(EN1990:2002)
Safety of people,
Safety of the structure
Protection of the contents
Design situations
(EN1990,cl.3.2(2)P)
EQU: Loss of equilibrium of the structure, (considering for sliding, overturning or uplift)
STR: Internal failure or excessive deformation of the structure of structural member (Design of structural for
strength of members and frames),
GEO: Failure due to excessive deformation of the ground (Design of structural members such as footing,
piles, basement walls, etc.),
Important notes
(EN1990,cl.3.2(2)P)
Favourable Unfavourable
Action
γ γ
6.10 Ed=ΣγG Gk +γQ Qk1 + γQ ψ0,2 Qk2 Permanent (dead,
0.9 1.1
earth), γG
Variable (imposed,
0 1.5
wind), γQ
Note: Single source is not applicable for EQU design situation. Different γ factors can be used in favourable and unfavourable
areas.
Persistent and transient design situation – STR/GEO Equation 6.10, 6.10a & 6.10b (Set B)
Favourable Unfavourable
Action
γ γ
6.10 Ed=ΣγG Gk +γQ Qk1 + γQ ψ0,2 Qk2 Permanent (dead,
1.0 1.0
earth), γG
Variable (imposed,
0 1.3
wind), γQ
Note: Single source is applicable for STR/GEO design situation.
Combination (sensitivity) factor, ψ
(CYS NA EN1990:2002, Table A1.1)
ψο ψ1 ψ2
Category Specific Use
A Domestic and residential 0.7 0.5 0.3
B Office 0.7 0.5 0.3
C Areas for Congregation 0.7 0.7 0.6
D Shopping 0.7 0.7 0.6
E Storage 1.0 0.9 0.8
F Traffic < 30 kN vehicle 0.7 0.7 0.6
G Traffic < 160 kN vehicle 0.7 0.5 0.3
H Roofs 0.7 0 0
Snow, altitude < 1000 m 0.5 0.2 0
Wind 0.5 0.2 0
Summary table of partial, combination and reduction factors for the STR and GEO ultimate limit states for
buildings
2.The combination value ψ0Qk (of an action is intended to take account of the
reduced probability of the simultaneous of two or more variable actions).
3. Frequent value ψ1Qk (exceeded only for a short period of time and is used
primary for the SLS and also the accidental ULS).
Characteristic combination
Equation 6.14b
Ed=Gk +Qk,1 + ψ0 Qk,2
Frequent combination
Equation 6.15b
Ed=Gk + ψ1Qk,1 + ψ2 Qk,2
Quasi-permanent combination
Equation 6.16b
Ed=Gk + ψ2Qk,1
Imposed Loads
Category of use
(EN1991-1-1:2002,Table 6.1)
Imposed loads
(EN 1991-1-1:2002, Table 6.2)
Category A
-Floors 1.5-2.0 2.0-3.0
-Stairs 2.0-4.0 2.0-4.0
-Balconies 2.5-4.0 2.0-3.0
Category C
-C1 2.0-3.0 3.0-4.0
-C2 3.0-4.0 2.5-7.0
-C3 3.0-5.0 4.0-7.0
-C4 4.5-5.0 3.5-7.0
-C5 5.0-7.5 3.5-4.5
Category D
-D1 4.0-5.0 3.5-7.0
-D2 4.0-5.0
Imposed load on Roof 3.5-7.0
(CYS NA EN1991-1-1, Table 6.10)
Imposed load,
Sub-category Actions qk
Q (kN)
(kN/m2)
Roof (inaccessible except for
H 0.4 1.0
normal maintenance and repair)
Permanent Loads
Permanent load
(EN 1991-1-1:2002, Table A.1-A.12)
Typical unit floor Typical loadings Typical unit floor Typical loadings
Season factor
(CYS EN1991-1-4,NA 2.4)
cseason=1.0
Directional factor
(CYSEN1991-1-4,NA 2.4)
cdir=1.0
(Conservative value for all direction)
Determination of cscd
Builiding with less than Natural frequency Walls≤100m high Chimney with circular
h≤15m f≤5Hz cross-sectional area and,
h≤60m
h≤6.5·diameter
cscd =1.0
Can be found
TERRAIN OROGRAPHY,
(EN1991-1-4, cl.4.3.3)
Consider Ignore
COUNTRY
Area with low vegetation such as
grass and isolated obstacles trees,
II 0.05 2
buildings) with separations of at least
20 obstacle height.
