NSCP 2015 SEISMIC ANALYSIS (STATIC FORCE PROCEDURE)
Building Data: Seismic Factors:
# suspended floors 5 Importance Factor, I  1 NSCP 2015 Section 208.4.2 (Table 208‐1)

Floor  Height  Dead Load  Soil profile type, S  SD NSCP 2015 Section 208.4.3 (Table 208‐2)


Level (m) (kN) Seismic Zone factor, Z  0.4 NSCP 2015 Section 208.4.4.1 (Table 208‐3)
5 3.1 4802.6 15.5 Siesmic source Type A NSCP 2015 Section 208.4.4.2 (Table 208‐4)
4 3.1 4802.6 12.4 Near source factor, Na  1.2 NSCP 2015 Section 208.4.4.3 (Table 208‐5)
3 3.1 4321.4 9.3 Near source factor, Nv  1.6 NSCP 2015 Section 208.4.4.3 (Table 208‐6)
2 3.1 3602.7 6.2 Seismic coefficient, Ca  0.528 NSCP 2015 Section 208.4.4.4 (Table 208‐7)
1 3.1 4556.6 3.1 Seismic coefficient, Cv  1.024 NSCP 2015 Section 208.4.4.4 (Table 208‐8)
0 0 Structural System Factor, R  6 NSCP 2015 (Table 208‐11A to 208‐11D)
‐1 0 Frame material factor, Ct  0.0488 NSCP 2015 Section 208.5.2.2
‐2 0 Base Shear Computation:
‐3 0 Fundamental Period of Vibration:
‐4 0  TA = Ct(hn)3/4 = 0.381 sec C t (h n ) 3/4  NSCP 2015 Sec 208.5.2.2 (Method A)
‐5 0 TB= sec (Method B, Computed using Rayleigh method)
‐6 0 T= 0.38 sec controls!
‐7 0 Total Design Base Shear:
‐8 0 V = (CvI/RT) x W = 0.447693 W         = 9887.70 kN NSCP 2015 Section 208.5.2.2 (Eq. 208‐8)
‐9 0 The total design base shear need not exceed:
‐10 0 V = (2.5CaI/R) x W = 0.2200 W         = 4858.90 kN  (✔) NSCP 2015 Section 208.5.2.2 (Eq. 208‐9)
‐11 0 The total base shear shall not be less than:
‐12 0 V = (0.11CaI) x W = 0.05808 W         = 1282.75 kN NSCP 2015 Section 208.5.2.2 (Eq. 208‐10)
‐13 0 For seismic Zone 4, the total base design shear shall not be less than:
‐14 0 V = (0.8ZNVI/R) x W = 0.085333 W         = 1884.66 kN NSCP 2015 Section 208.5.2.2 (Eq. 208‐11)
TOTAL: 15.5 22085.9 The Total Base Design Shear = 0.22 W         = 4858.9 kN

Floor  wh  Force at top due to whiplash effect


w (kN) h (m) F (kN)
level (kN∙m) for T ≤ 0.7 0
5 4802.6 15.5 74440.3 1717.11 for 0.7 < T <3.6 0.07TV = 129.66 Ft = 0 kN
4 4802.6 12.4 59552.2 1373.69 for T ≥ 3.6 0.25V = 1214.72
3 4321.4 9.3 40189 927.04
2 3602.7 6.2 22336.7 515.24
1 4556.6 3.1 14125.5 325.83 Vertical Distribution of forces:
0 0 0 0 0.00
‐1 0 0 0 0.00 Level n Fn
‐2 0 0 0 0.00 Level 8 F8
‐3 0 0 0 0.00 Level 7 F7
‐4 0 0 0 0.00 Level 6 F6
‐5 0 0 0 0.00 Level 5 F5 1717.11 kN
‐6 0 0 0 0.00 Level 4 F4 1373.69 kN
‐7 0 0 0 0 Level 3 F3 927.04 kN
‐8 0 0 0 0 Level 2 F2 515.24 kN
‐9 0 0 0 0 Level 1 F1 325.83 kN
‐10 0 0 0 0
‐11 0 0 0 0
‐12 0 0 0 0 *n = uppermost level (for n>8)
‐13 0 0 0 0 *Level 1 is the first suspended floor above the ground
‐14 0 0 0 0 *References:  ∙National Structural Code of the Philippines 2015
Σ = 22085.9 210643.8     ∙Uniform Building Code (UBC) 1997
*Programmed by: Kevin Saluague (kevinsaluague09@gmail.com)     ∙Wind and Earthquake Resistant Buildings by Taranath, Bungale