06 237256 001 - Print PDF
06 237256 001 - Print PDF
July 2014
Design, Installation,
Operation and
Maintenance Manual
R
FM
Questions concerning the information presented in this manual should be addressed to:
Kidde-Fenwal Inc.
400 Main Street
Ashland, MA 01721
Phone: (508) 881-2000
Fax: (508) 881-8920
SAFETY SUMMARY
Kidde ECS ADS fire suppression systems use pressurized equipment; therefore, personnel responsible for
fire suppression systems must be aware of the dangers associated with the improper handling, installation
or maintenance of this equipment.
Fire suppression system service personnel must be trained in the proper handling, installation and service
of Kidde ECS ADS Equipment and follow the instructions used in this manual and in the Safety Bulletin and
cylinder nameplate contained in Chapter 6.
Kidde has provided warnings and cautions at appropriate locations throughout the text of this manual.
These warnings and cautions are to be adhered to at all times. Failure to do so may result in serious injury
to personnel.
DEFINITIONS
Indicates an imminently hazardous situation which, if not avoided, could result in death,
WARNING serious bodily injury and/or property damage.
Pressurized (charged) cylinders are capable of violent discharge and, as such, are
extremely hazardous. Pressurized cylinders must be handled safely to avoid accidents
WARNING that could cause bodily injury, death, or property damage.
Before handling Kidde ECS ADS products, all personnel must be trained in the safe handling of the
containers as well as in the proper procedures for installation, removal, filling, and connection of other
critical devices, such as flex hoses, control heads, discharge heads, safety caps, and anti-recoil devices.
READ, UNDERSTAND and ALWAYS FOLLOW the design, installation, operation and maintenance manuals,
owners manuals, service manuals, etc., that are provided with the individual systems.
The instructions contained in this foreword and throughout the manual must be
followed in the exact sequence as written to prevent serious injury, death or
WARNING property damage.
MOVING CONTAINER
Containers must be shipped compactly in the upright position, and properly secured in place. Containers
must not be rolled, dragged or slid, nor allowed to be slid from tailgates of vehicles. A suitable hand truck,
fork truck, roll platform or similar device must be used.
ROUGH HANDLING
Containers must not be dropped or permitted to strike violently against each other or other surfaces.
STORAGE
Containers must be stored standing upright where they are not likely to be knocked over, or the containers
must be secured.
For additional information on safe handling of compressed gas cylinders, see CGA Pamphlet PI titled “Safe
Handling of Compressed Gases in Containers”. CGA pamphlets may be purchased from The Compressed
Gas Association: http://www.cganet.com
SAFETY CAP
• Each agent cylinder is factory equipped with a safety cap installed on the valve outlet, and securely
chained to the valve to prevent loss. This device is a safety feature, and will provide controlled safe
discharge when installed if the cylinder is actuated accidentally.
• The safety cap must be installed on the valve outlet AT ALL TIMES except when the cylinders are
connected into the system piping or being filled.
• The safety cap is intentionally chained to the cylinder valve to prevent loss while in service and must
not be removed from its chain.
PROTECTION CAP
A protection cap is factory installed on the actuation port and securely chained to the valve to prevent loss.
The cap is attached to the actuation port to prevent tampering or depression of the actuating pin. No
attachments (control head, pressure operated control head) are to be connected to the actuation port
during shipment, storage, or handling.
In order to prevent injury in the event of accidental cylinder discharge, the discharge
hose or valve outlet adapter must be connected to the system piping before attaching to
WARNING the cylinder valve outlet.
2. Remove safety cap and connect all cylinder valves into system piping using flex hose or valve outlet
adapter.
Control heads must be in the set position before attaching to the cylinder valve actuation
WARNING port, in order to prevent accidental discharge.
3. Remove protection cap and attach control heads, pressure control heads, pilot loops, etc. as required.
The cylinder valve safety cap must be immediately available for installation on the
cylinder valve outlet before disconnecting the cylinder discharge hose or valve adapter
WARNING from system piping. If the safety cap is missing obtain a new safety cap from Kidde Fire
Systems.
Failure to follow all instructions in this manual on the use and handling of system
components could result in serious bodily injury, death, and property damage in the
WARNING event of inadvertent and unexpected cylinder discharge.
CHAPTER 2 OPERATION
2-1 Introduction ......................................................................................... 2-1
2-2 System Controls and Indicators .............................................................. 2-1
2-2.1 General ............................................................................................... 2-1
2-3 Operating Procedures ............................................................................ 2-1
2-3.1 Automatic Operation ............................................................................. 2-1
2-3.2 Remote Manual Operation ...................................................................... 2-1
2-3.3 Local Manual Operation.......................................................................... 2-2
2-3.4 Local Manual Operation UL Listed 3-Way Directional Valves
(P/N 90-22003X-00X)............................................................................ 2-2
2-3.5 Post-Discharge Service .......................................................................... 2-2
2-4 Cylinder Recharge ................................................................................. 2-3
2-5 Special System Precautions .................................................................... 2-3
2-5.1 Systems Actuated with a Master Cylinder ................................................. 2-3
2-5.2 Systems Actuated with a Pilot Nitrogen Cylinder........................................ 2-3
CHAPTER 5 MAINTENANCE
5-1 Introduction ......................................................................................... 5-1
5-2 Maintenance Procedures ........................................................................ 5-1
5-2.1 General ............................................................................................... 5-1
5-3 Preventive Maintenance ......................................................................... 5-1
5-4 Inspection Procedures ........................................................................... 5-2
5-4.1 Weekly ................................................................................................ 5-2
5-4.1.1 Check Nitrogen Driver Cylinder Pressure .................................................. 5-2
5-4.2 Monthly ............................................................................................... 5-2
5-4.2.1 General Inspection ................................................................................ 5-2
5-4.2.2 Hazard Access ...................................................................................... 5-2
5-4.2.3 Inspect Hoses....................................................................................... 5-2
5-4.2.4 Inspect Pressure Control Heads............................................................... 5-2
5-4.2.5 Inspect Electric Control Heads ................................................................ 5-2
5-4.2.6 Inspect Cylinder and Valve Assembly for Both the Agent Cylinder
and Nitrogen Driver Cylinder .................................................................. 5-3
5-4.2.7 Inspect Brackets, Straps, Cradles and Mounting Hardware.......................... 5-3
5-4.2.8 Inspect Discharge Hoses ........................................................................ 5-3
5-4.2.9 Inspect Actuation Line ........................................................................... 5-3
5-4.2.10 Inspect Discharge Nozzles...................................................................... 5-3
5-4.2.11 Inspect Pull Stations.............................................................................. 5-3
5-4.2.12 Inspect Pressure Switches...................................................................... 5-3
5-4.3 Semi-Annual ........................................................................................ 5-4
5-4.3.1 Pressure Switch Test ............................................................................. 5-4
5-4.3.2 Electric Control Head Test ...................................................................... 5-4
5-4.3.3 Weighing Cylinders Using the Liquid Level Indicator ................................... 5-5
5-4.3.4 Weighing Cylinders without Using the Liquid Level Indicator........................ 5-8
5-4.4 2 Year ................................................................................................. 5-8
5-4.4.1 Blow Out Distribution Piping ................................................................... 5-8
5-4.5 5 Year ................................................................................................. 5-9
5-4.5.1 Inspection and Retest Procedures for Agent or Nitrogen Cylinders ............... 5-9
5-4.5.1.1 Cylinders Continuously in Service Without Discharge ................................. 5-9
5-4.5.1.2 Discharged Cylinders or Charged Cylinders that are Transported ................. 5-9
5-4.5.2 Retest ................................................................................................. 5-9
5-4.5.3 Flexible Hoses ...................................................................................... 5-9
5-5 Service ................................................................................................ 5-10
5-5.1 Cleaning .............................................................................................. 5-10
5-5.2 Nozzle Service ...................................................................................... 5-10
5-5.3 Repairs................................................................................................ 5-10
5-6 Removing an Agent Cylinder and Nitrogen Driver ...................................... 5-10
CHAPTER 1
GENERAL INFORMATION
1-1 INTRODUCTION
The Kidde Fire Systems® ECS Advanced Delivery Fire Suppression System (Kidde ECS ADS)
Series with 3M™ Novec™ 1230 Fire Protection Fluid (herein refer to as “agent”) is listed by
Underwriters Laboratories Inc. (UL) and approved by FM Approvals. These systems are
designed for total flooding in accordance with National Fire Protection Association (NFPA) 2001,
Standard for Clean agent Extinguishing Systems. These systems have been tested to UL 2166,
Standard for Halocarbon Clean agent Extinguishing System Units, and other parameters
established jointly by UL and FM Approvals. In any situation not specifically covered by this
manual, the application and installation of the system must meet the requirements of the
standards as stated. In any case, all installations must meet the requirements of the local
Authority Having Jurisdiction (AHJ).
Kidde ECS ADS Series uses a unique method for propelling the agent from the storage cylinder,
through the system piping and out of the discharge nozzles. Nitrogen gas pressure from a
separate storage cylinder is introduced into the vapor space of the cylinder at a controlled rate.
This nitrogen pressure acts to propel the liquid agent through the pipe system at a higher flow
rate than is possible from systems which combine the nitrogen with the agent in one storage
container. The Kidde ECS ADS Series is capable of using smaller pipe sizes to discharge larger
quantities of agent than stored-pressure technology. The Kidde ECS ADS Series can also propel
the agent longer distances through a pipe network, permitting the placement of storage
cylinders farther from the protected hazard.
The Kidde ECS ADS Series are extremely well suited to applications involving remote agent
storage, and situations which limit the maximum pipe size to be used. This system can be
successfully applied to many existing Halon 1301 system pipe networks, providing easy retrofit
of these systems to a new clean agent with long-term availability.
The complexity of nitrogen introduction into the cylinder vapor space, and the resulting flow of
the agent through the pipe network, does not allow for a simple method of manual hydraulic
flow calculation. For this reason, the clean agent flow calculations have been incorporated into
a computer software program that has been rigorously validated by testing. The calculation
routine determines the flow, density, and pressure of small quantities of agent as it progresses
through the pipe, while conserving mass, energy and momentum. This method tracks the
agent from initiation of discharge to the final vapor blowdown, and ensures each nozzle will
discharge the required mass of agent in the predicted time, and at a predicted nozzle discharge
pressure. The computer program will not permit the design of systems that fall outside the
predetermined parameters set by the standards previously discussed.
The system designer must become familiar with the hardware and design sections and the
latest version of the flow calculation software program. The required procedures must be used
to determine the proper system design for the hazard in question, as well as to input the design
parameters into the computer program (for more information see the latest version of the Flow
Calculation Software User’s Guide 06-237256-004).
System installers, inspectors and service personnel must become familiar with the hardware,
installation, inspection and service sections of this manual, as well as all WARNING and
CAUTION declarations in this manual. Failure to comply with all warnings may result in death,
serious injury and property damage.
1-2.1 Applications
The Kidde ECS ADS Series are used to suppress fires in specific hazards where:
• A clean agent is required to keep cleanup time and downtime to a minimum.
• An electrically non-conductive agent is required to avoid additional equipment damage.
• Suppression capability with low weight and small storage space is a factor.
• The hazard is occupied by personnel, creating human safety concerns.
Kidde ECS ADS Systems are designed for the following classes of fire:
• Class A Surface Type Fires: Wood, plastics or other type material
• Class B Fires: Flammable liquids (see Table 4-2)
• Class C Hazards: Energized electrical equipment
For hazards beyond the scope described above, the designer must consult with Kidde Fire
Systems and NFPA 2001 Edition 2012 on the suitability of the agent for protection, necessary
design concentration and personnel exposure effects from that concentration.
The agent shall not be used on fires involving the following materials, unless they have been
tested to the satisfaction of the AHJ:
• Certain chemicals or mixtures of chemicals, such as cellulose nitrate and gunpowder, that
are capable of rapid oxidation in the absence of air.
• Reactive metals such as lithium, sodium, potassium, magnesium, titanium, zirconium, ura-
nium and plutonium.
• Metal hydrides.
• Chemicals capable of undergoing autothermal decomposition, such as certain organic per-
oxides and hydrazine.
ADS Series Systems are especially suitable for:
• Data processing facilities
• Data and records storage areas
• Telecommunications facilities
• Electrical switchgear areas
• Process control rooms
• High-value medical facilities
• High-value industrial equipment areas
• Libraries, museums, art galleries and similar areas
• Anechoic and other environmental test chambers
• Flammable liquid storage and use areas
• Engine test stands
• Chemical mixing rooms
• Oil and gas production, refining and handling facilities
1-2.2.1 Toxicity
Unnecessary exposure to clean agents is to be avoided in accordance with the requirements of
NFPA-2001. As such, upon operation of a system pre-discharge alarm, all personnel should
immediately exit the protected space. In no case shall personnel remain in a room in which
there is a fire. In the very unlikely instance where a clean agent system should discharge
unexpectedly into an occupied room, all personnel should proceed in a calm and orderly
manner to an exit and leave the room.
The agent has been evaluated for cardiac sensitization in accordance with test protocols
approved by the United States Environmental Protection Agency (U.S. EPA). The EPA's SNAP
Program classifies the agent as acceptable for use as a total flooding agent in occupied spaces
with specific limitations. Refer to the SNAP program rules or NFPA 2001 for more information.
The agent has been judged acceptable by the U.S. EPA for use in occupied spaces when used
in accordance with the guidance of NFPA 2001. In accordance with NFPA 2001, Kidde
Engineered Systems designed for use with agent vapor concentrations up to ten volume
percent in air are permitted. See NFPA 2001, Sect. 1-6, Safety. Although the agent has low
toxicity at concentrations in air needed to extinguish most fires, certain safety considerations
must be observed when applying and handling the agent.
1-2.2.2 Decomposition
The interaction of agent vapor with flames during extinguishment results in the formation of
decomposition products including halogen acids. Early fire detection and prompt discharge of
the agent results in rapid flame extinguishment keeping the amount of decomposition product
formation to a minimum.
1-2.2.3 Cleanliness
The agent is clean and leaves no residue, thereby eliminating costly after-fire clean-up and
keeping expensive downtime to a minimum. Most materials such as steel, stainless steel,
aluminum, brass and other metals as well as plastics, rubber and electronic components are
unaffected by exposure to the agent during a discharge.
