[Ammonia Storage Shelter]_WATER SPRAY SYSTEM_HYDRAULIC CALCULATION

NS2-YT10-P0SGC-121061

7. EQUIVALENT TABLE

EQUIVALENT LENGTH TABLE (m)

DN INSIDE T B W S K V V V TYPE OF PIPE


TEE GATE CHECK WET DRY SPRAY
VALUE DIAMETER 45DEG. 90DEG.
PIECE VALVE VALVE/ VALVE VALVE VALVE
ELBOW ELBOW STRAINER
20 20.96 1.2 0.3 0.6 0 0 0 0 0 ASTM
25 26.64 1.5 0.3 0.6 0 0 0 0 0 ASTM
32 35.08 1.8 0.3 0.9 0 0 0 0 0 ASTM
40 40.94 2.4 0.6 1.2 0 0 0 0 0 ASTM
50 52.48 3.1 0.6 1.5 0.3 3.4 0 0 3.1 ASTM
65 62.68 3.7 0.9 1.8 0.3 4.3 0 0 0 ASTM
80 77.92 4.6 0.9 2.1 0.3 4.9 4.6 5 7.1 ASTM
100 102.26 6.1 1.2 3.1 0.6 6.7 5.4 7.4 21.4 ASTM
125 128.2 7.6 1.5 3.7 0.6 8.2 0 0 0 ASTM
150 154.08 9.2 2.1 4.3 0.9 9.8 9.6 9.9 26.9 ASTM
200 202.74 10.7 2.7 5.5 1.2 13.7 11.2 0 24.4 ASTM
250 254.56 15.3 3.4 6.7 1.5 16.8 0 0 0 ASTM
300 303.28 18.3 4.0 8.2 1.8 19.8 0 0 0 ASTM
350 339.76 21.70 5.0 10.0 2.1 22.8 0 0 0 ASTM
151 134.4 13.89 3.17 6.49 1.36 14.8 0 0 0 HDPE ISO 4427 SDR11
201 177.00 16.16 4.08 8.31 1.81 20.69 0 0 0 HDPE ISO 4427 SDR11
251 218.40 23.10 5.13 10.12 2.27 25.37 0 0 0 HDPE ISO 4427 SDR11
301 260.2 27.63 6.04 12.38 2.72 29.9 0 0 0 HDPE ISO 4427 SDR11
351 302.80 32.77 7.55 15.10 3.17 34.43 0 0 0 HDPE ISO 4427 SDR11

C - VALUE = 150 FOR HDPE PIPE


C- VALUE = 120 FOR ASTM PIPE

Rev.2 6 of 23
Appendix A: Hydraulic Calculation - Ammonia Tank-A

Builder : Mode of operation : Protected object :


Minimax GmbH Singapore Branch
25, International Business Park, #03-15/19, Effective area : pressure at sprinkler Group of operation area Description : Size :
German Centre, Singapore 609916 pump pressure of total operation area Water Spray System
Operator :
Roughness of pipe (C-value)150 and 120 Use of pipes according to DIN
Nghi-Son#2 Thermal Power Plant
Vietnam Supply of hydrants with water : l/min at node No. Strangrohr-No. : 0 ; Sprinkler-No. : 0

Project-No.: Operating company :


Ceiling protec. Rack protec.
NS2 Ammonia Storage Tank-A
Height of storage (m)
min. water admission (mm/min)
Person in charge : real effective area (ea) (m²)
Glen Golle max. protection area/sprinkler in ea (m²)
No. of sprinklers / effection area
No. of additional sprinkler / effection area
Date : Object :
hydraulic considered no.of sprinkler
14 June, 2019 Water Spray System
no. of protected decks
biggest distance of sprinkler (m)

Demand press required / Supply press available / cushion in bar 10.000 according Hazen-Williams

Water rate at point to feed in / Pump in l/min 3079.36


© By IDAT-GmbH 2000 - 2012 V 2.21 1226

hydraulic unfavourabelst element in the effective area


Sprinkler pipe-No. / No. ext. element
minimum pressure / Required density in bar
geodetic difference in height ext. element - point to feed in m
geodetic difference in height lowest element - point to feed in m 0.05
max. pressure of spray in the effective area in bar 7.623
min. pressure of spray in the effective area in bar 6.346
max. water speed in the effective area in m/s 8.58
No. of sprays in the effective area 63

Page 7 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 1

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
Z 2- 1 147 148 9.816 3079.4 300 120 4.43 2W+ 1S+ 1K 42.43 0.0002 1.79 0.1841 10.000 0.71 Pump=9464 lpm @10bar
Z 1- 1 147 146 9.816 -3079.4 300 120 6.88 1W 15.08 -0.0002 2.56 0.2481 10.064 0.71
H 2- 1 146 145 10.064 -3079.4 301 150 50.74 8W 200.40 -0.0003 1.60 0.1009 10.165 0.97
H 1- 1 145 144 10.165 -3079.4 201 150 16.83 2W 41.94 -0.0018 -1.60 -0.2336 9.931 2.09
V 5- 1 144 143 9.931 -3079.4 200 120 0.35 1W 5.85 -0.0014 -0.35 -0.0426 9.889 1.59
V 4- 1 143 142 9.889 -3079.4 150 120 2.17 1S+ 1K 12.87 -0.0054 -0.0699 9.819 2.75
V 3- 1 142 141 9.819 -3079.4 100 120 1.20 2S+ 1V 23.80 -0.0400 -1.20 -1.0688 8.750 6.25
V 2- 1 141 140 8.750 -3079.4 100 120 2.58 1W 5.68 -0.0400 -0.60 -0.2858 8.464 6.25
V 1- 1 140 139 8.464 -3079.4 100 120 4.47 3W 13.77 -0.0400 -1.10 -0.6582 7.806 6.25
F 1- 2 30 139 7.791 1491.6 65 120 0.96 0.96 0.1134 -0.96 0.0147 7.806 8.06
F 1- 1 139 85 7.806 -1587.8 65 120 1.34 1T 5.04 -0.1273 -1.34 -0.7729 7.033 8.58
R 7- 6 24 137 7.351 49.8 40 120 3.12 1T+ 1W 6.72 0.0017 1.47 0.1550 7.506 0.63
R 7- S2 138 137 7.474 14.00 38.3 38.3 15 120 1T 1.20 0.0268 0.0322 7.506 1.85
R 7- 5 137 135 7.506 88.1 40 120 2.80 2.80 0.0048 0.0135 7.520 1.11
R 7- S2 136 135 7.487 14.00 38.3 38.3 15 120 1T 1.20 0.0269 0.0322 7.520 1.85
R 7- 4 135 133 7.520 126.4 40 120 2.80 2.80 0.0094 0.0263 7.546 1.60
R 7- S2 134 133 7.514 14.00 38.4 38.4 15 120 1T 1.20 0.0270 0.0323 7.546 1.85
R 7- 3 133 131 7.546 164.7 40 120 2.80 2.80 0.0153 0.0429 7.589 2.09
R 7- S2 132 131 7.556 14.00 38.5 38.5 15 120 1T 1.20 0.0271 0.0325 7.589 1.86
R 7- 2 131 129 7.589 203.2 40 120 2.80 2.80 0.0226 0.0633 7.652 2.57
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

