15 Towers - Deviation Sheet - 283111 - DIGITAL,ADDRESSABLE FIRE ALARM SYSTEM

Latest SPEC
Sr. No. Category Page Spec Description Deviation
No.
1

1.6 COORDINATION
D. The Contractor shall coordinate with the IBMS Contractor and
2.2 GENERAL REQUIREMENS
other Security and Building Services Contractors as specified in
E. Provide full Read and Write capabilities including, but not limited to, the
this Specification Section, the relevant system Specifications and
following functions:
the IBMS Specifications.
1.System Scheduling.
1. All controls in case of fire shall remain with the fire alarm
283111 page 14 of 2.Data Trending. Comply, system control from the IBMS is against clause 1.6.D.1.
1 ULV system in accordance with the applicable NFPA codes.
Rev 1 46 3.Alarmmonitoring and routing. however, system control can be accomplished via Notifier Graphics Software
2. For the underground parking spaces, the control of the smoke
4.Monitoring of diagnostic data.
management equipment are carried by a dedicated smoke
5.Time synchronization.
management system/PLC. Fire alarm system is to providing a
6.Graphics. (These shall reside at IBMS application servers).
verified fire alarm signal “Smoke Zone in alarm condition” to the
7.Operation and maintenance.
parking smoke management system. For further details, refer to
mechanical & IBMS packages.

2.4 SYSTEM DESCRIPTION


H. System Alarm Capability during Circuit Fault Conditions: System wiring,
Comply and Exceed. The specs are indicating spare addresses on the loop card
including peerto-peer loop, and circuit arrangement prevent alarm capability
283111 page 15 of not less than 20%. Notifier SLC can accommodate up to 318 addresses (159
2 ULV reduction when an open circuit, ground or wire-to-wire short occurs, or an open
Rev 1 46 detectors, 159 modules); accordingly, one loop can support up to 255
circuit and a ground occur at the same time in Initiating-Device, Notification-
addressable devices
Appliance, and Signaling-Line Circuits.
3. Install no more than 200 addressable devices on each signaling-line circuit.

2.4 SYSTEM DESCRIPTION


283111 page 18 of Q. System Trouble and Supervisory Signal Actions:
3 ULV The system reports all the events immediately to all the monitoring stations
Rev 1 46 6. After a time delay of 200 seconds, transmit a trouble or supervisory signal to
the remote alarm receiving station.
2.4 SYSTEM DESCRIPTION
O. System shall be able to report a map of all initiating devices connected to the
283111 page 20 of
4 ULV system for confirmation of As-Built drawings, and it shall show physical wiring Do NOT Comply
Rev 1 46
of T-type by device type and number. Other proposed alternatives shall be
considered.
2.4 SYSTEM DESCRIPTION
Comply, Notifier loops can support up to 159 detectors and 159 modules
283111 page 20 of P. Expansion Capability: Increase number of devices in the future by 20 percent
5 ULV while the specifications are calling for 200 devices per loop; accoridngly
Rev 1 46 above those indicated without adding any internal or external components or
Notifier provides 59% extra devices to the specified capacity
cable conductors.

2.5 MAIN FIRE ALARM CONTROL PANEL (MFACP)


A. Cabinet:Lockable steel enclosure. Arrange interior components so operations
required for testing or for normal maintenance of the system are performed from Comply and exceed, Notifier panel have a QWERTY keypad which enables
283111 page 20 of the front of the enclosure. If more than one unit is required to form a complete system basic programming for devices like assigning zones, creating logic,
6 ULV
Rev 1 46 control panel, fabricate with matching modular unit enclosure to accommodate assign devices location on site without the need for laptop connection with
components and to allow ample gutter space for field wiring and interconnecting special software
panels. MFACP shall be of modular design and shall not have single point of
failure.

2.5 MAIN FIRE ALARM CONTROL PANEL (MFACP)


F. History log: The system shall provide a means to recall alarms and trouble
283111 page 21 of conditions in Comply and exceed, the control panel can accommodate up to 4000 events
7 ULV
Rev 1 46 chronological order for the purpose of recreating an event history. A minimum of and 1000 alarm events
1200
chronological events shall be provided.

2.5 MAIN FIRE ALARM CONTROL PANEL (MFACP)


G. Alphanumeric Display and System Controls: Arranged for interface between
human operator at fire alarm control panel and addressable system components
including annunciation and supervision. Display alarm, supervisory, and Comply - CPU2-3030D
283111 page 21 of
8 ULV component status messages and the programming and control menu. Comply and Exceed, 640 characters display, the system have QWERTY key
Rev 1 46
1. Annunciator and Display: Liquid-crystal type, 80 characters, minimum. pad for basic system programming CPU2-3030D
2. Keypad: Arranged to permit entry and execution of programming, display, and
control commands and to indicate control commands to be entered into the
system for control of smoke-detector sensitivity and other parameters.

