INSPECTION & TESTING REQUIREMENTS REVISION: 11/30/2015 CODE NUMBER: PAGE:

SAUDI ARAMCO FORM-175 REPLACES: 06/15/2011 IR120200 1 of 2


SCOPE: BUILDING: Metal; One Story, Pre-engineered.

TEST AND INSPECTION PER: 12-SAMSS-014, and Specifications as Noted Below.

(1).VISUAL INSPECTION BY BUYER INSPECTION REPRESENTATIVE


(2) REVIEW AND VERIFICATION OF MATERIAL CERTIFICATES AND INSPECTION RECORDS
(3) SUBMISSION OF MANUFACTURING, INSPECTION AND QUALITY RECORDS
0010
0012
***R
Pre-Fabrication/Production Requirements
Raw Material Certificates and Reports (MTR’s)
Specification Details / Notes:
Per ASTM or equivalent.

0022 R X Material Heat Numbers Steel elements shall be Traceable to Heat Numbers. Material
should be traceable through documentation and marking (hard
punch).

0032 R X Manufacturer’s Qualified/Certified Inspectors Processes of Welding, Painting and Coating.

0042 R X Approval drawings, Erection Drawings and Anchor bolt plan Verify approval Per 12-SAMSS-014.

0052 R Welding Procedure Specification (WPS) and Procedure Verify approval Per SAEP 352. AWS D1.1 or AWS D1.3.
Qualification Records (PQR

0062 R X Welder Qualification Records Per AWS D1.1 or AWS D1.3.

0072 R X NDT Personnel and Procedures When required, verify valid personnel qualification and
procedures.

0020
0010
*** In process inspection & test requirement
Workmanship, Components, and Dimensions:
Specification Details / Notes:

0020 R X a) Built-Up Sections, Rods, Rolled Steel Sections, Cold Form Note: Cable bracing is not allowed.
Zee, Cee Sections

0030 R X b) Structural Bolts, Nuts & Washers Fasteners shall be Hot Dip Galvanized

0040 R X c) Roof and Wall Coverings including Insulation As per 12-SAMSS-014

0050 R X d) Roof And Wall Fasteners Use ASTM B695 carbon steel. In "coastal" areas, use
austenitic (series 300) fasteners.

0060 R X e) Sealants and Closures As per 12-SAMSS-014

0070 R X f) Aluminum and/or Steel Windows

IR120200 Continued...
INSPECTION & TESTING REQUIREMENTS REVISION: 11/30/2015 CODE NUMBER: PAGE:
SAUDI ARAMCO FORM-175 REPLACES: 06/15/2011 IR120200 2 of 2
(1).VISUAL INSPECTION BY BUYER INSPECTION REPRESENTATIVE
(2) REVIEW AND VERIFICATION OF MATERIAL CERTIFICATES AND INSPECTION RECORDS
(3) SUBMISSION OF MANUFACTURING, INSPECTION AND QUALITY RECORDS
0080 R X g) Personnel & Equipment Doors, Locksets Per SA-175 code 120400 or 090700 if applicable.

0090 R X h) Translucent Roof Panels Shall be supported by Min. 3 Roof Purlins or 2-Span condition
(DWG Review)

0100 R X i) Eaves Gutter and Downspouts

0110 R X j) Ventilators, Louvers and Roof Openings

0120 R X k) Structural Framing Fabrication Per 12-SAMSS-014

0130 R X Welding Inspection 12-SAMSS-014:Visual weld inspection shall take place prior to
coating operations. (See Note 3.)

0140 R X Radiography Spot radiography shall be used on all butt-welded web and
flange splices per AWS D1.1.

0150 R X Hoists or Overhead Cranes. When applicable. Hoists and cranes shall meet CMAA (Crane Manufacturers
Association of America) specifications. For capacity over
5,000kg use 175 code # 313100.

0030
0010
*** R X
Final inspection & test requirements
Shop Assembly & Fabrication Tolerances
Specification Details / Notes:
12-SAMSS-014; AWS D1.1; MBMA: AISC Code of Standard
Practice

0020 R X Coating / Painting Per SAES-H-series and SA-175 code 091900.

0030 R X Erection Marking & Identification Per 12-SAMSS-007

0040 R X Marking, Handling and shipment

0050 R X Building Design & Fabrication certificate When requested in the PO.

Notes:
(1) Refer detailed instruction sheet 175 - 000003 of inspection requirement for ideal use of this form.
(2) Additional welding inspection may be called for by Buyer Inspection Representative using established AWS D1.1 guidelines.
(3) Additional welding inspection can be called for by Company Inspector using established AWS D1.1 guidelines. All welds shall be double-sided.

End of IR120200