Series MJC Multiple Jet Controls


DN20, DN25, DN40, and DN50, 12 bar
BSPT Inlet & Outlets Threads
General Features
• Available in four pipe sizes
Description • Fully automatic using proven frangi-
ble glass bulb as the heat detection
The TYCO Series MJC Multiple Jet medium
Controls are control valves with self-
contained heat actuating units. Avail- • Installed upright (heat sensitive bulb
able in DN20 through DN50 pipe sizes, at top) for water supplies from either
they are designed for use as the sys- a dry pipe or deluge system or pen-
tem control valve for fire protection sys- dent (heat sensitive bulb at bottom)
tems of limited size, where the MJCs for a water supply from a wet system
are located within the protected area. • Defined areas of protection to provide
Upon operation, the MJCs permit a flow total coverage of specific zones
of extinguishing medium (usually wa-
• DN25, DN40, and DN50 provided
ter) through open spray devices, such
as nozzles or non-automatic (open) with protective guard Technical
sprinklers.
The MJCs are typically used as an aux-
• DN25, DN40, and DN50 has option
for thermoelectric actuation that can Data
iliary deluge valve to control the flow of be used in combination with highly
Approvals
water to specific areas within a larger sensitive detection systems and/or
LPCB Approved
wet pipe, dry pipe, or deluge system. manual electric actuation
(Refer to Tables A, B, C, and D.)
As such they can be used with supply
piping from either a wet pipe system NOTICE Working Pressure Range
(Figure 1) or a dry pipe or deluge sys- The TYCO Series MJC Multiple Jet 1,4 to 12,0 bar
tem (Figure 2). Controls described herein must be in- Temperature Ratings
In all cases, waterflow alarms are pro- stalled and maintained in compliance Refer to Tables A, B, C, and D.
vided by the main automatic control with this document, as well as with the
valve for the system that supplies the applicable standards recognized by Pressure Loss
supply line to the Series MJC Multiple the Approval agency, in addition to the Refer to Graphs A and B.
Jet Controls (e.g., alarm valves, dry standards of any authorities having ju-
pipe valves, or deluge valves). risdiction. Failure to do so may impair Construction
the performance of these devices. The TYCO Series MJC Multiple Jet
For smaller design areas, the MJCs Controls are manufactured from cast
serve as an individual heat activation The owner is responsible for main- iron, leaded gun metal, copper, brass,
point and control valve (Figures 1A and taining their fire protection system nickle silver, and glass (Figures 3, 4, 5,
2A). For larger design areas, the MJCs and devices in proper operating con- and 6).
can be set up to provide multiple heat dition. Contact the installing contrac-
activation points, while still providing tor or product manufacturer with any
water flow through all discharge points questions.
with the activation of only one MJC
(Figures 1B and 2B). In this example,
water flows through the non-operated
MJC from outlet to outlet (Figure 9).

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 10 OCTOBER 2014 TFP1346


TFP1346
Page 2 of 10

FROM NORMALLY
WET LINE SUPPLY

TO OPEN TO OPEN
SPRINKLERS SPRINKLERS SUPPLY
OR NOZZLES OR NOZZLES PIPING

FRANGIBLE GLASS
BULB AT BOTTOM
MJC's
IN PENDENT
SUPPLY POSITION
PIPING

MJC
MJC's

OPEN
SPRINKLERS OPEN
FROM
OR NOZZLES SPRINKLERS
NORMALLY
OR NOZZLES
WET LINE
SUPPLY
FROM
NORMALLY NOTE:
WET LINE Supply piping and MJC's are to be
SUPPLY located in areas at 4°C or greater.

