Professional Documents
Culture Documents
Engineering Structures
journal homepage: www.elsevier.com/locate/engstruct
a r t i c l e i n f o a b s t r a c t
Article history: When grouted pipe splice connections are employed, the structural performance of the connected precast
Received 25 December 2013 concrete components is significantly influenced by the bond behavior between the main reinforcing bars
Revised 21 December 2015 and the surrounding grout. Owing to this important characteristic, the bond behavior, in particular the
Accepted 23 December 2015
local bond-stress slip relationship and the bond strength, of the main steel reinforcement bars embedded
Available online 18 January 2016
in grout needs to be investigated accordingly. This paper presents the bond behavior of main deformed
steel reinforcement bars confined by a grouted spiral connection. A total of 36 pullout specimens were
Keywords:
tested under increasing axial tensile load to investigate the effects of spiral confinement to the connected
Spiral confinement
Grouted splice connection
main steel bars. Parameters covered in this study were spiral diameter and spiral pitch distance. The
Bond stress experimental results showed that the spiral configurations influence the bond performance due to the
Slip effect of confinement generated by the spiral diameter and pitch distance. As compared to spiral pitch
distance, the spiral diameter provides more dominant confinement effect which subsequently increases
the bond strength significantly.
Ó 2016 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.engstruct.2015.12.038
0141-0296/Ó 2016 Elsevier Ltd. All rights reserved.
2 S.J.A. Hosseini, Ahmad Baharuddin Abd. Rahman / Engineering Structures 112 (2016) 1–13
Splice
Sleeves
Reinforcement bar
of lower wall
Fig. 1. Grouted splice sleeve connection in precast concrete wall panels [9].
introduced to bond clauses in design codes worldwide [17]. The objectives of this paper are:
Detailed evaluation of bond strength and bond behavior is
complicated, as the magnitude of bond strength is influenced by 1. To investigate the effects of spiral diameter and spiral
a wide range of factors. For example, the CEB-FIP Model Code 90 pitch distance in providing the confinement.
[18], includes not less than 10 parameters which influence the 2. To investigate the effects of confinement contributed by
anchorage bond behavior. the steel spiral in improving the bond strength of
Confinement has been attributed as one of the governing deformed steel bars in the grouted splice connection.
parameters that provide significant improvement in the anchorage
bond that could lead to a reduction in the required embedment 2. Descriptions of test specimens
length of the connected steel bars [19–22]. To provide confinement
to the connected main bars, various methods such as transverse A complete grouted spiral connection consists of spiral rein-
reinforcements [23], spirals [24,25], cylindrical pipes [19,25–28], forcement cage, two main reinforcement bars and non-shrink
square hollow sections [29] and wrapping of fiber reinforced poly- grout. Sections 2.1–2.4 discuss the components and material
mer (FRP) sheets [1] surrounding the anchorage bar zone have involved in making the connection.
been adopted. Confinement is known to control the spread of the
splitting cracks, either by bridging or by resisting the expansion
2.1. The spiral reinforcement cage
of materials surrounding the main steel bars. This effect increases
the bond strength between the deformed bars and the surrounding
The fabrication of the spiral reinforcement cage involved a spi-
grout and as a result a shorter embedded length for the main bars.
ral reinforcement that was welded to four (4) number of high yield
In Malaysia, the effect of spiral confinement on the bond
steel (Y) deformed bars in 10 mm diameter, denoted as 4Y10 (see
strength of deformed steel bars was experimentally investigated
Fig. 2). The 4Y10 splice bars were welded to the external diameter
by Hoseeini and Rahman [24,25]. The confinement was provided
of the spiral to provide the tensile resistance mechanism within
by means of spiral, similar to the proprietary grout filled splice
the grouted connection.