1-2.2.5 Storage
The agent is stored in steel cylinders as a liquid, super-pressurized with nitrogen to 360 psig
at 70°F (24.8 bar gauge at 21°C).
The nitrogen is stored in a seamless steel container at 1800 psig at 70°F (124 bar gauge at
21°C). The pressure of both containers (agent and nitrogen) varies substantially with
temperature, as illustrated in Tables 1-1 and 1-2. Tables 1-3 and 1-4 give the physical
properties of agent.
Pressure-Temperature Curve
Isometric Diagram
1300
1200
92.4 lb/ft3
1100
88.6 lb/ft3
1000
900
Pressure (psig)
800
700
600
70 lb/ft3
500
400
300
200
100
0
0 25 50 75 100 125 150 175 200 225
Temperature (°F)
Figure 1-1. Agent Pressure-Temperature Curve Isometric Diagram, U.S. Customary Units
Table 1-4. Agent Cylinder Pressure based on Agent Cylinder Fill Density vs Temperature,
U.S. Customary Units
Pressure, psig
Fill Density
Temp, °F
35 lb./ft.3 40 lb./ft.3 50 lb./ft.3 60 lb./ft.3 70 lb./ft.3
Pressure-Temperature Curve
Isometric Diagram
120
1480 kg/m3
100
Pressure/bar(g)
80 1420 kg/m3
60
40
1121 kg/m3
20
0
-20 -10 0 10 20 30 40 50 60 70 80 90 100
Temperature (°C)
Table 1-6. Agent Cylinder Pressure based on Agent Cylinder Fill Density vs Temperature, Metric Units
Pressure, kPa
Fill Density
Temp, °C
560 kg/m3 640 kg/m3 801 kg/m3 961 kg/m3 1121 kg/m3
CHAPTER 2
OPERATION
2-1 INTRODUCTION
This chapter describes the controls and indicators for the Kidde ECS ADS Series with 3M™
Novec™ 1230 Fire Protection Fluid (herein refer to as “agent”).
2-2.1 General
The agent storage container, also referred to as the agent cylinder-valve assembly, consists of
a steel cylinder fitted with a discharge valve assembly that includes a siphon tube that extends
nearly to the bottom of the cylinder. The agent storage container is super-pressurized to 360
psig with dry nitrogen. Additional nitrogen is stored in a secondary high-pressure cylinder.
When the secondary nitrogen cylinder discharge valve is actuated by a control head, the
nitrogen pressure operates a pneumatic control head on the agent cylinder while
simultaneously delivering nitrogen to the agent cylinder through the nitrogen diffuser check
valve. Pressurized agent is then propelled through the agent discharge valve and into the pipe
network.
The agent travels through the system pipe network to the discharge nozzle(s) where the agent
is discharged as fine droplets, which quickly vaporize in the air of the protected space. The
discharge nozzle(s) control the flow of the agent and ensure proper agent distribution
throughout the hazard.
Local manual control is not part of the normal system actuation and should only
CAUTION be used in an emergency as a last resort.
Operate as follows:
1. Proceed to the appropriate master nitrogen driver and the agent cylinder for the hazard.
2. Remove the safety pull pin from the nitrogen cylinder control head.
3. Operate the lever following instructions on the lever or control head nameplate.
4. Leave the hazard area immediately.
5. Allow no one to enter the hazard area. Call the fire department immediately.
2-3.4 Local Manual Operation UL Listed 3-Way Directional Valves (P/N 90-
22003X-00X)
Note: Not FM Approved for use with the Kidde ECS ADS Series (UL Listed only).
Local manual caution override operation of solenoid for directional valves is not part of the
normal system actuation and should only be used in an emergency as a last resort.
1. Proceed to the appropriate nitrogen pilot cylinder.
2. Remove the safety pull pin from the nitrogen pilot cylinder control head.
3. Operate the lever following instructions on the lever or control head nameplate.
4. Proceed to the appropriate directional valve for the zone requiring extinguishment.
5. Depress the red button on the solenoid and turn clockwise 1/4-turn to open the directional
valve.
Note: Turning the button clockwise 1/4-turn locks the valve open. The directional valve will
remain open as long as a minimum of 40 PSI (2.75 bar gauge) remains in the line to
the solenoid.
6. Proceed to the appropriate master nitrogen driver and the agent cylinder for the zone in
alarm.
7. Remove the safety pull pin from the nitrogen cylinder control head.
8. Operate the lever following instructions on the lever or control head nameplate.
Do not enter a hazard area with an open flame or lighted smoking materials.
The possible presence of flammable vapors may cause re-ignition or explosion.
Ensure fire is completely extinguished before ventilating the hazard area.
WARNING Before permitting anyone to enter the hazard area, ventilate the area to purge
all combustion gases and agent vapors. Alternatively, use self-contained
breathing apparatus when entering the hazard area after system discharge.
CHAPTER 3
COMPONENT DESCRIPTIONS
3-1 INTRODUCTION
This chapter provides a functional description of the modules and assemblies in the Kidde ECS
ADS Series.
fire suppression
panel detector
pressure
PRESSURE OPERATED SWITCH
3P.D.T.
operated electric
control
UL
FM
switch
head
valve
FOR FIRE
BREAK GLASS PULL HANDLE
PULL HARD
KIDDE-FENWAL
pull station
FOR FIRE
BREAK GLASS PULL HANDLE
PULL HARD
KIDDE-FENWAL
pressure
gauge
corner
valve pulley
cable operated
control head
nozzle
Agent N2
Storage Driver
Cylinder
Figure 3-2. Typical Agent System with Cable Operated Control Head
CYLINDER
Figure 3-3. 2300, 4070 and the 4890 cu. in. Nitrogen Drive Cylinder and Valve Assemblies, Vertical Mount
Only
Table 3-1. Dimensions, Agent Nitrogen Cylinder/Valve Assemblies for Vertical Installation Only
The Kidde ECS ADS Series engineered equipment listed herein is designed for an operating
temperature range of 32°F to 130°F (0°C to 54°C). The flow calculation software program is
designed for a 70°F (21°C) container operating/storage temperature (for more information see
latest version of the Flow Calculation Software User’s Guide 06-237256-004). Therefore, the
container operating and storage temperature must be in the range of 60°F to 80°F (16°C to
27°C) for a single unbalanced system protecting two or more separate hazards. If the
container operating and storage temperature is outside this range, an insufficient quantity of
agent may be discharged from one or more discharge nozzles.
Table 3-2. Fill Capacity: 2300, 4070 and the 4890 cu. in. Capacity Nitrogen Drive Cylinder and Valve
Assemblies, Vertical Mount Only
3.81"
(97 mm)
PISTON
BALL
RETAINER
STOP
CHECK BALL
CHECK
SPRING
3.94"
(100 mm) DISCHARGE
OUTLET
The safety cap must be installed on the discharge valve outlet whenever a
cylinder valve assembly is not connected to the system piping. Failure to install
WARNING the safety cap could result in serious bodily injury, death or property damage in
the event of inadvertent and unexpected cylinder discharge.
CYLINDER
C B
CYLINDER
NAMEPLATE
Figure 3-7. 200, 350, 600 and 900 lb. Cylinder and Valve Assemblies, Vertical Mount Only
Table 3-3. Dimensions, Agent Cylinder/Valve Assemblies for Vertical Installation Only
Valve Height
Height Diameter
Part Number With LLI
(C) (A)
(B)
Table 3-4. Fill Range Agent Cylinder/Valve Assemblies for Vertical Installation Only
The Kidde ECS ADS Series engineered equipment listed herein is designed for an operating
temperature range of 32°F to 130°F (0°C to 54°C). Table 3-7 shows the container pressure-
temperature relationship based on a maximum fill density of 70 lb./ft.3 (1121.3 kg/m3). The
latest version of the flow calculation software program is designed for a 70°F (21°C) container
operating/storage temperature (for more information see latest version of the Flow Calculation
Software User’s Guide 06-237256-004). Therefore, the container operating and storage
temperature must be in the range of 60°F to 80°F (16°C to 27°C) for a single unbalanced
system protecting two or more separate hazards. If the container operating and storage
temperature is outside this range, an insufficient quantity of agent may be discharged from
one or more discharge nozzles. Figure 3-8and Figure 3-9 represent the 2” and 3” valve
arrangements.
All agent cylinders can are supplied with an integral liquid level indicator (see Paragraph 3-
3.3). See Table 3-5 for discharge valve equivalent lengths.
Table 3-5. Discharge Valve Equivalent Lengths (for 200, 350, 600 and 900 lb. Cylinders)
ft. m ft. m
PRO CAP
ACTUATION
PORT
OUTLET
PROTECTION
CAP
SAFETY
CAP
PROTECTIVE
CAP
ACTUATION
PORT
VICTAULIC
FITTING AND PLUG
SAFETY
CAP
CAP
GRADUATED TAPE
P/N WK-283894-000
SHOWN IN MAGNETIC
READING TAKEN AT TOP INTERLOCK POSITION
EDGE OF FITTING READY TO TAKE READING.
O-RING
BRASS TUBE
TAPE INSIDE
BRASS TUBE AGENT
CYLINDER
AGENT LEVEL
MAGNETIC END OF
TAPE ENGAGES
IN MAGNETIC FIELD
OF FLOAT WHEN
TAPE IS PULLED
UP TO TAKE READING.
MAGNET EMBEDDED
IN FLOAT.
FLOAT - FLOATS ON SURFACE
OF AGENT.
FREE TO MOVE UP OR DOWN
OUTSIDE OF BRASS TUBE.
200 WK-283894-000
350 WK-283894-000
600 WK-283894-000
900 06-118266-00
3-3.4 Combined Cylinder Straps for 200 and 350 lb. Systems
(P/Ns 06-236127-001 and 06-236126-001)
The agent cylinder and nitrogen driver cylinders are secured in place using the combined
cylinder strap. The strap is to be bolted to a solid wall or a strut assembly in three locations:
left, right and center. Use 1/2” threaded rod and/or 1/2” diameter nuts, bolts and washers to
secure the mounting strap to a vertical surface. After the containers are securely mounted,
they can then be connected to the discharge piping per the system drawings. The Combined
Cylinder Strap is available for the 200 lb. cylinder (P/N 06-236127-001) and for the 350 lb.
cylinder (P/N 06-236126-001). See Figures 3-10 and 3-11 and Tables 3-9 and 3-10 on the
following page for more information.
B
F
D E
G
H
8.625 DIA.
(hole diameter)
12.905 DIA.
C
B
F
D E
G
H 10.875 DIA.
(hole diameter)
16.156 DIA. C
3-3.5 Nitrogen Driver Cylinder Mounting Equipment for 200 and 350 lb.
Systems
3-3.5.1 Nitrogen Driver Cylinder Mounting Straps (P/N WK-270014-000 and P/N
WK-270157-000)
Steel straps and brackets are used to mount the cylinders in a vertical position.
Cylinder straps (P/Ns WK-270014-000 and WK-270157-000) are available for both the 2300
cu. in. and the 4070 cu. in. drivers. See Figure 3-13 and Table 3-10and Table 3-11.
F (hole size)
3-3.5.2 Combined Nitrogen Driver Cylinder Mounting Straps for 600 and 900 lb.
Systems (P/N 06-236173-001 and P/N 06-236174-001)
Steel straps and brackets are used to mount the cylinders in a vertical position. Cylinder straps
(P/Ns 06-236173-001 and 06-236174-001) are available for both the 4070 cu. in. and the
4890 cu. in. drivers. See Figure 3-14and Figure 3-15 and Table 3-13 and Table 3-14.
C
D
F (hole size)
Figure 3-14. Cylinder Straps for the 4070 cu. in. Nitrogen Driver
C
D
F
Figure 3-15. Cylinder Straps for the 4890 cu. in. Nitrogen Driver
F (hole size)
Cylinder
Part Number Cylinder Size A B C D E F
O.D.
Cylinder
Part Number Cylinder Size A B C D E F
O.D.
NFPA requirements. In addition, a 24-hour back-up power source shall be provided per NFPA
requirements.
LOCKING PIN
SEAL WIRE
PU
ELECTRIC
LOCAL MANUAL
CONTROL HEAD
RELEASE LEVER
6.18" VOLTS
AMPS
(157 mm) PART NO.
SWIVEL NUT
INDICATOR AND TO RESET
RESET STEM
USE SCREWDRIVER
1-1/4” 18NF-3
THREAD
SET RELEASED
MADE IN U. S. A.
KIDDE-FENWAL, INC.
400 MAIN STREET
ASHLAND, MA 01721
4.00"
(102 mm)
PU
SEAL WIRE
INSTRUCTIONS
MAINTENANCE
PART NO.
SEE
FOR
INDICATOR AND
KIDDE-FENWAL, INC.
ASHLAND, MA 01721
400 MAIN STREET
SET
MADE IN U.S.A.
USE SCREWDRIVER
RESET STEM CONNECTION FOR
CONTROL HEAD
TO RESET
ELECTRIC
REMOTE PULL BOX
HZ AMPS
CABLE
VOLTS
PULL
PIPE OR CONDUIT
RELEASED
3/8" NPS MALE
LOCAL MANUAL
RELEASE LEVER
4.937”
(125 mm) SWIVEL NUT
1.500 (38 mm) HEX
CONNECTION FOR CABLE 1.250-18 NF-3 THREAD
HOUSING TO SECOND
CONTROL HEAD IF USED
3/8" NPS FEMALE.