R 7- S2 130 129 7.619 14.00 38.6 38.6 15 120 1T 1.20 0.0273 0.0328 7.652 1.87
R 7- 1 129 33 7.652 241.9 40 120 3.12 1T+ 1W 6.72 0.0312 -1.47 0.0658 7.718 3.06
R 6- 6 78 127 6.634 29.2 40 120 4.36 1T+ 1W 7.96 0.0006 -2.70 -0.2599 6.374 0.37
R 6- S2 128 127 6.346 14.00 35.3 35.3 15 120 1T 1.20 0.0231 0.0277 6.374 1.70
R 6- 5 127 125 6.374 64.4 40 120 2.80 2.80 0.0027 0.0076 6.381 0.82
R 6- S2 126 125 6.353 14.00 35.3 35.3 15 120 1T 1.20 0.0231 0.0277 6.381 1.70
R 6- 4 125 123 6.381 99.7 40 120 2.80 2.80 0.0061 0.0169 6.398 1.26
R 6- S2 124 123 6.370 14.00 35.3 35.3 15 120 1T 1.20 0.0231 0.0278 6.398 1.71
R 6- 3 123 121 6.398 135.1 40 120 2.80 2.80 0.0106 0.0297 6.428 1.71
R 6- S2 122 121 6.400 14.00 35.4 35.4 15 120 1T 1.20 0.0232 0.0279 6.428 1.71

Page 8 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 2

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
R 6- 2 121 119 6.428 170.5 40 120 2.80 2.80 0.0163 0.0457 6.474 2.16
R 6- S2 120 119 6.445 14.00 35.5 35.5 15 120 1T 1.20 0.0234 0.0281 6.474 1.72
R 6- 1 119 88 6.474 206.0 40 120 4.36 1T+ 1W 7.96 0.0232 2.70 0.4493 6.923 2.61
R 5- 6 75 117 6.634 45.8 40 120 4.36 1T+ 1W 7.96 0.0014 -2.70 -0.2534 6.380 0.58
R 5- S2 118 117 6.353 14.00 35.3 35.3 15 120 1T 1.20 0.0231 0.0277 6.380 1.70
R 5- 5 117 115 6.380 81.1 40 120 2.80 2.80 0.0041 0.0116 6.392 1.03
R 5- S2 116 115 6.364 14.00 35.3 35.3 15 120 1T 1.20 0.0231 0.0277 6.392 1.71
R 5- 4 115 113 6.392 116.4 40 120 2.80 2.80 0.0081 0.0226 6.414 1.47
R 5- S2 114 113 6.387 14.00 35.4 35.4 15 120 1T 1.20 0.0232 0.0278 6.414 1.71
R 5- 3 113 111 6.414 151.8 40 120 2.80 2.80 0.0132 0.0369 6.451 1.92
R 5- S2 112 111 6.423 14.00 35.5 35.5 15 120 1T 1.20 0.0233 0.0280 6.451 1.71
R 5- 2 111 109 6.451 187.3 40 120 2.80 2.80 0.0194 0.0544 6.506 2.37
R 5- S2 110 109 6.478 14.00 35.6 35.6 15 120 1T 1.20 0.0235 0.0282 6.506 1.72
R 5- 1 109 84 6.506 222.9 40 120 4.36 1T+ 1W 7.96 0.0268 2.70 0.4782 6.984 2.82
R 4- 16 81 107 6.634 32.3 50 120 1.26 1.26 0.0002 0.0003 6.634 0.25
R 4- S1 108 107 6.524 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0458 0.1098 6.634 2.47
R 4- 15 107 105 6.634 83.4 50 120 1.50 1.50 0.0013 0.0019 6.636 0.64
R 4- S1 106 105 6.526 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0458 0.1098 6.636 2.47
R 4- 14 105 103 6.636 134.5 50 120 1.50 1.50 0.0031 0.0047 6.641 1.04
R 4- S1 104 103 6.531 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0458 0.1099 6.641 2.47
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

R 4- 13 103 101 6.641 185.6 50 120 1.50 1.50 0.0057 0.0085 6.649 1.43
R 4- S1 102 101 6.539 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0459 0.1100 6.649 2.47
R 4- 12 101 99 6.649 236.7 50 120 1.50 1.50 0.0089 0.0134 6.663 1.82
R 4- S1 100 99 6.553 20.00 51.2 51.2 20 120 1T+ 2W 2.40 0.0459 0.1103 6.663 2.47
R 4- 11 99 97 6.663 287.9 50 120 1.50 1.50 0.0128 0.0193 6.682 2.22
R 4- S1 98 97 6.572 20.00 51.3 51.3 20 120 1T+ 2W 2.40 0.0461 0.1105 6.682 2.48
R 4- 10 97 95 6.682 339.2 50 120 1.50 1.50 0.0174 0.0261 6.708 2.61
R 4- S1 96 95 6.597 20.00 51.4 51.4 20 120 1T+ 2W 2.40 0.0462 0.1109 6.708 2.48
R 4- 9 95 93 6.708 390.6 50 120 1.50 1W 3.00 0.0226 0.0677 6.776 3.01
R 4- S1 94 93 6.664 20.00 51.6 51.6 20 120 1T+ 2W 2.40 0.0467 0.1120 6.776 2.49