sleeves that are widely used in precast concrete construction. In
Denmark and Sweden respectively, similar research works for
splicing tensile reinforcement bars using spiral sockets were car- 2.2. Main reinforcement bar
ried out by Efsen [30] and Tepfers [31–33]. Research results by
Efsen showed that spiral sockets were able to cause the spliced The geometrical details of main reinforcement bar connected by
reinforcement bars rupture outside the splice. Tepfers [32] investi- the grouted spiral connection are shown in Fig. 3. It is a deformed
gated the strength of tensile reinforcement splices confined by spi- bar and high yield (Y) steel with a diameter of 16 mm, denoted as
ral reinforcement where every overlap has a separate spiral. The Y16. The details of the deformed shape are: rib height = 1 mm, rib
splices were tested in reinforced concrete beams and the results spacing, c = 10 mm and rib inclination, b = 63.5°.
showed that the confining spiral contributed to the increase in
splice strength significantly. 2.3. Grouted spiral connection
Grouted spiral connections can be used as the horizontal joint
for connecting precast concrete wall-to-wall, wall-to-base, Fig. 4(a) and Table 1 show the details and Fig. 4(b) shows the
column-to-column and column-to-base. Higher bond strength pro- preparation of the grouted splice connection in joining the two
vided by the spiral confinement has led to a reduction in the main Y16 reinforcement bars. In this connection, the main rein-
embedded length of the connected main reinforcement bars. forcement bars are inserted into the spiral and then grouted with
Shorter embedded length facilitates the installation of precast con- the aid of PVC pipe.
crete components and grouting of the connections. The proposed The grouted splice connections are categorized in three series
grouted spiral connections can be adopted in Industrial Building namely S25, S35, and S45, with the spiral diameter of 25 mm,
Systems (IBS) and can become a substitute to other types of 35 mm, and 45 mm respectively. Each group had three different
mechanical spliced connections. pitch distances that were 15 mm, 25 mm, and 35 mm.
S.J.A. Hosseini, Ahmad Baharuddin Abd. Rahman / Engineering Structures 112 (2016) 1–13 3
(a) Details of specimen comprising main bars, spiral, and splice bars
Table 1
Dimensions of all series.
Series Specimen Number of Diameter of Spiral Pitch No. of Connection Main bar No. of
specimen cylindrical grout diameter distance coils (N) length Ls embedded splice bar
D (mm) Ds (mm) P (mm) (mm) length Le (mm)
Control specimen S1 3 110 No spiral No spiral No spiral 160 75 -
S2 3 110 25 15 12 160 75 -
S3 3 110 25 15 12 160 75 4
S25 P15 D25 3 110 25 15 12 160 75 4
P25 D25 3 110 25 25 8 160 75 4
P35 D25 3 110 25 35 6 160 75 4
S35 P15 D35 3 110 35 15 12 160 75 4
P25 D35 3 110 35 25 8 160 75 4
P35 D35 3 110 35 35 6 160 75 4
S45 P15 D45 3 110 45 15 12 160 75 4
P25 D45 3 110 45 25 8 160 75 4
P35 D45 3 110 45 35 6 160 75 4
tensile load over cross sectional area of the grout, rt = Tmax/A = 4.1.2. Control specimen S2
(24.01 103 N)/(p 10 mm)2/4) = 6.37 MPa. As this tensile resis- Specimen S2 consisted of grouted spiral without any
tance was exceeded, the grout cracked and fractured, and the splice bars. The spiral size was 25 mm in diameter with 15 mm
remaining grout in contact with the bar tended to move as a unit pitch distance. The purpose of specimen S2 was to see the influ-
with the main reinforcement bar, in the direction of the pulling ence of spiral in contributing the tensile resistance of the
force. connection.
S.J.A. Hosseini, Ahmad Baharuddin Abd. Rahman / Engineering Structures 112 (2016) 1–13 5
Table 2
Pullout test results of grouted splice connections.
