You are on page 1of 1

Actuator lifting test on DT. 03.03.

2017

10% interval command

Opening command from COP Pr (kg/cm²) Drop


Opening in field (mm)
Governor Panel w.r.t. Actuator Command
0 0
10 6
20 12
30 18
40 24 Control oil pressure was
50 30 dropping from 13.75 kg /
60 36 cm2 to 13.65 kg/ cm2
70 43
80 50
90 56
100 62
25% interval command

Opening command from COP Pr (kg/cm²) Drop


Opening in field (mm)
Governor Panel w.r.t. Actuator Command
0 0
25 14 Control oil pressure was
50 30 dropping from 13.75 kg /
75 46 cm2 to 13.48kg/ cm2
100 62
50% interval command

Opening command from COP Pr (kg/cm²) Drop


Opening in field (mm)
Governor Panel w.r.t. Actuator Command
0 0 Control oil pressure was
50 30 dropping from 13.75 kg /
100 62 cm2 to 12.00kg/ cm2

100% command

Opening command from COP Pr (kg/cm²) Drop


Opening in field (mm)
Governor Panel w.r.t. Actuator Command
0 0 Control oil pressure was
dropping from 13.75 kg /
100 62 cm2 to 11.40kg/ cm2
During 0 to 100% command standby COP auto started.