USE PNEUMATIC CONTROL
HEAD CABLE HOUSINGS
4.25"
(108 mm)
3/8" PIPE (OR 1/2" EMT
SWIVEL WITH ADAPTER
NUT P/N WK-843837-000)
1.50"
(38 mm)
5.25"
(133 mm)
1-1/4"-18 NF-3
FEMALE
LOCKING PIN
ALLOW APPROX. 2" (50 mm)
CLEARANCE FOR
OPERATION OF LEVER
CLOSED
LEVER
TO OPEN
3.17"
(81 mm)
SWIVEL
NUT
1.50"
(38 mm)
SET
1-1/4"-18 NF-3
FEMALE OPERATED
3.00"
(76 mm)
STEM
CLOSED
SEAL WIRE
OPEN
TO OPEN
PISTON BODY
SET
OPERATED
1.250-18 UNEF-3B
3.00"
(76.2 mm)
1.00" HEX
(25.4 mm) 1/8"-27 NPT
PRESSURE INLET
PISTON
2.19"
(55.6 mm) SWIVEL NUT
SET
OPERATED 1.250-18
UNEF-3B
1.50" HEX
(38 mm)
1.250-18 UNEF-3A
CAP RETAINER
0.125-27 NPT
3.48" PRESSURE INLET
(88.4 mm)
PISTON
BODY
SET
OPERATED
2 - NAMEPLATE
BRACKETS -
(SUPPLIED WITH
OPTIONAL
NAMEPLATE PULL BOX)
(BY INSTALLER) 4-COVER
SCREWS
FOR FIRE
BREAK GLASS PULL HANDLE
3/8” PIPE
PULL
5.87" HANDLE
(149 mm) PULL HARD
KIDDE-FENWAL
400 Main Street - Ashland, MA 01721-2150
Tel(508)881-3000 FAX(508)881-0020 1/16” CABLE
HAMMER
P/N
WK-800450-000
5.00" 2.25"
(127 mm) (57 mm)
BREAK GLASS
P/N WK-928103-000 PULL HANDLE
3-3.9.1 Actuation Assembly Kit for 200 and 350 lb. Cylinders (P/N 06-129882-001)
Gas pressure from the nitrogen cylinder is routed to the agent Cylinder Valve in order to
actuate the valve. Actuation of the agent valve is done by using the 200 and 350 lb. Actuation
Assembly Kit. See Figure 3-25 and Table 3-18 for more details. The kit consists of:
• (1) 3/4” Nitrogen Transfer Fitting, P/N 06-118220-001
• (2) 1/8” NPT x 1/4” flare, P/N 06-118191-001
• (1) 1/8” branch tee, P/N 06-118193-001
• (1) 3/16” flexible loop, P/N 06-118192-001
• (1) 1/8” Schrader valve, P/N WK-263303-000
• (1) 1/4” flare Schrader cap, P/N WK-263304-000
• (1) Pneumatic control head, P/N 82-878737-000
3 6 7
Figure 3-25. Actuation Assembly Kit for the 200 and 350 lb. ADS Series Cylinders
Table 3-18. Actuation Assembly Data for 200 and 350 lb. ADS Series Cylinders
3-3.9.2 Actuation Assembly Kit for 600 and 900 lb. cylinders (P/N 06-129985-001)
Gas pressure from the nitrogen cylinder is routed to the agent Cylinder Valve in order to
actuate the valve. Actuation of the agent valve is done by using the 600 and 900 lb. Actuation
Assembly Kit (P/N 06-129985-001). See Figure 3-26 and Table 3-19 for more details. The kit
consists of:
• (1) Nitrogen Transfer “Y” Fitting, P/N 06-236260-001
• (2) 1/8” NPT x 1/4” flare, P/N 06-118191-001
• (1) 1/8” branch tee, P/N 06-118193-001
• (1) 3/16” flexible loop, P/N 06-118192-001
• (1) 1/8” Schrader valve, P/N WK-263303-000
• (1) 1/4” flare Schrader cap, P/N WK-263304-000
• (1)Pneumatic control head, P/N 82-878737-000
3 6 7
4
1
8
3
Figure 3-26. Actuation Assembly Kit for the 600 and 900 lb. ADS Series Cylinders
Table 3-19. Actuation Assembly Data for 600 and 900 lb. ADS Series Cylinders
3/4-14NPT
1.375 HEX (REF) 1.375 HEX (REF)
1.500
1.000 DIA
DIA MIN.
1.625 DIA.
WK-877940-200 Nitrogen Pilot Cylinder, 1800 PSI at 70F (124 bar gauge at 20C)
WK-877845-000 Mounting Bracket
WK-699205-010 Mounting Adapter
GAUGE
PLUG OUTLET PORT-1/8" NPT FEMALE
ATTACH ADAPTER HERE
1-1/4"-18 NF-3
FOR CONTROL HEAD CONNECTION
16"
(406 mm)
3.56"
(90 mm)
STAINLESS STEEL
BRAID
0.250-45° SAE SWIVEL - BRASS EXTRUDED
7/16-20 (0.437- 20) THREAD TEFLON INNERCORE
Dimension A
Part Number
(inches) (mm)
06-118193-001 16 406
06-118193-003 22 559
06-118193-002 36 116
MALE CONNECTOR
1/8" NPT X 5/16" TUBING
P/N WK-699205-010
MALE ELBOW MALE BRANCH TEE
1/8" NPT X 5/16" TUBING 1/8" NPT X 5/16" TUBING
P/N WK-699205-030 P/N WK-699205-050
Figure 3-30. Tees, Elbows and Adapters for Nitrogen Pilot Actuation
Figure 3-31. Tees, Elbows and Adapters for Manifolded Cylinder Actuation
1.500 in.
(38 mm)
HEX.
1.000-16 UN-2A
VALVE SEAT
P/N 06-235930-001
COPPER GASKET
CUP CHECK ASSEMBLY P/N WK-326420-000
P/N 06-129860-001
SPRING
RETAINING RING
SPRING SEAT
O-RING
P/N WK-566109-160
3/4” CHECK
DIFFUSER BODY
HOSE
AGENT CYLINDER VALVE SYSTEM PIPE CONNECTION,
CONNECTION, SWIVEL NUT MALE NPT THREAD
D C
C D
Part Number Size (in.) A B
in. mm in. mm
WK-283905-000 2 2”11½ NPT 2.500”12 UNJ 3.12 79.25 3.00 HEX 76.2
DIRECTION
OF FLOW 1/4"-18NPT (TYP.)
2.00" .81"
(51 mm) (21 mm)
HEX
Note: Install the valve with the arrow pointing in the direction of flow.
Equivalent Length
Part Number Nomenclature Pipe Type
ft. m
VALVE BODY
B C
FOR CONNECTION TO SYSTEM
MANIFOLD
C CHECK
Part Number Nomenclature Pipe Type Equivalent Length (ft) Equivalent Length (m)
4.56 in.
(116 mm)
6.31 in.
(160 mm)
2” NPT
2” NPT
8.06 in.
(205 mm)
3" NPT
3" NPT 53°MAX. FEMALE
FEMALE SWING ANGLE
9.30 in.
(236 mm)
Part Number Description Pipe Type Equivalent Length (ft) Equivalent Length (m)
SWITCH 3PDT
BOX - 3 - ½” CONDUIT KNOCKOUTS
EACH SIDE
COVER
SIDE SECTION
STEM IN OPERATED
POSITION
TO RESET PUSH
SET POSITION
STEM TO SET
POSITION
3 POLE
PRESSURE
CLUTCH OPERATED
EXPLOSION
PROOF
SWITCH
3 POLE
6.31"
SINGLE
THROW
9.00"
(160.27 mm)
TOGGLE (228.6 mm)
SWITCH
6 - COVER
30 AMP 250 Vac SCREWS
20 AMP 600 Vac
2 HP 100-600 V
3 PHASE AC
INLET
GAS
OPERATING HEAD
PIPING TO HAZARD
AGENT
SOURCE
TOP VIEW
PIPING TO HAZARD
AGENT
SOURCE
TOP VIEW
Dimensions Valve
Part Number Nominal Breakaway
Working
with Solenoid Size Torque
A* B C* Pressure
90-220030-001 1/2” 3.50 in. 0.688 11.23 in. 400 PSIG 200 in.-lb.
90-220030-002 3/4” 4.00 in. 0.824 12.13 in. 400 PSIG 250 in.-lb.
90-220030-003 1” 4.00 in. 1.000 12.13 in. 400 PSIG 250 in.-lb.
90-220031-001 1¼” 6.00 in. 1.380 13.69 in. 400 PSIG 500 in.-lb.
90-220031-002 1½” 6.00 in. 1.500 13.69 in. 400 PSIG 500 in.-lb.
90-220031-003 2” 7.25 in. 2.000 15.66 in. 400 PSIG 800 in.-lb.
90-220032-001 3” 11.00 in. 3.000 21.44 in. 400 PSIG 3000 in.-lb.
90-220032-002 4” 13.38 in. 4.000 24.68 in. 400 PSIG 4300 in.-lb.
T-Flow L-Flow
Part Number Nominal Equivale Equivale
Material Inlets Port
with Solenoid Size nt nt
Length Length
90-220030-001 1/2” ENP Carbon Steel NPT Full 0.19 ft. 1.83 ft.
90-220030-002 3/4” ENP Carbon Steel NPT Full 0.37 ft. 3.61 ft.
90-220030-003 1” ENP Carbon Steel NPT Full 1.48 ft. 9.31 ft.
90-220031-001 1¼” ENP Carbon Steel NPT Full 1.19 ft. 11.65 ft.
90-220031-002 1½” ENP Carbon Steel NPT Full 1.77 ft. 12.08 ft.
90-220031-003 2” ENP Carbon Steel NPT Full 1.82 ft. 13.75 ft.
90-220032-001 3” ENP Carbon Steel Victaulic Full 5.00 ft. 26.01 ft.
90-220032-002 4” ENP Carbon Steel Victaulic Full 7.73 ft. 32.42 ft.
Maximu
Part Number Nominal Actuator Actuator Actuator Actuator Working
m
with Solenoid Size Mechanism Type Volume Torque Pressure
Pressure
90-220030-001 1/2” Rack and Spring Return 30 cu. in. 865 in.-lb. 115 PSIG 145 PSIG
Pinion
90-220030-002 3/4” Rack and Spring Return 30 cu. in. 865 in.-lb. 115 PSIG 145 PSIG
Pinion
90-220030-003 1” Rack and Spring Return 30 cu. in. 865 in.-lb. 115 PSIG 145 PSIG
Pinion
90-220031-001 1¼” Rack and Spring Return 61 cu. in. 1877 in.-lb. 115 PSIG 145 PSIG
Pinion
90-220031-002 1½” Rack and Spring Return 61 cu. in. 1877 in.-lb. 115 PSIG 145 PSIG
Pinion
90-220031-003 2” Rack and Spring Return 61 cu. in. 1877 in.-lb. 115 PSIG 145 PSIG
Pinion
90-220032-001 3” Rack and Spring Return 189 cu. in. 4887 in.-lb. 115 PSIG 145 PSIG
Pinion
903-220032-002 4” Rack and Spring Return 299 cu. in. 8288 in.-lb. 115 PSIG 145 PSIG
Pinion
Description Measurement
6.66
ASSEMBLY INLET,
1/4 NPT
ASSEMBLY OUTLET,
1/4 NPT
2.62"
(67 mm) NORMAL POSITION
(PRE-DISCHARGE)
DISCHARGE
INDICATION
POSITION
BODY
1.75"
(45 mm) GASKET
0.62"
2.13" (54 mm) DIA (16 mm)
COVER
0.62"
COVER SCREW (16 mm)
ID D
K
UL
2 - ½” E.M.T. CONNECTIONS
COMPRESSION TYPE
2.75"
(70 mm)
approx.
¾” NPT FEMALE
FOR ELECTRICAL
CONNECTION
NAMEPLATE
SWITCH - DOUBLE
POLE DOUBLE
MAIN
THROW
5.37" 2-COVER SCREWS
(136 mm) 6-CONNECTION
TOGGLE TERMINALS
4.62"
(117 mm)
TOGGLE
GUARDS
CONDULET
RESERVE BOX
2.75" 2.12"
(70 mm) Switch Rating: (54 mm)
30 Amps @ 120 Vac 2.50"
COMMON (64 mm)
A-1
L-1
B-1
A-2
L-2
B-2
WIRING DIAGRAM
ORIFICE
DIAMETER
C
B
SECTION A-A
B
Figure 3-54. Discharge Nozzle Dimensions, 3-D
O-RING SEAL
3/8” - NPT - (VENT VALVE
CONNECTION)
B (HEX)
3/8” - 18 NPT -
(CHARGE CONNECTION)
CYLINDER VALVE
OUTLET CONNECTION
A B
Part Number Cylinder Size (lb.)
in. mm in. mm
Note: The cylinder recharge adapter is not required for use with the 600 and 900 lb. cylinders.
RETAINING NUT
SAFETY DISC
SEAL WIRE
BODY
1.78"
(45 mm)
3-3.13.1 Detectors
Detectors (ionization, photoelectric, thermal, ultraviolet, ultraviolet/infrared, etc.) interfacing
with Kidde systems must be UL Listed and/or FM Approved for the intended application.
CHAPTER 4
DESIGN AND INSTALLATION
4-1 INTRODUCTION
The first part of this chapter outlines the steps needed to design a Kidde ECS ADS Series total
flooding fire extinguishing system including limitations imposed on the design by the system
hardware. The second part of this chapter explains equipment installation.
4-2.1 General
The design of a Kidde ECS ADS Series total flooding fire extinguishing system as described
herein is based on the requirements of National Fire Protection Association (NFPA) Standard
2001, Edition 2012. The Authority Having Jurisdiction (AHJ) may impose additional
requirements not specifically addressed here.
4-2.2 Application
The following steps must be taken to design a Kidde ECS ADS Series:
• Determine the classification of the fire hazard based on the type of combustible materials
contained in the protected enclosure. See Section 4-2.2.1.
• Determine the agent design concentration required for the hazard.
• Determine the number of nitrogen driver cylinders needed as required by the flow calcula-
tion software.
• Determine the minimum and maximum ambient temperature for the hazard.
• Determine the volume of the hazard.
• Determine the integrity of the hazard.
• Determine if any additional agent will be required to offset leakage of agent from the haz-
ard.
• Determine venting requirements for the hazard enclosure to avoid damage due to excess
positive or negative pressure differentials.
• Determine post-discharge ventilation requirements.
Note: Where earlier editions of NFPA 2001 are enforced, it is acceptable to use the
minimum design concentration based on the requirements of the edition. The governing
authority or authority having jurisdiction (AHJ) must specifically approve the design ap-
proach selected.
Note: Where NFPA 2001, 2008 ed. or earlier editions are enforced, it is acceptable to use the
minimum design concentrations based on the requirements of the accepted edition. The
governing authority or authority having jurisdiction (AHJ) must specifically approve the
design approach selected.
The latest version of the flow calculation software calculates the required agent quantity for
the designer. Refer to the latest version of the Flow Calculation Software User’s Guide 06-
237256-004 for more information.