Series Specimen Failure Bond Slip at Compressive Average Average Average Failure mode
load strength failure strength of failure bond slip at
Tmax (kN) smax (MPa) (mm) Sika grout load strength maximum
fc,g (MPa) Tmax (kN) smax (MPa) load (mm)
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
Control specimen S1 (A) 24.12 6.4a 4.02 62.4 24.01 6.37a 4.01 Grout tensile fracture
S1 (B) 23.6 6.26a 4 61.4
S1 (C) 24.32 6.45a 4.02 60
S2 (A) 24.64 6.54a 1.48 62.4 24.62 6.53a 1.48 Grout tensile fracture
S2 (B) 24.60 6.53a 1.5 61.4
S2 (C) 24.64 6.54a 1.48 60
S3 (A) 69.8 18.52 4.16 62.4 69.73 18.5 4.11 Bar bond slip
S3 (B) 69.9 18.54 4.05 61.4
S3 (C) 69.5 18.44 4.12 60
S25 P15 D25 (A) 70 18.57 4.16 62.4 69.5 18.42 4.11 Bar bond slip
P15 D25 (B) 69.5 18.44 4.12 61.4
P15 D25 (C) 69 18.30 4.05 60
P25 D25 (A) 68 18.04 3.9 62.4 67.5 17.92 3.87 Bar bond slip
P25 D25 (B) 67.5 17.9 3.88 61.4
P25 D25 (C) 67.2 17.83 3.85 60
P35 D25 (A) 66.5 17.64 4 62.4 66.3 17.5 3.99 Bar bond slip with radial cracks
P35 D25 (B) 66.4 17.61 4.05 61.4
P35 D25 (C) 66 17.51 3.94 60
S35 P15 D35 (A) 60.93 16.05 3.64 62.4 60.37 15.98 3.61 Bar bond slip
P15 D35 (B) 60.2 15.97 3.55 61.4
P15 D35 (C) 60 15.92 3.64 60
P25 D35 (A) 59 15.65 3.4 62.4 58.8 15.59 3.38 Bar bond slip with radial cracks
P25 D35 (B) 58.9 15.62 3.38 61.4
P25 D35 (C) 58.5 15.52 3.37 60
P35 D35 (A) 58 15.39 3.5 62.4 57.94 15.37 3.49 Bar bond slip with radial cracks
P35 D35 (B) 58 15.39 3.5 61.4
P35 D35 (C) 57.84 15.34 3.48 60
S45 P15 D45 (A) 52 13.79 3.12 62.4 51.56 13.67 3.09 Bar bond slip
P15 D45 (B) 51.2 13.58 3.1 61.4
P15 D45 (C) 51.5 13.66 3.05 60
P25 D45 (A) 50.7 13.45 3 62.4 50.4 13.37 2.97 Bar bond slip with radial cracks
P25 D45 (B) 50.5 13.40 2.98 61.4
P25 D45 (C) 50 13.26 2.95 60
P35 D45 (A) 49 13.00 3 62.4 49.31 13.1 2.99 Bar bond slip with radial cracks
P35 D45 (B) 49.47 13.12 2.99 61.4
P35 D45 (C) 49.47 13.12 2.99 60
a
Tensile strength of grout.
With the presence of spiral, specimen S2 could only sustained the external spiral. Then, the connection with this improvement
the tensile load up to 24.62 kN as compared to 24.01 kN in speci- was tested in specimen S3.
men S1 (see Table 2). Fig. 9(a) shows that specimen S2 failed due Table 2 shows the tensile test results including the failure load,
to grout fractured at mid-length, similar to specimen S1. The corre- bond strength and slip between the main reinforcement bars and
sponding bond strength of specimen S2 was 6.53 MPa, close to the surrounding grout. As compared to specimen S2, it can be seen that
bond strength of specimen S1, i.e. 6.37 MPa. by adding the 4Y10 splice bars, the bond strength of main rebars in
When the grout cracked and split at mid-length, the exposed specimen S3 had increased substantially by 2.8 times, from
spiral at mid-length elongated and could not sustain increasing 6.53 MPa to 18.5 MPa. The failure mode was no longer grout frac-
tensile loads. This gives an indication that the splice connection ture at mid-length. This shows that the 4Y10 splice bars and the
failure was governed by the maximum tensile strength of the grout spiral managed to bridge the tensile force in the connected main
and the spiral had no role in providing tensile resistance (see Fig. 9 rebars. The tensile force from one of the Y16 main rebar was able
(b)). On the other hand, one important observation shows that the to be transferred to the grout, then from the grout to the 4Y10
slip at failure load was reduced by 63% from 4.01 mm to 1.48 mm splice bars, then from 4Y10 splice bars to the grout, and finally
in specimen S2. This indicates that the spiral had considerably from the grout to the other Y16 main rebar, see Fig. 10(a).