Page 9 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 3

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
R 4- 8 93 91 6.776 442.2 50 120 1.50 1.50 0.0284 0.0426 6.818 3.41
R 4- S1 92 91 6.706 20.00 51.8 51.8 20 120 1T+ 2W 2.40 0.0469 0.1126 6.818 2.50
R 4- 7 91 89 6.818 494.0 50 120 2.39 2.39 0.0349 0.0833 6.902 3.81
R 4- S1 90 89 6.788 20.00 52.1 52.1 20 120 1T+ 2W 2.40 0.0475 0.1139 6.902 2.52
R 4- 6 89 88 6.902 546.1 50 120 0.50 0.50 0.0420 0.0210 6.923 4.21
R 4- 5 88 86 6.923 752.1 50 120 1.00 1.00 0.0759 0.0759 6.999 5.80
R 4- S1 87 86 6.883 20.00 52.5 52.5 20 120 1T+ 2W 2.40 0.0481 0.1154 6.999 2.53
R 4- 4 86 85 6.999 804.6 50 120 0.40 0.40 0.0859 0.0344 7.033 6.20
R 4- 3 85 84 7.033 -783.1 50 120 0.60 0.60 -0.0818 -0.0491 6.984 6.03
R 4- 2 84 82 6.984 -560.2 50 120 0.50 0.50 -0.0440 -0.0220 6.962 4.32
R 4- S1 83 82 6.847 20.00 52.3 52.3 20 120 1T+ 2W 2.40 0.0478 0.1148 6.962 2.53
R 4- 1 82 54 6.962 -507.9 50 120 1.14 1.14 -0.0367 -0.0418 6.920 3.91
R 3- 15 81 79 6.634 -32.3 50 120 1.14 1W 2.64 -0.0002 -0.0006 6.633 0.25
R 3- S1 80 79 6.524 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0458 0.1098 6.633 2.47
R 3- 14 79 78 6.633 18.8 50 120 0.50 1W 2.00 0.0001 0.0002 6.634 0.14
R 3- 13 78 76 6.634 -10.4 50 120 1.00 1W 2.50 -0.0000 -0.0001 6.633 0.08
R 3- S1 77 76 6.524 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0458 0.1098 6.633 2.47
R 3- 12 76 75 6.633 40.7 50 120 1.00 1.00 0.0003 0.0003 6.634 0.31
R 3- 11 75 73 6.634 -5.1 50 120 0.50 0.50 -0.0000 -0.0000 6.634 0.04
R 3- S1 74 73 6.524 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0458 0.1098 6.634 2.47
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

R 3- 10 73 71 6.634 45.9 50 120 2.39 2.39 0.0004 0.0010 6.635 0.35


R 3- S1 72 71 6.525 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0458 0.1098 6.635 2.47
R 3- 9 71 69 6.635 97.0 50 120 1.50 1.50 0.0017 0.0026 6.637 0.75
R 3- S1 70 69 6.528 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0458 0.1099 6.637 2.47
R 3- 8 69 67 6.637 148.1 50 120 1.50 1.50 0.0038 0.0056 6.643 1.14
R 3- S1 68 67 6.533 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0458 0.1100 6.643 2.47
R 3- 7 67 65 6.643 199.2 50 120 1.50 1.50 0.0065 0.0097 6.653 1.54
R 3- S1 66 65 6.543 20.00 51.2 51.2 20 120 1T+ 2W 2.40 0.0459 0.1101 6.653 2.47
R 3- 6 65 63 6.653 250.4 50 120 1.50 1.50 0.0099 0.0149 6.668 1.93
R 3- S1 64 63 6.557 20.00 51.2 51.2 20 120 1T+ 2W 2.40 0.0460 0.1103 6.668 2.47

Page 10 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 4

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
R 3- 5 63 61 6.668 301.6 50 120 1.50 1W 3.00 0.0140 0.0420 6.710 2.32
R 3- S1 62 61 6.599 20.00 51.4 51.4 20 120 1T+ 2W 2.40 0.0462 0.1110 6.710 2.48
R 3- 4 61 59 6.710 353.0 50 120 1.50 1.50 0.0187 0.0281 6.738 2.72
R 3- S1 60 59 6.626 20.00 51.5 51.5 20 120 1T+ 2W 2.40 0.0464 0.1114 6.738 2.49
R 3- 3 59 57 6.738 404.5 50 120 1.50 1.50 0.0241 0.0361 6.774 3.12
R 3- S1 58 57 6.662 20.00 51.6 51.6 20 120 1T+ 2W 2.40 0.0466 0.1120 6.774 2.49
R 3- 2 57 55 6.774 456.1 50 120 1.50 1.50 0.0301 0.0451 6.819 3.51
R 3- S1 56 55 6.706 20.00 51.8 51.8 20 120 1T+ 2W 2.40 0.0469 0.1126 6.819 2.50
R 3- 1 55 54 6.819 507.9 50 120 1.26 1W 2.76 0.0367 0.1013 6.920 3.91
R 2- 15 27 52 7.353 49.8 50 120 1.26 1.26 0.0005 0.0006 7.353 0.38
R 2- S1 53 52 7.232 20.00 53.8 53.8 20 120 1T+ 2W 2.40 0.0503 0.1208 7.353 2.60
R 2- 14 52 50 7.353 103.6 50 120 1.50 1.50 0.0019 0.0029 7.356 0.80
R 2- S1 51 50 7.235 20.00 53.8 53.8 20 120 1T+ 2W 2.40 0.0504 0.1208 7.356 2.60
R 2- 13 50 48 7.356 157.4 50 120 1.50 1.50 0.0042 0.0063 7.362 1.21
R 2- S1 49 48 7.242 20.00 53.8 53.8 20 120 1T+ 2W 2.40 0.0504 0.1209 7.362 2.60
R 2- 12 48 46 7.362 211.2 50 120 1.50 1.50 0.0072 0.0109 7.373 1.63
R 2- S1 47 46 7.252 20.00 53.9 53.9 20 120 1T+ 2W 2.40 0.0505 0.1211 7.373 2.60
R 2- 11 46 44 7.373 265.0 50 120 1.50 1.50 0.0110 0.0165 7.390 2.04
R 2- S1 45 44 7.268 20.00 53.9 53.9 20 120 1T+ 2W 2.40 0.0506 0.1214 7.390 2.60
R 2- 10 44 42 7.390 319.0 50 120 1.50 1.50 0.0155 0.0233 7.413 2.46
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

