Handbook Vacuum circuit-breakers

type VD4

12 kV, …4000 A, ... 50 kA


17.5 kV, …4000 A, …40 kA
24 kV, …2500 A, …25 kA

ABB Power Distribution

1
P 12244-3 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 3 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Contents Page
Foreword 3
General technical data
for medium-voltage switchgear 4
Switching with vacuum circuit-breakers 6
Vacuum circuit-breakers for switching
of all the loads which occur in practice 11
Vacuum circuit-breakers type VD4 13
Technical data 18
Ordering data and example 24
Ordering data 25
Technical data – Accessories 29
Ordering data – Accessories 35
Ordering data – Spare parts 36
Wiring diagrams 37
Dimension drawings 40

Foreword
This vacuum circuit-breaker Note: In practical grid operations it
manual is intended to serve In VDE standards 0670 and has however become usual to
electrical engineers engaged in 00/IEC Publications 694 and describe equipment for voltages
designing and planning switch- 62, the equipment described between  kV and 36 kV
gear installations as a work of refe- in this manual is referred to as as
rence combining both engineer- AC switchgear for voltages medium-voltage switchgear.
ing aids and a catalogue of switch- above  kV
In the individual equipment
gear equipment for the voltage and
descriptions and tables we have
range from  kV to 36 kV. In this high-voltage switchgear.
generally adopted this latter usage.
manual we have intentionally
surpassed the frame of reference
occupied by traditional catalogues.
3

P
P 12244-4 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 14.1.97 – Seite 4 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

General technical data for medium voltage switchgear

Rated short-circuit breaking When switchgear is used in sys- Rated insulation level
current (symmetrical) tems in the vicinity of generators,
In accordance with DIN VDE 0670,
or when there are motors in the
The figure quoted here represents Part 1000 and Part 6/IEC 694 and
system, a higher making current
the effective value for the symme- 298 and HD 448, the rated values
may become necessary. Please
trical short-circuit breaking current for insulating capacity (rated light-
contact us in such cases.
which the circuit-breaker is ning impulse withstand voltage
capable of interrupting at rated and rated power frequency with-
Surge current
voltage. stand voltage) for our switchgear
The value of the surge current is are related to normal atmospheric
Short-circuit breaking current equal to that of the short-circuit conditions (temperature 20 hC,
(asymmetrical) making current. barometric pressure 1.013 bar
(0.3 kPa), and humidity  g/m3).
The figure here refers to the effec-
Rated short-time current and
tive value of the asymmetrical Rated voltage Rated lightning Rated power
rated short-circuit duration impulse with- frequency with-
breaking current which the circuit- stand voltage stand voltage
(effektive value) (peak value) (effective value)
breaker is capable of interrupting According to VDE 0670, Part 1000 List 2
at rated voltage. When the DC and VDE 0101/IEC 694 and 56,
component is known, the asymme- the rated short-time current is kV kV kV
trical breaking current can be equal to the rated short-circuit 12 75 28
determined by applying the follow- breaking current for a given short- 17.5 95 38
ing formula: circuit duration t. The preferred 24 125 50
values for t are 1 s and 3 s.
+ 2 b2
Iasym. = I sym. öääää 36 170 70
Conversion of the short-time
I asym. = asymmetrical breaking (formerly: List 2 = Series N)
current for other times which are
current,
not quoted can be accomplished Installation altitude
I sym. = symmetrical breaking
in accordance with the formula
current, The values quoted in the tables
I2 = I  · öää
t  /t 2 are valid up to an altitude of
related DC component
in % I  = known short-time current for 1000 m above sea level. When
b =
short-circuit duration t  , and switchgear and switchboards are
00
I 2 = required short-time current installed at altitudes over 1000 m
In VDE 0670, Part 000 and VDE above sea level, the reduction in
for short-circuit duration t 2 .
00/IEC 694 and 56, the percent- dielectric strength of the air must
age value for the DC component It should be noted in connection be taken into account. In such
is defined as the ratio of I DC to I AC , with this conversion operation that cases, a correction factor k in
multiplied by 00. I AC (I AC = I eff · öä
2) it only takes account of the thermal accordance with the curve in the
is the amplitude of the symmetri- equivalent of the short-time cur- next figure is to be applied to the
cal short-circuit AC current at the rent, but not of the dynamic effect calculations.
time of observation, and I DC is the of the corresponding impulse
DC component. current.

Rated short-circuit making


current
According to VDE 0670, Part 000
and VDE 00/IEC 694 and 56,
the rated short-circuit making cur-
rent must be at least 2.5 times the
symmetrical breaking current.
This follows from the assumption
of a surge factor k = .8 in an
idealized network with a time
constant t = 45 ms corresponding Curve for determination of the correction
to cos f = 0.07. factor (to IEC and ASA)
k = Correction factor
H = Altitude

P
P 12244-5 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 17.2.97 – Seite 5 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Determination of test voltages: Determination of the rated If the minimum distances in the
voltage switchgear are smaller than those
Determine the correction factor
of the switchboard planned in
corresponding to the known instal- When the correction factor has
accordance with DIN 57101/VDE
lation altitude. Then divide the been determined, divide the rated
0101, the minimum distances for
appropriate lightning impulse voltage of the network concerned
the “tested connection zone” in the
withstand voltage or power fre- by this figure. The result is the new
appropriate outline drawing must
quency withstand voltage appli- rated voltage, which determines
be observed.
cable for the given rated voltage of the selection of the equipment to
the equipment by the correction be installed. Any connecting bars required are
factor. The test voltages thus ob- not included in the switchgear
Example calculation:
tained then apply to testing in high supply.
with values as above
voltage test laboratories located
Recommendation for the user:
below 1000 m above sea level, Rated
24 kV The connecting bars have to be
and are the governing voltages for voltage 3000 = = 30 kV
0.8 fitted with an insulating covering
insulation measurements.
(e.g. shrink-on sleeve) in areas
The equipment to be installed at
Example calculation: where clearances are smaller than
an altitude of 3000 m above sea
the specified minimum. The cor-
Installation altitude level is thus to be designed for a
ners of the bar ends at the switch-
H = 3000 m above sea level rated voltage of 36 kV.
ing device have to be bevelled.
Correction factor
k = 0.8 Tested connection zone
(DIN 57101/VDE 0101)
Rated voltage of the
existing system at 3000 m The overwhelming majority of
altitude = 24 kV switchgear equipment for rated
voltages between 12 kV and 36 kV
Test voltages for installation at up is not constructed according to
to 000 m above sea level: the minimum distances stipulated
Rated lightning in DIN 57101/VDE 0101, but with
impulse withstand type tested distances according to
voltage = 125 kV the values required by DIN 57111/
VDE 0111.
Rated power
frequency withstand
voltage = 50 kV
M M
Ligthning impulse
withstand
125 kV
voltage3000 = = 57 kV
200

0.8
Power frequency
withstand
50 kV
voltage 3000 = = 62.5 kV
0.8
The insulation of the equipment to
200

be installed must therefore with-


stand an impulse test voltage of
157 kV and an power frequency M M
M
withstand voltage of 62.5 kV
during testing in laboratories up to
1000 m above sea level. Tested connection zone on a circuit-breaker
M = Minimum distance to DIN 570/VDE 00

P
P 12244-6 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 6 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Switching with vacuum circuit-breakers

Older medium voltage circuit- The current-breaking process in neutralization of the negative
breakers interrupt the current to a vacuum circuit-breaker space charge brought about by
be switched by using a quenching the electrons.
On separation of current-carrying
medium to cool and deionize the
contacts, the vacuum arc is If the arc current exceeds a limit
arc which is created on contact
created by melting or explosive which depends on the contact
separation. The arc is then nor-
vaporization at the last metallic material, the cathodic melting
mally extinguished at the next cur-
point of contact, initially with only point splits into a corresponding
rent zero. The prefered quenching
a single melting point on the number of parallel cathode spots.
media are oil, air and sulphur
negative electrode, known as the Without the influence of an exter-
hexafluoride (SF6).
cathode spot. Figure 1 is a nal magnetic field, the melting
Vacuum circuit-breakers differ schematic representation of this points move around on the entire
from these breakers in that they process. cathode surface at high speed in
do not need any quenching medi- random directions, with adjacent
The cathode spot is a small,
um. In contrast to the switching spots repelling each other.
limited region of high temperature
arcs in air, SF6 or oil, a vacuum They thus constantly produce new
and high pressure, from which
contains no ionizable material metal vapour.
ions, electrons and neutral parti-
which would be required for an
cles are emitted. At the spot, there
independent thermal gas dis-
is a high prevailing current density
charge to take place. After the
(> 08A/cm 2) and a surface tempe-
separation of current-carrying con-
rature close to the boiling point of
tacts however, a metal vapour arc,
the contact material. The periph-
referred to below as the vacuum
eral areas of the cathode spot
arc for clarity’s sake, is created in
represent an intensive source of
the vacuum. The vacuum arc cre-
neutral metal vapour, which is ion-
ates the charge carriers required
ized in the discharge cone in front
for the current to pass through the
of the cathode. Over 90 % of the
vacuum by vaporization of the
total current is transported by elec-
electrode material itself. The
trons. The positive ions cause a
quenching process in a vacuum is
explained below, and this results
in the special characteristics of
vacuum circuit-breakers which are
then described.