improved the performance of connection in terms of reducing This internal componential interactions of force transfer among
the slip of the specimen. In other words, the spiral had the poten- main rebars, grout, spiral and 4Y10 splice bars relies mainly on
tial to restrain the slip movement as compared to specimen S1 bond mechanism. These bonds rely on chemical adhesion, interface
without spiral. friction and also mechanical interlocking between bar ribs and
grout keys [3,20,39]. However, according to Rehm [10], the
mechanical interlocking around a bar lug contributes the most in
4.1.3. Control specimen S3 bond resistance. This paper demonstrates that the mechanical
As can be seen from specimen S2, the spiral had the advantage interlocking in the grouted connection is enhanced by the confine-
of reducing the slip but still not able to transmit the tensile load ment effects contributed by the spiral and splice bars. By having
between the main rebars. To improve the tensile resistance, 4Y10 good mechanical interlocking due to good confinement, the bond
high yield steel splice bars were welded at equal spacing around strength increases very significantly.
6 S.J.A. Hosseini, Ahmad Baharuddin Abd. Rahman / Engineering Structures 112 (2016) 1–13
(a) No spiral (b) With spiral only (c) With spiral and
splice bars
Fig. 6. Details of the control specimens.
The failure mode of specimen S3 was bar pullout, see Fig. 10(b). complete configuration of the connection consisting the spiral and
This bar pullout occurred because of the 75 mm embedded length splice bars was able to transmit the tensile load between the con-
of the main bar that was short and not enough to generate an nected main rebars. Due to this success, more specimens similar to
anchorage force higher than the yield strength of the main bar. specimen S3 were tested to investigate the effects of connection
The 75 mm embedded length, suggested by Eligehausen et al. parameters to the bond stress behavior. The results of other spec-
[35], Soroushian and Choi [36] and Losberg [34], was used in these imens are shown in Table 2.
tests to ensure uniform bond stress along the embedded main bar The results shown in Table 2 are related to the effects of pitch
suitable for studying the bond behavior. distance and spiral diameter to the failure loads, bond strength
Fig. 10(b) also shows that the bar pullout failure was accompa- and slip of the connected main bars. Further discussions on the
nied by radial cracks of the grout. These radial cracks, which were effects of spiral diameter and pitch distance to the bond energy
also observed by Jorge [12], occurred due to grout tension failure. that provides the confinement to the connected main bars, are
The radial cracks had developed immediately before the sample given in Sections 5.1–5.3.
reached the failure load. This suggests that the crack opening had The higher bond strength of the grouted connection, shown in
contributed to the loss of bond between the grout and the main specimen series S25, S35 and S45, is associated with confinement
bar that eventually allowed the bar to slip. and mechanical interlocking between the main rebars and the sur-
On the other hand, from strain data shown in Fig. 11, it was rounding grout. Fig. 12(a) and (b) shows the forces, in particular
observed that all specimens had their tensile stresses below the the confinement stresses that enhance the bond resistance.
specified yield stress of 500 MPa, indicating that the main bar did When the pullout load is applied to the specimen, the ribs bear-
not yield during the test due to the short bar embedded length ing action against the grout occurred, see Fig. 12(a). This rib bear-
of 75 mm. Due to the limited embedded length, these grouted ing actions are horizontal bearing stresses and normal stresses. The
splice connections cannot achieve the full capacity of the main normal stresses that can cause radial cracks in the grout has been
reinforcement bars as bar pull out failure occurred below the the- confined effectively by the steel spiral and splice bars, see Fig. 12
oretical yielding strain of 2300 106 mm/mm. The results of (c). The magnitude of confinement can be measured by using the
other series are similar in which all the main bars remained elastic. bond energy approach, discussed in Section 5.3.