2.5 MAIN FIRE ALARM CONTROL PANEL (MFACP)


H. Voice Alarm: An emergency communication system shall be provided for
each FACP/MFACP, including central voice alarm system components complete
with microphones, preamplifiers, amplifiers, and tone generators. This shall
include speaker zone indication, digital voice units and microphone.
Construction shall be modular and capable of being field programmed. System
283111 page 21 of
9 ULV shall allow for redundancy such that failure of a microphone, preamplifier, Comply and exceed alarm channels are 8 available DVC-EM
Rev 1 46
amplifier, or tone generator shall not impair system operation. Features include
the following:
1. 3-alarm channels permit simultaneous transmission of different
announcements to different zones or floors automatically or by using the central
control microphone. All announcements are made over dedicated, supervised
communication lines.

2.5 MAIN FIRE ALARM CONTROL PANEL (MFACP)


I.2Selector panel controls simultaneous operation of telephones in selected zones
and permits up to 6 phones to be operated simultaneously. Ground faults and
283111 page 22 of Comply and exceed, up to 35 phones can be activated simultaneously (5
10 ULV open or shorted telephone lines are indicated on the panel front by individual
Rev 1 46 Channels with 7 Active FFT per channel) DVC-KD/ACM-24AT/AEM-24AT
LEDs. Zone-selector switches with associated LED indicators permit the
firefighter to activate selected telephone zones. LED indicators display elevator
recall status.

2.8 SYSTEM SMOKE DETECTORS


A. General Requirements for System Smoke Detectors:
8. Remote Control: Unless otherwise indicated, detectors shall be digital-
addressable type, individually monitored at fire alarm control panel for
calibration, sensitivity, and alarm condition and individually adjustable for
sensitivity by fire alarm control panel.
283111 page 24 of Partially comply,only fixed heat sensor is available for the Multi Sensor,fixed
11 ULV a. Multi-sensor: Rate-of-rise temperature characteristic of combination
Rev 1 46 temperature sensor is 57 deg only
smoke_x005f_x0002_and heat-detection units shall be selectable at fire alarm
control panel for 8 or 11 deg C (15 or 20 deg. F) per minute.
b. Multi-sensor: Fixed-temperature sensing characteristic of combination
smoke_x0002_and heat-detection units shall be independent of rate-of-rise
sensing and shall be settable at fire alarm control panel to operate at 57 or 68 deg
C (135 or 155 deg F).

Sensitivity Levels:
2.10 PROJECTED BEAM SMOKE DETECTORS
Level 1–25%;
E. For Iconic Tower; Intelligent single-ended reflective imaging beam smoke
Level 2– 30%;
detectors shall be used with the following features;
283111 page 26 of Level 3–40%;
13 ULV 5. Remote test station capable for electronic simulated smoke test from ground
Rev 1 46 Level 4–50%;
level
Acclimate Level 1–30 to 50%;
6. Four sensitivity levels (25%, 30%,40% & 50%)
Acclimate Level 2–40 to 50%
7. 50° horizontal and 20° vertical beam adjustment
10º horizontal &–/+vertical

2.11 MULTI SENSOR DETECTORS


F. Sensors: The detector shall be comprised of multiple sensing elements such as
283111 page 26 of a smoke and heat sensors, or a smoke and carbon monoxide sensors . Partially Comply FSP-951T-IV, Multi sensors have only fixed heat sensor
14 ULV
Rev 1 46 2. Heat sensor shall be as described in "Heat Detectors" Article. The proposped detector FSP-951T-IV does not have CO sensor.
3.Carbon monoxide sensor shall be as described in "Carbon Monoxide
Detectors" Article

2.13 HEAT DETECTORS


A. Continuous Linear Heat-Detector System: consisting of detector cable and
control unit
1. Detector Cable:
a. Shall be flexible in installation and recoverable after operation. It shall have
high sensitivity to small temperature variations and shall monitor the precise
Our technical offer is showing the restorable and fixed linear heat detection
283111 page 28 of point of risk. The analog sensor shall consist of a 4-core cable. Two of the four
16 ULV cable as it is more suitable for building appications while the specified system
Rev 1 46 color-coded conductors shall be insulated with a negative temperature coefficient
is more appropriate for tunnel appications
material. The other two conductors shall have normal PVC insulation. The cores
shall be twisted together and protected by an outer sheath of high temperature,
flame-retardant PVC insulation. The analogue sensor senses temperature
variations by continuously monitoring the resistance such that a change in
temperature produces a relative change in resistance between the two loops
within the sensor cable.

