Allowable Lateral Displacement for Shear Wall

As per UBC 97
Height of inter story of Shear Wall, Hs = 5.486 m
If, Building Period T<0.7 Sec, Then ∆all = 137.15 mm
If, Building Period T>0.7 Sec, Then ∆all = 109.72 mm

As per IBC 2012


Height of inter story of Shear Wall, Hs = 5.486 m
For group III, Then ∆all = 54.86 mm
For group II, Then ∆all = 82.29 mm
For group I, Then ∆all = 109.72 mm
29.6
SHEAR WALL REINFORCEMENT DESIGN
For wall Grid D-E Semi Basement
Concrete Strength = 20 N/mm2
Rebar Material type = 500 N/mm2

Thickness of Wall = 230 mm 9.05512 inch


Length = 5.00 m 16.4042 ft
Height = 3.35 m 11 ft
clear cover = 25 mm
Reinfocement in Wall:
Required Main/Vertical Reinf from Et = 2656 mm2 Total
Selet Rebar (A) = 10 ∅ in both faces
Required Spacing = 295.71 mm
Provide Spacing (Auto Suggestion) = 275.00
Finally Provided to fulfil min Req. = 150.00 mm
Minimum Required Reinf. Ratio = 0.0038    ACI 318-14 (11.6.2(a)
Provided Reinfocement Ratio = 0.00455 OK
Maximum Spacing = 690 mm 3xThickness
or 450 mm 18inch
or 1666.7 mm Length of Wall/3
Maximum Allowable Spacing = 450.0 mm OK
Required Shear/Horizontal Reinf from = 575 mm2 Total
Selet Rebar (A) = 10 ∅ in both faces
Required Spacing = 273.18 mm
Provide Spacing (Auto Suggestion) = 250.00
Finally Provided to fulfil min Req. = 200.00 mm
Minimum Required Reinf. Ratio = 0.0038    ACI 318-14 (11.6.2(b)
Provided Reinfocement Ratio = 0.00524 OK ACI 318-14 (2.2)

Maximum Spacing = 690 mm 3xThickness


or 450 mm 18inch
or 1000.0 mm Length of Wall/5
Maximum Allowable Spacing = 450.0 mm OK

10 ∅ @ 150 mm C/C

10 ∅ @ 200 mm C/C