Frequency (Hz) Phases Voltage (V) kVA kW kVA kW Rated Speed (RPM)
50 3 400/230V 7.8 6.24 8.4 6.72 1500
60 3 380/220V 10.8 8.6 11.6 9.3 1800
60 3 220/127V 10.8 8.6 11.6 9.3 1800
60 3 480/277V 10.8 8.6 11.6 9.3 1800

POWER FACTOR
3 Phase 0.8
1 Phase 1

ALL RATINGS ARE TO STANDARD REFERENCE CONDITIONS ISO 8528

Prime: This rating is for the supply of continuous electrical power, at variable load, in lieu of commercially purchase power. There is no limitation on the annual hours of operation and 10% over load power can be supplied for 1 hour
in 12.
Standby: This rating is for the supply of continuous electrical power, at variable load, in the event of a utility power failure. No overload is permitted.
"Stage IIIa" models are only emissions compliant at 50Hz Prime Power in accordance with 97-68EC.

JCB GENERATOR TECHNICAL SPECIFICATIONS. Tel: +44 (0)1889 590312. www.jcbgenerators.com. JCB reserves the right to change specifications without notice. Illustrations shown may include optional equipment and accessories.
YAN60_G8X_EN - Issued: 02/11/2018 14:14:39
G8X | G8QX

FUEL CONSUMPTION ENGINE


100% Load Prime L/h 2.62 1500 RPM
75% Load Prime L/h 1.98 Output Rating (PRP) kW 8.20
50Hz
50% Load Prime L/h 1.49 Output Rating (Standby) kW 9.00
100% Load Standby L/h 2.88 1800 RPM
100% Load Prime L/h 3.20 Output Rating (PRP) kW 10.70
75% Load Prime L/h 2.45 Output Rating (Standby) kW 11.77
60Hz
50% Load Prime L/h 1.89 Manufacturer and Model Yanmar 3TNV76GGEH
100% Load Standby L/h 3.42 Fuel Diesel
Injection Indirect
EXHAUST SYSTEM
O
Aspiration Natural
Maximum Temperature 100% Standby C 390.00 Cylinders 3
Exhaust Gas Flow 100% Standby m3/min 50Hz 2.08 mm
Bore and Stroke 76x82
Maximum Allowed Back Pressure mbar 9.80 Displacement L 1.116
O
Maximum Temperature 100% Standby C 425.00 Cooling Water
Exhaust Gas Flow 100% Standby m3/min 60Hz 2.60 Engine Oil Specification SEA 3 class 10W30 / API grade CD,CF
Maximum Allowed Back Pressure mbar 9.80 Compression Ratio 23.5:1
Exhaust Flange Size mm 50.00 Engine Oil Capacity L 3.50
Coolant Capacity L 3.70
AIR SYSTEM
Governor Mechanical
Intake Air Flow 100% Standby m3/h 45.16 Air Filter Dry
Total Cooling Air Flow 100% Standby m3/s 50Hz 0.583 Engine Oil Consumption 100% Load 0.27 g/kWh
Alternator Fan Airflow m3/s 0.09
FUEL SYSTEM
Intake Air Flow 100% Standby m3/h 54.19
Total Cooling Air Flow 100% Standby m3/s 60Hz 0.693 Diesel Specification EN590
Alternator Fan Airflow m3/s 0.108

JCB GENERATOR TECHNICAL SPECIFICATIONS. Tel: +44 (0)1889 590312. www.jcbgenerators.com. JCB reserves the right to change specifications without notice. Illustrations shown may include optional equipment and accessories.
YAN60_G8X_EN - Issued: 02/11/2018 14:14:39
G8X | G8QX

