Professional Documents
Culture Documents
SC Impedance Test
SC Impedance Test
EQA Group
Rev. No.: 01 Work Instruction For Low Voltage SHORT Doc. No:EQA-WI-47
Rev. Date: 02-08-2003 CIRCUIT IMPEDANCE Test on Transformer Page No. 1 of 3
1. RECORD OF REVISIONS
Rev. Date Details Prepared Reviewed Approved
No. by by by
00 01.01.03 First Time issued for QMS Engineer SH AGM
00 02..08.03 Revised clause 6.7 as per final Engineer SH AGM
audit comment
2 SCOPE
The test procedure guides the EQA engineer in carrying out low voltage short circuit impedance test
on power transformers.
3. INPUTS
Sr. No. Activity / Documents
3.1 Supplies Requirements:
.1. Single Phase 230 V AC
.2. Three Phase 440 V AC
3.2 Instruments:
.1. 2 pole switch or MCCB or any isolation switch
.2. Excitation Transformer 230/13-52 V
.3. 1 variac 0-260 V or 3 variac 0-470V
.4. Voltmeter 650 V or Multimeter
.5. Multi ratio current transformer only when needed.
.6. Suitable Range Ammeter or Multimeter
4. REFERENCE :
4.1 Manufacturer manual
4.2 Earlier Test record
6. PREREQUISITES
Sr. No. Activity
6.1 Ensure that the transformer under test is de-energized. In the case of system transformers,
ensure that the maintenance engineer has taken the necessary permits and isolated the
transformer.
6.2 Ensure that no parallel circuits are connected to the transformer under test and there are no
shorts on the secondary side. In the case of neutral grounded transformers, ensure that the
ground connection to neutral is removed..
6.3 Interconnecting Transformers of Gas Insulated Sub-stations with SF6 to oil bushings are
tested through earth switches (QE3). In such cases, ensure that the earth switches are closed
and earthing strips removed.
6.4 From the winding diagram of the transformer name plate, note the winding to be applied
The Tata Power Company Ltd. EQA Group
Rev. No.: 01 Work Instruction For Low Voltage SHORT Doc. No:EQA-WI-47
Rev. Date: 02-08-2003 CIRCUIT IMPEDANCE Test on Transformer Page No. 2 of 3
7. ACTIVITIES
Sr. No. Activity / Documents
7.1 Make the test connections for A-N ( A-B in case of ) as per fig (C ).
7.2 Short the corresponding secondary (or tertiary winding).
7.3 Switch on the supply and gradually increase current by variac till adequate current flows
through the winding. Wait for few seconds for the current to stabilize.
7.4 Record corresponding current and voltage readings.
7.5 Compute actual impedance Z=V/I and compare that with expected values.
7.6 Compute the maximum deviation among the phases of the same winding and record
(maximum value minimum value) x100
% Deviation
maximum value
7.6 Repeat the test on other phases and for other winding combinations.
The Tata Power Company Ltd. EQA Group
Rev. No.: 01 Work Instruction For Low Voltage SHORT Doc. No:EQA-WI-47
Rev. Date: 02-08-2003 CIRCUIT IMPEDANCE Test on Transformer Page No. 3 of 3
8. RECORDS
Sr. No. Activity / Documents
8.1 Relevant section of Transformer Test form
9. LIMITS
Sr. No. Activity / Documents
9.1 Deviation among the phases of same winding : 2%
Deviation with expected value : 10%
Transformer
E Excitation Under Test
230 V Transformer
AC
Supply
V
1Ø Variac
External Short