Minimum
Extinguishing
Design
Fuel Concentration
Concentration
vol. % (1)
Minimum
Extinguishing
Design
Fuel Concentration
Concentration
vol. % (1)
0 0.9856 0.0445 0.0478 0.0503 0.0534 0.0630 0.0648 0.0764 0.0882 0.1003 0.1127
10 1.0100 0.0434 0.0467 0.0491 0.0521 0.0615 0.0632 0.0745 0.0861 0.0979 0.1100
20 1.0344 0.0424 0.0456 0.0479 0.0509 0.0601 0.0617 0.0728 0.0841 0.0956 0.1074
30 1.0588 0.0414 0.0445 0.0468 0.0497 0.0587 0.0603 0.0711 0.0821 0.0934 0.1049
32 1.0637 0.0412 0.0443 0.0466 0.0495 0.0584 0.0600 0.0708 0.0817 0.0930 0.1045
40 1.0832 0.0405 0.0435 0.0458 0.0486 0.0574 0.0589 0.0695 0.0803 0.0913 0.1026
50 1.1077 0.0396 0.0425 0.0448 0.0475 0.0561 0.0576 0.0680 0.0785 0.0893 0.1003
60 1.1321 0.0387 0.0416 0.0438 0.0465 0.0549 0.0564 0.0665 0.0768 0.0874 0.0981
70 1.1565 0.0379 0.0407 0.0429 0.0455 0.0537 0.0552 0.0651 0.0752 0.0855 0.0961
80 1.1809 0.0371 0.0399 0.0420 0.0446 0.0526 0.0541 0.0637 0.0736 0.0838 0.0941
90 1.2053 0.0364 0.0391 0.0411 0.0437 0.0516 0.0530 0.0624 0.0721 0.0821 0.0922
100 1.2297 0.0357 0.0383 0.0403 0.0428 0.0505 0.0519 0.0612 0.0707 0.0804 0.0904
110 1.2541 0.0350 0.0376 0.0395 0.0420 0.0495 0.0509 0.0600 0.0693 0.0789 0.0886
120 1.2785 0.0343 0.0369 0.0388 0.0412 0.0486 0.0499 0.0589 0.0680 0.0774 0.0869
130 1.3029 0.0336 0.0362 0.0381 0.0404 0.0477 0.0490 0.0578 0.0667 0.0759 0.0853
140 1.3273 0.0330 0.0355 0.0374 0.0397 0.0468 0.0481 0.0567 0.0655 0.0745 0.0837
150 1.3518 0.0324 0.0349 0.0367 0.0389 0.0460 0.0472 0.0557 0.0643 0.0732 0.0822
160 1.3762 0.0319 0.0342 0.0360 0.0382 0.0452 0.0464 0.0547 0.0632 0.0719 0.0807
Notes
(1) 4.20 is the MDC for Class A & C where AHJ requires 2008 edition (or earlier) of NFPA 2001
(2) 4.55 is the MDC for Class A where AHJ requires 2012 edition (or later) of NFPA 2001
(3) 4.73 is the MDC for Class C where AHJ requires 2012 edition or later) of NFPA 2001
(4) 5.85 is the lowest MDC for Class B where AHJ requires 2000 edition or later) of NFPA 2001. Higher values may
apply. See Table 4-2.
Agent quantity required for a hazard can be calculated at any temperature and agent design concentration using the
equations below.
W = (V/s)(C/(100 - C))
where:
W = agent quantity, lb
C = agent design concentration, vol. %
s = specific volume of superheated agent vapor can be approximated by the formula, ft3/lb, calculated using
the equation below.
s = 0.9856 + 0.002441 * t
t = design temperature in the hazard area, °F
V = volume of the protected hazard, ft3
-20 0.0609 0.7197 0.7735 0.8141 0.8640 1.0200 1.0478 1.2356 1.4274 1.6235 1.8239
-15 0.0623 0.7038 0.7565 0.7962 0.8450 0.9975 1.0247 1.2084 1.3960 1.5878 1.7838
-10 0.0637 0.6887 0.7402 0.7790 0.8268 0.9761 1.0027 1.1824 1.3660 1.5536 1.7454
-5 0.0650 0.6742 0.7246 0.7626 0.8093 0.9555 0.9816 1.1575 1.3372 1.5209 1.7086
0 0.0664 0.6603 0.7096 0.7469 0.7926 0.9358 0.9613 1.1336 1.3096 1.4895 1.6734
5 0.0678 0.6469 0.6953 0.7318 0.7766 0.9168 0.9419 1.1106 1.2831 1.4594 1.6395
10 0.0691 0.6341 0.6815 0.7173 0.7612 0.8987 0.9232 1.0886 1.2577 1.4304 1.6070
15 0.0705 0.6218 0.6683 0.7033 0.7464 0.8812 0.9052 1.0675 1.2332 1.4026 1.5758
20 0.0719 0.6099 0.6555 0.6899 0.7322 0.8644 0.8880 1.0471 1.2097 1.3759 1.5457
25 0.0733 0.5985 0.6433 0.6770 0.7185 0.8482 0.8714 1.0275 1.1871 1.3501 1.5168
30 0.0746 0.5875 0.6314 0.6646 0.7053 0.8327 0.8554 1.0087 1.1653 1.3253 1.4890
35 0.0760 0.5769 0.6201 0.6526 0.6926 0.8176 0.8399 0.9905 1.1443 1.3014 1.4621
40 0.0774 0.5667 0.6091 0.6410 0.6803 0.8031 0.8251 0.9729 1.1240 1.2784 1.4362
45 0.0787 0.5568 0.5985 0.6299 0.6685 0.7892 0.8107 0.9560 1.1044 1.2561 1.4112
50 0.0801 0.5473 0.5882 0.6191 0.6570 0.7757 0.7968 0.9396 1.0855 1.2346 1.3871
55 0.0815 0.5381 0.5783 0.6087 0.6460 0.7626 0.7834 0.9238 1.0673 1.2139 1.3637
60 0.0828 0.5292 0.5688 0.5986 0.6353 0.7500 0.7705 0.9085 1.0496 1.1938 1.3412
65 0.0842 0.5206 0.5595 0.5889 0.6250 0.7378 0.7579 0.8938 1.0325 1.1744 1.3194
70 0.0856 0.5122 0.5506 0.5794 0.6149 0.7260 0.7458 0.8794 1.0160 1.1556 1.2982
Notes
(1) 4.20 is the MDC for Class A & C where AHJ requires 2008 edition (or earlier) of NFPA 2001
(2) 4.55 is the MDC for Class A where AHJ requires 2012 edition (or later) of NFPA 2001
(3) 4.73 is the MDC for Class C where AHJ requires 2012 edition or later) of NFPA 2001
(4) 5.85 is the lowest MDC for Class B where AHJ requires 2000 edition or later) of NFPA 2001. Higher values may
apply. See Table 4-2.
Agent quantity required for a hazard can be calculated at any temperature and agent design concentration using the
equations below.
W = (V/s)(C/(100 - C))
where:
W = agent quantity, kg
C = agent design concentration, vol. %
s = specific volume of superheated agent vapor can be approximated by the formula, m3/kg, calculated
using the equation below.
s = 0.0664+ 0.0002741* t
t = design temperature in the hazard area, °C
V = volume of the protected hazard, m3
4-2.2.9 Manifolds
When multiple cylinders are needed, they may be connected to the same set of distribution
piping through a manifold. This is necessary in two circumstances:
• A connected reserve supply of the agent is required.
• The quantity of agent required is greater than the maximum fill of a single cylinder.
In accordance with standards set by NFPA 2001 Edition 2012:
• All cylinders on the same manifold must be the same size and contain the same quantity
of agent.
• Each cylinder must have an El-check or swing-check valve to prevent back flow of agent
through the discharge hose, in the event that the system is discharged while a cylinder is
removed for maintenance.
• Each agent cylinder must have the correct nitrogen driver connected directly to that agent
cylinder. Nitrogen drivers are not connected to the manifold, only the agent cylinders.
Standard check valves MUST be installed and modeled in the calculation software whenever
any of the following conditions exist:
• Multiple cylinders connected to a manifold.
• A connected reserve supply is required.
The latest version of the Flow Calculation Software User’s Guide, P/N: 06-
237256-004, is the only calculation method to be used with Kidde ECS ADS
CAUTION equipment. No other calculation method is acceptable.
The system designer must become familiar with the latest version of the Flow Calculation
Software User’s Guide, P/N: 06-237256-004, to determine the proper procedures for applying
the input parameters to the computer program. There are a number of limitations to these
input parameters that must be observed if accurate results are to be obtained. Most of these
limitations are in the program. However, there are certain restrictions that must be addressed
by the system designer before applying the input data. The following sections describe the
essential design parameters and design limitations which must be considered.
OUT OUT OUT - 50% OUT - 50% OUT - 85% OUT - 15%
IN OUT
IN - 100% OUT - 65% IN - 100% OUT - 90%
HAZARD A
HAZARD A
HAZARD B
6 NOM PIPE HAZARD B
DIAM. MINIMUM
6 NOM PIPE
DIAM. MINIMUM
Horizontal Feed
HAZARD A HAZARD A
HAZARD B
6 NOM PIPE
6 NOM PIPE HAZARD B DIAM. MINIMUM
DIAM. MINIMUM
Pipe Diameters
Pipe Size
ft. inches mm
1/2” 0.25 3 76
3/4” 0.375 4.5 110
1” 0.5 6 150
1¼” 0.625 7.5 190
1½” 0.75 9 230
2” 1 12 300
2½” 1.25 15 380
3” 1.5 18 460
4” 2 24 610
42.5' 42.5'
(12.95 m) (12.95 m)
d = 47.5' d = 30.0'
(14.48 m) (9.14 m)
42.5' 42.5'
(12.95 m) (12.95 m)
• Multiple Nozzles-Nozzles whose discharge patterns will intersect must be placed at least
6 ft. (1.8 m) apart to assure adequate agent distribution.
• Walls and Obstructions-Agent discharged from the nozzle requires a certain length from
the nozzle to vaporize into a gas. If the agent comes into contact with a surface before the
agent is fully atomized, frosting can occur. As a result, the concentration throughout the
enclosure will be less than required to appropriately protect the space. Therefore, nozzles
must be located with at least 4 ft. (1.2 m) of clearance from walls and/or significant ob-
structions (ex. high-rise racking and columns). If this requirement cannot be met, addition-
al agent may be discharged to compensate for this agent "loss". Please consult Kidde Fire
Systems for assistance.
For subfloor areas, consideration should be given to reducing nozzle spacing when obstruc-
tions that would impede the uniform distribution of the agent throughout the area are pres-
ent. Nozzle coverage area for 12 inch high subfloors must be reduced from 42.5 ft. x 42.5
ft. to 21.25 ft. x 21.25 ft. in such obstructed conditions.
• Subfloor Reduced Coverage Area-Nozzle coverage area must be reduced to 21.25 ft. x
21.25 ft. for enclosure heights 6 to less than 12 inches (6.48 m x 6.48 m for heights 0.15
to less than 0.3 m). Any system designed for a space less than 12 inches (305 mm) in
height is not a UL Listed or an FM Approved design.
40’ Max
1/4 in. (9 mm) 0.68 0.31 0.41 0.19 0.30 0.14 0.18 0.08
3/8 in. (10 mm) 1.55 0.70 0.93 0.42 1.06 0.48 0.64 0.29
1/2 in. (15 mm) 2.58 1.17 1.55 0.70 1.95 0.88 1.17 0.53
3/4 in. (20 mm) 4.53 2.05 2.72 1.23 3.68 1.67 2.21 1.00
1 in. (25 mm) 7.29 3.31 4.37 1.98 6.08 2.76 3.65 1.65
1¼ in. (32 mm) 12.67 5.75 7.60 3.45 10.83 4.91 6.50 2.95
1½ in. (40 mm) 17.46 7.92 10.48 4.75 15.06 6.83 9.04 4.10
2 in. (50 mm) 29.82 13.53 17.89 8.12 25.96 11.78 15.58 7.07
2½ in. (65 mm) 44.06 19.99 26.44 11.99 38.51 17.47 23.11 10.48
3 in. (80 mm) 71.34 32.36 42.80 19.42 62.96 28.56 37.78 17.13
3½ in. (90 mm) 98.32 44.60 58.99 26.76 87.46 39.67 52.48 23.80
4 in. (100 mm) 129.28 58.64 77.57 35.18 115.87 52.56 69.52 31.53
5 in. (125 mm) 205.71 93.31 123.43 55.99 187.31 84.96 112.39 50.98
6 in. (150 mm) 286.54 129.97 171.92 77.98 262.77 119.19 157.66 71.51
Note: The pipe friction factor embodied in the energy conservation equation used to calculate pressure drop
for two-phase flow in fire protection systems is based on the premise that highly turbulent flow is
present in the pipeline. Also, a high degree of turbulence must be maintained in pipe sections that
approach dividing points. The pipe size that can be used for a given flow rate is thus based upon the
minimum flow rate required to maintain complete turbulence.
This limitation is tabulated in the table and is automatically taken into consideration when the com-
puter selects pipe sizes for the system. Flow rates as low as 60% of the tabulated minimum rates may
be used in branch lines that lead directly to nozzles with no intervening flow division.
This table is intended for use as a guide only. The latest version of the flow calculation software
must be used for the final design (for more information see latest version of the Flow
Calculation Software User’s Guide, P/N: 06-237256-004).
Nitrogen Driver
With Master Control
Elbow Head
Tee (Typ.) Agent Cylinder
Actuation Assembly
Kit (Typ.)
14 Slave sets of Agent and Master
Nitrogen Driver Cylinders Cylinder Set
Figure 4-4. Pressure Actuation using Pressure from 1 Master Nitrogen Driver Cylinder to Actuate a
Maximum of Fourteen Slaves (Fifteen Sets Total), Close-coupled
4-2.5.2 Cylinders Not Close-coupled Using Pressure From a Master Nitrogen Driver
Note: See Figure 4-5.
For cylinders not close-coupled using pressure from one master nitrogen driver and agent
cylinder set, a maximum of fourteen slave cylinders (maximum fifteen cylinders in a group)
can be actuated by that one master cylinder, using pressure operated control heads on the
slave cylinders. The slave cylinder operation will be through a 5/16” O.D. x 0.035” wall
stainless steel tubing actuator line having a maximum total length of 800 ft. (244 m) or 400
ft. (122 m) of 1/4” Schedule 40 pipe.
