This document is a site acceptance test report for measuring busbar contact resistance at the Power supply to Plot P18 at Zayed Military City project. It details the measured contact resistance values in micro-ohms for each feeder connection which were all found to be within acceptable limits. The test was performed on May 4th, 2020 using a calibrated Megger MOM200A microhm meter by Alphapower and witnessed by representatives from Time Electro and ADDC.
This document is a site acceptance test report for measuring busbar contact resistance at the Power supply to Plot P18 at Zayed Military City project. It details the measured contact resistance values in micro-ohms for each feeder connection which were all found to be within acceptable limits. The test was performed on May 4th, 2020 using a calibrated Megger MOM200A microhm meter by Alphapower and witnessed by representatives from Time Electro and ADDC.
This document is a site acceptance test report for measuring busbar contact resistance at the Power supply to Plot P18 at Zayed Military City project. It details the measured contact resistance values in micro-ohms for each feeder connection which were all found to be within acceptable limits. The test was performed on May 4th, 2020 using a calibrated Megger MOM200A microhm meter by Alphapower and witnessed by representatives from Time Electro and ADDC.
Military City Project no.: D108337 Substation: SWH38A1 Location: Plot P18, Zayed Military City
Client ADDC Site Ref. 33/11kV PU - 1 / 11kV Switchgear
Contractor Time Electro Feeder No. K01 to K09 Testing Company Alphapower Date of Test 04.05.2020 SITE ACCEPTANCE TEST REPORT FOR BUSBAR CONTACT RESISTANCE MEASUREMENT
1. BUSBAR CONTACT RESISTANCE MEASUREMENT
Injected Current: 100 A dc Ambient Temperature: 29˚C
Measured Contact Resistance (µΩ) Sr.No. FEEDER REFERENCE Remarks L1 L2 L3 1 K01 – K02 326 319 316 OK 2 K02 – K03 421 428 418 OK 3 K03 – K04 426 423 416 OK 4 K04 – K05 532 536 527 OK 5 K05 – K06 548 542 525 OK 6 K06 – K07 413 408 399 OK 7 K07 – K08 416 414 415 OK 8 K08 – K09 404 406 399 OK 9 K01 – K09 470 477 446 OK
2. REMARKS:
3. TEST EQUIPMENT DETAILS:
Description Make Model Serial No Calibration Due Date
Micro Ohm meter Megger MOM200A 1202852 28.05.2020
TESTED BY CONTRACTOR WITNESSED /APPROVED BY
COMPANY ALPHAPOWER TIME ELECTRO ADDC NAME JAYAPRAKASH M P