R 2- S1 43 42 7.291 20.00 54.0 54.0 20 120 1T+ 2W 2.40 0.0507 0.1217 7.413 2.61
R 2- 9 42 40 7.413 373.0 50 120 1.50 1W 3.00 0.0207 0.0622 7.475 2.87
R 2- S1 41 40 7.353 20.00 54.2 54.2 20 120 1T+ 2W 2.40 0.0511 0.1227 7.475 2.62
R 2- 8 40 38 7.475 427.2 50 120 1.50 1.50 0.0266 0.0400 7.515 3.29
R 2- S1 39 38 7.392 20.00 54.4 54.4 20 120 1T+ 2W 2.40 0.0514 0.1233 7.515 2.63
R 2- 7 38 36 7.515 481.6 50 120 1.50 1.50 0.0333 0.0499 7.565 3.71
R 2- S1 37 36 7.441 20.00 54.6 54.6 20 120 1T+ 2W 2.40 0.0517 0.1240 7.565 2.64
R 2- 6 36 34 7.565 536.1 50 120 2.39 2.39 0.0406 0.0969 7.662 4.13
R 2- S1 35 34 7.537 20.00 54.9 54.9 20 120 1T+ 2W 2.40 0.0523 0.1255 7.662 2.65
R 2- 5 34 33 7.662 591.0 50 120 1.15 1.15 0.0486 0.0559 7.718 4.55

Page 11 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 5

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
R 2- 4 33 31 7.718 832.9 50 120 0.35 0.35 0.0916 0.0321 7.750 6.42
R 2- S1 32 31 7.623 20.00 55.2 55.2 20 120 1T+ 2W 2.40 0.0528 0.1268 7.750 2.67
R 2- 3 31 30 7.750 888.1 50 120 0.40 0.40 0.1032 0.0413 7.791 6.84
R 2- 2 30 28 7.791 -603.5 50 120 1.10 1.10 -0.0505 -0.0555 7.736 4.65
R 2- S1 29 28 7.609 20.00 55.2 55.2 20 120 1T+ 2W 2.40 0.0528 0.1266 7.736 2.66
R 2- 1 28 1 7.736 -548.3 50 120 1.14 1.14 -0.0423 -0.0482 7.688 4.22
R 1- 14 27 25 7.353 -49.8 50 120 1.14 1W 2.64 -0.0005 -0.0013 7.351 0.38
R 1- S1 26 25 7.231 20.00 53.8 53.8 20 120 1T+ 2W 2.40 0.0503 0.1208 7.351 2.60
R 1- 13 25 24 7.351 4.0 50 120 1.15 1W 2.65 0.0000 0.0000 7.351 0.03
R 1- 12 24 22 7.351 -45.8 50 120 0.35 0.35 -0.0004 -0.0001 7.351 0.35
R 1- S1 23 22 7.230 20.00 53.8 53.8 20 120 1T+ 2W 2.40 0.0503 0.1208 7.351 2.60
R 1- 11 22 20 7.351 8.0 50 120 1.50 1.50 0.0000 0.0000 7.351 0.06
R 1- S1 21 20 7.230 20.00 53.8 53.8 20 120 1T+ 2W 2.40 0.0503 0.1208 7.351 2.60
R 1- 10 20 18 7.351 61.8 50 120 2.39 2.39 0.0007 0.0018 7.353 0.48
R 1- S1 19 18 7.232 20.00 53.8 53.8 20 120 1T+ 2W 2.40 0.0503 0.1208 7.353 2.60
R 1- 9 18 16 7.353 115.6 50 120 1.50 1.50 0.0024 0.0036 7.357 0.89
R 1- S1 17 16 7.236 20.00 53.8 53.8 20 120 1T+ 2W 2.40 0.0504 0.1208 7.357 2.60
R 1- 8 16 14 7.357 169.4 50 120 1.50 1.50 0.0048 0.0072 7.364 1.30
R 1- S1 15 14 7.243 20.00 53.8 53.8 20 120 1T+ 2W 2.40 0.0504 0.1210 7.364 2.60
R 1- 7 14 12 7.364 223.2 50 120 1.50 1.50 0.0080 0.0120 7.376 1.72
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

R 1- S1 13 12 7.255 20.00 53.9 53.9 20 120 1T+ 2W 2.40 0.0505 0.1211 7.376 2.60
R 1- 6 12 10 7.376 277.0 50 120 1.50 1.50 0.0120 0.0179 7.394 2.13
R 1- S1 11 10 7.272 20.00 53.9 53.9 20 120 1T+ 2W 2.40 0.0506 0.1214 7.394 2.61
R 1- 5 10 8 7.394 331.0 50 120 1.50 1W 3.00 0.0166 0.0498 7.444 2.55
R 1- S1 9 8 7.321 20.00 54.1 54.1 20 120 1T+ 2W 2.40 0.0509 0.1222 7.444 2.61
R 1- 4 8 6 7.444 385.1 50 120 1.50 1.50 0.0220 0.0330 7.477 2.97
R 1- S1 7 6 7.354 20.00 54.2 54.2 20 120 1T+ 2W 2.40 0.0511 0.1227 7.477 2.62
R 1- 3 6 4 7.477 439.3 50 120 1.50 1.50 0.0281 0.0421 7.519 3.39
R 1- S1 5 4 7.395 20.00 54.4 54.4 20 120 1T+ 2W 2.40 0.0514 0.1233 7.519 2.63
R 1- 2 4 2 7.519 493.7 50 120 1.50 1.50 0.0348 0.0522 7.571 3.80