800 ft. (243.8 m) Max. Length 400 ft. (121.9 m) Max. Length
of 5/16” Stainless Steel Tubing of 1/4” Sch. 40 Pipe
Nitrogen Driver
5/16" O.D. X 0.032" Wall With Master Control
Steel Tubing or Head
1/4” Schedule 40 Pipe Tee 5/16" O.D. X 0.032" Wall
Elbow Agent Cylinder
Steel Tubing or
Actuation Assembly 1/4” Schedule 40 Pipe
Kit (Typ.)
14 Slave sets of Agent and Master
Nitrogen Driver Cylinders Cylinder Set
Figure 4-5. Pressure Actuation Using Pressure from 1 Master Nitrogen Driver Cylinder to Actuate a
Maximum of Fourteen Slaves (Fifteen Sets Total), Not Close-coupled
500 ft. (152.4 m) Max Length 250 ft. (76.2 m) Max Length
of 5/16” Stainless of 1/4” Sch. 40 Pipe
Steel Tubing Maximum 100 ft. of
Flare 5/16 O.D. X 0.032" wall
Stainless steel tubing
Nitrogen
Slave Nitrogen Driver (Typ.) Transfer Hose
with Pneumatic Control Head Master Control
Head
Nitrogen Driver
5/16" O.D. X 0.032" Wall Tee Agent Cylinder With Pneumatic Control
Steel Tubing or Head (P/N 82-878737-000)
Elbow Actuation Assembly
1/4” Sch. 40 Pipe
Kit (Typ.)
Figure 4-6. Pressure Actuation Using Pressure from 1 Master Nitrogen Pilot Cylinder to Actuate a Maximum
of Fifteen Sets of ADS Cylinders, Not Close-coupled
Figure 4-7. Pressure Actuation Using Pressure from 1 Master Nitrogen Pilot Cylinder to Actuate a Maximum
of Fifteen Sets of Kidde ECS ADS Series Cylinders, Close-coupled.
4-2.5.5 Manifold Arrangement Kits for Use with Single Driver ADS Series Systems
(P/N 06-129944-X0X)
Manifold actuation arrangement kits are convenient and easy to install. Kits are available in
two, three, four and five system manifolds. See Figure 4-4 and Table 4-8 for a listing of
hardware included in the kit.
"X" ± 0.187
06-118193-00X
06-118285-001
06-118284-001
82-878737-000
878737
KIT
P/N 06-129882-001
Figure 4-8. Manifold Arrangement Kits for use with Single Driver ADS Series Systems
Table 4-8. Manifold Arrangement Kit Contents for Single Driver ADS Series System
P/N 06-118193-003
P/N 06-118193-002
P/N 82-878737-000
P/N 06-118285-001
P/N 06-118284-001
Actuation Assembly
Pneumatic Actuator
22” Flex Hose
Number of
Cylinders
Kit P/N
4-2.6 Pressure Actuation Limitations for Dual Driver Kidde ECS ADS Series
Cylinders
Four modes of pressure actuation of the Kidde ECS ADS Series cylinders are available.
When agent cylinders are all connected to a common manifold, they shall be at the same size,
same fill density, and same orifice fitting.
3" Valve
Control Head
Actuation Assembly
Kit (Typ.), P/N 06-129985-001
Figure 4-9. Close-coupled Manifold using pressure from a Master Nitrogen Driver for use with Large Single
Hazard Arrangements
4-2.6.2 Cylinders Not Close-coupled Using Pressure From a Master Nitrogen Driver
Note: See Figure 4-10.
For cylinders not close-coupled using pressure from one master nitrogen driver and agent
cylinder set, a maximum of fourteen slave sets (maximum fifteen sets in a group) can be
actuated by that one master cylinder, using pressure operated control heads on the slave
cylinders. The slave cylinder operation will be through a 5/16” O.D. x 0.035” wall stainless steel
tubing actuator line having a maximum total length of 800 ft. (244 m) or 400 ft. (122 m) of
1/4” Schedule 40 pipe.
1/4" Sch 40 or
5/16 O.D. X 0.035" wall
Stainless steel tubing
Figure 4-10. Not Close-coupled Manifold Using Pressure from a Master Nitrogen Driver for use with Large
Single Hazard Arrangements
Figure 4-11. Close-coupled Manifold Using Pilot Nitrogen Cylinder Pressure for use with Large Single
Hazard Arrangements
1/4" Sch 40 or
5/16 O.D. X 0.035" wall Control
Stainless steel tubing Head
Nitrogen Pilot
with Control Head
3" Valve
Plain Nut Discharge Head (Typ.), P/N WK-872450-000
Actuation Assembly Kit (Typ.)
Figure 4-12. Not Close-coupled Manifold Using Pressure from a Pilot Nitrogen Driver for use with Large
Single Hazard Arrangements
4-2.6.5 Manifold Arrangement Kits for Use with Dual Driver ADS Series Systems (P/N
06-129986-X0X)
Manifold Arrangement Kits for use with the Dual Driver ADS Series Systems are available in
two, three and four system manifolds. See Figure 4-13 and Table 4-9 for a listing of hardware
included in the kit.
"X" ± 0.187
06-118193-00X
06-118285-001
06-118284-001
82-878737-000
KIT
P/N 06-129882-001
Figure 4-13. Manifold Arrangement Kit for use with Dual Driver ADS Series Systems
Table 4-9. Manifold Arrangement Kit Contents for Dual Driver ADS Series System
P/N 06-118193-002
P/N 82-878737-000
P/N 06-129985-001
Pneumatic Actuator
Actuation Assembly
P/N 06-118285-001
P/N 06-118284-001
16” Flex Hose
The pneumatic actuator and pneumatic solenoid are rated for a pressure of 100
to 150 PSI (6.89 to 10.34 bar gauge). A pressure regulator must be installed in
line to reduce the nitrogen pressure that is being released from the pilot
WARNING cylinder. Pressure regulator, P/N 06-118334-001 or 38-509803-001, is factory
set to 116 PSI (8 bar gauge).
E Electric
Channels Needed = Swing Check Control Head
# of Directional Valves or Check Vavle S/O Pressure Regulator
(P/N 06-118334-001)
Factory Set to 116 PSI (8 bar)
3-Way Ball 3-Way Ball
VALVE 1 VALVE 2 S/O Safety Outlet (P/N 82-844346-000)
Electric Control E E E
Head
Flex Hose or
Hard Pipe • Nitrogen pilot line connected to
each 3-way ball valve.
1/4 inch Sch 40 pipe or
Nitrogen Pilot 5/16 O.D. X 0.035" wall • Electric control heads on each
Electric Control Stainless steel tubing nitrogen pilot cylinder to control
Head Agent Agent Agent the directional valves.
Tank N2 Tank N2 Tank N2
• Each pilot cylinder could also be
#3 #2 #1 manually actuated.
• All cylinders must be of the same size and fill density.
Nitrogen Pilot • All nitrogen drivers must be of the same size and pressure (1800 PSIG).
Note: Two 3-way ball valves are shown for reference.
General usage is not limited to two 3-way valves.
SIDE VIEW
E E E
Note: The arrangements shown above use the larger cylinders 600 and 900 lb.)
for the purpose of clarity. This concept can also be achieved using the 200 and 350 lb. cylinders.
Figure 4-14. Arrangement 1: 3-Way Ball Valves with Nitrogen Pilot Cylindes Dedicated for Each Directional
Valve Protecting Three Hazards
Note: No pneumatic solenoid required for each 3-way ball valve.
Swing Check
Channels Needed = # of Pressure Regulator
Directional Valves + 1
or Check Valve S/O (P/N 06-118334-001)
Sol. Sol.
Factory Set to 116 PSI (8 bar)
3-Way Ball 3-Way Ball S/O Safety Outlet (P/N 82-844346-000)
VALVE 1 VALVE 2
Electric
Control Head E E E
Flex Hose or
Hard Pipe
• Nitrogen pilot line connected to each
3-way ball valve.
1/4" Sch 40 Pipe or
5/16 O.D. X 0.035" wall • Electric control head and one pilot
Nitrogen Pilot cylinder feeds all the ball valves.
Stainless steel tubing
Agent Agent Agent • Each 3-way ball valve is with a solenoid
N2 N2 N2
Tank Tank Tank pneumatic actuator (rotates 90°).
#3 #2 #1
• All cylinders must be of the same size and fill density.
• All nitrogen drivers must be of the same size and pressure (1800 PSIG).
Note: Two 3-way ball valves are shown for reference.
General usage is not limited to two 3-way valves.
SIDE VIEW
E E E
Note: The arrangements shown above use the larger cylinders (600 and 900 lb.)
for the purpose of clarity. This concept can also be achieved using the 200 and 350 lb. cylinders.
Figure 4-15. Arrangement 2: 3-Way Ball Valves with One Nitrogen Pilot Controlled by a 24 Vdc Solenoids
Protecting Three Hazards
Note: Each 3-way ball valve will have individual electric pneumatic solenoids.
N2 PILOT
CYLINDER
¼” CHECK VALVE
P/N WK-264985-000
N2 PILOT
CYLINDER NITROGEN
DRIVER
Pulley
Control Head Part Max. Cable
Type Number Length (ft.)
P/N 81-803808-000 P/N WK-844648-000
4-3.1 General
All Kidde ECS ADS Series equipment must be installed to facilitate proper inspection, testing,
manual operation, recharging and any other required maintenance as may be necessary.
Equipment must not be subject to severe weather conditions or mechanical, chemical, or other
damage that could render the equipment inoperative. Equipment must be installed in
accordance with NFPA Standard 2001.
4-3.2.1 Threads
Threads on all pipe and fittings must be tapered threads conforming to ANSI Specification
B1.20.1. Joint compound, tape or thread lubricant must be applied only to the male threads of
the joint, excluding the first two threads.
4-3.2.2 Pipe
Piping must be of noncombustible material having physical and chemical characteristics, such
that its integrity under stress can be predicted with reliability. The latest version of the flow
calculation software has only been verified for the specific types and schedule of pipe and
fittings covered in this manual. There is a risk that the system may not supply the required
quantity of agent in unbalanced systems when other pipe types and fittings are used.
4-3.2.2.3 Fittings
Class 150 and cast iron fittings must not be used. Fittings used must be minimum 300 lb. class
conforming to ASTM A-197 and have a minimum working pressure of 402 PSIG (28 bar gauge).
Flanged fittings must be 300 lb. class, American Standard, forged carbon steel.
Pressure/temperature ratings of the fitting manufacturer must not be exceeded. Teflon tape
must be applied on male threads for threaded fittings. All grooved couplings/fittings must be
listed/approved for internal pressures no less than 402 PSIG (28 bar gauge). Fittings with
higher pneumatic ratings, such as forged steel fittings, are also acceptable for use.
Concentric bell reducers are the only means for reducing pipe size. Reductions can be made
after a tee or after a union. Where reducers are used at tees, the reducers must be downstream
of each tee. Reductions made after a union are possible only if the next change in direction
(tee split) is located a minimum of six nominal pipe diameters downstream of the concentric
bell reducer. Gaskets for flanged fittings shall be flat gray asbestos, neoprene impregnated.
The calculation software has only been verified for use with the piping, inside
pipe diameter and fittings specified in this manual. When unspecified piping and
CAUTION fittings are used, there is a risk that the system will not supply the required
quantity of the agent.
PIPING TO
HAZARD A
PIPING TO
HAZARD B
3-Way
VALVE 2
PIPING TO
HAZARD A
PIPING TO
HAZARD B
(In Alarm)
90° counterclockwise
turn to Hazard B.
3-Way
VALVE 2
3. Connect the actuators on the directional valves to the pneumatic source in one of two ways
(see Figures 4-15 and 4-16 for piping and wiring diagrams):
For pilot cylinder actuation, all directional valves must have a 24 Vdc solenoid (for UL Listed
3-Way Directional Valves, use P/N 06-118384-001; for FM Approved 3-Way Directional
Valves, use P/N 06-118329-001) and a 24 Vdc connection from the control panel.
– Connect the pilot cylinder to the second pressurization port of the solenoid actuator us-
ing the actuation line.
– Connect each of the solenoids and the electric control head to the control panel so that
the electric control head fires and the correct directional valve operates for the desired
hazard.
– Test each hazard with the control panel by listening for the solenoid click at each direc-
tional valve.
– Reconnect all electrical connections.
– Attach an electric control head to the pilot cylinder (being sure it is set before installa-
tion).
4. Set the control panel to provide a delay between the firing of the pilot cylinders for the di-
rectional valves and the firing of the Kidde ECS ADS Series. The delay depends on the 3-
way Directional Valve used. For the UL Listed 3-Way Directional Valves (P/N 90-22003X-
00X), set the value to 17 seconds (see Table 4-12). This delay provides sufficient time for
the valves to fully open before the system is discharged.
PEGAsys or other
S
Release
FM Approved/UL Listed Selector Valve
Circuit
fire alarm suppression Solenoid (see note 1)
control panel
S
Release Selector Valve
Circuit Solenoid (see note 1)
S
Release Nitrogen Pilot
Circuit Control Head (see note 2)
S
Release Nitrogen Driver
Circuit Control Head (see note 2)
S
Release Nitrogen Driver
Circuit Control Head (see note 2)
Figure 4-19. Typical Single Panel System Release Circuit Wiring (see Notes below)
S
Release Nitrogen Pilot
Circuit Control Head (see note 2)
S
Release + Release
Circuit _ Control Relay (see note 3)
Initiating EOLR
Circuit
Circuit
S
Release Nitrogen Driver
Circuit Control Head (see Note 2)
S
Release Nitrogen Driver
Circuit Control Head (see Note 2)
Panel 2
Figure 4-20. Typical Multiple Panel System Release Circuit Wiring (see Notes below)
Notes:
1. Must use Pneumatic Solenoid (P/N 06-118329-001). Ratings: 24 Vdc, 11.0 W; 2.0 Vdc min-
imum dropout.
2. Must use 24 Volt DC control head. The fire alarm suppression panel release circuit must be
capable of supplying a minimum of 24 Vdc at 2.8 Amps for 30 milliseconds for control head
P/N WK-890181-000 and a minimum of 24 Vdc at 0.5 Amps continuous for control head
P/N 81-100000-001.
