Opening in field (mm) Governor Panel w.r.t. Actuator Command 0 0 10 6 20 12 30 18 40 24 Control oil pressure was 50 30 dropping from 13.75 kg / 60 36 cm2 to 13.65 kg/ cm2 70 43 80 50 90 56 100 62 25% interval command
Opening command from COP Pr (kg/cm²) Drop
Opening in field (mm) Governor Panel w.r.t. Actuator Command 0 0 25 14 Control oil pressure was 50 30 dropping from 13.75 kg / 75 46 cm2 to 13.48kg/ cm2 100 62 50% interval command
Opening command from COP Pr (kg/cm²) Drop
Opening in field (mm) Governor Panel w.r.t. Actuator Command 0 0 Control oil pressure was 50 30 dropping from 13.75 kg / 100 62 cm2 to 12.00kg/ cm2
100% command
Opening command from COP Pr (kg/cm²) Drop
Opening in field (mm) Governor Panel w.r.t. Actuator Command 0 0 Control oil pressure was dropping from 13.75 kg / 100 62 cm2 to 11.40kg/ cm2 During 0 to 100% command standby COP auto started.