PD = vapour pressure
of cathode material
PM = magnetic
PM PD PM pressure

0 8 A/m 3 Cathode

Fig. : Single cathode spot of a 00 A vacuum arc


[]

P
P 12244-7 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 8.1.97 – Seite 7 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

The form of discharge described anode spots. In interrupters for Today, a composite material of
above characterizes the “diffuse high short-circuit currents, local copper and chromium is
vacuum arc”. This process is sche- overheating is avoided and the employed to reduce the chopping
matically represented in figure 2a. overall contact erosion kept low by current. When this material is used,
The only active electrode is the constant forced motion of the arc the chopping currents become as
cathode. The entire surface of the melting points. low as in circuit-breakers with
anode forms a condensation sur- liquid or gaseous quenching
Figure 3 is a schematic diagram
face for vapour particles and media, and no longer lead to the
of a spiral electrode of a type similar
charge carriers, thus functioning feared overvoltages.
to that used by ABB Calor Emag.
merely as a collector. There is no
arc column, at least at currents The current path induced by this
within the rated current range of special shaping of the contacts
the circuit breaker. Contact ero- creates a magnetic field whose
sion is thus negligibly low on inter- tangential force vectors act on the
ruption of currents up to the rated melting points and thus deflect the
level. vacuum arc. The melting points
move around on the contacts at
The second form of discharge is
high velocity. This not only keeps
the “contracted vacuum arc” in the
burn-off low in general, but also
high-current range, which occurs
allows higher breaking currents to
at currents of approx. 10 kA and
be mastered.
above with cylindrical electrodes
of copper. This process is schema- With the reduction in the instanta-
tically represented in figure 2c. The neous current values, the energy
contracted vacuum arc is a high- supplied may under certain cir-
pressure metal vapour arc with cumstances no longer be suffi-
anode voltage drop and a thermal cient to maintain the last arc spot.
column, which develops from the A depletion of charge carriers can
initial diffusion by the formation of cause the arc current to chop
anode spots (see figure 2b) and abruptly prior to the natural current
grouping of the opposite cathode zero, which may cause high over-
spots into a single cathodic melt- voltages at existing network induc-
ing point. The anode shows dis- tances.
tinct fusing after subjection to

spiral electrode

A A A

K K K

a) b) c)

Fig. 2: Schematic diagrams of various modes of vacuum arc Fig. 3: Electrode configurations with creation of an inherent
[] [] magnetic field
a) Diffused
b) Anode contraction
c) Contraction at A and K

P
P 12244-8 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 8 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

The structure of a vacuum The external structure is character- tion on the contacts is impossible
interrupter ized by the ceramic insulator () in the vacuum. Sliding or shifting
manufactured in aluminium oxide. motions to remove such contami-
There are considerable differen-
The two stainless steel chamber nation layers, such as are neces-
ces in the manufacturing technolo-
lids (7) are hard-soldered to the sary in circuit-breakers with other
gies for vacuum interrupters.
insulator. The heart of a vacuum quenching principles, can there-
A fundamental distinction can be interrupter is formed by the con- fore be dispensed with. The simple
made between two groups: tacts (2 and 3), which are manu- contacts are, on the other hand,
1. Vacuum interrupters which factured from pure copper-chro- necessary, because no contact
are evacuated individually on mium composite material. The cur- springs can be used. These would
pumping stands, and whose rent is fed to the contacts via termi- be annealed at the high brazing
extraction outlets are cold- nals (8 and 9) of pure oxygen-free temperatures.
welded by compression on copper. Transmission of the switch-
completion of the pumping ing motion into the interrupter Properties of vacuum
process (pinch-off-method). chamber is effected by a bellows interrupters
(4) of stainless steel, one side of
2. Vacuum interrupters which The fast reduction in charge car-
which is brazed to the moving pin
are evacuated in a brazing rier density in the vacuum arc and
and the other to a chamber lid,
oven, and which become the rapid condensation of the
forming a gas-tight seal.
sealed after cooling (seal- metal vapour on the contact sur-
brazing method). Screens (5) are fitted to protect the faces at the current zero lead to
bellows and insulator from spatter- an extremely fast dielectric recov-
The seal-brazing method has ing liquid electrode material, and ery. This is shown in figure 5.
the advantage that evacua- for better distribution of the electri-
tion takes place at higher The dielectric strength in vacuum
cal field.
temperatures, and the interrupters rises to very high
vacuum itself achieves a It is a characteristic feature of values almost immediately after
higher degree of purity. vacuum interrupters that they have the current zero. In comparison,
butt contacts touching only at their the values for circuit-breakers with
At ABB Calor Emag, vacuum inter- facing surfaces. Such simple con- various other quenching media
rupters are only manufactured by tacts are possible because oxida- are also shown, making it clear
the seal-brazing method (figure 4). tion or formation of contamina- that much slower rises in dielec-

0
Dielectric recovery voltage

7

4 Vacuum
3
5
2
6

7 Time
8

Fig. 4: Interrupter manufactured by the seal-brazing method Fig. 5: Dielectric recovery of the contact gap in relation to the
[] time after quenching of the switching arc at the current
1 Insulator 6 Guide bushing
zero (current 600 A rms )
2 Fixed contact 7 Lid
3 Movable contact 8 Threaded terminal Switching media: vacuum, sulphur hexafluoride (SF6 ),
4 Metal bellows 9 Cylindrical terminal nitrogen (N 2 ) and hydrogen (H 2 )
5 Screen 10 Threaded terminal
(Gas pressure  bar without switching medium flow)
Electrode spacing 6.35 mm (constant: disregarding
the contact opening time)

P
P 12244-9 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 8.1.97 – Seite 9 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

tric strength between the contacts typical for vacuum circuit-breakers or almost homogeneous field the
are exhibited when using sulphur type VD4 from ABB Calor Emag. dielectric strength of a vacuum
hexafluoride, nitrogen (the funda- gap for AC and DC voltage grows
There will surely only be rare
mental quenching medium in air- in approximately direct proportion
occasions when the application
blast circuit-breakers) or hydrogen to the square root of the flashover
exceeds the capability of the
(the fundamental quenching medi- sparking distance. This depen-
vacuum circuit-breaker. In other
um in oil circuit-breakers). With dence has also been confirmed
words, the summed switching
this virtually immediate dielectric experimentally for the lightning
capacity requirements will not
recovery, vacuum circuit-breakers impulse withstand voltage.
under normal circumstances
are particularly good for switching
reach the limits of an interrupter.
circuits with very high rates of rise
of transient recovery voltage. One important condition for the
Switching of capacitors, during perfect function of a vacuum inter-
which the contact gap is sub- rupter is the quality of the vacuum.
jected to high voltage stresses, is The flashover in a vacuum at pres-
also safely mastered by vacuum sures less than 10–4 mbar is inde-
circuit-breakers. pendent of pressure, and is deter-
mined by processes at the elec-
As a high dielectric strength
trodes. It cannot be compared with
between the contacts is achieved
a breakdown in other media. This
even with small clearances, break-
follows from the fact that the free
ing is also ensured when the
path lengths for the charge carri-
opening of the contacts takes
ers become so large that surge
place a few milliseconds before
processes in the residual gas
the current zero in the first phase
become insignificant for the break-
to be quenched. This reduces the
down process. In a homogeneous
arcing times to approximately half
of those in minimum-oil or SF6 cir-
cuit-breakers, and helps in con-
junction with the low arc voltage to
keep contact erosion to a mini-
mum.

Working life of vacuum


interrupters
The life of traditional circuit-break-
ers was mostly limited by wear of
the interrupters and contacts. As a
general rule, this can be excluded
with vacuum interrupters.
The low contact erosion in vacuum Breakers with
interrupters means that within the rated short-circuit
rated current range, the mechani- breaking currents
cal and not the electrical stresses 16 kA
are the decisive factor for the work- 20 kA
25 kA
Number of on/off

ing life of the interrupter or circuit- 31.5 kA


breaker. Even on interruption of
operations n

40 kA
high currents, the consumption of 50 kA
contact material remains low. It is
therefore possible to interrupt the
rated short-circuit breaking cur-
rent of an interrupter up to 100
times, depending on the type. The
number of permissible breaking Breaking current IA (kA)
operations relative to the current
to be interrupted is shown in
figure 6 for a number of circuit- Fig. 6: Permissible number of switching operations of the vacuum interrupters
breakers. The curves shown are as a function of the breaking current I a , (250 A)

P
P 12244-10 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 8.1.97 – Seite 10 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Breakdown in accordance with Interrupters which have been sub- production, and another after a
Paschen‘s Law only occurs at jected to such stresses, i.e. occa- specified “quarantine” period.
pressures greater than 10 –3 mbar sional interruption of service cur- Interrupters are only released for
(figure 7). rents, as a rule have a working life further use if the absolute pres-
of approx. 30 years. sure value in the second meas-
The vacuum insulation is self-
urement and the progress of the
healing, i.e. it is perfectly possible
Testing of vacuum interrupters pressure meet the extremely
for the original or even a greater
stringent quality standards. This
dielectric strength to be achieved Both the specified quality of the
then ensures that the effective
after a single breakdown. raw materials and the manufac-
leakage rate of the interrupter
ture of the resulting individual
It is known from statistically signi- chamber is smaller than the toler-
parts for the interrupters in
ficant measurements on stored able value if no external damage
accordance with the drawings are
interrupters carried out over many occurs.
continuously monitored. The parts
years that their working life is in
are cleaned by the latest chemical
excess of 20 years. A further con-
and physical methods before
tributing factor to this is the getter-
being finally assembled in a spe-
ing material inside the interrupter
cial clean room (class 100),
chambers, which can absorb a
evacuated in the oven and brazed
certain quantity of penetrating gas.
together.
As already mentioned, copper and
The actual final inspection (figure
chromium vapours, which have a
8) after manufacture has two aims:
great affinity to oxygen and hydro-
determination of the internal pres-
gen and can thus bind part of the
sure and of the leakage rate.
free hydrogen and oxygen atoms
Whereas pressure measurement
and molecules, arise during inter-
here is still only just within the
ruption of currents in an interrupt-
capabilities of metrology, there is
er chamber. This reduces the
no method of measuring the low
pressure in the chamber, and the
leakage rate required. Two pres-
working life is further prolonged
sure measurements are therefore
by switching of currents in the
carried out: one immediately after
rated current range.

Fig. 7: Breakdown voltage U between parallel plates and with a


[] homogeneous electrical field in relation to the product
of gas pressure p x distance between plates d (in mm)
(Paschen curve). Applicable for air.
Literature
[] Dr.-Ing. U. Reininghaus
Vacuum circuit-breakers/minimum oil circuit-breakers
VDE/GTW-seminar Fig. 8: Computer-aided automated final testing
High and medium voltage switchgear and switchboards of vacuum interrupters

0

P
P 12244-11 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 17.2.97 – Seite 11 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Vacuum circuit-breakers for switching of all the loads


which occur in practice
1 Breaking of short-circuit The normal autoreclosing chopping current is determined by
currents sequence to VDE 0670, Part 102/ the contact material, and is below
ICE 56 is: 5 A (average approx. 3.5 A) with
1.1 Autoreclosing sequence
the materials currently used, thus
O – 0.3 s – CO – 3 mins – CO.
Short-circuits in overhead lines causing no dangerous overvolt-
caused by external factors (storms, Further autoreclosing sequences ages. If the occurrence of multiple
thunderstorms or animals) consti- on request. restriking is expected in certain
tute an extremely high proportion load circuits, overvoltage protec-
.2 Multi-shot autoreclosing
of the faults in overhead line sys- tion is recommended.
tems. The faults mostly persist for Thanks to the short charging times
of the motor-operated mechanism See also page 2.
a short time only. When the short-
circuit current has been switched used to charge the operating 2.1 Tranformers
off, electrical restablishment mechanism springs, vacuum
Oil-insulated transformers or cor-
rapidly occurs, and so the line can circuit-breakers are also able to
respondingly dimensioned cast
be switched on again after a short perform a number of short-circuit
resin transformers for distribution
time (approx. 0.3 s). In such cases, current breaking operations in
networks require no overvoltage
circuit-breakers with autoreclosing rapid sequence.
protection.
systems are used. These are cap-
able of autoreclosing operations Arc furnace transformers and dry-
2 Switching of small type transformers designed for
up to their rated short-circuit
inductive loads special purposes require overvolt-
breaking currents. If the short-cir-
cuit should still persist when the The chopping current is of para- age protection in the form of metal
breaker recloses, the subsequent mount importance in determining oxide surge arresters due to their
second opening operation the size of overvoltages during special construction and method
ensures that the faulty feeder is switching operations. In vacuum of operation.
finally switched off. circuit-breakers, the size of the