FIGURE 1A FIGURE 1B
FIGURE 1
TYPICAL PIPING ARRANGEMENT
NORMALLY WET LINE SUPPLY
(Series MJC Multiple Jet Controls in Pendent Position with Heat Sensitive Bulb at Bottom)

FRANGIBLE GLASS
BULB AT TOP

TO OPEN TO OPEN
SPRINKLERS SPRINKLERS
OR NOZZLES OR NOZZLES

FROM NORMALLY
DRY LINE SUPPLY
MJC's
IN UPRIGHT
POSITION
MJC
MJC's
SUPPLY
PIPING

OPEN
SPRINKLERS OPEN
OR NOZZLES SPRINKLERS
OR NOZZLES
FROM
NORMALLY
DRY LINE SUPPLY
SUPPLY PIPING
FROM
NORMALLY
DRY LINE
SUPPLY
FIGURE 2A FIGURE 2B
FIGURE 2
TYPICAL PIPING ARRANGEMENT
NORMALLY DRY LINE SUPPLY
(Series MJC Multiple Jet Controls in Upright Position with Heat Sensitive Bulb at Top)
TFP1346
Page 3 of 10

Design Since the MJCs utilize a thermal sens-


ing element similar to that used for a
sizes or plugging one of the two unions
on the DN50 size will convert a double
Criteria standard response, standard coverage,
frangible glass bulb type sprinkler, the
outlet MJC into a single outlet (Fig-
ures 4, 5, and 6). In all cases, the inlet
positioning rules for MJCs are the same is sealed from the outlet(s), and there
Ambient Temperature as standard sprinklers. The heat sen- is a normally open flow path from the
For normally wet pipe systems, do not sitive bulb to ceiling distance and the outlet-to-outlet of double outlet MJCs
install Series MJC Multiple Jet Controls area of thermal coverage is based on (Figure 9).
in areas that are subject to freezing. standard coverage sprinklers as a func- In the standby mode, the system sup-
Water Supply tion of the protected hazard and ceil- ply is sealed by the Diaphragm, that is
Water should be free of particles and/ ing construction provided in the ap- restrained by the Plunger. In the DN20
or site debris. Do not use sea or brack- plicable standards recognized by the assembly, the Plunger is held in posi-
ish water. Approval agency for standard cover- tion directly by the frangible glass Bulb.
age sprinklers. In the DN25, DN40, and DN50 assem-
Piping Arrangements blies, the Plunger is indirectly held in
A “wet supply line” is typically being Pressure Loss
Graph A provides the pressure loss ver- position by the frangible Bulb and the
supplied from an alarm valve (Figure Lever Arm (Figures 3, 4, 5, and 6).
1) and the “dry supply line” is typically sus flow for the MJC configured as a
being supplied from either a dry pipe single outlet, and Graph B provides the The frangible glass Bulb contains a liq-
valve or deluge valve (Figure 2). Water- pressure loss versus flow for the MJC uid that has a freeze-point below -50°C
flow alarms, system pressure gauges, configured for double outlets. and a high coefficient of expansion. A
and flow test capability are therefore predetermined amount of vapor is her-
Thermoelectric Actuation metically sealed within the frangible
provided by the alarm, dry pipe, or del- When the Thermoelectric Actuation
uge valve. is applied, the MJCs can be operated glass Bulb. The liquid naturally expands
automatically as part of a heat/smoke under the influence of increasing tem-
Sequence of Operation detection system or manually. In ei- perature as occurs in the event of a fire,
• For a wet pipe system supply, water ther case, suitable control equipment thus increasing the internal pressure
is readily available for flow through must be selected based on the actua- within the frangible glass Bulb until the
the TYCO Series MJC Multiple Jet tor electrical ratings (Figure 7), the re- vapor is absorbed and subsequently
Controls; however, water is only al- quirements of the customer, and the shatters the frangible glass Bulb allow-
lowed past the MJCs when the glass codes governing installation of electric ing the MJCs to open. The temperature
bulb in the MJCs is actuated by heat detection systems. The actuator leads at which this happens is determined
(or the thermoelectric actuator). are encased in a flexible conduit (Figure by the amount of vapor held within the
7) for attachment to an electrical junc- frangible glass Bulb thus the operating
• For a dry pipe system supply, oper- tion box.
ation of the glass bulb in the MJCs temperature of the MJCs can be accu-
when actuated by heat (or the ther- When considering the power supply for rately controlled (Figures 3, 4, 5, and 6).
moelectric actuator) releases air operating the Thermoelectric Actuators, In the event of a fire the frangible glass
pressure to permit operation of a dry be aware that the Thermoelectric Ac- Bulb shatters and directly releases the
pipe valve, and then upon operation tuator, after operation, may be an open Plunger Valve of the DN20 MJCs or in-
of the dry pipe valve, water becomes circuit, short circuit, or connected to directly releases the Plunger by releas-
available to flow through the operat- earth. Therefore, it is essential that the ing the Lever Arm of the DN25, DN40,
ed MJCs. power supply be suitably protected. or DN50 MJCs. This action in turn al-
• For a deluge system supply and upon The recommended storage life (at am- lows water pressure to lift the Dia-
operation of the deluge system in re- bient temperature) for the Thermoelec- phragm and allow water pressure to
sponse to a dedicated supplemen- tric Actuator according to the supplier pass through to the distribution piping
tal detection system, water becomes is 10 years (for METRON™* Actuators, and water distribution devices onto the
available to the MJCs; however, water refer to DR2005/C1). The working tem- fire (Figures 3, 4, 5, and 6).
is only permitted past the glass bulb perature for the Thermoelectric Actua- When a Thermoelectric Actuator is
in the MJCs if the glass bulb has been tor is -40°C to 100°C (for up to 20 hours
provided any temperature greater than utilized (Figure 7), the Thermoelectric
actuated by heat (or the thermoelec- 70°C occurs immediately prior to firing). Actuator responds to a Control Panel
tric actuator). Storage temperature is -30°C to 70°C. by passing a small electrical current
After 10 years, the TYCO Series MJC through it causing a pin to be extend-
MJC Installation Position ed, shattering the glass Bulb and actu-
The MJCs is installed in the upright po- Multiple Jet Controls supplier should
be contacted regarding the suitability ating the MJC. The Control Panel may
sition (heat sensitive bulb at top as il- be automatically operated by a heat or
of the unit for continued use.
lustrated in Figures 3, 4, 5, and 6) when smoke detection system or manually
supplied from a dry pipe or deluge sys- operated by a manual pull station.
tem, or can be installed in the pendent
position for a wet pipe system supply
Operation
(heat sensitive bulb at bottom). For ex- The DN20 TYCO Series MJC Multi-
ample, in a wet pipe system supply, the ple Jet Controls has an inlet connect-
MJCs can be installed above a ceiling ed to either a single or double outlet
where its heat sensitive bulb is exposed (Figure 3). For the DN25, DN40, and
below the ceiling line. In all cases, the DN50 MJCs, the central inlet is con-
heat sensitive bulb must be in the pro- nected to the double outlets (Figures 4,
tected area. 5, and 6). Using a cap instead of one of
the two unions on the DN25 and DN40
TFP1346
Page 4 of 10

