Professional Documents
Culture Documents
www.tyco-fire.com
Contacts
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
FROM NORMALLY
WET LINE SUPPLY
TO OPEN TO OPEN
SPRINKLERS SPRINKLERS SUPPLY
OR NOZZLES OR NOZZLES PIPING
FRANGIBLE GLASS
BULB AT BOTTOM
MJC's
IN PENDENT
SUPPLY POSITION
PIPING
MJC
MJC's
OPEN
SPRINKLERS OPEN
FROM
OR NOZZLES SPRINKLERS
NORMALLY
OR NOZZLES
WET LINE
SUPPLY
FROM
NORMALLY NOTE:
WET LINE Supply piping and MJC's are to be
SUPPLY located in areas at 4°C or greater.
FIGURE 1A FIGURE 1B
FIGURE 1
TYPICAL PIPING ARRANGEMENT
NORMALLY WET LINE SUPPLY
(Series MJC Multiple Jet Controls in Pendent Position with Heat Sensitive Bulb at Bottom)
FRANGIBLE GLASS
BULB AT TOP
TO OPEN TO OPEN
SPRINKLERS SPRINKLERS
OR NOZZLES OR NOZZLES
FROM NORMALLY
DRY LINE SUPPLY
MJC's
IN UPRIGHT
POSITION
MJC
MJC's
SUPPLY
PIPING
OPEN
SPRINKLERS OPEN
OR NOZZLES SPRINKLERS
OR NOZZLES
FROM
NORMALLY
DRY LINE SUPPLY
SUPPLY PIPING
FROM
NORMALLY
DRY LINE
SUPPLY
FIGURE 2A FIGURE 2B
FIGURE 2
TYPICAL PIPING ARRANGEMENT
NORMALLY DRY LINE SUPPLY
(Series MJC Multiple Jet Controls in Upright Position with Heat Sensitive Bulb at Top)
TFP1346
Page 3 of 10
Components:
1 - Body 12 - O-Ring ** MJC shown
2 - Inlet * 13 - O-Ring upright; may be
3 - Diaphragm Housing ** oriented as
5
4 - Plunger 14 - Spring Plate ** pendent.
5 - Bulb 11 14
6 - Gasket * Temperature rating
7 - Compression and year of manu-
facture indicated on 13 10
Screw
8 - Upper Cone Inlet wrench flat.
Assembly 1 12
9 - Union ** Single Outlet
10 - Thrust Plate only. 4
11 - Lower Cone
BULB SEAT
DETAIL
109 mm 165 mm
82,5 mm 82,5 mm 82,5 mm 56 mm 7
8
5
9 3/4"
BSPT SEE DETAIL
113 mm ABOVE 4
WRENCHING 6 1
SQUARE 30 mm
ACROSS FLATS 3/4" BSPT 3 2
48 mm 19,0 mm DIA.
SINGLE OUTLET DOUBLE OUTLET ORIFICE
FIGURE 3
DN20 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE818 SINGLE OUTLET AND FIGURE FE186 DOUBLE OUTLET
Components:
1- Body 9 - Compression 15 - Warning * Temperature rating
2- Inlet * Screw Label and year of manu-
3- Diaphragm 10 - Plunger 16 - Pipe Cap facture indicated on
4- Plunger Cap (Single Outlet Inlet wrench flat.
5- Bulb 11 - Lower Cone only)
6- Union 12 - Lower Tip MJC shown
7- Lever 13 - Guard upright; may be
8- Upper Cone 14 - Guard Screw oriented as
Assembly pendent.
196 mm 111 mm
98 mm 76 mm 98 mm 98 mm
9 10 7 15
8 13
6 1"
BSPT
5 1
16 145 mm
11 4
62 mm
WRENCHING 12 14
SQUARE 38 mm 1" BSPT 3 2
ACROSS FLATS
25,4 mm DIA.
SINGLE OUTLET DOUBLE OUTLET ORIFICE
FIGURE 4
DN25 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE190 SINGLE AND DOUBLE OUTLET
TFP1346
Page 5 of 10
Components:
1- Body 9 - Compression 15 - Warning * Temperature rating
2- Inlet * Screw Label and year of manu-
3- Diaphragm 10 - Plunger 16 - Pipe Cap facture indicated on
4- Plunger Cap (Single Outlet Inlet wrench flat.
5- Bulb 11 - Lower Cone only)
6- Union 12 - Lower Tip MJC shown
7- Lever 13 - Guard upright; may be
8- Upper Cone 14 - Guard Screw oriented as
Assembly pendent.