Oscillogram of an autoreclosing sequence, VD4, 2 kV, 40 kA




P
P 12244-12 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 14.1.97 – Seite 12 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

2.2 Switching of motors dielectric strength of the contact – Arc furnace transformers and
gap is re-established after the cur- dry-type transformers desig-
Overvoltage protection measures
rent has been interrupted. The ned for special purposes
are not necessary for motors
circuit-breakers in this manual are (these occasionally have a
which are not switched during the
notable for extremely fast re- reduced dielectric strength
start-up phase, or for motors with
establishment of the contact gap. and therefore require special
starting currents of 600 A and
protection).
more. If it is expected that motors They are capable of interrupting
with starting currents of up to capacitive currents up to 0.8 times – Shunt reactors
600 A are to be switched off dur- their rated current without restrik- (These must not be confused
ing the start-up phase, metal oxide ing, and thus without overvoltages. with current limiting reactors,
surge arresters have to be used which can be switched per-
When immediately adjacent ca-
as overvoltage protection devices. fectly.)
pacitor banks are operated in par-
The surge arresters can be instal- allel, the extent of the expected – Stalled motors or motors in
led either in the vicinity of the inrush currents is to be checked – the start-up phase with a
motors or in the switchgear panel. also with regard to the stress on starting current below 600 A.
the capacitors. Limit values for
In these cases surge arresters,
2.3 Generators vacuum circuit-breakers will be
e.g. ABB types MVR and MVF,
advised on request.
The same procedure has to be should be installed as close to the
adopted for small generators as load as possible.
for small motors. The short-circuit
Switching surges The loads listed above is thus
currents in small generators are
securely protected.
comparable with the starting cur- It is occasionally said that vacuum
rents of motors. circuit-breakers create high
switching overvoltages. Modern
With large generators, overvoltage
vacuum circuit-breakers like the
protection is usually provided in
VD4 do not create any higher
the light of external overvoltages.
switching overvoltages than the
proven minimum-oil circuit-
2.4 Shunt reactors
breakers.
These are as a rule connected to
The extent of the voltage surges
the transmission network via ter-
which occur during switching is
tiary windings. At operating voltages
not only dependent on the circuit
of 25 kV and over, surge arresters
breaker. It is also decisively
should always be fitted.
influenced by the circuit data, and
is furthermore subject to a high
statistical scatter. This is why it has
not yet been possible to design
3 Switching of capacitive test circuits which can achieve
loads reproducible results. Indication of
maximum overvoltage factors is
3.1 Switching of cables and
thus problematic at the least.
overhead lines under
no-load conditions Whether a voltage surge is dan-
gerous or not fundamentally
The relatively small capacitive cur-
depends on the dielectric strength
rents which occur when overhead
of the connected load. Regret-
lines and cables under no load
tably, the surge withstand capabil-
are switched off can be securely
ity of high voltage motors, for
handled without restriking and
example, has not yet been stand-
thus without switching overvolt-
ardized as for other equipment.
ages.
In practice, therefore, one finds
both motors with sufficiently high
3.2 Switching of capacitor
insulation levels, and other with
banks
lower insulation levels. For safety’s
Successful switching of capacitors sake, it is recommended that
without restriking is essentially a surge arrestors always be installed
matter of the speed at which the with the following loads:

2

P
P 12244-13 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 9.1.97 – Seite 13 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Vacuum circuit-breakers type VD4

The vacuum circuit-breakers of all load breaking operations which


type VD4 conform to the stipula- occur in practice, and in particular
tions for AC switchgear and con- for switching of:
trolgear for voltages above  kV as x short-circuit currents,
contained in DIN VDE 0670, Part x overhead lines under load and
101 – Circuit-breakers, in IEC
no-load conditions,
Publication 56, and in the stand- x cables under load and no-load
ards of various major industrial
conditions,
countries. x transformers under load and
The circuit-breakers are notable no-load conditions,
for their compact design, small x generators under load and
dimensions together with high no-load conditions,
capacity, and robust construction. x ripple control systems,
x capacitor banks (also parallel
The operating mechanisms have
switching) and
a low maintenance requirement x motors with starting currents
and the interrupters are mainte-
above 600 A.
nance-free throughout their ser-
(see pages  to 2.)
vice lives. They are well suited to

Fig. 9: Vacuum circuit-breaker, type VD4, Fig. 0: Vacuum circuit-breaker, type VD4,
for 2 kV, mechanism side for 24 kV, pole side

3

P
P 12244-14 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 17.2.97 – Seite 14 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

VD4: Pole parts with impact- The pole parts consist of the upper VD4: Wear-resistant operating
protected interrupters connection (3), vacuum interrupt- mechanism
er (5), lower connection (4), with
The vacuum circuit-breakers of The dielectric strength of the
the roller or swivel contact (6.2)
type VD4 are constructed in vacuum allows extremely small
and contact force spring (7). The
column form and designed for contact gaps to be used. The con-
movable contacts in the vacuum
fixed installation or mounting on tact gap in 12 kV interrupters is
interrupter chambers are operated
circuit-breaker trucks and with- thus only 10 mm, and that in 36 kV
from below by the insulated cou-
drawable modules. interrupters only a few millimetres
pling rods (8).
more. The moving parts in the
For effective protection from dam-
interrupter chamber are low in
age resulting from physical
mass. The contact velocity during
impact, the pole parts are installed
opening and closing operations is
in strong tubular insulators of cast
around 1 m/sec. This is a quarter
resin. Any external impact on the
of the normal value for other break-
poles first affects the cast resin
ers. The force required for switch-
enclosure, damage to which can
ing is extremely low.
be easily seen.
The stored-energy spring mecha-
nism in the mechanism housing
() is optimally set to provide the
energy required by the vacuum
interrupters (5) during switching,
so that no contact bounce and
thus also no unneccessary con-
tact welding can occur. Opening
is assisted by the contact force
springs (7) and the opening
spring (9). The circuit-breakers
are suitable for autoreclosing
without any additional modifica-
tions, and the good interrupter
characteristics also make the ver-
sions with motor drive suitable for
multi-shot autoreclosing.

Reliable function
The required switching energy is
provided by charging a spiral
spring (33) via a chain drive (34)
fitted with a ratchet (35), either with
a charging motor or by manual
pumping of a charging lever.
The breaker is closed either
mechanically by an “ON” push-
button, or electrically by means of
Fig. : Section of a vacuum circuit-breaker, type VD4, 2 kV, 250 A, 3.5 kA,
a shunt release.
schematic diagram The release mechanism (3) then
 Breaker mechanism housing releases the drive shaft (30), which
. Front plate, removable is turned through a specified dis-
2 Insulated pole tube tance by the charged spiral spring
3 Upper breaker terminal
4 Lower breaker terminal
(33). A cam disk (2) mounted on
5 Vacuum interrupter the drive shaft (30), and a pair of
(6. Swivel contact, 630 A) shift levers (20) cause the mov-
6.2 Roller contact, 250 A able contacts (5.3) in the vacuum
7 Contact force spring interrupter chambers (5) of each
8 Insulated coupling rod
9 Opening spring pole to move upwards.
20 Shift lever pair

4

P
P 12244-15 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 15 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

– The cam disk (2) is extre- With this special design, the timing There is still sufficient energy
mely important here: of the force provided by the stored in the spiral spring (33) for
mechanism is ideally adapted to this motion. At the same time, the
Its curvature ensures that the drive
the force requirement of the energy available from the contact
shaft (30) first turns without load
vacuum interrupter during the force spring (7) and opening
(through an angle of approx. 50 h),
opening and closing action. The spring (9) in each pole is re-
and only then does the cam (2)
spring forces remain relatively leased, and the movable contact
apply force to the shift lever (20).
small, which again leads to low (5.3) in the vacuum interrupter
This force transmission is termi-
wear on the mechanical parts. chamber (5) is moved in the
nated at an operating angle of
“OFF” direction. The precise
approx. 260 h. The drive shaft (30) The dimensioning of the spiral
motion sequence and the opening
then turns without load through spring (33) is such that both the
speed are determined by the pair
the remaining 10 h until the total contact force springs (7) and the
of shift levers (20) and the cam
closing angle of 270 h is reached. opening springs (9) are tension-
(2) located on the drive shaft in
This system precludes jarring and ed during the closing operation.
such a way as securely to prevent
shudder, and prevents the con-
Opening of the circuit-breaker is the contacts from bouncing.
tacts from bouncing. The course
effected either mechanically with
of the closing motion is deter-
the “OFF” push-button, or electric- Rated operating sequence
mined by the gradient of the cam
ally by means of various releases
disk (2). The rated operating sequence for
(shunt release OFF, undervoltage
vacuum circuit-breakers is nor-
release, 2nd shunt release and
mally determined by the mechani-
current transformer (CT) release.
cal properties of the circuit-break-
The drive shaft (30) is released by
er operating mechanism. The
the release mechanism (3) to
time for dielectric recovery of the
allow it to turn further.
contact gap is negligible. In distri-
bution networks which require an
autoreclosing sequence, the oper-
ating times for the autoreclosing
sequence O – 0.3 s – CO are de-
fined by the switching times of the
autoreclosing relays.
If the circuit-breaker operating
mechanism spring is recharged
manually or by the charging motor
after the first closing operation, the
breaker mechanism has sufficient
energy for an autoreclosing cycle.
Only the maximum recharging
time of max. 5 s for the charging
motor is decisive for the duration
of the further pauses.
Examples of rated operating
sequences:
O – 3 min – C O – 3 min – C O
O – 0.3 sec – C O – 3 min – C O
O – 0.3 sec – C O – 5 sec – C O
In VD4 vacuum circuit-breakers,
Fig. 2: Fundamental structure of the stored-energy spring mechanism the same operating mechanism is
used from the lowest to the
6 Socket 20 Shift lever pair
9 Charging lever 2 Cam disk highest rated and short-circuit
5 Vacuum interrupter 30 Drive shaft breaking currents.
5.3 Movable contact 3 Release mechanism
(6. Swivel contact, 630 A) 32 Stop disk
6.2 Roller contact, 250 A 33 Drum with spiral spring
7 Contact force spring 34 Chain
8 Insulated coupling rod 35 Ratchet wheel
9 Opening spring 50 Left hand control cam

5

P
P 12244-16 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 16 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