Components:
1 - Body 12 - O-Ring ** MJC shown
2 - Inlet * 13 - O-Ring upright; may be
3 - Diaphragm Housing ** oriented as
5
4 - Plunger 14 - Spring Plate ** pendent.
5 - Bulb 11 14
6 - Gasket * Temperature rating
7 - Compression and year of manu-
facture indicated on 13 10
Screw
8 - Upper Cone Inlet wrench flat.
Assembly 1 12
9 - Union ** Single Outlet
10 - Thrust Plate only. 4
11 - Lower Cone
BULB SEAT
DETAIL
109 mm 165 mm
82,5 mm 82,5 mm 82,5 mm 56 mm 7
8
5
9 3/4"
BSPT SEE DETAIL
113 mm ABOVE 4

WRENCHING 6 1
SQUARE 30 mm
ACROSS FLATS 3/4" BSPT 3 2
48 mm 19,0 mm DIA.
SINGLE OUTLET DOUBLE OUTLET ORIFICE
FIGURE 3
DN20 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE818 SINGLE OUTLET AND FIGURE FE186 DOUBLE OUTLET

Components:
1- Body 9 - Compression 15 - Warning * Temperature rating
2- Inlet * Screw Label and year of manu-
3- Diaphragm 10 - Plunger 16 - Pipe Cap facture indicated on
4- Plunger Cap (Single Outlet Inlet wrench flat.
5- Bulb 11 - Lower Cone only)
6- Union 12 - Lower Tip MJC shown
7- Lever 13 - Guard upright; may be
8- Upper Cone 14 - Guard Screw oriented as
Assembly pendent.

