Professional Documents
Culture Documents
Contents
• Principle of cooling load
• Why cooling load & heat gains are different
• Design conditions
• Understand CLTD/CLF method
• An example
Cooling Load
• It is the thermal energy that must be removed
from the space in order to maintain the
desired comfort conditions
• HVAC systems are used to maintain thermal
conditions in comfort range
Purpose of Load Estimate
• Load profile over a day
• Peak load (basis for equipment sizing)
• Operation Energy analysis
• HVAC Construction cost
Principles of cooling Load Estimate
• Enclosure heat transfer characteristics
– Conduction
– Convection
– radiation
• Design conditions
– Outdoor & indoor
• Heat Gains
– Internal
– External or Solar
• Thermal capacity
Space Characteristics
• orientation
• Size and shape
• Construction material
• Windows, doors, openings
• Surrounding conditions
• Ceiling
Space Characteristics
• Occupants (activity, number, duration)
• Appliances (power, usage)
• Air leakage (infiltration or exfiltration)
• Lighting (W/m2)
Indoor Design Conditions
Basic design parameters
• Air temperature
– Typically 22-26 C
• Air velocity
– 0.25 m/s
• Relative humidity
– 30-70 %
• See ASHRAE 55 – 2004 Comfort Zone
Indoor Design Conditions
• Indoor air quality
– Air contaminants
– Air cleaning
• Acoustic requirements
• Pressurization requirements
Outdoor Design Conditions
• Weather data required for load calculation
– Temperature & humidity
– Wind speed, sky clearness , ground reflectance etc
• Design outdoor conditions data can be found
in ASHRAE Fundamentals Handbook
Outdoor Design Conditions
• ASHRAE Fundamentals 2001
– Design severity based on 0.4%, 1%, & 2% level
annually (8760h)
– For example at 1% level, the value is exceeded in
0.01x8760h = 87.6 h in a year
Outdoor Design For Cooling
Criteria: 0.4% DB and MWB
Miri 0.4% 1% 2%
Malaysia
Solar Transmission 3 4 7 4
Occupants 3 3 3 0
Lights 5 5 8 4
Equipment 10 1 29 21
Outdoor air bypassed 7 8 5 6
Outdoor air not 72 79 48 64
bypassed
Lighting: 4-8%
W/m2)
•Where light is continuously
on, CLF=1
Internal Loads- People
• Q people-s = No x sensible heat gain/p x CLF
• Q people-L = No x latent heat gain/p
Internal Load – Equipment Heat
• Cooling of electrical equipment in MCC/SG is an important
function of HVAC system offshore. The components
include:
• Transformers
• Motors
• Medium/high voltage switchgears
• Cables & trays
• Motor starters
• Inverters
• Battery chargers
• Circuit breakers
• Unit panel board etc
• Heat dissipation from these equipments are mainly based
data published by the manufacturers
Typical Outdoor & Indoor Design
Conditions Used Here
Conditions Dry-bulb % RH Moisture content,
temperature (C) kg/kg
Difference 13 0.016
2 m/s
1 0.52 0.56 0.59
Ventilation- sensible
Bypass air (0.1 bypass factor) 10% x outdoor air
Sensible heat of bypass air
Ventilation - Latent
Latent heat of bypass air
Cooling Load Calculations
Items Procedures
Design conditions Outdoor 35C, 70% RH
Indoor 22C, 55 RH
ERSH
RSH
Sensible heat of air bypass
Effective Room Sensible Heat
ERLH
People
Latent heat of air bypass
Effective Room Latent Heat
RSHF
ESHF
GSHF
Sensible Heat Factor (SHF)
• Ratio of sensible to total heat
– SHF = Sensible heat/ total heat
= SH/ (SH + LH)
A low value of SHF indicates a high latent heat load,
which is common in humid climate.
• In the above example,
– Calculate the SHF of the room (RSHF)
– Calculate the effective room sensible heat factor
(ESHF)
– Calculate the SHF of the coil (GSHF)
Selection of Air Conditioning
Apparatus
• The necessary data required are:
– GTH ( Grand total heat load)
– Dehumidified air quantity
– Apparatus dew point
These determine the size of the apparatus and
refrigerant temperature.