VD4: Equipment installed detector installed in the blower’s have been developed as a tailor-
impeller to monitor the airflow. made response to the technical
The following mechanical devices
data, thus creating a particularly
are installed in the mechanism The components for the blower
economical variant for the large
housing: cooling system, consisting of the
numbers of circuit-breakers
cooling fan and monitoring relay
1 push-button for closing required in distribution networks.
unit, are supplied loose.
1 push-button for opening
1 indicator for the switch position The required current transformer is Vacuum circuit-breakers
1 indicator for the charging con- not supplied with the circuit- for 36 kV
dition of the mechanism spring breaker, as it is as a rule sufficient
A wide variety of demands
1 operating cycle counter to add an additional core to one
are placed on circuit-breakers for
of the other current transformers
The available releases, auxiliary 36 kV.
which are required for other pur-
switches and charging motor
poses. Required core data on Vacuum circuit-breakers for 36 kV
which can be fitted to the operat-
request. are available for use in SF6-insu-
ing mechanism are listed in the
lated switchgears and as switch-
table on page 30. The wiring dia-
VD4: Large range of variants ing devices for special switchgear
gram for the release system is
types with air insulation.
shown on page 37. VD4..E – Vacuum circuit-breaker
for electrical power distribution Please contact us direct if you
Circuit-breakers with fan cooling require 36 kV circuit-breakers.
A special variant has been devel-
Certain circuit-breakers of type oped for service in electrical utility
Vacuum circuit breaker type
VD4 can be operated at higher networks:
VD4 on withdrawable module
rated currents when fitted with an
The vacuum circuit-breaker type
additional lateral-flow blower. The vacuum circuit-breaker of
VD4..E
type VD4 can also be supplied as
In such cases a lateral-flow blower
This type (see fig. 3) has the a withdrawable module with inter-
fitted with a special air channelling
extremely high reliability of the locks. Isolating contact arms can
system is located at a particular
basic VD4 version, but has a rated be fitted to the upper and lower
distance below the circuit-breaker,
current and rated short-circuit terminals without additional sup-
and directs an additional flow of
breaking current limited to the ser- port for installation on the with-
cold air at the breaker poles when
vice requirements in distribution drawable module.
a certain operating current level is
networks.
exceeded. The power supply to
the blower motor is provided by a Smaller interrupters and a simpli-
current transformer. There is a flow fied pole design with flat terminals

Fig. 3: Vacuum circuit-breaker, type VD4E, for 2 kV, Fig. 4: VD4 circuit-breaker on withdrawable module
630 A, pole side

6

P
P 12244-17 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 17.2.97 – Seite 17 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Special versions quently switching operating cur- VD4: Top quality


of the vacuum circuit-breaker rents, and occasionally short-cir-
The foundation stone for the high
cuit currents. A vacuum circuit-
The excellent properties of the quality of the VD4 vacuum circuit-
breaker developed for this pur-
vacuum interrupters facilitate the breakers was laid as early as the
pose handles up to 100,000 oper-
construction of special switchgear development phase, with type
ating cycles (Manufacturer of the
for particular applications. testing in the company’s own test
circuit-breaker with ABB Calor
laboratories. Drawing on the
Overhead traction lines in railways Emag interrupters: ABB Sécheron
results obtained, modern manu-
can be subjected to such high S.A., Geneva, Switzerland).
facturing methods and the best
loads in short-circuit conditions
On offshore platforms, very effici- possible materials are used to
that they melt out. To prevent this,
ent power generation facilities produce a high quality product. In
a circuit-breaker with an extremely
with low impedances have to be order to ensure that the quality of
short opening time is required. On
installed to cover the high energy the VD4 circuit-breakers meets the
the other hand, the breakers must
requirement of the drilling equip- specifications, all areas from
be capable of interrupting
ment and pump motors. Short line development through material
16 2/3 Hz currents up to 25 kA at
distances and large copper cross- purchasing to production are
15 kV. This is something special,
sections result in low ohmic resist- incorporated in an efficient
because this current has three
ances, which lead to extremely quality assurance system to
times the half-wave duration of
large time constants in short-cir- DIN EN ISO 900.
50 Hz current. The arcing times
cuit conditions. The consequence
thus become longer, and the stres-
is that the DC component of the
ses on the contacts considerably
short-circuit current decays very
greater. A vacuum circuit-breaker
slowly.
which has an opening time of
approx. 18 ms and can safely pro- ABB Calor Emag have vacuum
tect the traction lines has been circuit-breakers specially suited
successfully constructed. for these loads.
Electric locomotives are switched We will be pleased to provide you
off at almost every prolonged stop. with project-related information on
Locomotive circuit-breakers there- the special versions of our
fore have to be capable of fre- vacuum circuit-breakers.

Fig. 5: Final testing of a vacuum circuit-breaker of type VD4

7

P
P 12244-18 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 18 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Technical data

Rated voltage kV 12 Closing time ms approx. 60


Rated frequency Hz 50...60
Opening time ms „ 45
Rated lightning impulse kV 75
withstand voltage „ 15
.2/50 m s (peak value) Arcing time (50 Hz) ms
Rated power frequency kV 28 Total opening time ms „ 60
withstand voltage
50 Hz,  min. (effective value) Rated operating O-3min-CO-3min-CO
Rate of rise of transient kV/m s 0.34 sequence
recovery voltage
Peak of transient kV 20.6 Rated operating O-0.3s-CO-3min-CO
recovery voltage sequence with autoreclosing

Type Rated current Rated Short-circuit Rated Rated


short-circuit breaking short-circuit short-circuit
breaking current making duration
current asymm. ) current )
symm. )

A kA kA kA s
VD4 1206..16 630 16 17.4 40 3
..20 20 21.8 50 3
..25 25 27.3 63 3
..31 31.5 34.3 80 3
VD4 1212..16 1250 16 17.4 40 3
..20 20 21.8 50 3
..25 25 27.3 63 3
..31 31.5 34.3 80 3
..40 40 43.6 100 3
VD4 1212..50 1250 50 55.8 1253) 3
VD4 1216..25 1600 25 27.3 63 3
..31 31.5 34.3 85 3
..40 40 43.6 100 2) 3
..50 50 55.8 125 3 3
VD4 1220..25 2000 25 27.3 63 3
..31 31.5 34.3 85 3
..40 40 43.6 100 2) 3
..50 50 55.8 125 3) 3
VD4 1225..25 2500 25 27.3 63 3
..31 31.5 34.3 85 3
..40 40 43.6 100 2) 3
..50 50 55.8 125 3) 3
VD4 1231..25 3150 25 27.3 63 3
..31 31.5 34.3 85 3
..40 40 43.6 100 2) 3
..50 50 55.8 125 3) 3
VD4 1240..25 4000 4) 25 27,3 63 3
..31 31.5 34.3 85 3
..40 40 43.6 100 2) 3
..50 50 55.8 125 3) 3
1) When the operating voltage is less than the rated voltage, the same values as for rated voltage always apply. Higher values on request.
2) 25 kA possible
3) 35 kA possible
4 ) Breaker with forced ventilation

8

P
P 12244-19 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 9.1.97 Seite 19 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Technical data

Rated voltage kV 17.5 Closing time ms approx. 60


Rated frequency Hz 50...60
Opening time ms „ 45
Rated lightning impulse kV 95
withstand voltage „ 15
.2/50 m s (peak value) Arcing time (50 Hz) ms
Rated power frequency kV 38 Total opening time ms „ 60
withstand voltage
50 Hz,  min. (effective value) Rated operating O-3min-CO-3min-CO
Rate of rise of transient kV/m s 0.42 sequence
recovery voltage
Peak of transient kV 30 Rated operating O-0.3s-CO-3min-CO
recovery voltage sequence with autoreclosing

Type Rated current Rated Short-circuit Rated Rated


short-circuit breaking short-circuit short-circuit
breaking current making duration
current asymm. ) current )
symm. )

A kA kA kA s
VD4 1706..16 630 16 17.4 40 3
..20 20 21.8 50 3
..25 25 27.3 63 3
VD4 1712..16 1250 16 17.4 40 3
..20 20 21.8 50 3
..25 25 27.3 63 3
..31 31.5 34.3 80 3
..40 40 43.6 1002) 3
VD4 1716..20 1600 20 21.8 50 3
..25 25 27.3 63 3
..31 31.5 34.3 80 3
..40 40 43.6 100 2) 3
VD4 1720..20 2000 20 21.8 50 3
..25 25 27.3 63 3
..31 31.5 34.3 80 3
..40 40 43.6 100 2) 3
VD4 1725..20 2500 20 21.8 50 3
..25 25 27.3 63 3
..31 31.5 34.3 80 3
..40 40 43.6 100 2) 3
VD4 1731..20 3150 20 21.8 50 3
..25 25 27.3 63 3
..31 31.5 34.3 80 3
..40 40 43.6 100 2) 3
VD4 1740..20 4000 3) 20 21.8 50 3
..25 25 27.3 63 3
..31 31.5 34.3 80 3
..40 40 43.6 100 2) 3
) When the operating voltage is less than the rated voltage, the same values as for rated voltage always apply. Higher values on request.
2) 25 kA possible
3) Breaker with forced ventilation

9

P
P 12244-20 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 20 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Technical data

Rated voltage kV 24 Closing time ms approx. 60


Rated frequency Hz 50...60
Opening time ms „ 45
Rated lightning impulse kV 125
withstand voltage „ 15
.2/50 m s (peak value) Arcing time (50 Hz) ms
Rated power frequency kV 50 Total opening time ms „ 60
withstand voltage
50 Hz,  min. (effective value) Rated operating O-3min-CO-3min-CO
Rate of rise of transient kV/m s 0.47 sequence
recovery voltage
Peak of transient kV 41 Rated operating O-0.3s-CO-3min-CO
recovery voltage sequence with autoreclosing

Type Rated current Rated Short-circuit Rated Rated


short-circuit breaking short-circuit short-circuit
breaking current making duration
current asymm. ) current )
symm. )

A kA kA kA s
VD4 2406..16 630 16 17.4 40 3
..20 20 21.8 50 3
..25 25 27.3 63 3
VD4 2412..16 1250 16 17.4 40 3
..20 20 21.8 50 3
..25 25 27.3 63 3
VD4 2416..16 1600 16 17.4 40 3
..20 20 21.8 50 3
..25 25 27.3 63 3
VD4 2420..16 2000 16 17.4 40 3
..20 20 21.8 50 3
..25 25 27.3 63 3
VD4 2425..16 2500 16 17.4 40 3
..20 20 21.8 50 3
..25 25 27.3 63 3
) When the operating voltage is less than the rated voltage, the same values as for rated voltage always apply. Higher values on request.