196 mm 111 mm

98 mm 76 mm 98 mm 98 mm
9 10 7 15

8 13
6 1"
BSPT
5 1
16 145 mm
11 4

62 mm
WRENCHING 12 14
SQUARE 38 mm 1" BSPT 3 2
ACROSS FLATS
25,4 mm DIA.
SINGLE OUTLET DOUBLE OUTLET ORIFICE
FIGURE 4
DN25 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE190 SINGLE AND DOUBLE OUTLET
TFP1346
Page 5 of 10

Components:
1- Body 9 - Compression 15 - Warning * Temperature rating
2- Inlet * Screw Label and year of manu-
3- Diaphragm 10 - Plunger 16 - Pipe Cap facture indicated on
4- Plunger Cap (Single Outlet Inlet wrench flat.
5- Bulb 11 - Lower Cone only)
6- Union 12 - Lower Tip MJC shown
7- Lever 13 - Guard upright; may be
8- Upper Cone 14 - Guard Screw oriented as
Assembly pendent.

230 mm 101 mm

115 mm 90 mm 115 mm 115 mm


9 10 7 15

8 13
6 1"
BSPT
5 1
16 160 mm
11 4

WRENCHING 72 mm 12 14
SQUARE 51,5 mm 1-1/2" 3 2
ACROSS FLATS BSPT
38,1 mm DIA.
SINGLE OUTLET DOUBLE OUTLET ORIFICE
FIGURE 5
DN40 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE181 SINGLE AND DOUBLE OUTLET

Components:
1 - Body 8 - Top Plate * 14 - Upper Cone 21 - Pipe Plug * Temperature rating
2 - Inlet 9 - Top Plate Assembly (Single Outlet only) and year of manu-
3 - Diaphragm Screw 15 - O-Ring 22 - Transit Plug facture indicated on
4 - Plunger 10 - Union Half 16 - Lower Cone (Remove at Top Plate.
5 - Bulb 11 - Union Nut 17 - Lower Tip installation)
6 - Compression 12 - Union Joint 18 - Guard MJC shown upright;
Screw Ring 19 - Guard Screw may be oriented as
7 - Lever 13 - Stop Screw 20 - Warning Label pendent.

225 mm 136 mm

112,5 mm 135 mm 112,5 mm 112,5 mm 84 mm 52 mm


6 13 7 20 18

14 8

21 9 12 11 5 4
1-1/2"
BSPT 16 19
182 mm 17
15
1
64 mm 2
WRENCHING 10 3
HEX 76,2 mm 22
ACROSS FLATS 50,0 mm DIA.
SINGLE OUTLET DOUBLE OUTLET ORIFICE 2" BSPT
FIGURE 6
DN50 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE192 SINGLE AND DOUBLE OUTLET
TFP1346
Page 6 of 10

1,00
0,80
0,60
0,50
0,40
0,30
OUTLET
NOMINAL PRESSURE DROP

0,20

)
250

280

640
80)
IN BAR

(K=

(K=

(K=

(K=
0,10
INLET
20

25

40

50
0,08
DN

DN

DN

DN
0,06
0,05
0,04
OPERATED
0,03 SINGLE OUTLET
MJC
0,02

0,01
10 20 30 40 60 100 200 400 600 1000
FLOW RATE IN LITERS PER MINUTE (LPM)
GRAPH A
NOMINAL PRESSURE LOSS VERSUS FLOW
SINGLE OUTLET

1,00
0,80
0,60
0,50
0,40
0,30
OUTLET OUTLET
NOMINAL PRESSURE DROP

0,20
)

