Low-Voltage Fuses

MINIZED
5SG7 N-type MINIZED fuse switch-disconnectors

■ Technical data
N-type MINIZED D01 draw-out assembly
Valid standards DIN VDE 0638/09.81, EN 60 947-3/12.92
Dimensions DIN 43 880
Main switch characteristic DIN VDE 0113
Dielectric characteristic DIN VDE 0110
Number of poles 1-pole, 2-pole, 3-pole, 1-pole + N, 3-pole + N
Rated voltage V 230/400 AC (also suitable for networks of 240/415 AC )
48 DC 1-pole, 110 DC 2-pole
Rated breaking capacity kA 50
Rated insulation voltage V 400 AC
(acc. to EN)
Rated impulse withstand voltage V 2,500 AC
(acc. to EN)
Utilization category acc. to DIN VDE 0638 A AC-22 (16), AC-23 (10), DC-22 (16)
Utilization category acc. to DIN EN 60 947-3 A AC-22b (16), AC-23b (10), DC-22b (16)
Mounting position vertical
Ambient temperature °C -5 to +40, humidity 90 % at 20
Degree of protection IP 00 acc. to DIN 40 050
IP 20 after installation in a distribution board with front cover
Terminals connection terminal up to 16 mm2 (stranded) with +/- screws
(Pozidriv Z1), safe to touch on both sides
Sealing ensured when switched on
N-type MINIZED D02 screw connection,
MINIZED D02 draw-out assembly
Valid standards DIN VDE 0638/09.81, EN 60 947-3/12.92
Dimensions DIN 43 880
Main switch characteristic DIN VDE 0113
Dielectric characteristic DIN VDE 0110
Number of poles 1-pole, 2-pole, 3-pole, 1-pole + N, 3-pole + N
Rated voltage V 230/400 AC (also suitable for networks of 240/415 AC)
65 DC 1-pole, 110 DC 2-pole
Rated breaking capacity kA 50
Rated insulation voltage V 456 AC
(acc. to EN)
Rated impulse withstand voltage V 2,500 AC
(acc. to EN)
Utilization category acc. to DIN VDE 0638 A AC-22 (63), AC-23 (35), DC-22 (63)
Utilization category acc. to DIN EN 60 947-3 A AC-22b (63), AC-23b (35), DC-22b (63)
Mounting position vertical
Ambient temperature °C -5 to +40, humidity 90 % at 20
Degree of protection IP 00 acc. to DIN 40 050
IP 20 after installation in a distribution board with front cover
Terminals anti-slip terminal up to 35 mm2 (stranded) with +/- screws (Pozidriv Z2)
safe to touch on both sides
Sealing ensured when switched on or off

Siemens I 2.1 · 2001 1/15