20

P
P 12244-21 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 18.2.97 – Seite 21 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Technical data

See note on page 6


Rated voltage kV 36 Closing time ms approx. 50
Rated frequency Hz 50...60
Rated lightning impulse kV 70 Opening time ms approx. 60
withstand voltage „ 15
.2/50 m s (peak value) Arcing time (50 Hz) ms
Rated power frequency kV 70 Total opening time ms approx. 75
withstand voltage
50 Hz,  min. (effective value) Rated operating O-3min-CO-3min-CO
Rate of rise of transient kV/m s 0.57 sequence
recovery voltage
Peak of transient kV 62 Rated operating O-0.3s-CO-3min-CO
recovery voltage sequence with autoreclosing

Rated current Rated Short-circuit Rated Rated


short-circuit breaking short-circuit short-circuit
breaking current making duration
current asymm. ) current )
symm. )

A kA kA kA s
1250 25 27.3 63 3
31.5 34.3 80 3
1600 25 27.3 63 3
31.5 34.3 80 3
2000 25 27.3 63 3
31.5 34.3 80 3
) When the operating voltage is less than the rated voltage, the same values as for rated voltage always apply. Higher values on request.

2

P
P 12244-22 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 22 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Technical data

Type VD4..E
Rated voltage kV 12 Closing time ms approx. 60
Rated frequency Hz 50...60
Opening time ms „ 45
Rated lightning impulse kV 75
withstand voltage „ 15
.2/50 m s (peak value) Arcing time (50 Hz) ms
Rated power frequency kV 28 Total opening time ms „ 60
withstand voltage
50 Hz,  min. (effective value) Rated operating O-3min-CO-3min-CO
Rate of rise of transient kV/m s 0.34 sequence
recovery voltage
Peak of transient kV 20.6 Rated operating O-0.3s-CO-3min-CO
recovery voltage sequence with autoreclosing

Type Rated current Rated Short-circuit Rated Rated


short-circuit breaking short-circuit short-circuit
breaking current making duration
current asymm. ) current )
symm. )

A kA kA kA s
VD4 1206..16E 630 16 17.4 40 3
..20E 20 21.8 50 3
..25E 25 27.3 63 3
) When the operating voltage is less than the rated voltage, the same values as for rated voltage always apply. Higher values on request.

Type VD4..E
Rated voltage kV 17.5 Closing time ms approx. 60
Rated frequency Hz 50...60
Opening time ms „ 45
Rated lightning impulse kV 95
withstand voltage „ 15
.2/50 m s (peak value) Arcing time (50 Hz) ms
Rated power frequency kV 38 Total opening time ms „ 60
withstand voltage
50 Hz,  min. (effective value) Rated operating O-3min-CO-3min-CO
Rate of rise of transient kV/m s 0.42 sequence
recovery voltage
Peak of transient kV 30 Rated operating O-0.3s-CO-3min-CO
recovery voltage sequence with autoreclosing

Type Rated current Rated Short-circuit Rated Rated


short-circuit breaking short-circuit short-circuit
breaking current making duration
current asymm. ) current )
symm. )

A kA kA kA s
VD4 1706..16E 630 16 17.4 40 3
) When the operating voltage is less than the rated voltage, the same values as for rated voltage always apply. Higher values on request.

22

P
P 12244-23 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 9.1.97 – Seite 23 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Technical data

Type VD4..E
Rated voltage kV 24 Closing time ms approx. 60
Rated frequency Hz 50...60
Opening time ms „ 45
Rated lightning impulse kV 125
withstand voltage „ 15
.2/50 m s (peak value) Arcing time (50 Hz) ms
Rated power frequency kV 50 Total opening time ms „ 60
withstand voltage
50 Hz,  min. (effective value) Rated operating O-3min-CO-3min-CO
Rate of rise of transient kV/m s 0.47 sequence
recovery voltage
Peak of transient kV 41 Rated operating O-0.3s-CO-3min-CO
recovery voltage sequence with autoreclosing

Type Rated current Rated Short-circuit Rated Rated


short-circuit breaking short-circuit short-circuit
breaking current making duration
current asymm. ) current )
symm. )

A kA kA kA s
VD4 2406..16E 630 16 17.4 40 3
) When the operating voltage is less than the rated voltage, the same values as for rated voltage always apply. Higher values on request.

23

P
P 12244-24 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 24 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Ordering data and example

Key to type numbers

Symbol Meaning

st shunt

Rated breaking current (kA)


release OFF
Add-on equipment type

Rated current/00 (A)

Control voltage (V)


Design figure

rated voltage

Current type
Basic type
Sub-type

Code for

Version

V Vacuum circuit-breaker

with spring mechanism


D also suitable for autoreclosing

4 Column-type design

G with manual charging mechanism and basic releases


M with motor-operated and manual charging mechanisms and extended set of releases

12 12 kV
17 17.5 kV
24 24 kV

G DC
W AC, 50 Hz

Smallest pole centre distance


P for 12/7.5 kV, 150 mm (20 mm for high current breakers)
for 24 kV, 210 mm
A Non-standard version
E Circuit-breaker for service in electrical power distribution networks

Ordering example : (Basic vacuum circuit-breaker version)


Breaker version Type designation
Vacuum circuit-breaker V . . . . . . . . . . . . . .
with spring operating mechanism . D . . . . . . . . . . . . .
in column design . . 4 . . . . . . . . . . . .
with manual charging mechanism . . . G . . . . . . . . . . .
Rated voltage 2 kV . . . .  2 . . . . . . . . .
Rated current 250 A . . . . . .  2 . . . . . . .
with st shunt release OFF 0 V DC . . . . . . . . G   0 . . .
Pole centres 50 mm . . . . . . . . . . . . P . .
Rated short-circuit breaking current 25 kA . . . . . . . . . . . . . 2 5
Complete type designation V D 4 G  2  2 G   0 P 2 5
Quoting the complete type designation (in accordance with the above ordering example) provides a sufficient description of the basic circuit-
breaker.
In addition, for circuit-breakers with motor-operated charging mechanisms and extended sets of releases, the control voltage for the motor and that
for the closing release must be stated.
Any further shunt releases and auxiliary switches to be fitted (from the tables of accessories on pages 35) should be included in the order
text.
Ordering example 2: (Vacuum circuit-breaker with charging motor and accessories)
Breaker version Ordering details
Vacuum circuit-breaker Vacuum circuit-breaker
Basic version, see expample  Breaker type V D 4 M  2  2 G   0 P 2 5
with charging motor 0 V DC with charging motor 0 V DC
with st shunt relase OFF 0 V DC with basic set of releases,
with shunt release ON 0 V DC with st shunt releases OFF and
with blocking magnet 0 V DC shunt release ON 0 V, DC
with undervoltage release 00 V AC with undervoltage release 00 V AC
with additional auxiliary switch 3 NOC + 2 NCC with additional auxiliary switch 3 NOC + 2 NCC

24

P
P 12244-25 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 9.1.97 – Seite 25 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Ordering data
Type VD4 for 2 kV

Rated Rated Rated Type Pole Hand-operated breakers Motor-operated breakers Dimension Instruction
volt- current break- centres with standard set of releases with standard set of release drawing manual
age ing
current Order reference Weight Order reference Weight No. No.

kV A kA mm kg kg GCEM BA
2 630 16 VD4 150 VD4G1206..P16 67 VD4M1206..P16 69 370536 352
210 VD4G1206.. 16 72 VD4M1206.. 16 74
20 150 VD4G1206..P20 67 VD4M1206..P20 69
210 VD4G1206.. 20 72 VD4M1206.. 20 74
25 150 VD4G1206..P25 67 VD4M1206..P25 69
210 VD4G1206.. 25 72 VD4M1206.. 25 74
31.5 150 VD4G1206..P31 78 VD4M1206..P31 80
210 VD4G1206.. 31 83 VD4M1206.. 31 85
1250 16 150 VD4G1212..P16 68 VD4M1212..P16 70
210 VD4G1212.. 16 73 VD4M1212.. 16 75
20 150 VD4G1212..P20 68 VD4M1212..P20 70
210 VD4G1212.. 20 73 VD4M1212.. 20 75
25 150 VD4G1212..P25 68 VD4M1212..P25 70
210 VD4G1212.. 25 73 VD4M1212.. 25 75
31.5 150 VD4G1212..P31 79 VD4M1212..P31 81
210 VD4G1212.. 31 84 VD4M1212.. 31 86
40 210 VD4G1212..P40 92 VD4M1212..P40 94 700081 352
1250 50 210 VD4G1212..P50 145 VD4M1212..P50 147 370562 359
275 VD4G1212.. 50 153 VD4M1212.. 50 155
1600 25 210 VD4G1216..P25 145 VD4M1216..P25 147
275 VD4G1216.. 25 153 VD4M1216.. 25 155
31.5 210 VD4G1216..P31 145 VD4M1216..P31 147
275 VD4G1216.. 31 153 VD4M1216.. 31 155
40 210 VD4G1216..P40 145 VD4M1216..P40 147
275 VD4G1216.. 40 153 VD4M1216.. 40 155
50 210 VD4G1216..P50 145 VD4M1216..P50 147
275 VD4G1216.. 50 153 VD4M1216.. 50 155
2000 25 210 VD4G1220..P25 145 VD4M1220..P25 147
275 VD4G1220.. 25 153 VD4M1220.. 25 155
31.5 210 VD4G1220..P31 145 VD4M1220..P31 147
275 VD4G1220.. 31 153 VD4M1220.. 31 155
40 210 VD4G1220..P40 145 VD4M1220..P40 147
275 VD4G1220.. 40 153 VD4M1220.. 40 155
50 210 VD4G1220..P50 145 VD4M1220..P50 147
275 VD4G1220.. 50 153 VD4M1220.. 50 155
2500 25 275 VD4G1225.. 25 157 VD4M1225.. 25 159
31.5 275 VD4G1225.. 31 157 VD4M1225.. 31 159
40 275 VD4G1225.. 40 157 VD4M1225.. 40 159
50 275 VD4G1225.. 50 157 VD4M1225.. 50 159
3150 25 275 VD4G1231.. 25 258 VD4M1231.. 25 260 700116 359
31.5 275 VD4G1231.. 31 258 VD4M1231.. 31 260
40 275 VD4G1231.. 40 258 VD4M1231.. 40 260
50 275 VD4G1231.. 50 258 VD4M1231.. 50 260
4000 ) 25 275 VD4G1240.. 25 258 VD4M1240.. 25 260
31.5 275 VD4G1240.. 31 258 VD4M1240.. 31 260
40 275 VD4G1240.. 40 258 VD4M1240.. 40 260
50 275 VD4G1240.. 50 258 VD4M1240.. 50 260
) Breaker with forced ventilation

25

P
P 12244-26 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 17.2.97 – Seite 26 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Ordering data
Type VD4 for 7.5 kV

Rated Rated Rated Type Pole Hand-operated breakers Motor-operated breakers Dimension Instruction
volt- current break- centres with standard set of releases with standard set of release drawing manual
age ing
current Order reference Weight Order reference Weight No. No.