70)

50)

20)
125
IN BAR

=3

=5

=9
(K=

0,10
(K

(K

(K

INLET
20

25

40

50

0,08
DN

DN

DN

DN

0,06
0,05
0,04
OPERATED
0,03 DOUBLE OUTLET
MJC
0,02

0,01
10 20 30 40 60 100 200 400 600 1000
FLOW RATE IN LITERS PER MINUTE (LPM)
GRAPH B
NOMINAL PRESSURE LOSS VERSUS FLOW
DOUBLE OUTLET
TFP1346
Page 7 of 10

Installation Inspection, testing, and maintenance


must be performed in accordance with
The TYCO Series MJC Multiple Jet the requirements of the authority having
Controls must be installed per the sys- jurisdiction, and any impairment must
tem designer’s specifications, which be immediately corrected. MJCs that
have been based on the information are found leaking or exhibiting visible
provided in the Design Criteria section. signs of corrosion must be replaced.
Also, replace any MJCs that have a
Exercise care to avoid damage to the cracked bulb or that has lost liquid from
MJCs before, during, and after installa- its bulb. (Refer to Installation Section.)
tion. Replace MJCs damaged by drop-
ping, striking, wrench twist/slippage, Inspections will be limited to a visual
or the like. Also, replace any MJCs that inspection as would be performed for
have a cracked bulb or that has lost liq- automatic sprinklers and at a frequen-
uid from its bulb. The DN25, DN40, and cy as required for automatic sprinklers.
DN50 MJCs are provided with a Notifi- The TYCO Series MJC Multiple Jet
cation Tag (Figure 8). Controls, by the nature of their design,
cannot be trip tested.
Do not install a TYCO Series MJC Mul-
tiple Jet Control if the bulb is cracked The owner is responsible for the in-
or there is a loss of liquid from the bulb. spection, testing, and maintenance of
With the MJC held so that the bulb is their fire protection system and devices
horizontal, a small air bubble should be in compliance with this document, as
present. The diameter of the air bubble well as with the applicable standards of
is approximately 4,5 mm to 6,4 mm for any authorities having jurisdiction. Con-
the 68°C to 141°C temperature ratings. tact the installing contractor or product
manufacturer with any questions.
The MJCs utilize a frangible glass bulb
heat sensitive element. Handle with Automatic sprinkler systems should be
care. The DN25, DN40, and DN50 inspected, tested, and maintained by a
MJCs are provided with a guard. Re- qualified Inspection Service in accor-
moval of the guard voids the manufac- dance with local requirements and/or
turer’s warranty. national codes.

Care and Limited


Maintenance Warranty
Before closing a fire protection system For warranty terms and conditions, visit
main control valve for maintenance www.tyco-fire.com.
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection sys- Ordering
tems from the proper authorities and
notify all personnel who may be affect- Procedure
ed by this decision.
Multiple Jet Control
After a fire, replace all TYCO Series Specify: (specify size and temperature
MJC Multiple Jet Controls that have rating) TYCO MJC Series Multiple Jet
operated with new Series MJC Multiple Control, Figure (specify) Multiple Jet
Jet Controls of the same type and tem- Control (with electrical actuator, if ap-
perature rating. Complete the replace- plicable), P/N (specify from Tables A,
ment as soon as possible and after the B, C, or D).
system is drained. Spare Series MJC
Multiple Jet Controls should be kept on
site at all times to ensure replacements
are installed with minimum of delay.
Never paint, plate, or coat, or otherwise
alter MJCs after they leave the facto-
ry. Modified MJCs must be replaced.
MJCs that have been exposed to corro-
sive products of combustion, but have
not operated, should be replaced if they
cannot be completely cleaned by wip-
ing the MJCs with a cloth or by brush-
ing it with a soft bristle brush.
Exercise care to avoid damage to the
MJCs before, during, and after installa-
tion. MJCs damaged by dropping, strik-
ing, wrench twist/slippage, or the like,
must be replaced.
TFP1346
Page 8 of 10