Page 12 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 6

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
R 1- S1 3 2 7.447 20.00 54.6 54.6 20 120 1T+ 2W 2.40 0.0517 0.1241 7.571 2.64
R 1- 1 2 1 7.571 548.3 50 120 1.26 1W 2.76 0.0423 0.1167 7.688 4.22
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

Page 13 of 23
Appendix A: Hydraulic Calculation - Ammonia Tank-B

Builder : Mode of operation : Protected object :


Minimax GmbH Singapore Branch
25, International Business Park, #03-15/19, Effective area : pressure at sprinkler Group of operation area Description : Size :
German Centre, Singapore 609916 pump pressure of total operation area Water Spray System
Operator :
Roughness of pipe (C-value)150 and 120 Use of pipes according to DIN
Nghi-Son#2 Thermal Power Plant
Vietnam Supply of hydrants with water : l/min at node No. Strangrohr-No. : 0 ; Sprinkler-No. : 0

Project-No.: Operating company :


Ceiling protec. Rack protec.
NS2 Ammonia Storage Tank-B
Height of storage (m)
min. water admission (mm/min)
Person in charge : real effective area (ea) (m²)
Glen Golle max. protection area/sprinkler in ea (m²)
No. of sprinklers / effection area
No. of additional sprinkler / effection area
Date : Object :
hydraulic considered no.of sprinkler
09 April, 2019 Water Spray System
no. of protected decks
biggest distance of sprinkler (m)

Demand press required / Supply press available / cushion in bar 10.000 according Hazen-Williams

Water rate at point to feed in / Pump in l/min 3049.60


© By IDAT-GmbH 2000 - 2012 V 2.21 1226

hydraulic unfavourabelst element in the effective area


Sprinkler pipe-No. / No. ext. element
minimum pressure / Required density in bar
geodetic difference in height ext. element - point to feed in m
geodetic difference in height lowest element - point to feed in m 0.05
max. pressure of spray in the effective area in bar 7.480
min. pressure of spray in the effective area in bar 6.217
max. water speed in the effective area in m/s 8.49
No. of sprays in the effective area 63

Page 14 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 1

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
Z 2- 1 147 148 9.816 3049.6 300 120 4.43 2W+ 1S+ 1K 42.43 0.0002 1.79 0.1840 10.000 0.70 Pump=9464 lpm @10bar
Z 1- 1 147 146 9.816 -3049.6 300 120 6.88 1W 15.08 -0.0002 2.56 0.2482 10.064 0.70
H 2- 1 146 145 10.064 -3049.6 301 150 50.74 8W 200.40 -0.0003 1.60 0.1019 10.166 0.96
H 1- 1 145 144 10.166 -3049.6 201 150 16.83 2W 41.94 -0.0018 -1.60 -0.2323 9.934 2.07
V 5- 1 144 143 9.934 -3049.6 200 120 0.35 1W 5.85 -0.0014 -0.35 -0.0425 9.891 1.57
V 4- 1 143 142 9.891 -3049.6 150 120 2.87 1S+ 1K 13.57 -0.0053 -0.0723 9.819 2.73
V 3- 1 142 141 9.819 -3049.6 100 120 1.20 2S+ 1V 23.80 -0.0393 -1.20 -1.0519 8.767 6.19
V 2- 1 141 140 8.767 -3049.6 100 120 2.58 1W 5.68 -0.0393 -0.60 -0.2818 8.485 6.19
V 1- 1 140 139 8.485 -3049.6 100 120 9.03 3W 18.33 -0.0393 -1.10 -0.8274 7.658 6.19
F 1- 2 30 139 7.645 1477.5 65 120 0.96 0.96 0.1114 -0.96 0.0128 7.658 7.98
F 1- 1 139 85 7.658 -1572.1 65 120 1.34 1T 5.04 -0.1249 -1.34 -0.7612 6.897 8.49
R 7- 6 24 137 7.213 49.3 40 120 3.12 1T+ 1W 6.72 0.0016 1.47 0.1553 7.368 0.62
R 7- S2 138 137 7.336 14.00 37.9 37.9 15 120 1T 1.20 0.0264 0.0316 7.368 1.83
R 7- 5 137 135 7.368 87.2 40 120 2.80 2.80 0.0047 0.0132 7.381 1.10
R 7- S2 136 135 7.350 14.00 38.0 38.0 15 120 1T 1.20 0.0264 0.0317 7.381 1.83
R 7- 4 135 133 7.381 125.2 40 120 2.80 2.80 0.0092 0.0258 7.407 1.58
R 7- S2 134 133 7.375 14.00 38.0 38.0 15 120 1T 1.20 0.0265 0.0318 7.407 1.84
R 7- 3 133 131 7.407 163.2 40 120 2.80 2.80 0.0151 0.0421 7.449 2.07
R 7- S2 132 131 7.417 14.00 38.1 38.1 15 120 1T 1.20 0.0266 0.0320 7.449 1.84
R 7- 2 131 129 7.449 201.3 40 120 2.80 2.80 0.0222 0.0622 7.511 2.55
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