kV A kA mm kg kg GCEM BA
7,5 630 16 VD4 150 VD4G1706..P16 67 VD4M1706..P16 69 370536 352
210 VD4G1706.. 16 72 VD4M1706.. 16 74
20 150 VD4G1706..P20 67 VD4M1706..P20 69
210 VD4G1706.. 20 72 VD4M1706.. 20 74
25 150 VD4G1706..P25 78 VD4M1706..P25 80
210 VD4G1706.. 25 83 VD4M1706.. 25 85
1250 16 150 VD4G1712..P16 68 VD4M1712..P16 70
210 VD4G1712.. 16 73 VD4M1712.. 16 75
20 150 VD4G1712..P20 68 VD4M1712..P20 70
210 VD4G1712.. 20 73 VD4M1712.. 20 75
25 150 VD4G1712..P25 79 VD4M1712..P25 81
210 VD4G1712.. 25 84 VD4M1712.. 25 86
31.5 150 VD4G1712..P31 89 VD4M1712..P31 91
210 VD4G1712.. 31 92 VD4M1712.. 31 94
40 210 VD4G1712..P40 145 VD4M1712..P40 147 370562 359
275 VD4G1712.. 40 153 VD4M1712.. 40 155
1600 20 210 VD4G1716..P20 145 VD4M1716..P20 147
275 VD4G1716.. 20 153 VD4M1716.. 20 155
25 210 VD4G1716..P25 145 VD4M1716..P25 147
275 VD4G1716.. 25 183 VD4M1716.. 25 155
31.5 275 VD4G1716.. 31 153 VD4M1716.. 31 155
40 275 VD4G1716.. 40 153 VD4M1716.. 40 155
2000 20 210 VD4G1720..P20 145 VD4M1720..P20 147
275 VD4G1720.. 20 153 VD4M1720.. 20 155
25 210 VD4G1720..P25 145 VD4M1720..P25 147
275 VD4G1720.. 25 153 VD4M1720.. 25 155
31.5 275 VD4G1720.. 31 153 VD4M1720.. 31 155
40 275 VD4G1720.. 40 153 VD4M1720.. 40 155
2500 20 275 VD4G1725.. 20 150 VD4M1725.. 20 159
25 275 VD4G1725.. 25 157 VD4M1725.. 25 159
31.5 275 VD4G1725.. 31 157 VD4M1725.. 31 159
40 275 VD4G1725.. 40 157 VD4M1725.. 40 159
3150 20 275 VD4G1731.. 20 258 VD4M1731.. 20 260 700116 359
25 275 VD4G1731.. 25 258 VD4M1731.. 25 260
31.5 275 VD4G1731.. 31 258 VD4M1731.. 31 260
40 275 VD4G1731.. 40 258 VD4M1731.. 40 260
4000 ) 20 275 VD4G1740.. 20 258 VD4M1740.. 20 260
25 275 VD4G1740.. 25 258 VD4M1740.. 25 260
31.5 275 VD4G1740.. 31 258 VD4M1740.. 31 260
40 275 VD4G1740.. 40 258 VD4M1740.. 40 260
) Breaker with forced ventilation

26

P
P 12244-27 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 9.1.97 – Seite 27 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Ordering data
Type VD4 for 24 kV

Rated Rated Rated Type Pole Hand-operated breakers Motor-operated breakers Dimension Instruction
volt- current break- centres with standard set of releases with standard set of release drawing manual
age ing
current Order reference Weight Order reference Weight No. No.

kV A kA mm kg kg GCEM BA
24 630 16 VD4 210 VD4G2406..P16 74 VD4M2406..P16 76 370559 352
275 VD4G2406.. 16 79 VD4M2406.. 16 81
20 210 VD4G2406..P20 74 VD4M2406..P20 76
275 VD4G2406.. 20 79 VD4M2406.. 20 81
25 210 VD4G2406..P25 74 VD4M2406..P25 76
275 VD4G2406.. 25 79 VD4M2406.. 25 81
1250 16 210 VD4G2412..P16 76 VD4M2412..P16 78
275 VD4G2412.. 16 81 VD4M2412.. 16 83
20 210 VD4G2412..P20 76 VD4M2412..P20 78
275 VD4G2412.. 20 81 VD4M2412.. 20 83
25 210 VD4G2412..P25 80 VD4M2412..P25 82
275 VD4G2412.. 25 85 VD4M2412.. 25 87
1600 16 275 VD4G2416.. 16 165 VD4M2416.. 16 167 370563 359
20 275 VD4G2416.. 20 165 VD4M2416.. 20 167
25 275 VD4G2416.. 25 165 VD4M2416.. 25 167
2000 16 275 VD4G2420.. 16 165 VD4M2420.. 16 167
20 275 VD4G2420.. 20 165 VD4M2420.. 20 167
25 275 VD4G2420.. 25 165 VD4M2420.. 25 167
2500 16 275 VD4G2425.. 16 165 VD4M2425.. 16 167
20 275 VD4G2425.. 20 165 VD4M2425.. 20 167
25 275 VD4G2425.. 25 165 VD4M2425.. 25 167

27

P
P 12244-28 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 9.1.97 – Seite 28 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Ordering data
Type VD4..E for 2 kV

Rated Rated Rated Type Pole Hand-operated breakers Motor-operated breakers Dimension Instruction
volt- current break- centres with standard set of releases with standard set of release drawing manual
age ing
current Order reference Weight Order reference Weight No. No.

kV A kA mm kg kg GCEM BA
2 630 16 VD4..E 150 VD4G1206..P16E 64 VD4M1206..P16E 66 700098 377
210 VD4G1206.. 16E 69 VD4M1206.. 16E 71
20 150 VD4G1206..P20E 64 VD4M1206..P20E 66
210 VD4G1206.. 20E 69 VD4M1206.. 20E 71
25 150 VD4G1206..P25E 64 VD4M1206..P25E 66
210 VD4G1206.. 25E 69 VD4M1206.. 25E 71

Type VD4..E for 7.5 kV

Rated Rated Rated Type Pole Hand-operated breakers Motor-operated breakers Dimension Instruction
volt- current break- centres with standard set of releases with standard set of release drawing manual
age ing
current Order reference Weight Order reference Weight No. No.

kV A kA mm kg kg GCEM BA
7.5 630 16 VD4..E 210 VD4G1706.. 16E 69 VD4M1706.. 16E 71 700098 377

Type VD4..E for 24 kV

Rated Rated Rated Type Pole Hand-operated breakers Motor-operated breakers Dimension Instruction
volt- current break- centres with standard set of releases with standard set of release drawing manual
age ing
current Order reference Weight Order reference Weight No. No.

kV A kA mm kg kg GCEM BA
24 630 16 VD4..E 210 VD4G2406..P16E 71 VD4M2406..P16E 73 700099 377
275 VD4G2406.. 16E 76 VD4M2406.. 16E 78

28

P
P 12244-29 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 9.1.97 – Seite 29 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Technical data – Accessories

Operating mechanisms When the circuit-breaker is used ing command is active. The break-
for autoreclosing, recharging after er can only be closed again when
The basic version of the circuit- each closing operation is neces- the closing command has been
breakers is fitted with a manually sary, so as to make available the interrupted.
charged spiral spring operating required motive energy for the
mechanism. The charging times, recharging
OFF-ON-OFF switching cycle.
times, power consumption while
On circuit-breakers with charging The anti-pumping relay K0 (wiring the operating mechanism is in
motor, the spiral spring is charged diagram in Fig. 6, page 37) pre- operation and the type of motor
by the electric motor installed in vents repeated ON-OFF switching protection are listed in the table
the operating mechanism housing. operations when, for example, a below:
This automatically recharges the circuit-breaker is tripped by a pro-
spring as required after a closing tection relay in response to a pri-
operation without subsequent mary side fault and at the same
opening. time an electrical permanent clos-

Technical data of the charging motors

Rated voltage Power consumption Motor protection Charging time


(ABB Stotz mcb) (maximum)

V VA/W ) A s 2)
AC S28K
110 150 1.6 15
220 150 0.75 15
240 170 0.75 15

DC S282K
24 130 4.0 15
48 130 3.0 15
60 130 2.0 15
110 140 1.0 15
125 160 1.0 15
220 140 0.75 15
240 150 0.75 15
1) Approx. value
2) At rated voltage

29

P
P 12244-30 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 17.2.97 – Seite 30 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Releases Shunt release ON (Y3) circuit-breakers whose stored-


energy spring mechanisms are
Shunt release OFF (Y2/Y9) Apart from the OFF releases, a
charged by an electric motor.
closing release (shunt release
The shunt release OFF allows
ON) can also be installed in hand-
each vacuum circuit-breaker to be
operated circuit-breakers for
tripped by separately located pro-
closing. This closing release is
tection relays or by the remote
included in the basic version of
control system.

Technical data of OFF-/ON releases

Shunt release OFF Shunt release ON

Type VD4/VD4..E VD4/VD4..E


Current DC ) AC ) DC ) AC )
50...60 Hz 50...60 Hz

Rated voltage 24 V 110 V 24 V 100 V


48 V 220 V 48 V 110 V
60 V 240 V 2) 60 V 220 V
110 V 110 V 240 V 2)
125 V 2) 125 V 2)
220 V 220 V
240 V 2) 240 V 2)

Power consumption:
Latch open cc. 250/310 W cc. 250/310 VA cc. 250/310 W cc. 250/310 VA
Latch closed cc. 250/310 W cc. 250/310 VA cc. 250/310 W cc. 250/310 VA

Voltage range:
Trip 0.7.... x U N 0.85.... x U N
Close 0.85.... x U N 0.85.... x U N

Max. permissible
energized period 0 s 0 s 0 s 0 s
1) Other voltages on request
2) Power consumption 30 VA or 30 W

30

P
P 12244-31 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 31 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Undervoltage release (Y4) The time-delayed undervoltage If the current transformer used to
relay is supplied in an encap- supply the RN3U is fitted at the
The undervoltage releases are nor-
sulated version. It should be instal- outgoing side of the circuit-break-
mally supplied for undelayed
led separately from the circuit- er, the tripping coil must be
opening. They trip as soon as the
breaker and connected directly to provided with a supply voltage of
voltage falls below 35 to 70 per-
the voltage to be monitored. The 110 V DC from a battery to assist
cent of its rated level. Circuit-
supply voltage is 100/110 V, 50 Hz. in closing. In such cases a differ-
breakers with undervoltage re-
With other supply voltages, ent type of undervoltage release is
leases can only be switched on
a matching transformer must be required. The time-delayed under-
again when the voltage has
connected in series. The time- voltage relay RN3U (version with
increased to above 85 % of its
delayed undervoltage relay is closing assistance) can be set
rated value.
excited when the voltage falls with the integral coding switch to a
If opening of the circuit-breaker below 70 percent of its rated level. time lag of 0.5 to 2 s in steps of
during short-term drops in voltage The relay can be set with the inte- 0.5 s.
is to be prevented, the undervolt- gral coding switch to a time lag of
(See page 35 and wiring diagram
age release can be connected to 0.5 – 4 s, in steps of 0.5 s.
on page 39.)
a time-delayed undervoltage relay
At the end of the set time, the time-
(RN3U).
delayed undervoltage relay acts
on the undervoltage release instal-
led in the operating mechanism
and trips the circuit-breaker.