ELECTRICAL CHARACTERISTICS
GUARD BROKEN Nominal Energy . . . . . . . . . . . . . . . . . . 6 millijoules
AWAY TO SHOW Resitance Range . . . . . . . . . . . . . . . . . 0.9 - 1.6 Ω GUARD BROKEN
DETAIL Maximum No Fire Current AWAY TO SHOW
30 sec. Pulse . . . . . . . . . . . . . . . . . . . 0.15 A DETAIL
0.05 sec. Pulse . . . . . . . . . . . . . . . . . 0.3 A BULB
BULB
Minimum Single Firing Current
D.C. . . . . . . . . . . . . . . . . . . . . . . . . . . 0.6 A ACTUATOR
10 ms. Pulse . . . . . . . . . . . . . . . . . . . 0.9 A
Recommended Single Firing Current . . 1.0 A
Recommended Series Firing Current . . 3.0 A
Maximum Monitoring Current . . . . . . . . 0.01 A

ACTUATOR ADAPTER

TOP PLATE FLEX TOP PLATE


ACTUATOR CONDUIT ACTUATOR
SUPPORT SUPPORT
CONDUIT
ADAPTER CONNECTOR

FLEX ACTUATOR ACTUATOR


CONDUIT LEADS LEADS
FIGURE 7
OPTIONAL THERMO-ELECTRIC ACTUATOR FOR
DN25, DN40, AND DN50 SERIES MJC MULTIPLE JET CONTROLS

GUARD NO ADHESIVE OUTLET OUTLET


THIS PORTION (WATER FLOW BULB (WATER FLOW
OF LABEL THROUGH MJC IN PLUNGER THROUGH MJC IN
EITHER DIRECTION) EITHER DIRECTION)
LEVER

INLET
DIAPHRAGM
(PRESSURE
NON-OPERATED FROM SUPPLY,
MJC NO WATER FLOW)

OUTLET OUTLET
GUARD BULB (WATER FLOW (WATER FLOW
WARNING WARNING FROM MJC) PLUNGER FROM MJC)
SIDE SIDE
FIGURE 8
NOTIFICATION TAG FOR
DN25, DN40, AND DN50 SERIES
MJC MULTIPLE JET CONTROLS

DIAPHRAGM INLET
(WATER FLOW
OPERATED FROM SUPPLY)
MJC

FIGURE 9
MJC MULTIPLE JET CONTROLS
OPERATION
TFP1346
Page 9 of 10

FIGURE MAXIMUM BULB


NUMBER TEMPERATURE TEMPERATURE PART
DN APPROVALS LIQUID
and RATING WHERE MJC IS NUMBER
COLOR
STYLE LOCATED
57°C 27°C Orange MJCSO0027A
68°C 38°C Red MJCSO0027B
FIGURE FE818 79°C 49°C Yellow MJCSO0027D
20 2
SINGLE OUTLET
93°C 63°C Green MJCSO0027E
141°C 111°C Blue MJCSO0027G
57°C 27°C Orange MJCDO0027A
68°C 38°C Red MJCDO0027B
FIGURE FE186 79°C 49°C Yellow MJCDO0027D
20 1
DOUBLE OUTLET
93°C 63°C Green MJCDO0027E
141°C 111°C Blue MJCDO0027G
Notes:
1. Approved by the Loss Prevention Certification Board (LPCB Refer to No. 007f/01).
2. Approved by the Loss Prevention Certification Board (LPCB Refer to No. 007f/02).
TABLE A
LABORATORY LISTINGS AND APPROVALS
FOR DN20 SERIES MJC MULTIPLE JET CONTROLS

FIGURE MAXIMUM PART PART


BULB
NUMBER TEMPERATURE TEMPERATURE NUMBER NUMBER
DN APPROVALS LIQUID
and RATING WHERE MJC IS DOUBLE SINGLE
COLOR
STYLE LOCATED OUTLET OUTLET