R 7- S2 130 129 7.479 14.00 38.3 38.3 15 120 1T 1.20 0.0268 0.0322 7.511 1.85
R 7- 1 129 33 7.511 239.6 40 120 3.12 1T+ 1W 6.72 0.0306 -1.47 0.0616 7.573 3.03
R 6- 6 78 127 6.504 28.9 40 120 4.36 1T+ 1W 7.96 0.0006 -2.70 -0.2600 6.244 0.37
R 6- S2 128 127 6.217 14.00 34.9 34.9 15 120 1T 1.20 0.0226 0.0271 6.244 1.69
R 6- 5 127 125 6.244 63.8 40 120 2.80 2.80 0.0027 0.0074 6.252 0.81
R 6- S2 126 125 6.225 14.00 34.9 34.9 15 120 1T 1.20 0.0226 0.0272 6.252 1.69
R 6- 4 125 123 6.252 98.8 40 120 2.80 2.80 0.0059 0.0166 6.268 1.25
R 6- S2 124 123 6.241 14.00 35.0 35.0 15 120 1T 1.20 0.0227 0.0272 6.268 1.69
R 6- 3 123 121 6.268 133.7 40 120 2.80 2.80 0.0104 0.0292 6.298 1.69
R 6- S2 122 121 6.270 14.00 35.1 35.1 15 120 1T 1.20 0.0228 0.0274 6.298 1.69

Page 15 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 2

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
R 6- 2 121 119 6.298 168.8 40 120 2.80 2.80 0.0160 0.0449 6.342 2.14
R 6- S2 120 119 6.315 14.00 35.2 35.2 15 120 1T 1.20 0.0229 0.0275 6.342 1.70
R 6- 1 119 88 6.342 204.0 40 120 4.36 1T+ 1W 7.96 0.0227 2.70 0.4459 6.788 2.58
R 5- 6 75 117 6.505 45.4 40 120 4.36 1T+ 1W 7.96 0.0014 -2.70 -0.2536 6.251 0.58
R 5- S2 118 117 6.224 14.00 34.9 34.9 15 120 1T 1.20 0.0226 0.0272 6.251 1.69
R 5- 5 117 115 6.251 80.3 40 120 2.80 2.80 0.0041 0.0114 6.262 1.02
R 5- S2 116 115 6.235 14.00 35.0 35.0 15 120 1T 1.20 0.0227 0.0272 6.262 1.69
R 5- 4 115 113 6.262 115.3 40 120 2.80 2.80 0.0079 0.0222 6.285 1.46
R 5- S2 114 113 6.257 14.00 35.0 35.0 15 120 1T 1.20 0.0228 0.0273 6.285 1.69
R 5- 3 113 111 6.285 150.3 40 120 2.80 2.80 0.0129 0.0362 6.321 1.90
R 5- S2 112 111 6.293 14.00 35.1 35.1 15 120 1T 1.20 0.0229 0.0275 6.321 1.70
R 5- 2 111 109 6.321 185.4 40 120 2.80 2.80 0.0191 0.0534 6.374 2.35
R 5- S2 110 109 6.346 14.00 35.3 35.3 15 120 1T 1.20 0.0231 0.0277 6.374 1.70
R 5- 1 109 84 6.374 220.7 40 120 4.36 1T+ 1W 7.96 0.0263 2.70 0.4743 6.848 2.79
R 4- 16 81 107 6.505 32.0 50 120 1.26 1.26 0.0002 0.0003 6.505 0.25
R 4- S1 108 107 6.397 20.00 50.6 50.6 20 120 1T+ 2W 2.40 0.0449 0.1078 6.505 2.44
R 4- 15 107 105 6.505 82.5 50 120 1.50 1.50 0.0013 0.0019 6.507 0.64
R 4- S1 106 105 6.399 20.00 50.6 50.6 20 120 1T+ 2W 2.40 0.0449 0.1079 6.507 2.44
R 4- 14 105 103 6.507 133.1 50 120 1.50 1.50 0.0031 0.0046 6.512 1.03
R 4- S1 104 103 6.404 20.00 50.6 50.6 20 120 1T+ 2W 2.40 0.0450 0.1079 6.512 2.44
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

R 4- 13 103 101 6.512 183.8 50 120 1.50 1.50 0.0056 0.0084 6.520 1.42
R 4- S1 102 101 6.412 20.00 50.6 50.6 20 120 1T+ 2W 2.40 0.0450 0.1081 6.520 2.45
R 4- 12 101 99 6.520 234.4 50 120 1.50 1.50 0.0088 0.0132 6.533 1.81
R 4- S1 100 99 6.425 20.00 50.7 50.7 20 120 1T+ 2W 2.40 0.0451 0.1083 6.533 2.45
R 4- 11 99 97 6.533 285.1 50 120 1.50 1.50 0.0126 0.0189 6.552 2.20
R 4- S1 98 97 6.444 20.00 50.8 50.8 20 120 1T+ 2W 2.40 0.0452 0.1086 6.552 2.45
R 4- 10 97 95 6.552 335.9 50 120 1.50 1.50 0.0171 0.0256 6.578 2.59
R 4- S1 96 95 6.469 20.00 50.9 50.9 20 120 1T+ 2W 2.40 0.0454 0.1089 6.578 2.46
R 4- 9 95 93 6.578 386.7 50 120 1.50 1W 3.00 0.0222 0.0665 6.644 2.98
R 4- S1 94 93 6.534 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0458 0.1100 6.644 2.47