230 mm 101 mm
8 13
6 1"
BSPT
5 1
16 160 mm
11 4
WRENCHING 72 mm 12 14
SQUARE 51,5 mm 1-1/2" 3 2
ACROSS FLATS BSPT
38,1 mm DIA.
SINGLE OUTLET DOUBLE OUTLET ORIFICE
FIGURE 5
DN40 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE181 SINGLE AND DOUBLE OUTLET
Components:
1 - Body 8 - Top Plate * 14 - Upper Cone 21 - Pipe Plug * Temperature rating
2 - Inlet 9 - Top Plate Assembly (Single Outlet only) and year of manu-
3 - Diaphragm Screw 15 - O-Ring 22 - Transit Plug facture indicated on
4 - Plunger 10 - Union Half 16 - Lower Cone (Remove at Top Plate.
5 - Bulb 11 - Union Nut 17 - Lower Tip installation)
6 - Compression 12 - Union Joint 18 - Guard MJC shown upright;
Screw Ring 19 - Guard Screw may be oriented as
7 - Lever 13 - Stop Screw 20 - Warning Label pendent.
225 mm 136 mm
14 8
21 9 12 11 5 4
1-1/2"
BSPT 16 19
182 mm 17
15
1
64 mm 2
WRENCHING 10 3
HEX 76,2 mm 22
ACROSS FLATS 50,0 mm DIA.
SINGLE OUTLET DOUBLE OUTLET ORIFICE 2" BSPT
FIGURE 6
DN50 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE192 SINGLE AND DOUBLE OUTLET
TFP1346
Page 6 of 10
1,00
0,80
0,60
0,50
0,40
0,30
OUTLET
NOMINAL PRESSURE DROP
0,20
)
250
280
640
80)
IN BAR
(K=
(K=
(K=
(K=
0,10
INLET
20
25
40
50
0,08
DN
DN
DN
DN
0,06
0,05
0,04
OPERATED
0,03 SINGLE OUTLET
MJC
0,02
0,01
10 20 30 40 60 100 200 400 600 1000
FLOW RATE IN LITERS PER MINUTE (LPM)
GRAPH A
NOMINAL PRESSURE LOSS VERSUS FLOW
SINGLE OUTLET
1,00
0,80
0,60
0,50
0,40
0,30
OUTLET OUTLET
NOMINAL PRESSURE DROP
0,20
)
70)
50)
20)
125
IN BAR
=3
=5
=9
(K=
0,10
(K
(K
(K
INLET
20
25
40
50
0,08
DN
DN
DN
DN
0,06
0,05
0,04
OPERATED
0,03 DOUBLE OUTLET
MJC
0,02
0,01
10 20 30 40 60 100 200 400 600 1000
FLOW RATE IN LITERS PER MINUTE (LPM)
GRAPH B
NOMINAL PRESSURE LOSS VERSUS FLOW
DOUBLE OUTLET
TFP1346
Page 7 of 10
ELECTRICAL CHARACTERISTICS
GUARD BROKEN Nominal Energy . . . . . . . . . . . . . . . . . . 6 millijoules
AWAY TO SHOW Resitance Range . . . . . . . . . . . . . . . . . 0.9 - 1.6 Ω GUARD BROKEN
DETAIL Maximum No Fire Current AWAY TO SHOW
30 sec. Pulse . . . . . . . . . . . . . . . . . . . 0.15 A DETAIL
0.05 sec. Pulse . . . . . . . . . . . . . . . . . 0.3 A BULB
BULB
Minimum Single Firing Current
D.C. . . . . . . . . . . . . . . . . . . . . . . . . . . 0.6 A ACTUATOR
10 ms. Pulse . . . . . . . . . . . . . . . . . . . 0.9 A
Recommended Single Firing Current . . 1.0 A
Recommended Series Firing Current . . 3.0 A
Maximum Monitoring Current . . . . . . . . 0.01 A
ACTUATOR ADAPTER
INLET
DIAPHRAGM
(PRESSURE
NON-OPERATED FROM SUPPLY,
MJC NO WATER FLOW)
OUTLET OUTLET
GUARD BULB (WATER FLOW (WATER FLOW
WARNING WARNING FROM MJC) PLUNGER FROM MJC)
SIDE SIDE
FIGURE 8
NOTIFICATION TAG FOR
DN25, DN40, AND DN50 SERIES
MJC MULTIPLE JET CONTROLS
DIAPHRAGM INLET
(WATER FLOW
OPERATED FROM SUPPLY)
MJC
FIGURE 9
MJC MULTIPLE JET CONTROLS
OPERATION
TFP1346
Page 9 of 10