The spiral and four splice bars had enhanced the property of
5. Analysis of results bonding by confining the grout and subsequently gripping the
main reinforcement bars firmly, Thus, providing resistance of ten-
Section 4 has discussed the development of load transfer in the sile load in ensuring the continuity of jointed main reinforcement
grouted spiral connection. Results of specimen S3 showed that the bars.
S.J.A. Hosseini, Ahmad Baharuddin Abd. Rahman / Engineering Structures 112 (2016) 1–13 7
Fig. 9. Specimen S2: (a) Failure mode. (b) Force transfer mechanism.
Table 3
Bond strength with respect to different spiral diameters (MPa).
20
with different pitch distances of 15, 25 and 35 mm. Referring to
Pitch distance of 15 mm, U
19 Fig. 15(a), the smaller pitch distance is able to increase the bond
Pitch distance of 25 mm, V strength but at very moderate rate as can be seen from the moder-
18 ate slope of the curves.
Pitch distance of 35 mm, W Regardless of spiral diameters, the test results indicate that by
Bond strength (MPa)
17
having a smaller pitch distance leads to higher bond strength. How-
16 ever the influence of reducing spiral pitch distance in increasing the
bond strength is not that significant as can be seen from the gradual
15 slopes of all the three curves X, Y and Z. For example, by reducing
the spiral pitch distance from 35 mm to 15 mm, the bond strength
14 managed to increase slightly from 17.59 MPa to 18.44 MPa.
Another important observation can be obtained by comparing
13
Figs. 12 and 15(a). It can be seen that the effect of the spiral diam-
12 eter is more dominant in increasing the bond strength as compared
20 25 30 35 40 45 to the effect of pitch distance. The evident is based on the steep
Spiral Diameter (mm) slope of curves U, V and W in Fig. 12 as compared to gradual slope
of curves X, Y, Z in Fig. 15(a). To compare the incremental percent-
Fig. 13. Bond stress versus spiral diameter. age, refer Tables 3 and 4. It can be seen that, as the spiral diameter
decreased from 45 mm to 25 mm, the bond strength increased by
34%, however, when the pitch distance decreased from 35 mm to
surrounding the connected main rebars. With the smaller width of 15 mm, the bond strength increased by 4.8% only.
confined grout, the splitting expansion of grout can be delayed and
the early loss of bond can be prevented.
5.3. Bond energy
For other cases of the connections with different pitch distances
of 25 and 35 mm, the results show similar trend of significant bond
As discussed earlier, the effect of spiral diameter is the domi-
strength improvement, such that significant increase in bond
nant factor in the confinement properties. So, to describe further
strength when spiral diameter decreases.
the confinement effect on the bond stress–slip, Fig. 16 shows the
plot of bond stress versus slip for specimens with different
5.2. Effect of pitch distance diameters.
According to Alavi-Fard and Marzouk [41], the bond energy is
Table 4 and Fig. 15(a) show the response on bond strength with recommended to be used to evaluate the bond behavior. The area
respect to spiral pitch distance, while Fig. 15(b) shows the spirals under the bond stress–slip is defined as the bond energy [41].
Fig. 14. Confined cross sectional areas of grout with different spiral diameters.
Table 4
Bond strength with respect to different pitch distance.
20
Spiral diameter of 25 mm, X
19
(b)
Fig. 15. (a) Response of bond strength versus pitch distance. (b) Connections with different pitch distances.
T max
lb ¼ ð2Þ
p db smax
where
Maximum fracture failure load of the main bar,
pðd2 Þ
T max ¼ As f t ¼ 4 b f t ¼ 114:5 kN.