ALTERNATOR MECHANICAL FEATURES


Poles 4 Cooling Pack ●
Winding Connections Star (3Ph) / Parallel (1Ph) Air Filter ●
Insulation Class H Mechanical Governor ●
Enclosure IP23 Electronic Governor x
Exciter System Self-excited, brushless High Coolant Temperature Sender ●
Voltage Regulator A.V.R. (electronic) Low Oil Pressure Sender ●
Steady State Voltage Regulation +/- 1.0% Advanced Coolant Temperature Sender x
Bearing Single Bearing Advanced Oil Pressure Sender x
Coupling Flexible Disc Oil Temperature Sender x
Cooling Direct drive centrifugal blower fan Water Level Sender x
Coating Winding Protection Standard Radiator Guards ●
Hot Component Guards ●
STARTING SYSTEM
Manual Oil Drain Pump (Canopy) ●
Starter Motor kW 1.10 Water Jacket Heater x
Battery Capacity Ah 66 Manual Fuel Fill ∆
Number of Batteries 1 Electric Fuel Fill x
Auxiliary Voltage V 12 Racor Fuel Filter (No Alarm) x
Racor Fuel Filter (With Alarm) x
BATTERY FEATURES Pre-Filter with Separator x
Battery Isolator ∆ Fuel Level Sender ●
Battery Type Dry External Fuel Fill x
Battery Size (Ah) 66 3 Way Fuel Valve and Coupling Nest x
Number of Batteries 1 Industrial Silencer ●
Battery Charger x
Standard: ● Not Available: x Optional: ∆
Standard: ● Not Available: x Optional: ∆

JCB GENERATOR TECHNICAL SPECIFICATIONS. Tel: +44 (0)1889 590312. www.jcbgenerators.com. JCB reserves the right to change specifications without notice. Illustrations shown may include optional equipment and accessories.
YAN60_G8X_EN - Issued: 02/11/2018 14:14:39
G8X | G8QX

ELECTRICAL FEATURES JCB COMMUNICATION AND CONTROL


AVR DSR ● KS1 ∆
AVR DER x CP1 ●
Winding Protection Standard ● CP2 ∆
Winding Protection Standard + ∆ ATP ∆
Winding Protection Grey ∆ Standard: ● Not Available: x Optional: ∆
Winding Protection Total ∆
Winding Protection Total + ∆ REFERENCE STANDARDS
MAUX ●
PMG ∆ JCB Generators are CE certified and conform to the following Directives (subject to a country requiring such standard):
Anti-Condensation Heater ∆  EN 12100, EN13857, EN60204
Miniature Circuit Breaker (Integrated busbar) ●  2006/42/CE Machinery safety
 2006/95/EC Low voltage
Moulded Case Circuit Breaker (with integrated busbar) x
 2004/108/CE Electromagnetic compatibility
Earth Leakage Protection (Shunt Trip) ●  2000/14/EC Sound Power Level (amended by 2005/88/EC)
Synchronisation x  97/68/EC Emissions(amended by 2002/88/EC & 2004/26/EC)
 Power according to ISO 8528 and ISO 3046
Socket Box (inclusive of heavy duty busbar & micro switch) x  Ambient reference conditions 1000mbar, 25°C, 30% relative humidity ISO3046
Preparation for Earth Spike ● Information based on standard specification equipment unless otherwise stated.
Optional Voltages ∆
Remote Screen x
Panel Door Micro Switch x
Copper Busbar/Tails x
Emergency Stop Button x
External Emergency Stop Button ●
Standard: ● Not Available: x Optional: ∆

JCB GENERATOR TECHNICAL SPECIFICATIONS. Tel: +44 (0)1889 590312. www.jcbgenerators.com. JCB reserves the right to change specifications without notice. Illustrations shown may include optional equipment and accessories.
YAN60_G8X_EN - Issued: 02/11/2018 14:14:39
G8X | G8QX

WEIGHT AND DIMENSIONS – Open Set CANOPY/SKID


Length mm 1450 Lockable Maintenance Access Doors ●
Width mm 620 Control Panel Viewing Window ●
Height mm 1286 Fork Pockets ●
Shipping Volume (sea ready) m3 1.16 Single Lift Point x
Weight* Kg 279 Rental Sledging Base x
*Standard build with all fluids except fuel
Bunding ●
Bund Level Indicator ∆
WEIGHT AND DIMENSIONS – Canopy set
50mm Rock Wool Sound Insulation ●
Length mm 1475 Yellow Paint ●
Width mm 750 Red Paint ∆
Height mm 1104 White Paint ∆
Shipping Volume (sea ready) m3 1.41 Residential Silencer ●
Weight* Kg 456 Standard: ● Not Available: x Optional: ∆
*Standard build with all fluids except fuel

FUEL TANK OPTIONS


Material Capacity (L)
Standard Tank – Open Set Plastic 23
Standard Tank – Canopy Set Plastic 60

SOUND PRESSURE (CANOPY ONLY)


LpA (7m) 50Hz dB(A) 62
LpA (7m) 60Hz dB(A) 64

JCB GENERATOR TECHNICAL SPECIFICATIONS. Tel: +44 (0)1889 590312. www.jcbgenerators.com. JCB reserves the right to change specifications without notice. Illustrations shown may include optional equipment and accessories.