3. Release control relays are only required if the nitrogen driver solenoids are released by a
separate panel. Relays employed must be electrically compatible with the release circuit
output characteristics for both pull-in and dropout voltages.
4. A means of manual release of the system shall be provided. Manual release shall be accom-
plished by a mechanical manual release, or by an electrical manual release, when the con-
trol equipment monitors the battery voltage level of the standby battery supply and will
provide a low battery signal. The release shall cause simultaneous operation of automati-
cally operated valves controlling agent release and distribution.
*Refer to the Detection and Control panel Installation, Operation, and Maintenance Manual for
complete details.
The referenced control heads and solenoids are compatible with Kidde panels.
The use of other panels to operate these control heads and solenoids has not
WARNING been verified and could result in system malfunction.
For 2 inch valves, to avoid possible personal injury, always connect a valve
outlet adapter to the system piping (union connection) before connecting to an
WARNING agent cylinder valve.
Install valve outlet adapter (WK-283905-000 on 2 inch valves) in system piping. Tighten
securely and continue with threaded rigid pipe. Install a union for ease of disconnecting the
cylinder. Check valves must be used for connecting multiple cylinders on to manifold.
3 inch valves include a grooved coupling at the discharge port.
B
FACE OF
PIPE FITTING
C (HOSE SIZE)
A
Figure 4-21. Installation of the Flexible Hose Directly into System Piping
Table 4-13. Installation of the Flexible Hose Directly into System Piping, English Units
Dimensions in Inches
Cylinder Capacity
A B C
Table 4-14. Installation of the Flexible Hose Directly into System Piping, Metric Units
Dimensions in Millimeters
Cylinder Capacity
A B C
Kidde ECS ADS Series Cylinders must be located and mounted where they will
not be accidently damaged or moved. If necessary, install suitable protection to
WARNING prevent the cylinder from damage or movement.
The Kidde ECS ADS Series cylinders assemblies should be located in a place that is readily
accessible for the purpose of manual actuation and inspection, service and maintenance. The
cylinders shall be located in an environment protected from the weather and where the
ambient temperature is between 60°F (26°C) and 80°F (27°C). External heating or cooling
may be required to maintain this temperature range. The following installation instructions
must be followed in the exact sequence outlined below to prevent accidental discharge, bodily
injury and property damage.
15° 45°
4-3.10.2 Installation of a Single Cylinder and Single Driver Kidde ECS ADS Series
System
Kidde ECS ADS Series Cylinders must be located and mounted where they will
not be accidently damaged or moved. If necessary, install suitable protection to
WARNING prevent the cylinder from damage or movement.
1. Position Kidde ECS ADS Series and nitrogen driver cylinders in designated location, and se-
cure in place with cylinder strap and attaching hardware. Cylinders, straps and brackets
must be properly anchored to structural supports to adequately secure the Kidde ECS ADS
Series cylinders (see Figure 4-25, Figure 4-26, Figure 4-27, and Figure 4-28). Orient cyl-
inder with valve outlet angled toward system piping.
2. Remove the safety cap from the cylinder valve outlet port.
3. Connect a 2-inch flexible discharge hose or valve outlet adapter to the cylinder outlet port.
See Section 4-3.9 for more information.
Note: If a valve outlet adapter is used, a union must be installed in the discharge piping.
4. Install supervisory pressure switches (if applicable). Refer to Paragraph 4-3.21 for instal-
lation instructions.
3 6 7
4
1. FITTING–NITROGEN TRANSFER
2. VALVE–PNEUMATIC ACTUATOR
3. FITTING–FLARED 1/8" x 1/4”
4. HOSE–FLEXIBLE 3/16”
5. TEE–1/8" BRANCH
6. VALVE–SCHRADER
3
7. CAP–SCHRADER VALVE
The control head must be in the SET position (that is, the actuating pin must be
in the fully retracted or SET position) before attaching it to an agent cylinder in
WARNING order to prevent accidental discharge and possible personal injury.
16. Install the pneumatic control head to the top of the 2-inch valve (actuation port).
17. Attach the 1-inch transfer hose to the top of the 3/4-inch transfer fitting. Torque to 60-80
ft-lbs to prevent leakage.
21.75 in.
(552 mm)
8
5
3
6
19.00 in 1. ASSY - CYL. AND VALVE AGENT ASSY
(483 mm) 2. ASSY - CYL. AND VALVE NITROGEN DRIVER
300
600
PSI 900
3. HOSE - FLEXIBLE DISCHARGE
BACK VIEW 4. STRAP - TWO CYLINDER
0 1200
KIDDE-FENWAL
263144
1500
1
30.00 in.
(762.mm) 2
FRONT VIEW
16-19 in.
(403-479 mm)
12.75 in. Dia. 8.50 in. Dia.
(324 mm) (216 mm)
3
21.75 in.
(552 mm)
8 5
0 1200
KIDDE-FENWAL
263144
1500
4
58.00 in.
51.03 in. (1473 mm)
(1270 mm)
37.00 in.
(940 mm)
1
2
FRONT VIEW
18.5-21.5in.
(470-546 mm)
16.00 in. Dia. 10.50 in. Dia.
(406 mm) (267 mm)
8 5
65.25 in.
(1810 mm)
37.0 in.
(940 mm)
2
18.0 in.
(457 mm)
21.5-24.5 in.
(545-622 mm)
22.0 in. 10.50 in.
(559 mm) (267 mm)
6
5 1. ASSY - CYL. AND VALVE AGENT ASSY
34.0 in. 8 2. ASSY - CYL. AND VALVE NITROGEN DRIVER
(867 mm)
3. HOSE - FLEXIBLE DISCHARGE
4. STRAP - AGENT CYLINDER
5. ASSY - DISCHARGE HEAD
6. ASSY - ACTUATION
7. FITTING - ORIFICE
8. HOSE - HIGH PRESSURE
9. STRAP NITROGEN DRIVER CYLINDER
4 9
70 in. 64 in.
(1778 mm) 900 lb. 4890 (1626 mm)
cu. in. 69.22 in.
58.6 in. (1758 mm)
(1488 mm) 1 71.25 in.
(1810 mm)
44.6 in.
(1133 mm)
22 in.
(559 mm) 2
23-26 in.
(581-657 mm)
24 in. 11.25 in.
(610 mm) (286 mm)
19. Remove the red protective cap from the nitrogen driver valve.
20. Attach the plain-nut discharge head to the valve on the nitrogen cylinder.
21. Remove the protection cap from the nitrogen driver cylinder valve actuation port.
Control heads must be in the SET position (that is, the actuating pin must be in
the fully retracted or SET position) before attaching to the Kidde ECS ADS Series
WARNING cylinders in order to prevent accidental discharge and possible personal injury.
22. Install the control head to the nitrogen driver cylinder valve actuation port.
ORIFICE FITTING
CHECK DIFFUSER
Figure 4-29. Single Driver Based Agent Cylinder and Valve Assembly with Assembled Actuation
Components
4-3.10.3 Installation of a Single Cylinder and Two Driver Kidde ECS ADS Series System
(600 and 900 lb. Systems Only)
Kidde ECS ADS Series Cylinders must be located and mounted where they will
not be accidently damaged or moved. If necessary, install suitable protection to
WARNING prevent the cylinder from damage or movement.
1. Position Kidde ECS ADS Series and nitrogen driver cylinders in designated location, and se-
cure in place with cylinder strap and attaching hardware. Cylinders, straps and brackets
must be properly anchored to structural supports to adequately secure the Kidde ECS ADS
Series cylinders (see Figure 4-32 and Figure 4-33). Orient cylinder with valve outlet angled
toward system piping.
2. Remove the safety cap from the cylinder valve outlet port.
3. Connect a 3-inch flexible discharge hose or grooved piping to the cylinder outlet port. See
Section 4-3.9 for more information.
4. Install supervisory pressure switches (if applicable). Refer to Paragraph 4-3.21 for instal-
lation instructions.
3 6 7
4
1
8
3
Item
Qty. Part Number Description
No.
5. Apply thread tape to the 3/4-in. HEX nipple and thread into the “Y” transfer fitting.
6. Apply thread tape to the NPT male thread of the first 1/8-in. x 1/4-in. flared fitting, thread NPT male into
the nitrogen transfer fitting and tighten.
7. Remove the safety cap from the 3/4-inch check diffuser.
8. Install the orifice fitting to the 3/4-inch check diffuser.
9. Take the two assembled components and thread into orifice fitting attached to the nitrogen diffuser as-
sembly, then tighten.
10. Apply thread tape to the male end of 1/8-in. branch tee and thread into the pressure op-
erated control head (P/N 82-878737-000). Tighten the branch tee.
11. Apply thread tape to the NPT male thread of the second 1/8-in. x 1/4-in. flared fitting and
thread into one side of the 1/8-in. branch tee. Tighten the flared fitting.
12. Apply thread tape to the male end of the Schrader valve. Securely threading the male end
into the open end of the 1/8-in. branch tee. Apply Schrader cap to Schrader fitting.
13. Connect 1/4-in. actuation hose to flare fitting that was applied to the 1/8-in. branch tee.
14. Connect the other end of the 1/4-in. actuation hose into the flare fitting that was connected
in the busing previously.
15. Remove the protection cap from the cylinder valve.
16. Using a suitable wrench, assemble control head to cylinder valve and tighten swivel nut se-
curely.
17. Remove the protection cap from the cylinder valve actuation port.
The control head must be in the SET position (that is, the actuating pin must be in the fully
retracted or SET position) before attaching it to an agent cylinder in order to prevent
WARNING accidental discharge and possible personal injury.
18. Install the pneumatic control head to the top of the 3-inch valve (actuation port).
19. Attach the plain-nut discharge head to the bell fitting on the nitrogen transfer hose. Torque
to 60-80 ft-lbs to prevent leakage.
20. Remove the red protective cap from the nitrogen driver valve.
21. Attach the plain-nut discharge head to the valve on the nitrogen cylinder.
Note: Repeat Steps 19 through 21 when a second driver is used.
22. Remove the protection cap from the nitrogen driver cylinder valve actuation port.
Control heads must be in the SET position (that is, the actuating pin must be in
the fully retracted or SET position) before attaching to the Kidde ECS ADS
WARNING cylinders in order to prevent accidental discharge and possible personal injury.
23. Install the control head to the nitrogen driver cylinder valve actuation port.
TO PLAIN NUT
DISCHARGE HEAD.
CONNECTED TO
NITROGEN DRIVER (TYP.)
ORIFICE FITTING
CHECK DIFFUSER
Figure 4-31. Dual Driver Based Agent Cylinder and Valve Assembly with Assembled Actuation Components
10.55 in.
(268 mm)
3
36.0 in.
SIDE VIEW 7
(914 mm)
8 5
6
34.0 in.
(867 mm)
FRONT VIEW
9
4
21.5-24.5 in.
(545-622 mm)
22.0 in. 10.55 in.
(559 mm) (268 mm)
Figure 4-32. Dual Driver Installation, Vertical Mounting for 600 lb. Systems
11.25 in.
(286 mm)
3 36.0 in.
(914 mm)
6
34.0 in. 8 5
(867 mm)
4 9
70 in. 64 in.
(1778 mm) 900 lb. 4890 (1626 mm)
cu. in. 69.22 in. 1. ASSY - CYL. AND VALVE PHOENIX ASSY
58.6 in. (1758 mm) 2. ASSY - CYL. AND VALVE NITROGEN DRIVER
(1488 mm) 1 71.25 in. 3. HOSE - FLEXIBLE DISCHARGE
(1810 mm) 4. STRAP - HFC-227EA CYLINDER
44.6 in. 5. ASSY - DISCHARGE HEAD
(1133 mm) 6. ASSY - ACTUATION
7. FITTING - ORIFICE
2 8. HOSE - HIGH PRESSURE
22 in.
(559 mm) 9. STRAP NITROGEN DRIVER CYLINDERS
23-26 in.
(581-657 mm)
24 in. 11.25 in.
(610 mm) (286 mm)
Figure 4-33. Dual Driver Installation, Vertical Mounting for 900 lb. Systems
Before installing a control head on a nitrogen driver cylinder valve, ensure the
control head is in the SET position (that is, the actuating pin is in the fully
retracted or SET position). Failure to position the control head in the SET
WARNING position will result in accidental discharge and possible personal injury when
the control head is installed on the driver valve.
1. Remove the protection cap from the nitrogen driver cylinder actuation port. Ensure the con-
trol head is in SET position (that is, the actuating pin is in the fully retracted or SET posi-
tion).
2. Install the electric control head on the cylinder actuation port. Tighten the swivel nut.
3. Make all electrical connections (see Figure 4-34).
OPTIONAL CONNECTION
FOR MICROSWITCH
PLUS OR HOT CONNECTION (TERMINAL 2)
(TERMINAL 3)
MINUS, NEUTRAL
OR GROUND CONNECTION
(TERMINAL 1)
TERMINAL STRAP
3 2
MICROSWITCH
MICROSWITCH
LEVER
SWIVEL
INDICATOR AND NUT
RESET STEM CAM
1.00" HEX
(25.4 mm) 1/8"-27 NPT
PRESSURE INLET
PISTON
2.19"
(55.6 mm) SWIVEL NUT
SET
OPERATED 1.250-18
UNEF-3B
1.50" HEX
(38 mm)
Ensure that the pilot line is not pressurized and the actuating pins are in the SET
position (that is, the actuating pins are in the fully retracted or SET position).
Failure to follow this procedure will result in accidental discharge and possible
WARNING death, personal injury, and property damage when the control head is installed
on the valve.
1/16” CABLE
MINUS, NEUTRAL
OR GROUND
THREAD CABLE CONNECTION
THRU HOLE IN
OPERATING LEVER TERMINAL STRIP
POSITION CABLE
OPTIONAL CONNECTION
BLOCK APPROXIMATELY
FOR MICROSWITCH
AS SHOWN LEAVING
1/4” - 1/2” GAP
MICROSWITCH
SWIVEL NUT
INDICATOR AND
RESET STEM MICROSWITCH
LEVER
CAM
To ensure the manual lever does not snag or trap the cable, make sure the local
manual release lever is in the SET position with the locking pin and seal wire
CAUTION installed before assembling the control head cover to the body.