Main bar diameter, db = 16 mm.
Tensile strength of Y16 main bar, f t = 570 N/mm2.
smax is the bond strength between the main bar and the sur-
rounding grout obtained from experiments.
Table 5 Table 6
Bond energy at failure of grouted spiral connections. Embedded length of main bar.
Series Specimen Bond energy at failure Average bond Spiral diameter, Proposed bond Required embedded
N/mm2 mm = N/mm energy N/mm Ds (mm) strength, smax (MPa) length, lb (mm)
S25 P15 D25 (A) 37.7 36.8 Ds 6 25 17.5 lb1 ¼ p114:510
3
16ð17:5Þ ¼ 130 mm
P15 D25 (B) 37.3
25 < Ds 6 35 15 lb2 ¼ 114:510
3
p16ð13Þ ¼ 175 mm
P25 D25 (A) 33.9 33.1
P25 D25 (B) 33
P25 D25 (C) 32.4
P35 D25 (A) 34.6 35
P35 D25 (B) 34.9
P35 D25 (C) 35.5
Table 7
S35 P15 D35 (A) 28.3 28
Ultimate tensile test by Norliana [42].
P15 D35 (B) 27.2
P15 D35 (C) 28.5 Specimen Grout Spiral Embedded Failure Failure
P25 D35 (A) 25.4 25 strength diameter, Ds length, lb load mode
P25 D35 (B) 25 (MPa) (mm) (mm) (kN)
P25 D35 (C) 24.6
P35 D35 (A) 26 25.9 D2 66.95 33 180 109.44 Bar slippage
P35 D35 (B) 26 E2 200 110.06 Bar
P35 D35 (C) 25.7 fractured
19 Pitch distance of 15 mm
18
Pitch distance of 25 mm
17
Pitch distance of 35 mm
Bond Strength (MPa)
16
11
10
20 30 40 50
Spiral Diameter (mm)
Fig. 17. Experimental bond strength for different series for embedment length 75 mm and grout compressive strength of about 60 MPa.
12 S.J.A. Hosseini, Ahmad Baharuddin Abd. Rahman / Engineering Structures 112 (2016) 1–13
Slip
Fig. 18. Specimen D2, bar slippage failure at 109.44 kN with main bar embedded length of 180 mm [42].
Fig. 19. Specimen E2, bar fractured failure at 110.06 kN with main bar embedded length of 200 mm [42].
7. Conclusion References
The effect of confinement on the behavior of the grouted splice [1] Tibbetts AJ, Oliva MG, Bank LC. Durable fiber reinforced polymer bar splice
connections for precast concrete structures. Composites Ploycon. Tampa, FL
connection was investigated. An empirical model for predicting the USA: American Composites Manufacturers Association; 2009 [January 15–17,
local bond stress–slip relationship of two steel main bars con- 2009].
nected by the grouted spiral connection under increasing tensile [2] ACI Committee 550R. Design Recommendations for precast concrete
structures. Reported by ACI-ASCE Committee 550; 1996.
load was developed. [3] ACI Committee 550. Emulating Cast-in-Place Detailing in precast Concrete
It is concluded that: Structures. ACI 550.1R-01. Farmington Hills, MI: American Concrete Institute;
2009.
[4] Tokyo Steel Corp. Tokyo Steel Corp. BCJ-C1659; 1994.
1. The use of splice bars and spiral in the grouted connection [5] Jansson PO. Evaluation of grout-filled mechanical splices for precast concrete.
increased the bond strength of the connected main bars by Construction and technology division report 07 TI-2094; 2008.
2.8 times. The spiral acts as the main shear keys to resist [6] Coogler KL, Harries KA, Gallick M. Experimental study of offset mechanical lap
splice behavior. J ACI Struct 2008;105(4):478–87.
shear force, while the splice bars act as the main bridging
[7] Ling Jen Hua, Rahman Ahmad Baharuddin Abd, Ibrahim Izni Syahrizal, Hamid
mechanism to transmit tension force. Zuhairi Abdul. Behaviour of grouted pipe splice under incremental tensile load.