N/A 57°C 27°C Orange MJCDO0034A MJCSO0034A

1 68°C 38°C Red MJCDO0034B MJCSO0034B


FIGURE FE190
25 DOUBLE OUTLET 79°C 49°C Yellow MJCDO0034D MJCSO0034D
WITH GUARD
N/A 93°C 63°C Green MJCDO0034E MJCSO0034E
141°C 111°C Blue MJCDO0034G MJCSO0034G
57°C 27°C Orange 25013 *- - -
FIGURE FE2656
DOUBLE OUTLET 68°C 38°C Red 25015 *- - -
25 WITH GUARD N/A
AND ELECTRICAL 79°C 49°C Yellow 25017 *- - -
ACTUATOR**
93°C 63°C Green 25019 *- - -
Notes:
1. Approved by the Loss Prevention Certification Board (LPCB Refer to No. 007f/03).
N/A: Not Approved
* Not Available
** On request, avaiable with Walkbery flex cable.
TABLE B
LABORATORY APPROVALS AND PART NUMBERS
FOR DN25 SERIES MJC MULTIPLE JET CONTROLS
TFP1346
Page 10 of 10

FIGURE MAXIMUM PART PART


BULB
NUMBER TEMPERATURE TEMPERATURE NUMBER NUMBER
DN APPROVALS LIQUID
and RATING WHERE MJC IS DOUBLE SINGLE
COLOR
STYLE LOCATED OUTLET OUTLET

N/A 57°C 27°C Orange MJCDO0048A MJCSO0048A

1 68°C 38°C Red MJCDO0048B MJCSO0048B


FIGURE FE181
40 DOUBLE OUTLET 79°C 49°C Yellow MJCDO0048D MJCSO0048D
WITH GUARD
N/A 93°C 63°C Green MJCDO0048E MJCSO0048E
141°C 111°C Blue MJCDO0048G MJCSO0048G
57°C 27°C Orange 25025 *- - -
FIGURE FE2378
DOUBLE OUTLET 68°C 38°C Red 25027 *- - -
40 WITH GUARD N/A
AND ELECTRICAL 79°C 49°C Yellow 25029 *- - -
ACTUATOR**
93°C 63°C Green 25031 *- - -
Notes:
1. Approved by the Loss Prevention Certification Board (LPCB Refer to No. 007f/03).
N/A: Not Approved
* Not Available
** On request, avaiable with Walkbery flex cable.
TABLE C
LABORATORY APPROVALS AND PART NUMBERS
FOR DN40 SERIES MJC MULTIPLE JET CONTROLS

FIGURE MAXIMUM PART PART


BULB
NUMBER TEMPERATURE TEMPERATURE NUMBER NUMBER
DN APPROVALS LIQUID
and RATING WHERE MJC IS DOUBLE SINGLE
COLOR
STYLE LOCATED OUTLET OUTLET

N/A 57°C 27°C Orange MJCDO0060A MJCSO0060A

1 68°C 38°C Red MJCDO0060B MJCSO0060B


FIGURE FE192
50 DOUBLE OUTLET 79°C 49°C Yellow MJCDO0060D MJCSO0060D
WITH GUARD
N/A 93°C 63°C Green MJCDO0060E MJCSO0060E
141°C 111°C Blue MJCDO0060G MJCSO0060G
57°C 27°C Orange 25037 *- - -
FIGURE FE2073
DOUBLE OUTLET 68°C 38°C Red 25039 *- - -
50 WITH GUARD N/A
AND ELECTRICAL 79°C 49°C Yellow 25041 *- - -
ACTUATOR**
93°C 63°C Green 25043 *- - -
Notes:
1. Approved by the Loss Prevention Certification Board (LPCB Refer to No. 007f/03).
N/A: Not Approved
* Not Available
** On request, avaiable with Walkbery flex cable.
TABLE D
LABORATORY APPROVALS AND PART NUMBERS
FOR DN50 SERIES MJC MULTIPLE JET CONTROLS

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright © 2014 Tyco Fire Products, LP. All rights reserved.