Technical data of undervoltage releases

Type VD4/VD4..E
Current DC ) AC
50...60 Hz

Rated voltage 24 V 100 V


48 V 110 V
60 V 220 V )
110 V 240 V )
125 V
220 V
240 V
Power consumption: instantaneous 10 W 11 VA
delayed – 10 VA
Voltage range ...1.1 x U N ...1.1 x U N
Voltage to permit closing: instantaneous > 0.85 x UN > 0.85 x UN
delayed > 0.7 x UN > 0.7 x UN
Tripping voltage: instantaneous 0.35...0.7 x UN 0.35...0.7 x UN
delayed < 0.7 x UN < 0.7 x UN
Response time: instantaneous immediate
delayed Standard version:
Range of 0.5...4 s can be set in steps of 0.5 s on
the opening delay device.
Version with closing assistance:
Range of 0.5...2 s can be set in steps of 0.5 s on
the opening delay device.
Max. permissible energized period unlimited
1) Not for RN3U

3

P
P 12244-32 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 32 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Current transformer release (Y7) The winding of the current transfor- In exceptional cases where the
mer release is designed in such a user has already fitted specially
In switchgear which have no
way that tripping can occur at a adapted intermediate current
secure auxiliary voltage supply for
current as low as 0.7 · IN. transformers, the current transfor-
the releases, provision can be
When determining the capacity of mer release can also be supplied
made for the use of current trans-
the main current transformer, the without intermediate CTs. Here, a
former releases. These obtain their
consumption of any additional bridge-connected rectifier must be
tripping current from the second-
overcurrent relays should be installed in series before the
ary windings of main current trans-
taken into account. The coil of the release coil.
formers via an intermediate cur-
current transformer release and
rent transformer which is mounted There are different versions avail-
the intermediate current transform-
separately. In normal operation, able for tripping readiness at  and
er are designed to complement
the windings of the current trans- 0.3 A. A further type is available for
each other, so as to guarantee
former release are shorted by aux- use with inverse-time overcurrent
secure tripping in all cases.
iliary switches in the protection relay with current transformer trip-
relay. The auxiliary switches are (See table on page 35 and circuit ping of type WI  – 3 (Manufacturer
only opened when the relay res- diagram on page 38.) SEG).
ponds, so that the current flows
(See table on page 35.)
through the windings of the cur-
rent transformer release. The latch
of the release is thus closed and
the breaker tripped.

Technical data of indirect overcurrent releases

Type VD4/VD4..E
Power consumption in continuous operation
(aux. current transformer shorted):
2-phase connection 3.5 VA
3-phase connection 2 VA
Power consumption on tripping:
2-phase connection 15 VA
3-phase connection 15 VA
Tripping readiness at: 0.7 x I N
Power consumption of the aux. current transformer ) Winding A 1 VA
at I N = 5 A Winding B 1 VA
and continuous operation (secondary winding shorted) Winding C 1.5 VA
Power consumption of the aux. current transformer ) Winding A 15 VA
at IN = 5 A Winding B 15 VA
and continuous operation, secondary winding open (may be operated open) Winding C 25 VA
Primary current of the aux. current transformer 3x5A
Secondary current of the aux. current transformer approx. 0.4 A
1) See wiring diagram on page 38

32

P
P 12244-33 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 9.1.97 – Seite 33 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Blocking magnet (Y1) magnet can be installed in the for 100 ms before a closing com-
spring mechanism to prevent the mand can be executed.
For electrical interlocking of the
circuit-breaker from being closed
vacuum circuit-breaker with dis-
when off circuit. The blocking
connectors, doors etc., a blocking
magnet must always be energized
Technical data of blocking magnets

Type VD4/VD4..E
Current DC AC 50...60 Hz

Rated voltage 24 V 110 V


48 V 220 V
60 V 240 V
110 V
125 V
220 V
240 V
Power consumption: Latch open 10 W 10 VA
Latch closed 10 W 10 VA
Voltage range 0.85.... x UN 0.85.... x UN
Max. closing period unlimited unlimited

Auxiliary switches
The vacuum circuit-breakers switches for control, interlock as shown in the table on
can be fitted with auxiliary and annunciation functions page 34.
Technical data of the 5-pole auxiliary switch

Rated voltage 24 V...220 V AC/DC


Test voltage 2.5 kV
Operating current I th2 = 0 A
Volume resistance 3 mΩ
Permissible limit temperatures of the materials used – 20 hC . . . + 20 hC
Contact overtemperature at rated load approx. 20 K
Rated operating
Rated current and switching capacity to use category AC- and DC- at Rated current A current A

220 V AC, cos f = 0.7 2.5 25

24 V DC, time constant 1 ms 10 12


15 ms 10 12
50 ms 8 10
200 ms 6 7.7
60 V DC, time constant 1 ms 8 10
15 ms 6 8
50 ms 5 6
200 ms 4 5.4
110 V DC, time constant 1 ms 6 8
15 ms 4 5
50 ms 2 4.6
200 ms 1 2.2
220 V DC, time constant 1 ms 1.5 2.0
15 ms 1.0 2.0
50 ms 0.75 1.7
200 ms 0.5 1.0

33

P
P 12244-34 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 9.1.97 – Seite 34 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Available releases and auxiliary switches

Description Remarks

Y2 1st shunt release x


Y9 2nd shunt release 1
Y3 Shunt release ON X, 2
Y1 Blocking magnet 1
Y4 Undervoltage release 3
Y4 Undervoltage release, delayed 3
Y7 Current transformer release with intermediate current transformer 3
S1 5-pole auxiliary switch X
S2 Auxiliary switch on blocking magnet Y
S3 5-pole auxiliary switch X
S4 5-pole auxiliary switch x
S5 5-pole auxiliary switch 4
S7 Auxiliary switch for fault annunciation x
M1 Charging motor including anti-pumping relay K0 X

Remarks
x = Basic circuit-breaker version for manual charging mechanism
X = Addition for basic circuit-breaker version with motor-operated charging mechanism
1 = 5-pole auxiliary switch S3 required.
(Auxiliary switch S3 is included in the supply of releases Y and Y9)
2 = 5-pole auxiliary switches S and S3 required.
(Auxiliary switches S and S3 are included in the supply of release Y3)
3 = max.  x Y4 and  x Y7 possible
4 = Possible additional equipment

34

P
P 12244-35 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 17.2.97 – Seite 35 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Ordering data – Accessories

Type VD4/VD4..E
Description Order ref.

Shunt release ON (Y3) AC/DC GCE7179611R0102 )


with K0-relay, auxiliary switches (S) and (S3)
Blocking Magnet (Y) 5) GCE7179611R0103 )
with auxiliary switch (S2)
1st shunt release OFF (Y2) AC/DC GCE7179611R0101 )
with auxiliary switches (S4) and (S7)
2nd shunt release OFF (Y9) 5) AC/DC GCE7179611R0106 )
Undervoltage release (Y4) AC/DC GCE7179611R0104 3)
Undervoltage release (Y4) GCE7179611R0111 3)
for time-delayed undervoltage relay (0.5 . . . 4 s)
Undervoltage release (Y4) GCE7179611R0112
for time-delayed undervoltage relay –
version with closing assistance (0.5 . . . 2 s)
Time-delayed release undervoltage relay RN3U GCE9010379R0101
adjustable 0.5...4 s
Supply voltage 00/0 V, 50 Hz
Note: Version with closing assistance adjustable 0.5 . . . 2 s
Auxiliary transformer 220 V/0 V GCE0912021P0100
Current transformer release (Y7) GCE7179611R0108 3)
with
intermediate current transformer (prim. 5 A) to be installed separately GCE9476148R0100
Current transformer release (Y7) GCE7179611R0109 3)
without intermediate current transformer tripping at 0 V/0.3 A4)
Current transformer release (Y7) GCE7179611R0110
without intermediate current transformer tripping bei .0 A4)
Current transformer release (Y7) GCE7179611R0109
for use with inverse-time overcurrent relay with current
transformer tripping, type WI  – 3 (manufacturer SEG) 4)
Auxiliary switch (S3) GCE7002397R0122
Auxiliary switch (S5) GCE7179611R0107 2)
Chassis
p = 150 GCE9371153R0117
p = 210 GCE9371153R0118
p = 275 GCE9371153R0119
p = 210 (high current) GCE9371153R0121
p = 275 (high current) GCE9371153R0122
Insulating cover for upper pole tube GCE9371447P0101
Hand lever for charging GCE9477394R0101
1) When ordering, add the code letter for the type of current (W for AC and G for DC) and the coil voltage, to the order ref..
The standard voltages are 100, 110, 220, 240 V AC, 50 + 60 Hz, and 24, 48, 60, 110 and 220, 240 V DC. Other voltages on request.
2) State the contact types.
3 ) Fitting of one current transformer release and one undervoltage release is possible.
4 ) Rectifier order ref. GCE9476838P0100 is required. (Included with the current transformer release.)
5 ) Auxiliary switch S3 required for manual charging mechanism.

35

P
P 12244-36 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 20.1.97 – Seite 36 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Ordering data – Spare parts

Breaker poles – Types VD4/VD4..E

Description Type Rated voltage Rated current Rated breaking Order ref.
current

Breaker pole, VD4 12 kV 630 A 16...25 kA GCE7003312R0105


complete 31.5 kA GCE7003312R0131
1250 A 16...25 kA GCE7003312R0125
31.5 kA GCE7003312R0131
40 kA GCE7003312R0115
50 kA GCE7179616R0127
1600 A 25...31.5 kA GCE7179616R0101
40 kA GCE7179616R0106
50 kA GCE7179616R0111
2000 A 25...31.5 kA GCE7179616R0101
40 kA GCE7179616R0106
50 kA GCE7179616R0111
2500 A 25...31 5 kA GCE7179616R0101
40 kA GCE7179616R0106
50 kA GCE7179616R0111
3150 A 25...50 kA GCE7179616R0126

VD4..E 12 kV 630 A 16...25 kA GCE7001850R0105

VD4 17.5 kV 630 A 16...20 kA GCE7003312R0105


25 kA GCE7003312R0131
1250 A 16...25 kA GCE7003312R0131
31.5 kA GCE7003312R0101
40 kA GCE7179616R0127
1600 A 20 / 25 kA GCE7179616R0101
31.5 kA GCE7179616R0106
40 kA GCE7179616R0111
2000 A 20 / 25 kA GCE7179616R0101
31.5 kA GCE7179616R0106
40 kA GCE7179616R0111
2500 A 20 / 25 kA GCE7179616R0101
31.5 kA GCE7179616R0106
40 kA GCE7179616R0111
3150 A 20...40 kA GCE7179616R0126

VD4..E 17.5 kV 630 A 16 kA GCE7001850R0106

VD4 24 kV 630 A 16...25 kA GCE7003324R0104


1250 A 16...25 kA GCE7003324R0106
1600 A 16...25 kA GCE7179617R0101
2000 A 16...25 kA GCE7179617R0101
2500 A 16...25 kA GCE7179617R0101

VD4..E 24 kV 630 A 16 kA GCE7001860R0101

Charging motor – Types VD4/VD4..E


Description Type Operating voltage Order ref.