2. The use of smaller spiral diameter results in higher bond Construct Build Mater J 2012;33:90–8.
[8] Pecce M, Manfredi G, Realfonzo R, Cosenza E. Experimental and analytical
energy and better confinement that delays the radial crack
evaluation of bond properties. J Mater Civil Eng 2001;3(4).
propagation. This characteristic increases the bond strength [9] Loh HY. Development of grouted splice sleeve and its performance under axial
of the connected main rebars. tension. Msc. Universiti Teknologi Malaysia; 2008.
3. Reducing the pitch distance of the spiral, only increases the [10] Rehm G. The basic principles of the bond between steel and concrete. Cement
and Concrete Association, A translation from Ueber die Grundlagen des
bond strength slightly. Verbundes zwischen Stahl und Beton, Deutscher Ausschuss für Stahlbeton,
4. The influence of spiral diameter is more significant in Berlin, Wilhelm Ernst & Sohn; 1961.
improving the confinement effects as compared to the [11] Goto Y. Cracks formed in concrete around deformed tension bars. ACI-J
1971:244–51 (Detroit).
influence of pitch distance. [12] Jorge S, Dias-da-Costa D, Júlio ENBS. Influence of anti-corrosive coatings on the
5. The splice sleeve connection with pitch distance of 25 mm bond of steel rebars to repair mortars. Eng Struct 2012;36:372–8.
reached the bond strength with lower slip. This means that [13] Ogura Noriyuki, Bolander John E, Ichinose Toshikatsu. Analysis of bond
splitting failure of deformed bars within structural concrete. Eng Struct
the pitch distance of 25 mm provides the most optimum 2008;30:428–35.
pitch distance in controlling the slip in comparison with [14] Haskett Matthew, Oehlers Deric John, Mohamed Ali MS. Local and global bond
other pitch distances. characteristics of steel reinforcing bars. Eng Struct 2008;30:376–83.
[15] Wang Huanzi. An analytical study of bond strength associated with splitting of
6. The bond strength increases almost proportionally with the
concrete cover. Eng Struct 2009;31:968–75.
increment of grout compressive strength. [16] Azizinamini A, Chisala M, Ghosh SK. Tension development length of
reinforcing bars embedded in high-strength concrete. Eng Struct 1995;17
(7):512–22.
[17] Cairns J, Plizzari GA. Towards a harmonised European bond test. Mater Struct
2003;36(October):498–506.
Acknowledgement [18] CEB-FIP. Model Code 1990. Thomas Telford, London; 1993. p. 437 [ISBN 0 7277
1696].
The authors would like to thank the Universiti Teknologi Malay- [19] Einea A, Yamane T, Tadros MK. Grout-filled pipe splices for precast concrete
construction. Precast/Prestr Concrete I J 1995;40(1):82–93.
sia (UTM) – Malaysia for the financial support offered in conduct- [20] Untrauer RE, Henry RL. Influence of normal pressure on bond strength. ACI J
ing this experimental study. 1965;65(5):577–85.
S.J.A. Hosseini, Ahmad Baharuddin Abd. Rahman / Engineering Structures 112 (2016) 1–13 13
[21] Robins PJ, Standish IG. The influence of lateral pressure upon anchorage bond. [32] Tepfers, R. A theory of bond applied to overlapped tensile reinforcement
Mag Concr Res 1984;36(129). splices for deformed bars. Publication 73:2. Division of concrete structures,
[22] Moosavi M, Jafari A, Khosravi A. Bond of cement grouted reinforcing bars Chalmers University of Technology, Göteborg; 1973 May. p. 328.
under constant radial pressure. Cem Concr Compos 2005;27(11):103–9. [33] Tepfers R. Overlap splices for ribbed bars for free use in a concrete structure.