8. Assemble control head to nitrogen valve actuation port. Tighten swivel nut securely.
The cable operated control head (P/N 81-979469-000) must not be used with
the stackable pressure operated control head (P/N 82-878750-000). Installing
CAUTION the cable operated control head on the actuation port of the stackable pressure
operated control head will cause the device to malfunction.
Control heads must be in the SET position (that is, the actuating pin must be in
the fully retracted or SET position) before attaching to the Kidde ECS ADS
WARNING cylinders in order to prevent accidental discharge and possible personal injury.
When attaching or removing the supervisory pressure switch from the cylinder
valve, attach a wrench to the fitting and hold securely while tightening or
CAUTION loosening the pressure switch.
VALVE
WRENCH FLATS
SUPERVISORY PRESSURE
SWITCH FITTING
PRESSURE SWITCH
ELECTRICAL CABLE
FOR SWITCH CONNECTION
FACTORY SEALED
LEADWIRES 36 in. LONG ± 1 in.
CAUTION LABEL
O-RING
3 1 2
• 5A 24 Vdc (Resistive)
• 5A 240 Vac (Resistive)
Figure 4-39. Supervisory Pressure Switch Connection Diagram and Electrical Rating
Note: When cylinder supervisory pressure switch (P/N 06-118262-001) is connected to a su-
pervised control panel circuit, and the switch is wired NC under pressure, it is not pos-
sible to distinguish between a wiring fault and a loss of container pressure. This
configuration should only be used if accepted by the Authority Having Jurisdiction.
Important: Leak test the pressure switch connection with an agent leak detector or a bub-
bling solution. If the connection leaks, the switch may be tightened further until the leak is
eliminated, again, be sure to have a counter wrench on the switch port.
To ensure that all control solenoids and relays are in the correct position after
installing, testing or servicing a system, the following procedure must be
followed immediately before placing a system into service:
1. Remove all control head solenoids from the cylinders.
2. Completely de-energized all control panels, including removal of battery
power.
WARNING 3. Re-energize panels and verify that the panels are in normal operating
condition with no alarms or troubles.
4. Reinstall the solenoids on the cylinders.
Failure to adhere to this sequence may result in equipment malfunction when
the suppression system activates.
CHAPTER 5
MAINTENANCE
5-1 INTRODUCTION
This chapter contains maintenance instructions for the Kidde ECS ADS Series. These
procedures must be performed regularly in accordance with regulations. If problems arise,
corrective action must be taken.
3M™ Novec™ 1230 Fire Protection Fluid (herein refer to as “agent”) and
nitrogen cylinder valve assemblies must be handled, installed, inspected, and
serviced only by qualified and trained personnel in accordance with the
instructions contained in this manual and Compressed Gas Association (CGA)
WARNING pamphlets C-1, C-6, and P-1. CGA pamphlets may be obtained from Compressed
Gas Association: http://www.cganet.com. Before performing maintenance
procedures, refer to the material safety data sheets and safety bulletins in the
appendix of this manual.
5-2.1 General
A regular program of systematic maintenance must be established for continuous, proper
operation of each Kidde ECS ADS Series. A periodic maintenance schedule must be followed
and an inspection log maintained for ready reference. As a minimum, the log must record:
• Inspection interval
• Inspection procedure performed
• Maintenance performed, if any, as a result of inspection
• Name of inspector performing task
If inspection indicates areas of rust or corrosion are present, immediately clean and repaint the
area. Perform cylinder hydrostatic pressure testing in accordance with Paragraph 5-4.5.1,
Paragraph 6-3.3, and Paragraph 6-4.1 of this manual.
5-4.1 Weekly
5-4.2 Monthly
Before resetting the lever/pressure operated control head, all pressure must be
relieved from the cylinder and actuation lines.
Pressure can be relieved from unvented actuation tubing by loosening the
WARNING fitting on the control head slightly and allowing the line to bleed out completely.
Failure to perform this action can result in damage to the control head.
5-4.2.6 Inspect Cylinder and Valve Assembly for Both the Agent Cylinder and
Nitrogen Driver Cylinder
Inspect the agent cylinder and valve assembly for leakage, physical damage such as cracks,
dents, distortion and worn parts. Check the safety disc for damage. Replace damaged safety
disc per Paragraph 6-2.1.5. If damaged parts are found on the agent cylinder or cylinder valve,
replace as required. If necessary, clean the cylinder and associated parts as directed in
Paragraph 5-5.1.
Inspect the nitrogen driver cylinder and valve assembly for leakage, physical damage such as
cracks, dents, distortion and worn parts. Check the safety disc and pressure gauges for
damage. Replace damaged gauges or safety disc per Paragraph 6-2.2.3. If the gauge pressure
is not normal (1800 PSIG at 70 °F [124 bar gauge at 21 °C]), remove and recharge the cylinder
as described in Paragraph 6-4.2 and Paragraph 6-4.3. If damaged, parts are found on the
nitrogen driver cylinder and valve assembly, replace as required.
5-4.3 Semi-Annual
All control heads must be removed from the nitrogen driver cylinders and
nitrogen pilot cylinders before testing to prevent possible personal injury,
WARNING death, or property damage in the event of accidental cylinder discharge.
1. Remove all electric control heads from all cylinders and nitrogen pilot cylinders serving the
hazard area being tested. Let the electric control heads hang freely from the flexible electric
conduit connections. Leave all pressure operated control heads and pilot actuation hoses
attached to the cylinders.
2. Operate the system electrically. This can be done by actuating the system at the system
control panel or from an electric pull station.
3. Ensure all electric control heads have operated, (that is, the indicator on the electric control
head has moved to the RELEASED position). If any control heads have not operated, check
the circuit for electric continuity to these particular heads and repeat the test. Replace all
damaged heads. Repeat the test if any control heads have been replaced.
Control head must be reset to the SET position (fully retracted actuation pin)
before reconnecting to a cylinder valve. Failure to follow this instruction will
CAUTION result in cylinder discharge when attempting to install the control head.
4. Observe the instructions on the caution label attached to each electric control head. Re-
place any damaged heads which fail to reset properly before reconnecting to the cylinder.
Reattach all electric control heads to threaded port on cylinder valve or pressure operated
control head. Tighten the swivel nut securely. Make certain each electric control head is in
the SET position before reconnecting to the cylinders. Failure to follow this procedure will
result in accidental discharge.
CAP
GRADUATED TAPE
P/N WK-283894-000
SHOWN IN MAGNETIC
READING TAKEN AT TOP INTERLOCK POSITION
EDGE OF FITTING READY TO TAKE READING.
O-RING
BRASS TUBE
TAPE INSIDE
BRASS TUBE AGENT
CYLINDER
AGENT LEVEL
MAGNETIC END OF
TAPE ENGAGES
IN MAGNETIC FIELD
OF FLOAT WHEN
TAPE IS PULLED
UP TO TAKE READING.
MAGNET EMBEDDED
IN FLOAT.
FLOAT - FLOATS ON SURFACE
OF AGENT.
FREE TO MOVE UP OR DOWN
OUTSIDE OF BRASS TUBE.
LLI Chart
200 lb. Cylinder
27
26
25
24
23
22
21
20
19
18
17
LLI Reading (in.)
16
15 130 F
14
70 F
13
12 0F
11
10
9
8
7
6
5
4
3
2
1
0
85 105 125 145 165 185
Agent Weight (lb.)
LLI Chart
350 lb. Cylinder
24
23
22
21
20
19
18
17
16
15
LLI Reading (in.)
14
13 130 F
12 70 F
11 0F
10
9
8
7
6
5
4
3
2
1
0
150 170 190 210 230 250 270 290 310 330 350
Agent Weight (lb.)
LLI Chart
600 lb. Cylinder
25
24
23
22
21
20
19
18
17
16
LLI Reading (in.)
15
14 130 F
13
70 F
12
0F
11
10
9
8
7
6
5
4
3
2
1
0
250 270 290 310 330 350 370 390 410 430 450 470 490 510 530 550 570 590 610
Agent Weight (lb.)
LLI Chart
900 lb. Cylinder
28
27
26
25
24
23
22
21
20
19
18
17
LLI Reading (in.)
16
15 130 F
14 70 F
13 0F
12
11
10
9
8
7
6
5
4
3
2
1
0
390 410 430 450 470 490 510 530 550 570 590 610 630 650 670 690 710 730 750 770 790 810 830 850 870 890 910
Agent Weight (lb.)
Install protection cap on agent cylinder valve actuation port and safety cap on
cylinder valve outlet port. Disconnect system actuation assembly, discharge
WARNING hoses and flexible pilot hoses to prevent accidental system discharge and
possible personal injury.
5-4.4 2 Year
Do not use water or oxygen to blow out pipe lines. Using oxygen is especially
WARNING dangerous since even a minute amount of oil may cause an explosion.
1. Remove any nozzles from piping to allow any foreign matter to blow clear.
2. Remove all pressure operated control heads from cylinders.
3. Open the control valves and keep them open long enough to ensure the pipes are clean.
4. Blow out all distribution piping with air or nitrogen to ensure that it is not obstructed.
5. Reinstall the nozzles in their original locations.
6. Reconnect all control heads.
5-4.5 5 Year
5-4.5.2 Retest
DOT 3AA Nitrogen Driver cylinders and DOT 4BW500 agent cylinders used exclusively in the
agent service that are commercially free from corroding components are required to be
hydrostatically retested and restamped every five years, in accordance with DOT Regulatory
Compliance Guide, 49 CFR 180.209 prior to recharge and shipment. An alternate option is an
external visual inspection performed in lieu of the hydrostatic test at the time the periodic
retest becomes due (in accordance with CFR Paragraph 180.209). Therefore, the retest can be
performed by either of the following methods:
5-5 SERVICE
5-5.1 Cleaning
Remove dirt from metallic parts using a lint-free cloth moistened with dry cleaning solvent. Dry
parts with a clean, dry, lint-free cloth or air blow dry. Wipe non-metallic parts with clean, dry,
lint-free cloth. Remove corrosion with crocus cloth.
Note: If the system utilizes directional valves, verify that the mufflers and the bleed vent hole
at the end of the solenoid are not clogged. Air blow as required to allow for proper vent-
ing.
5-5.3 Repairs
Replace all damaged parts found during inspection. Replacement procedures for Kidde ECS
ADS Series cylinders are provided below. Since replacement for other system components are
similar, refer to installation drawings and Kidde ECS ADS Series assembly drawings for
guidance.
Kidde ECS ADS Series cylinders must be refilled or replaced when a cylinder indicates a loss in
weight in excess of 5% of the original charged net weight, or immediately after discharge.
Do not disconnect the flexible discharge hose or valve outlet adapter prior to
removing a pressure-operated or electric control head from a nitrogen driver
WARNING cylinder. Before replacing a Kidde ECS ADS Series cylinder in a hazard area
group, ensure the pilot line is completely vented of all pressure.
To prevent possible injury to personnel, each cylinder must have its safety cap
WARNING installed immediately upon disconnecting the discharge hose or valve adapter.
5. Immediately install the safety cap on the agent cylinder valve outlet port.
6. Remove attaching hardware or cylinder straps. Remove the cylinders from there bracket.
Weigh the cylinders using a platform scale, if applicable.
2. Remove the safety cap from the agent cylinder valve outlet port.
3. Immediately reconnect the valve outlet adapter or flexible discharge hose to the agent cyl-
inder outlet port and connect to system piping.
4. Remove the protection cap from the agent cylinder actuation port.
Control head must be reset to the SET position (fully retracted actuation pin)
before reconnecting to a cylinder valve. Failure to follow this instruction will
WARNING result in cylinder discharge when attempting to install the control head.
5. Install the pressure operated control head to the top of the agent cylinder valve.
6. Connect associated actuation hoses, transfer fittings, orifice fitting and transfer hose.
7. Connect transfer hose to discharge head.
8. Attach discharge head to nitrogen driver cylinder valve.
9. Install control head to nitrogen driver.
Discharge hoses or valve outlet adapters must be connected into system piping
CAUTION (union connection) before attaching to cylinder valves.
2. Remove the safety caps from the agent cylinder valve outlet ports.
3. Immediately reconnect flexible discharge hoses or valve outlet adapters to the cylinder
valve outlet ports. Connect all agent cylinders to system piping.
4. Remove the protection caps from all agent cylinder actuation ports and connect the pres-
sure operated control heads to the top of all the agent cylinder valves.
Control head must be reset to the SET position (fully retracted actuation pin)
before reconnecting to a cylinder valve. Failure to follow this instruction will
WARNING result in cylinder discharge when attempting to install the control head.
5. Install all pressure operated control heads with flexible actuation hoses or tubing on the
agent cylinder valve actuation ports. Tighten the swivel nuts.
6. Connect all associated actuation hoses, transfer fittings, orifice fittings and transfer hoses.
7. Connect the discharge heads to the transfer hoses.
8. Reinstall all pressure operated control heads with flexible actuation hoses or tubing on all
the nitrogen driver cylinders (refer to Paragraph 4-2.5.5 for the 200 and 350 lb. cylinders;
refer to Paragraph 4-2.6.5 for the 600 and 900 lb. cylinders).
9. Connect the discharge heads to the nitrogen driver cylinders.
10. Connect the control head to the actuation port of the master nitrogen driver cylinder.
Ensure the control head is in the SET position (that is, the actuating pin is in the
fully retracted or SET position) before attaching it to the cylinder valve.
IF THE CONTROL HEAD IS IN THE ACTUATED POSITION, THE CYLINDER VALVE
WARNING WILL DISCHARGE ON ATTEMPTING TO PLACE THE CONTROL HEAD ON THE
VALVE ACTUATION PORT.
7. Both the valve body and the control head hex nut are 1-1/2” across the flats. Hold the valve
body using a 1-1/2” wrench (preferred) or a suitable smooth jawed adjustable wrench.
8. Position the control head in the desired orientation and hand tighten the hex-nut. Using a
torque wrench1 fitted with a 1-1/2” crowfoot wrench, tighten to a minimum torque of 60
ft. lb.2.
9. Reinstall outlet fitting and connect to system hose, tubing or pipe (as appropriate).
1 Recommended 10-100 ft. lb. 1/2” drive torque wrench. Other ranges are acceptable pro-
vided 40-60 ft. lb. is within optimum tolerance for the tool.
2 Set wrench to a minimum setting of 55 ft. lb. (most styles of crowfoot will increase the
actual torque value by approximately 10% since a typical 1-1/2” crowfoot wrench has a
center-to-center dimension of 2”. Actual minimum torque value is 60 ft. lb. Calculate effect
of crowfoot using tool manufacturer’s data.