Charging motor VD4/VD4..E DC 24 V GCE0940084P0101


(with gearbox) DC 48 V GCE0940084P0103
DC 60 V GCE0940084P0104
DC/AC 110 V GCE0940084P0105
DC/AC 220/240 V GCE0940084P0106

36

P
P 12244-37 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 20.1.97 – Seite 37 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Wiring diagrams

Type VD4/VD4..E ), 2)

M – M0

Ù
OFF
ON

Standard arrangement

Type 2

Special arrengement for -S5

Type 9 Type 20 Type 22 Type 23 Type 24

-S1 Auxiliary switch on operating mechanism -Y1 Blocking magnet -V1 Series rectifier for -Y1
-S2 Auxiliary switch on blocking magnet -Y2 Shunt release OFF -V2 Series rectifier for -Y2
-S3 Auxiliary switch on breaker shaft -Y3 Shunt release ON -V3 Series rectifier for -Y3
-S4 Auxiliary switch on breaker shaft -Y4 Undervoltage release und -K0
-S5 Auxiliary switch on breaker shaft -Y7 Current transformer release -V4 Series rectifier for -Y4
-S7 Auxiliary switch for fault annunciation -Y9 2nd shunt release OFF -V7 Series rectifier for -Y7
(fleeting contact, time ‰30 ms) -V9 Series rectifier for -Y9
1)
-M0 Charging motor for stored-energy
Shown with the stored-energy spring mechanism in the discharged condition.
2) When this equipment is ordered, the actual scope of supply is documented in the order documents. spring mechanism
3 ) External operation
-K0 Anti-pumping relay
4 ) Only when Y1 is not fitted
5 ) V 7 is fitted only for current transformer without intermediate current transformer -R0 Series resistor

The connections to auxiliary switches S, S2, S3, S4 and S5, and to series
rectifiers V, V2, V3, V9 are designed for 4.8 x 0.8 receptacles in acc. with DIN 46 247 Part 2.
Series rectifiers V4 and V7 have screw terminals.
Auxiliary switch S7 has plug-in terminals whose mating contacts are supplied.

Fig. 6: Wiring diagram no. GCES700005


Equipment for 24, 48, 60, 0, 25, 220, 240 V DC; 0, 220, 240 V AC

37

P
P 12244-38 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 9.1.97 – Seite 38 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Current transformer release (standard version)

Fig. 7: Wiring diagram no. GCES371959


Three-phase tripping with three single-pole protection relays

38

P
P 12244-39 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 17.2.97 – Seite 39 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Supply voltage Terminals tv(s) 0.5  .5 2 2.5 3 3.5 4


100 V, AC 1–2 S 1 x x x x x x x x
110 V, AC 1–3
2 x x x x x x x x
3 x x x x x x x x
4 x x x x x x x x
ON OFF Time setting

Fig. 8: Time-delayed undervoltage relay, type RN3U (0.5 . . . 4 s)

Fig. 9: Time-delayed undervoltage relay, type RN3U, version with closing assistance (0.5 . . . 2 s)

39

P
P 12244-40 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 9.1.97 – Seite 40 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Dimension drawings

Type VD4

K = Cable entry
Rated Rated Rated T = Bore for handling, both sides
voltage current breaking D = Lid: add-on item
current A = View “A”
GA = Tested zone
kV A kA p a a c f M = Minimum distance, corresponding to dimension a to
12/17.5 630/ ...25 150 450 395 400 300 DIN VDE 00
1250 210 570 515 520 390 A1 = Connection terminal for 630 A
12 630/ 31.5 150 450 395 400 300 A2 = Connection terminal for 250 A
1250 210 570 515 520 390 A4 = Connection terminal bar to DIN 46433
X = PE conductor connection – use a contact washer

Fig. 20: Dimensional drawing no. GCEM370536


x 2/7.5 kV, 630 A and 250 A, ... 25 kA
x 2 kV, 630 A and 250 A, 3.5 kA

40

P
P 12244-41 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 10.1.97 – Seite 41 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Type VD4

K =
Cable entry
Rated Rated Rated T =
Bore for handling, both sides
voltage current breaking D =
Lid: add-on item
current A =
View “A”
GA =
Tested zone
kV A kA p a a c f M =
Minimum distance, corresponding to dimension a to
17.5 1250 31.5 150 450 395 400 300 DIN VDE 00
210 570 515 520 390 A4 = Connection terminal bar to DIN 46433
12 1250 40 210 570 515 520 390 X = PE conductor connection – use a contact washer

Fig. 2: Dimensional drawing no. GCEM70008


x 2 kV, 250 A, 40 kA
x 7.5 kV, 250 A, 3.5 kA

4

P
P 12244-42 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 14.1.97 – Seite 42 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Type VD4

K = Cable entry
Rated Rated Rated M = Minimum distance, corresponding
voltage current breaking to dimension a to DIN VDE 00
current T = Lifting hole, both sides
X = PE conductor connection – use a
kV A kA p a a c d e f g h i k contact washer
2 1250 50 210 610 555 560 600 20 415 64 45 320 616
Note:
275 750 695 700 750 25 545 39 20 345 746
Lifting lug T only fitted for transport,
1600/ ...50 210 610 555 560 600 20 415 64 45 320 616 remove prior to commissioning and
2000 275 750 695 700 750 25 545 39 20 345 746 store.
2500 ...50 275 750 695 700 750 25 545 39 20 345 746
7.5 1250 40 210 610 555 560 600 20 415 64 45 320 616
275 750 695 700 750 25 545 39 20 345 746
1600/ ...40 210 610 555 560 600 20 415 64 45 320 616
2000 275 750 695 700 750 25 545 39 20 345 746
2500/ ...40 275 750 695 700 750 25 545 39 20 345 746

Fig. 22: Dimensional drawing no. GCEM370562


x 2 kV, 250 ... 2500 A, ... 50 kA
x 7.5 kV, 250 ... 2500 A, 40 kA

42

P
P 12244-43 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 10.1.97 – Seite 43 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Type VD4

Note: K = Cable entry


Lifting lug T only fitted for transport, M = Minimum distance, corresponding
remove prior to commissioning and to dimension a to DIN VDE 00
store. T = Bore for handling, both sides
X = PE conductor connection – use a
contact washer

Fig. 23: Dimensional drawing no. GCEM7006


x 2 kV, 350 A, ... 50 kA
x 7.5 kV, 350 A, 40 kA

43

P
P 12244-44 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 10.1.97 – Seite 44 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Type VD4

K = Cable entry
Rated Rated Rated T = Bore for handling, both sides
voltage current breaking D = Lid: add-on item
current A = View “A”
GA = Tested zone
kV A kA p a a c f g M = Minimum distance, corresponding to dimension a to
24 630/ ...25 210 570 515 520 390 580 DIN VDE 00
1250 275 700 645 650 488 710 A1 = Connection terminal for 630 A
A2 = Connection terminal for 250 A and 630/250 at 25 kA
A4 = Connection terminal bar to DIN 46433
X = PE conductor connection – use a contact washer

Fig. 24: Dimensional drawing no. GCEM700559


24 kV, 630 A und 250 A, ... 25 kA

44

P
P 12244-45 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 10.1.97 – Seite 45 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Type VD4

K = Cable entry
M = Minimum distance, corresponding to dimension a to DIN VDE 00
T = Bore for handling, both sides
X = PE conductor connection – use a contact washer
Note:
Lifting lug T only fitted for transport, remove prior to commissioning and store.

Fig. 25: Dimensional drawing no. GCEM370563


24 kV, 1600 A and 2500 A, ... 25 kA

45

P
P 12244-46 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 13.1.97 – Seite 46 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Type VD4..E

K =
Cable entry
Rated Rated Rated T =
Bore for handling, both sides
voltage current break- D =
Lid: add-on item
ing A =
View “A”
current GA =
Tested zone
kV A kA p a a c f M =
Minimum distance, corresponding to dimension a to
12 630 ...25 150 450 395 400 300 DIN VDE 00
210 570 515 520 390 A4 = Connection terminal bar to DIN 46433
17.5 630 16 210 570 515 520 390 X = PE conductor connection – use a contact washer

Fig. 26: Dimensional drawing to GCEM700098


2 kV, 630 A, ... 25 kA
7.5 kV, 630 A, 6 kA

46

P
P 12244-47 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 10.1.97 – Seite 47 Black Magenta Yellow

Vacuum circuit-breakers type VD4 A

Type VD4..E

K =
Cable entry
Rated Rated Rated T =
Bore for handling, both sides
voltage current break- D =
Lid: add-on item
ing A =
View “A”
current GA =
Tested zone
kV A kA p a a c f M =
Minimum distance, corresponding to dimension a to
24 630 16 210 570 515 520 390 DIN VDE 00
275 700 645 650 488 A4 = Connection terminal bar to DIN 46433
X = PE conductor connection – use a contact washer

Fig. 27: Dimensional drawing no. GCEM700099


24 kV, 630 A, 6 kA

47

P
P 12244-48 – Calor Emag – Schaltgeräte Handbuch, englisch – os – 17.2.97 – Seite 48 Black Magenta Yellow

A Vacuum circuit-breakers type VD4

Time delayed undervoltage relay, type RN3U

Fig. 28: Dimensional drawing no. GCEM 900001P0101


Time delayed undervoltage relay, type RN3U

Intermediate instrument transformer

Fig. 29: Dimensional drawing no. GCEM371959


Intermediate instrument transformer for transformer current tripping

48

P
We reserve the right to make changes in the course of technical development.
Leaflet no. DECMS 2067 96 E Printed in Germany (11.99-500-PPI)

ABB Calor Emag Mittelspannung GmbH ABB Sace T.M.S. S.p.A


Oberhausener Strasse 33 Petzower Strasse 8 Via Friuli, 4
D-40472 Ratingen D-14542 Glindow I-24044 Dalmine
Phone: +49(0)21 02/12-12 30, Fax: +49(0)21 02/12-19 16 Phone: +39 035/395111, Fax: +39 035/395874
E-mail: calor.info@de.abb.com E-mail: sacetms.tipm@it.abb.com
Internet: http://www.abb.de/calor Internet: http://www.abb.com

You might also like