATION.
22kV SWITCHGEAR EARTHING SWITCH 7. AS PER ADDC STANDARD PRACTICE THE INCOMERS AND THE
22kV, 25kA (1sec.) 1X48v BATTERY + CHARGER BUS COUPLER SHALL BE OFF LOAD MANUALLY OPERATED
(SPACE SHALL BE PROVIDED) SWITCHES WITH MECHANICAL INTERLOCK.
DMS INTERFACE
630A 630A 630A
M M

INTERLOCK INTERLOCK INTERLOCK


VACUUM CIRCUIT BREAKER (WITHDRAWABLE TYPE)

CURRENT TRANSFORMER
600/400/1A 100-50/1A 600/400/1A

A VOLTAGE TRANSFORMER (INDUCTIVE)


600/400/1A 100-50/1A 600/400/1A

600/400/1A A
600/400/1A A PHASE INDICATOR AND INTERLOCKING

X
FACILITIES (EACH PHASE)

MINIATURE CIRCUIT BREAKER (MCB)


X

X
kWh DIGITAL KILOWATT HOUR METER
COPPER CABLE COPPER CABLE COPPER CABLE

OFF-LOAD ISOLATOR
(CABLE FEEDER) (CABLE FEEDER)
OT
FUSED SWITCH (WITH HRC FUSE)

> FAULT INDICATOR

MOTOR DRIVE WITH INTERLOCKING SYSTEM (FOR FUTURE


TRANSFORMER I M
INSTALLATION)
22 / 0.4 kV
M MOTOR DRIVE WITH INTERLOCKING SYSTEM

XLPE (Single-Core) FUSE


COPPER CABLE
OT TRANSFORMER OIL TEMPERATURE

V VOLTMETER WITH SELECTOR SWITCH


STATION CUBICLE DB
A AMMETER

OPTIONAL
kWh
FIBRE OPTIC CABLE

SHORT CIRCUIT PROTECTION

2700 A x
M OVER CURRENT PROTECTION

0 ISSUED FOR TENDER 26 NOV 15 SBE EOO


EARTH FAULT & STAND BY EARTH FAULT PROTECTION

0.4kV, 2700 A, 50kA (1sec.) LINE DIFFERENTIAL PROTECTION

DIRECTIONAL OVER CURRENT PROTECTION


DEVELOPMENT OF
400A 400A 400A 400A 400A 400A 400A 400A 400A NORTH AL WATHBA
DIRECTIONAL EARTH FAULT PROTECTION
INFRASTRUCTURE

OUTGOING FEEDERS OUTGOING FEEDERS

x WITHDRAWABLE AIR CIRCUIT BREAKER


M

FEEDER PILLAR

FEEDER FEEDER FEEDER FEEDER


PILLAR-1 PILLAR-2 PILLAR-3 PILLAR-4

22/0.4 kV DISTRIBUTION
SUBSTATION
1 TRANSFORMER (TYPICAL
SUBSTATION SCHEMATIC)

5099558-EL-C-0018 0