283111 page 28 of
17 ULV 2.14/B.2Obscuration Sensitivity Range: 0.005 - 6 percent obs/ft. Comply and exceed, sensitivty ranges from 0.0016%/ft. obs – 6.25%/ft. obs
Rev 1 46
283111 page 29 of 2.14/B.9Provide software-programmable relays rated at 2 A at 30-V dc for alarm
18 ULV Comply, up to 12 programmable relays are available
Rev 1 46 and fault conditions.
283111 page 30 of
19 ULV 2.14/C.2.gMinor and urgent LED fault indicators Comply
Rev 1 46

2.15/AGeneral Requirements for Notification Appliances: Individually


283111 page 30 of Comply with deviation, addressable control module will be added to each
20 ULV addressed, connected to a signaling-line circuit, equipped for mounting as
Rev 1 46 Notification Device
indicated, and with screw terminals for system connections

2.15/CBells: Electric-vibrating, 24-V dc, under-dome type; with provision for


283111 page 31 of housing the operating mechanism behind the bell. When operating, bells provide
21 ULV Partially comply, 81 db at 3 m - SSM24-10
Rev 1 46 a sound-pressure level of 87 dB, measured 3 m from the bell. 254-mm (10-inch)
size, unless otherwise indicated. Bells are weatherproof where indicated.

283111 page 31 of
22 ULV 2.15/DHorns shall produce a sound pressure level of 90 dBA dBA+88
Rev 1 46
2.15/F.2Low-Range Units: to include round baffles, steel with white finishes.
The rear of the speaker shall be completely sealed protecting the cone during and
Partially comply, the speaker body is made of fire resistant poly/ carbonate -
283111 page 31 of after installation. Speaker shall be provided for use with 70 volt systems.
23 ULV SPCRL
Rev 1 46 Speakers shall provide power taps at ½ W, 1W and 2 Watts. Speakers shall
SPSCRL/SPSCWK/SPRL
provide UL confirmed 87 dBA output at 2 watts. Speaker sound dispersion angle
shall be minimum 120º

2.15/F.3High Directivity Units: shall be similar to ceiling type with rectangular


283111 page 31 of shape and surface mount rated 2 to 15 Watts for high ceiling spaces
24 ULV Comply and Exeed, Horn speaker can be utilised with 102 dB at 15W
Rev 1 46 (Acoustically challenging areas). Speakers shall provide UL confirmed 98 dBA
output at 15 watts. Speaker sound dispersion angle shall be minimum 150º.

2.16/A.6Selector panel controls to provide for simultaneous operation of up to


283111 page 32 of Comply and exceed, up to 35 phones can be activated simultaneously (5
25 ULV six telephones in selected zones. Indicate ground faults and open or shorted
Rev 1 46 Channels with 7 Active FFT per channel) DVC-KD/ACM-24AT/AEM-24AT
telephone lines on the panel front by individual LEDs

2.19/HThe FSCS shall be mounted in an aluminum frame with non-glare,


minimum 4.76-mm- (3/16-inch-) thick, clear acrylic cover over a graphic
283111 page 35 of Comply with deviation, graphical presenatation will be presented on the
26 ULV representation of the facility smoke management system fans, dampers, elevators
Rev 1 46 graphical annuciation system
/ stairwell pressurization system, smoke control doors / windows / curtains and
related HVAC equipment.
283111 page 35 of
27 ULV 2.19/IThe FSCS shall operate only when activated by a fire service key Do NOT Comply.
Rev 1 46

2.20/ADescription: LED indicating light near each smoke detector that may not
be readily visible, and each sprinkler water-flow switch and valve-tamper switch.
Light shall be wired in such a way as to flash when the associated device is in an
283111 page 35 of alarm or trouble mode. Lamp is flush mounted in a single gang wall plate. A red, Partially Comply, No Remote LED Indicators can be attached to Water Flow
28 ULV
Rev 1 46 laminated, phenolic-resin identification plate at the indicating light identifies, in or Tamper switches
engraved white letters, device initiating the signal and room where the smoke
detector or valve is located. For water-flow switches, the identification plate also
designates protected spaces downstream from the water-flow switch.

2.24/B.2Battery Charger: Solid-state, fully automatic, variable-charging-rate


type. Provide capacity for 150 percent of the connected system load while
283111 page 38 of
30 ULV maintaining batteries at full charge. If batteries are fully discharged, the charger Power Supply can fully charge batteries in 48 Hours as per the NFPA72
Rev 1 46
recharges them completely within 4 hours. Charger output is supervised as part
of system power supply supervision.