Page 16 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 3

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
R 4- 8 93 91 6.644 437.9 50 120 1.50 1.50 0.0279 0.0418 6.686 3.37
R 4- S1 92 91 6.575 20.00 51.3 51.3 20 120 1T+ 2W 2.40 0.0461 0.1106 6.686 2.48
R 4- 7 91 89 6.686 489.1 50 120 2.39 2.39 0.0342 0.0818 6.768 3.77
R 4- S1 90 89 6.656 20.00 51.6 51.6 20 120 1T+ 2W 2.40 0.0466 0.1119 6.768 2.49
R 4- 6 89 88 6.768 540.7 50 120 0.50 0.50 0.0412 0.0206 6.788 4.17
R 4- 5 88 86 6.788 744.7 50 120 1.00 1.00 0.0745 0.0745 6.863 5.74
R 4- S1 87 86 6.750 20.00 52.0 52.0 20 120 1T+ 2W 2.40 0.0472 0.1133 6.863 2.51
R 4- 4 86 85 6.863 796.7 50 120 0.40 0.40 0.0844 0.0338 6.897 6.14
R 4- 3 85 84 6.897 -775.4 50 120 0.60 0.60 -0.0803 -0.0482 6.848 5.97
R 4- 2 84 82 6.848 -554.7 50 120 0.50 0.50 -0.0432 -0.0216 6.827 4.27
R 4- S1 83 82 6.714 20.00 51.8 51.8 20 120 1T+ 2W 2.40 0.0470 0.1128 6.827 2.50
R 4- 1 82 54 6.827 -502.9 50 120 1.14 1.14 -0.0360 -0.0411 6.786 3.87
R 3- 15 81 79 6.505 -32.0 50 120 1.14 1W 2.64 -0.0002 -0.0006 6.504 0.25
R 3- S1 80 79 6.396 20.00 50.6 50.6 20 120 1T+ 2W 2.40 0.0449 0.1078 6.504 2.44
R 3- 14 79 78 6.504 18.6 50 120 0.50 1W 2.00 0.0001 0.0002 6.504 0.14
R 3- 13 78 76 6.504 -10.3 50 120 1.00 1W 2.50 -0.0000 -0.0001 6.504 0.08
R 3- S1 77 76 6.396 20.00 50.6 50.6 20 120 1T+ 2W 2.40 0.0449 0.1078 6.504 2.44
R 3- 12 76 75 6.504 40.3 50 120 1.00 1.00 0.0003 0.0003 6.505 0.31
R 3- 11 75 73 6.505 -5.1 50 120 0.50 0.50 -0.0000 -0.0000 6.505 0.04
R 3- S1 74 73 6.397 20.00 50.6 50.6 20 120 1T+ 2W 2.40 0.0449 0.1078 6.505 2.44
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

R 3- 10 73 71 6.505 45.4 50 120 2.39 2.39 0.0004 0.0010 6.506 0.35


R 3- S1 72 71 6.398 20.00 50.6 50.6 20 120 1T+ 2W 2.40 0.0449 0.1078 6.506 2.44
R 3- 9 71 69 6.506 96.0 50 120 1.50 1.50 0.0017 0.0025 6.508 0.74
R 3- S1 70 69 6.400 20.00 50.6 50.6 20 120 1T+ 2W 2.40 0.0450 0.1079 6.508 2.44
R 3- 8 69 67 6.508 146.6 50 120 1.50 1.50 0.0037 0.0055 6.514 1.13
R 3- S1 68 67 6.406 20.00 50.6 50.6 20 120 1T+ 2W 2.40 0.0450 0.1080 6.514 2.45
R 3- 7 67 65 6.514 197.2 50 120 1.50 1.50 0.0064 0.0096 6.523 1.52
R 3- S1 66 65 6.415 20.00 50.7 50.7 20 120 1T+ 2W 2.40 0.0450 0.1081 6.523 2.45
R 3- 6 65 63 6.523 247.9 50 120 1.50 1.50 0.0097 0.0146 6.538 1.91
R 3- S1 64 63 6.430 20.00 50.7 50.7 20 120 1T+ 2W 2.40 0.0451 0.1083 6.538 2.45

Page 17 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 4

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
R 3- 5 63 61 6.538 298.6 50 120 1.50 1W 3.00 0.0137 0.0412 6.579 2.30
R 3- S1 62 61 6.470 20.00 50.9 50.9 20 120 1T+ 2W 2.40 0.0454 0.1090 6.579 2.46
R 3- 4 61 59 6.579 349.5 50 120 1.50 1.50 0.0184 0.0276 6.607 2.69
R 3- S1 60 59 6.497 20.00 51.0 51.0 20 120 1T+ 2W 2.40 0.0456 0.1094 6.607 2.46
R 3- 3 59 57 6.607 400.5 50 120 1.50 1.50 0.0236 0.0355 6.642 3.09
R 3- S1 58 57 6.532 20.00 51.1 51.1 20 120 1T+ 2W 2.40 0.0458 0.1099 6.642 2.47
R 3- 2 57 55 6.642 451.6 50 120 1.50 1.50 0.0295 0.0443 6.686 3.48
R 3- S1 56 55 6.576 20.00 51.3 51.3 20 120 1T+ 2W 2.40 0.0461 0.1106 6.686 2.48
R 3- 1 55 54 6.686 502.9 50 120 1.26 1W 2.76 0.0360 0.0994 6.786 3.87
R 2- 15 27 52 7.214 49.3 50 120 1.26 1.26 0.0005 0.0006 7.215 0.38
R 2- S1 53 52 7.096 20.00 53.3 53.3 20 120 1T+ 2W 2.40 0.0495 0.1187 7.215 2.57
R 2- 14 52 50 7.215 102.6 50 120 1.50 1.50 0.0019 0.0029 7.218 0.79
R 2- S1 51 50 7.099 20.00 53.3 53.3 20 120 1T+ 2W 2.40 0.0495 0.1187 7.218 2.57
R 2- 13 50 48 7.218 155.9 50 120 1.50 1.50 0.0041 0.0062 7.224 1.20
R 2- S1 49 48 7.105 20.00 53.3 53.3 20 120 1T+ 2W 2.40 0.0495 0.1188 7.224 2.58
R 2- 12 48 46 7.224 209.2 50 120 1.50 1.50 0.0071 0.0107 7.234 1.61
R 2- S1 47 46 7.115 20.00 53.3 53.3 20 120 1T+ 2W 2.40 0.0496 0.1190 7.234 2.58
R 2- 11 46 44 7.234 262.5 50 120 1.50 1.50 0.0108 0.0162 7.251 2.02
R 2- S1 45 44 7.131 20.00 53.4 53.4 20 120 1T+ 2W 2.40 0.0497 0.1192 7.251 2.58
R 2- 10 44 42 7.251 315.9 50 120 1.50 1.50 0.0152 0.0229 7.273 2.43
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