[23] Soroushian P, Choi Ki-Bong, Park Gill-Hyun, Aslani Farhang. Bond of deformed Nordic Concrete Research Publication No 7. Nordic Concrete Federation, Oslo;
bars to concrete: effects of confinement and strength of concrete. ACI Mater J 1988. p. 273–83.
1991;88(3):227–32. [34] Losberg A. Sprickbildning i kontinuerliga betongbeläggningar och andra
[24] Hosseini SJA, Rahman AB Abd. Effects of spiral diameter on the bond stress– betongkonstruktioner, låsta mot rörelser av temperatur och krympning.
slip relationship in grouted sleeve connector. Malay J Civil Eng 2013;12(1). (Cracks in continuous concrete road slabs and other concrete structures
[25] Hosseini SJA, Rahman AB Abd. Analysis of spiral reinforcement in grouted pipe locked against movements from temperature and shrinkage). Chalmers
splice connectors. Gradevinar 2013(65):1–10. University of Technology, Department of Building Technology No. 607; 1962.
[26] Ling JH, Rahman AB Abd, Hamad Z Abd, et al. Structural performance of splice p. 45.
connector for precast concrete structures. In: Joint conference 7th Asia Pacific [35] Eligehausen R, Popov EP, Bertero VV. Local bond stress–slip relationships of
structural engineering & construction conference (APSEC 2009) & 2nd deformed bars under generalized excitations. Rep. No. 83/23, Earthquake
European Asian Civil Engineering Forum (EACEF 2009). Pulau Langkawi, Engrg. Res. Ctr. (EERC), Univ. of California, Berkeley, California; 1983.
Malaysia: Universiti Teknologi Malaysia (UTM), Universitas Pelita Harapan [36] Soroushian P, Choi Ki-Bong. Local bond of deformed bars with different
(UPH); 2009. diameters in confined concrete. ACI Struct J 1989;86(2):217–22.
[27] Enin E, Morcous G. Non-proprietary bar splice sleeve for precast concrete [37] ACI-116. Cement and concrete terminology ACI 116R-00; 2000.
construction. Eng Struct 2015;83:154–62. [38] British Standards BSI. Structural use of concrete – Part 1: code of practice for
[28] Sayadi Ali A, Rahman Ahmad Baharuddin Abd, Jumaat Mohd Zamin Bin, design and construction; 1997.
Johnson Alengaram U, Ahmad Sayadi. The relationship between interlocking [39] Thompson MK, Jirsa James O, Breen JE, Klingner RE. Anchorage behaviour of
mechanism and bond strength in elastic and inelastic segment of splice sleeve. headed reinforcement. Literature review; 2002.
Constr Build Mater 2014;55:227–37. [40] Einea A, Yehia S, Tadros MK. Lap splices in confined concrete. ACI Struct J
[29] Ling JH, Rahman AB Abd, Ibrahim IS, et al. Tensile performance of ribbed 1999;96(6):937–46.
hollow section splice sleeve connector under direct tensile load. In: 2nd [41] Alavi-Fard M, Marzouk H. Bond of high-strength concrete under monotonic
construction industry research achievement international conference (CIRAIC pullout loading. Mag Concr Res 2004;56(9):545–57.
2009). Kuala Lumpur, Malaysia: Construction Research Institute of Malaysia [42] Norliana M. The behavior of sleeve connection with spiral reinforcement and
(CREAM), Construction industry development board (CIDB); 2009. additional longitudinal bar under direct tensile load. Msc. Thesis, Universiti
[30] Efsen A. Spiral socket splices for deformed bars. Laboratoriet for Teknologi Malaysia; 2009.
Bygningsteknik, Danmarks Tekniske Höjskole, Meddelelse Copenhagen 1957; [43] ACI Committee 408, A.C.I., Bond and development of straight reinforcing bars
Nr. 8; 1957. p. 13. in tension; 2003.
[31] Tepfers R. Cracking of concrete cover along anchored deformed reinforcing
bars. Mag Concr Res 1979;31(106):3–12.