Area with regular cover of vegetation
or buildings or woth isolatd obstacles
III with seperations of maximum 20 0.3 5
obstacle height (such as villages,
suburban terrain, permanent forest). TOWN
Area in which at least 15% of the
IV* surface is covered with building and 1.0 10
their average height exceeds 15m.
*
For buildings in terrain category IV, displacement height hdis should be consider and information can be found in Aneex A.5 of EN1991-1-4:2005
vm(z)=cr(z).co(z).vb
Air density:ρ=1.25kg/m3
EXTERNAL WIND PRESSURE/FORCE ON WALLS
Reference height ze, depending on h and b, and corresponding velocity pressure profile
(EN1991-1-4, Fig. 7.4)
Values of external pressure coefficient for vertical walls of rectangular plan buildings
(EN1991-1-4, Tab.:4.1)
ZONE A B C D E
h/d cpe,10 cpe,1 cpe,10 cpe,1 cpe,10 cpe,1 cpe,10 cpe,1 cpe,10 cpe,1
5 -1.2 -1.4 -0.8 -1.1 -0.5 +0.8 +1.0 -0.7
1 -1.2 -1.4 -0.8 -1.1 -0.5 +0.8 +1.0 -0.5
≤0.25 -1.2 -1.4 -0.8 -1.1 -0.5 +0.7 +1.0 -0.3
Note: Values for cpe,1 are intended for the design of small elements and fixings with an element of 1m 2 or
less such as cladding elements and roofing elements. Values for cpe,10 may be used for the design of the
overall load bearing structure of buildings. The external pressure coeffiecient cpe,1 and cpe,10 is using for
loadaded area of 1m2 and 10m2 respectively.
Key for vertical walls –Mono&dual pitch Key for vertical walls – Flat Roof
Roof (EN1991-1-4, Fig.7.5)
(EN1991-1-4, Fig.7.5)
Zone
Roof type F G H I
cpe,10 cpe,1 cpe,10 cpe,1 cpe,10 cpe,1 cpe,10 cpe,1
Sharp eaves -1.8 -2.5 -1.2 -2.0 -.07 -1.2 +0.2
hp/h=0.025 -1.6 -2.2 -1.1 -1.8 -0.7 -1.2 -0.2
With
hp/h=0.05 -1.4 -2.0 -0.9 -1.6 -0.7 -1.2 +0.2
Parapets
hp/h=0.10 -1.2 -1.8 -0.8 -1.4 -0.7 -1.2 -0.2
r/h=0.05 -1.0 -1.5 -1.2 -1.8 -0.4 +0.2
Curved
r/h=0.10 -0.7 -1.2 -0.8 -1.4 -0.3 -0.2
Eaves
r/h=0.20 -0.5 -0.8 -0.5 -0.8 -0.3 +0.2
a=30o -1.0 -1.5 -1.0 -1.5 -0.3 -0.2
Mansard
a=45o -1.2 -1.8 -1.3 -1.9 -0.4 +0.2
Eaves
a=60o -1.3 -1.9 -1.3 -1.9 -0.5 -0.2
Note: Values for cpe,1 are intended for the design of small elements and fixings with an element of 1m2 or
less such as cladding elements and roofing elements. Values for cpe,10 may be used for the design of the
overall load bearing structure of buildings. The external pressure coeffiecient cpe,1 and cpe,10 is using for
loadaded area of 1m2 and 10m2 respectively.
Pitch Zone for wind direction θ=0o Zone for wind direction θ=180o
Angle F G H F G H
a cpe,10 cpe,1 cpe,10 cpe,10 cpe,1 cpe,10 cpe,10 cpe,1 cpe,10 cpe,1 cpe,10 cpe,1
5o -1.7 -2.5 -1.2 -2.0 -0.6 -1.2 -2.3
-2.5 -1.3 -2.0 -0.8 -1.2
+0.0 +0.0 +0.0
15o -0.9 -2.0 -0.8 -1.5 -0.3
-2.5 -2.8 -1.3 -2.0 -0/9 -1.2
+0.2 +0.2 +0.2
30o -0.5 -1.5 -0.5 -1.5 -0.2
-1.1 -2.3 -0.8 -1.5 -0.8
+0.7 +0.7 +0.4
45o -0.0 -0.0 -0.0
-0.6 -1.3 -0.5 -0.7
+0.7 +0.7 +0.6
60o +0.7 +0.7 +0.7 -0.5 -1.0 -0.5 -0.5
75o +0.8 +0.8 +0.8 -0.5 -1.0 -0.5 -0.5