2.26/C.Local functions and display at the digital alarm communicator transmitter


shall include the following:
1. Verification that both telephone lines are available.
283111 page 39 of
31 ULV 2. Programming device. Comply with deviation, the DACT communicates its status to the CPU display
Rev 1 46
3. LED display.
4. Manual test report function and manual transmission clear indication.
5. Communications failure with the central station or fire alarm control panel.

283111 page 40 of 2.28 SYSTEM PRINTER: Printer shall be listed and labeled as an integral part
33 ULV Do not comply, Desktop dot matrix printer will be provided
Rev 1 46 of fire alarm system.
Honeywell
Sensitivity Levels:
2.10 PROJECTED BEAM SMOKE DETECTORS
Level 1–25%;
E. For Iconic Tower; Intelligent single-ended reflective imaging beam smoke
Level 2– 30%;
detectors shall be used with the following features;
283111 page 26 of Level 3–40%;
1 ULV 5. Remote test station capable for electronic simulated smoke test from ground
Rev 1 46 Level 4–50%;
level
Acclimate Level 1–30 to 50%;
6. Four sensitivity levels (25%, 30%,40% & 50%)
Acclimate Level 2–40 to 50%
7. 50° horizontal and 20° vertical beam adjustment
10º horizontal &–/+vertical

2.13 HEAT DETECTORS


283111 page 27 of B. Heat Detector, Combination Type: Actuated by either a fixed temperature of
2 ULV 9 deg c/minute
Rev 1 46 57 deg C (135 deg F) or a rate of rise that exceeds 8 deg C (15 deg F) per minute
unless otherwise indicated.

2.13 HEAT DETECTORS


D. Continuous Linear Heat-Detector System: consisting of detector cable and
control unit
1. Detector Cable:
283111 page 28 of
3 ULV b. For tunnel application,the detector cable shall be fiber optic based with the Linear heat detector system shall be configure direct from control unit
Rev 1 46
following requirements:
2) Control unit should have the capability to be interfaced via a data link to a PC.
The PC shall include system software for displaying real time zone temperatures
and identification of the actual position of a cable break or fire condition

2.15 NOTIFICATION APPLIANCES


D. Horns: Electric-vibrating-polarized type, 24-V dc; with provision for housing
283111 page 31 of
4 ULV the operating mechanism behind a grille. Horns shall produce a sound-pressure dBA+88
Rev 1 46
level of 90 dBA, measured 3 m (10 feet) from the horn, using the coded signal
prescribed in UL 464 test protocol.

2.15 NOTIFICATION APPLIANCES


F. Voice/Tone Notification Appliances:
283111 page 31 of 3. High Directivity Units: shall be similar to ceiling type with rectangular shape
5 ULV 101 dB @ 15 Watts, Dispersion angle: 70 Degrees
Rev 1 46 and surface mount rated 2 to 15 Watts for high ceiling spaces (Acoustically
challenging areas). Speakers shall provide UL confirmed 98 dBA output at 15
watts. Speaker sound dispersion angle shall be minimum 150º.

2.16 FIREFIGHTERS' TWO-WAY TELEPHONE COMMUNICATION


SERVICE
A. Dedicated, two-way, supervised, telephone voice communication links
283111 page 32 of
6 ULV between fire alarm control panel, the fire command center, and remote Support System Status LEDs only and can be monitored from Software
Rev 1 46
firefighters' telephone stations.Supervised telephone lines shall be connected to
talk circuits by controls in a control module. Provide the following:
7. Display: digital to indicate location of caller.
0

2.21 GRAPHIC ANNUNCIATOR


283111 page 36 of A. Graphic Annunciator Panel(Minic Panel):
7 ULV Normal Mimic panel without touch screen
Rev 1 46 4. Graphic representation of the facility shall be represented on high resolution,
colorful touch screens indicating each detector in its actual location.

283111 page 40 of 2.27 RADIO ALARM TRANSMITTER FOR ICONIC TOWER meet NFPA 72, chapter 26 requirements. (Compliant with NFPA72 2010 and
8 ULV
Rev 1 46 C. Transmitter shall comply with NFPA 1221 and 47 CFR 90. 2013 supervision requirements.)

2.27 RADIO ALARM TRANSMITTER FOR ICONIC TOWER


A.Description: Manufacturer's standard commercial product; factory assembled,
wired, and tested; ready for installation and operation.
283111 page 40 of
9 ULV 5. Antenna: Omnidirectional, coaxial half-wave, dipole type with driving point The Radio communicator with built in antenna
Rev 1 46
impedance matched to transmitter and antenna cable output impedance. Wind-
load strength of antenna and mounting hardware and supports shall withstand
160 km/h with a gust factor of 1.3 without failure.