Step 1
Command “ Oil circulation pump” ON
Command “ Generator Space heater off”
Creep detection blocked
Guide vane fully closed
Ensure Hydraulic lock disengage
Step 2
Command “ Raw Cooling water system on”
Command “ Treated Cooling water system on”
Ensure all the steps mentioned above are normalized. Also ensure Raw and treated CW flow
normal
Step 3
Runner aeration equipment valve open
Overhead tank CW valve open
CW valve for shaft seal open
Shaft seal hydrostatic pump ON
Ensure CW flow to all the bearings, Generator air cooler & governor PP set is normal. Ensure
that shaft seal CW pressure and flow normal. Also ensure shaft seal hydro static feed flow
normal.
Step 4
Open Bypass valve of MIV
Open MIV after pressure on both sides are equalized
Close Bypass valve of MIV
Step 5
Step 6
Ensure GCB open, speed > 90 %, field breaker open, MIV fully open, Line charge sel. off
SPIN MODE
Ensure program changeover conditions PC 1 as mentioned above are through
Step 7
Open Earth switch
Close Isolator Breaker
Close field Breaker
Excitation ON
GENERATION MODE
NB: During the start of Unit and its auxiliaries, local checks/ observations need to be carried out
on each equipment/system for normal running and to find out any abnormality like excessive
vibrations, noise, leakage etc.