R 2- S1 43 42 7.154 20.00 53.5 53.5 20 120 1T+ 2W 2.40 0.0498 0.1196 7.273 2.58
R 2- 9 42 40 7.273 369.4 50 120 1.50 1W 3.00 0.0204 0.0611 7.335 2.85
R 2- S1 41 40 7.214 20.00 53.7 53.7 20 120 1T+ 2W 2.40 0.0502 0.1205 7.335 2.59
R 2- 8 40 38 7.335 423.2 50 120 1.50 1.50 0.0262 0.0393 7.374 3.26
R 2- S1 39 38 7.253 20.00 53.9 53.9 20 120 1T+ 2W 2.40 0.0505 0.1211 7.374 2.60
R 2- 7 38 36 7.374 477.0 50 120 1.50 1.50 0.0327 0.0490 7.423 3.68
R 2- S1 37 36 7.301 20.00 54.0 54.0 20 120 1T+ 2W 2.40 0.0508 0.1219 7.423 2.61
R 2- 6 36 34 7.423 531.1 50 120 2.39 2.39 0.0398 0.0952 7.518 4.09
R 2- S1 35 34 7.395 20.00 54.4 54.4 20 120 1T+ 2W 2.40 0.0514 0.1233 7.518 2.63
R 2- 5 34 33 7.518 585.5 50 120 1.15 1.15 0.0477 0.0549 7.573 4.51

Page 18 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 5

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
R 2- 4 33 31 7.573 825.1 50 120 0.35 0.35 0.0900 0.0315 7.605 6.36
R 2- S1 32 31 7.480 20.00 54.7 54.7 20 120 1T+ 2W 2.40 0.0519 0.1246 7.605 2.64
R 2- 3 31 30 7.605 879.8 50 120 0.40 0.40 0.1014 0.0406 7.645 6.78
R 2- 2 30 28 7.645 -597.8 50 120 1.10 1.10 -0.0496 -0.0546 7.590 4.61
R 2- S1 29 28 7.466 20.00 54.6 54.6 20 120 1T+ 2W 2.40 0.0518 0.1244 7.590 2.64
R 2- 1 28 1 7.590 -543.1 50 120 1.14 1.14 -0.0415 -0.0474 7.543 4.18
R 1- 14 27 25 7.214 -49.3 50 120 1.14 1W 2.64 -0.0005 -0.0013 7.213 0.38
R 1- S1 26 25 7.094 20.00 53.3 53.3 20 120 1T+ 2W 2.40 0.0494 0.1187 7.213 2.57
R 1- 13 25 24 7.213 4.0 50 120 1.15 1W 2.65 0.0000 0.0000 7.213 0.03
R 1- 12 24 22 7.213 -45.3 50 120 0.35 0.35 -0.0004 -0.0001 7.213 0.35
R 1- S1 23 22 7.094 20.00 53.3 53.3 20 120 1T+ 2W 2.40 0.0494 0.1187 7.213 2.57
R 1- 11 22 20 7.213 7.9 50 120 1.50 1.50 0.0000 0.0000 7.213 0.06
R 1- S1 21 20 7.094 20.00 53.3 53.3 20 120 1T+ 2W 2.40 0.0494 0.1187 7.213 2.57
R 1- 10 20 18 7.213 61.2 50 120 2.39 2.39 0.0007 0.0017 7.214 0.47
R 1- S1 19 18 7.096 20.00 53.3 53.3 20 120 1T+ 2W 2.40 0.0495 0.1187 7.214 2.57
R 1- 9 18 16 7.214 114.5 50 120 1.50 1.50 0.0023 0.0035 7.218 0.88
R 1- S1 17 16 7.099 20.00 53.3 53.3 20 120 1T+ 2W 2.40 0.0495 0.1187 7.218 2.57
R 1- 8 16 14 7.218 167.8 50 120 1.50 1.50 0.0047 0.0071 7.225 1.29
R 1- S1 15 14 7.106 20.00 53.3 53.3 20 120 1T+ 2W 2.40 0.0495 0.1188 7.225 2.58
R 1- 7 14 12 7.225 221.1 50 120 1.50 1.50 0.0079 0.0118 7.237 1.70
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

R 1- S1 13 12 7.118 20.00 53.4 53.4 20 120 1T+ 2W 2.40 0.0496 0.1190 7.237 2.58
R 1- 6 12 10 7.237 274.4 50 120 1.50 1.50 0.0117 0.0176 7.254 2.11
R 1- S1 11 10 7.135 20.00 53.4 53.4 20 120 1T+ 2W 2.40 0.0497 0.1193 7.254 2.58
R 1- 5 10 8 7.254 327.9 50 120 1.50 1W 3.00 0.0163 0.0490 7.303 2.53
R 1- S1 9 8 7.183 20.00 53.6 53.6 20 120 1T+ 2W 2.40 0.0500 0.1200 7.303 2.59
R 1- 4 8 6 7.303 381.5 50 120 1.50 1.50 0.0216 0.0324 7.336 2.94
R 1- S1 7 6 7.215 20.00 53.7 53.7 20 120 1T+ 2W 2.40 0.0502 0.1205 7.336 2.59
R 1- 3 6 4 7.336 435.2 50 120 1.50 1.50 0.0276 0.0414 7.377 3.35
R 1- S1 5 4 7.256 20.00 53.9 53.9 20 120 1T+ 2W 2.40 0.0505 0.1212 7.377 2.60
R 1- 2 4 2 7.377 489.1 50 120 1.50 1.50 0.0342 0.0513 7.428 3.77

Page 19 of 23
Calculation of pressure loss : Name of project : NS2 No. of protection area : 1 Date : 09 April, 2019 Page : 6

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
R 1- S1 3 2 7.307 20.00 54.1 54.1 20 120 1T+ 2W 2.40 0.0508 0.1219 7.428 2.61
R 1- 1 2 1 7.428 543.1 50 120 1.26 1W 2.76 0.0415 0.1146 7.543 4.18
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

Page 20 of 23
FOR REFERENCE

PIPING RING MAIN

GRAPHIC SCALE
0 5 10 25 50 100 200m

A1 (841 x 594)
Page 21 of 23
FOR REFERENCE

GRAPHIC SCALE
0 5 10 25 50 100 200m

A1 (841 x 594)
Page 22 of 23
FOR REFERENCE

GRAPHIC SCALE
0 5 10 25 50 100 200m

A1 (841 x 594)
Page 23 of 23