Nitrogen drive cylinders must be empty before replacing the pressure gauge.
Failure to empty the cylinder will result in cylinder discharge when attempting
WARNING to replace the gauge, resulting in possible personal injury, death, or property
damage.
CHAPTER 6
POST-DISCHARGE MAINTENANCE
6-1 INTRODUCTION
Follow these procedures after the system has been activated and discharged 3M™ Novec™
1230 Fire Protection Fluid (herein refer to as “agent”).
Before removing the valve, make certain all pressure has been relieved from the
cylinder. To relieve any remaining pressure, make sure the cylinder is secure,
WARNING then depress the pressure switch Schrader valve until all pressure is relieved.
1. Remove the valve with the siphon tube from the cylinder.
2. Remove the cylinder neck O-ring (Item 4 in Figure 6-1) and discard the O-ring.
3. Remove the valve cap, spring and piston assembly.
Note: Remove all internal components of the agent valve from the top of the assembly. How-
ever, if there is excessive friction at the piston O-ring, the siphon tube may have to be
removed and the piston assembly pushed out the valve body from the bottom.
4. Remove the valve cap O-ring (Item 1) and piston O-ring (Item 2). Discard the O-rings.
5. Remove the seat retainer from the piston by first unscrewing the 4 cap screws, followed by
the hex nut.
6. Remove the seat O-ring (Item 3) and discard the O-ring.
7. Examine the Schrader valve core pin (Item 5) for any evidence of bending or other damage.
Depress the pin and make certain it snaps back freely. Replace the valve core if necessary
using a standard Schrader core wrench. When reinstalling a new Schrader core element,
torque to 1½ to 3 in.-lbf (169 to 339 mN-m).
After reinstalling a Schrader core, the distance from the top of the core pin to
the control head seating surface must be between 0.515 to 0.565 inch (13 mm
CAUTION to 14 mm) when in the shut or non-actuated position. See the Gauging Distance
in Figure 6-1.
8. Check the piston assembly for any scratches, gouging, or deformation. If present, replace
the parts as necessary.
Make certain that the Teflon backup ring is below this O-ring as shown in
CAUTION Figure 6-2.
2. Apply lubricant to the Seat O-ring (Item 3) and install the O-ring onto the seat retainer.
(See Figure 6-3)
3. Place the piston retainer back into the piston. Secure the retainer with the 4 cap screws.
Torque the cap screws to 85-90 in-lbs (9-10 N-m).
4. Screw the hex nut onto the piston and torque to 30-35 ft-lbs (41-47 N-m).
5. Ensure the Seat O-ring protrudes a minimum of 0.02 in. (0.5 mm) above the conical seat-
ing surface of the piston.
6. Press the piston back into the valve body.
7. Install the spring.
8. Apply lubricant to the Cap O-ring (Item 1). Install the Cap O-ring onto the groove in the
valve cap.
9. Screw the valve cap onto the valve body and torque to 50-55 ft-lbs (68-75 N-m).
10. If you had to remove the siphon tube for valve disassembly, wire brush the siphon tube
threads to remove the old Loctite® residue.
11. Apply a film of Loctite primer to the siphon tube threads and allow three to five minutes to
dry (see Table 6-2 for Loctite references).
12. Apply a film of Loctite sealant to the threads and reinstall the siphon tube.
13. Apply lubricant to the Neck O-ring (Item 4). Install the Neck O-ring onto the valve neck
groove.
14. Screw the valve and siphon tube onto the cylinder, and torque to 50 to 55 ft-lb (68 to 75
N-m).
Gauging Dimension:
.515 - .565 in. Valve Core
Valve Cap
Cap O-ring
Spring
Piston Piston O-ring
Back-up Ring
Seat Retainer
Hex Nut
Cap Screw
Seat O-ring
Safety Cap
Neck O-ring
Siphon Tube
Piston O-ring
Hex Nut
Piston
Seat O-ring
Seat Retainer
Cap Screws
Valve Cap
Pilot Check
WK-923066-000
Pilot Check Spring
WF-230640-000
Piston O-Ring
Valve Cap O-Ring WK-566103-370
WK-566102-410 Back-Up Teflon Ring
Spring WK-554003-400
Piston
Retainer O-Ring
WK-566103-400
Safety Cap
Refill Part
(½ inch NPT Thread)
Valve Cap
Pilot Check
Spring
Disk
Retaining Ring
Make certain that the Teflon® back-up ring is below the O-ring as shown in
CAUTION Figure 6-6.
Piston O-ring
Whenever the valve is rebuilt, the Safety Disc Assembly must be replaced.
CAUTION
Before removing the Safety Burst Disc Assembly, make sure that all pressure
has been relieved from the cylinder. To relieve any remaining pressure, restrain
WARNING the cylinder and depress the pressure check in the Supervisory Pressure Switch.
1. Remove and discard the safety burst disc assembly (see Figure 6-7 and Figure 6-8).
2. Apply lubricant to the packing O-ring of the new safety burst disc assembly.
3. Install the new safety disc assembly to the cylinder. Torque to the appropriate value listed
in Table 6-4.
Install only the type of safety burst disc assembly specified in Table 6-4 for the
corresponding cylinder size. Installation of an incorrect safety burst disc
WARNING assembly could result in a violent rupture of the cylinder and cause death,
serious injury and/or property damage.
Packing O-ring
Packing O-ring
Before disassembly of valve, relieve all pressure from the cylinder. Contents
WARNING under pressure can cause personal injury or property damage.
COPPER GASKET
WK-326420-000
VALVE SEAT - WK-202490-000
Install only the type of safety burst disc that is specified for the nitrogen
cylinder. Installation of an incorrect safety burst disc assembly could result in
WARNING a violent rupture of the cylinder and cause death, serious injury and/or
property damage.
Never reinstall a used safety disc or washer. Once the safety disc retaining nut,
washer, and safety disc have been removed they must be replaced with new
WARNING parts.
2300 through 4890 cu. in. 81-902048-000 WK-220034-000 350 ± 35 in. lb. 2900-3250
3.81"
(97 mm)
PISTON
BALL
RETAINER
STOP
CHECK BALL
CHECK
SPRING
3.94"
(100 mm) DISCHARGE
OUTLET
Before disassembly of check diffuser, make certain all pressure has been
relieved from the cylinder. To relieve any remaining pressure, depress the
WARNING pressure switch Schrader valve until all pressure is relieved.
VALVE SEAT
P/N 06-235930-001
COPPER GASKET
CUP CHECK ASSEMBLY P/N WK-326420-000
P/N 06-129860-001
SPRING
RETAINING RING
SPRING SEAT
O-RING
P/N WK-566109-100
3/4” CHECK
DIFFUSER BODY
Agent charging equipment consists of an agent storage cylinder, piping adapter, control valves,
strainer, pressure gauge, flexible hoses, seating adapter, recharge adapter, pump, regulated
nitrogen supply, scale and interconnecting plumbing. Recharge equipment must be suitable for
the purpose intended and must be compatible with the agent. A typical agent charging system
schematic is shown in Figure 6-12.
Note: During recharge, the cylinder pressure gauge is not to be used to determine
charging pressure.
Locate the charging equipment in a clean, well-ventilated area near the agent supply
and cylinder storage. There should be sufficient room for moving the cylinders to and
from the charging equipment.
R
12 P 8 7
Flex Hose
11 22 N2
15
19
20 23 6
16
2 Flex Hose 21
18 17
14
Agent Cylinder
Supply Container 13
4
3
1
9 Scale 5
10
1. Check the cylinder for the last hydrostatic test date prior to charging. Perform any required
DOT hydrostatic tests (see Paragraph 6-2.5).
2. Check the cylinder valve assembly for any unacceptable physical defects (for example,
cracks of any kind, elongated pits of any length, inclusions of any size, pitting, bulging,
dents, corrosion, fire damage, mechanical defects, scratches, nicks or gouges if more than
superficial in nature). These defects shall be cause for rejection.
3. Weigh the cylinder and valve assembly to verify the quantity of agent in the cylinder. En-
sure that no more than 10 PSIG (0.7 bar gauge) of nitrogen is in cylinder before beginning
the fill procedures.
3M™ Novec™ 1230 Fire Protection Fluid (agent)) is a colorless and odorless
liquid with a boiling point of 120 °F (48.9 °C). When discharged into air the
agent liquid evaporates to form vapor-air mixtures that are very effective for
extinguishing fires when used at or above the minimum recommended agent
design concentrations, or MDC. The MDC for most applications is usually less
CAUTION than the NOAEL of agent vapor, which is 10 vol. %. As stated in NFPA 2001,
unnecessary exposure of personnel to halocarbon clean agent vapors at
concentrations up to the NOAEL, shall be avoided. In the event of accidental
discharge into occupied spaces means shall be provided to limit personnel
exposure to agent vapors to no longer than five (5) minutes.
Note: Drierite filter (Item 2) should be installed on agent supply container (Item 1) prior to
beginning filling. Drierite filters are designed to remove moisture from the air to prevent
contamination of fluid.
4. Connect the agent supply line to the agent supply cylinder valve (Item 3). Close all valves
in the charging system.
5. Open the supply valves (Items 3, 9, and 14). Start the pump (Item 10), then crack the vent
valve (Item 20) until agent is present. Close vent valve (Item 20) and shut off pump (Item
10).
6. Position the agent cylinder and valve assembly (Item 4) (with safety cap and pilot actuation
port protection cap in place and properly connected) on a weigh scale (Item 5). Record the
weight from the scale. The empty weight of the cylinder and valve assembly must be
stamped on the cylinder valve nameplate.
7. Remove the safety cap and immediately connect the cylinder assembly into the charging
system by assembling the recharge adapter (Item 17) with O-ring packing to the cylinder
assembly outlet port.
Note: The main piston in the cylinder valve assembly will unseat, permitting flow into the as-
sembly when a 10 PSIG (0.7 bar gauge) differential (approximate) exists at the outlet
port. Initial valve assembly seating occurs with pressure equalization. Final valve as-
sembly seating occurs with removal of pressure from valve assembly outlet port and
subsequent momentary application of 450 to 600 PSIG (31 to 41 bar gauge) of nitrogen
discussed below.
8. Open valve (Item 18) and start the pump (Item 10). Monitor the weigh scale (Item 5).
When the scale indicates the correct charge weight, shut off the pump (Item 10) and close
the supply valves (Item 18 and 14).
Note: The 360 PSIG (27.92 bar gauge) pressure applies to the filling procedure with nitrogen
and agent at 70 ± 10 °F (21 ± -12 °C). When the temperature is other than 70 °F (21
°C), refer to Table 6-10 for required total pressure. Do not fill agent cylinders at tem-
peratures below 60 °F (16 °C) or above 90 °F (27 °C).
Temperature Pressure
Note: 360 PSIG + 20, - 0 PSIG, at 70 °F (25 bar gauge +1.4, -0 bar gauge at 21 °C) is the
final pressure required after the charged cylinder has had sufficient time to stabilize.
Additional nitrogen may be required to attain the 360 PSIG (25 bar gauge) after the
stabilization period has elapsed.
9. If nitrogen is required, open the hand-wheel valve on the nitrogen supply valve (Item 7),
nitrogen valve (Item 16), and valve (Item 11). Adjust the regulator (Item 8) until the mas-
ter pressure gauge (Item 12) shows a pressure indication of 360 PSIG + 20, -0 PSIG (25
bar gauge + 1.4, -0 bar gauge).
10. Open the hose control valve (Item 18) and let nitrogen flow into the cylinder until the mas-
ter pressure gauge indicates 360 PSIG (25 bar gauge). Cylinder agitation will assist with
the equilibrium of nitrogen and agent Addition of nitrogen may be necessary as the cylinder
equilibrates.
11. Close the hose control valve (Item 18). Remove the pilot actuation port protection cap and
assemble the seating adapter (Item 21) with the flexible hose to the cylinder valve actua-
tion port. Adjust the regulator to 450 to 600 PSIG. Open valve (Item 22) to momentarily
apply nitrogen pressure to the actuation port to firmly seat the cylinder valve piston.
12. While momentarily maintaining pressure on the actuation port, open vent valve (Item 19)
on the recharge adapter (Item 17) to rapidly vent agent from the valve assembly outlet
port. The sudden pressure decrease at the valve outlet will ensure the valve seat stays in
the closed position.
13. Leave vent valve (Item 19) open. Close valve (Item 22) and open valve (Item 23) to vent
nitrogen from the seating adapter.
Any hissing or discharge coming from vent valve (Item 19) indicates that the
piston is not sealed properly or has opened. If this occurs, close valve (Item 19)
CAUTION and repeat steps 12 and 13. Verify that the cylinder valve piston remains closed.
14. Keep vent valve (Item 19) open. Close valve (Item 23), and once again open valve (Item
22) to reapply nitrogen pressure to the actuation port. While momentarily maintaining
pressure on the actuation port, remove the recharge adapter (Item 17) from the cylinder
valve outlet port and immediately install the safety cap. Close the vent valve (Item 19).
Nitrogen pressure must be maintained on the actuation port while removing the
charging adapter and installing the safety cap to ensure that the cylinder valve
WARNING does not inadvertently actuate while the valve outlet port is wide open. Failure
to follow this could result in injury and damage to property.
15. Close the nitrogen supply valve (Item 7) and open vent valve (Item 23) to vent nitrogen
from the supply line.
16. Remove the seating adapter (Item 21) from the cylinder valve and reinstall the actuation
port protection cap. Close valves (Items 22 and 23).
17. Weigh the fully charged cylinder. The weight must agree with the weight stamped on
the cylinder valve nameplate. Record the date of recharge on the cylinder record tag.
18. Monitor the cylinder valve gauge. The gauge indicator must read 360 PSIG + 25, -0 PSIG
at 70°F (25 bar +1.7, -0 bar gauge at 21°C) after the stabilization period.
19. The cylinder is now ready for the leak test (refer to Paragraph 6-3.3).
The agent cylinders have been designed for a maximum fill density of 70 lb./ft³
(1121 kg/m³) and super pressurized with nitrogen to 360 PSIG + 20 PSIG at 70 °F
CAUTION (25 bar gauge +1.4, -0 bar gauge at 21 °C). It is important that these values not be
exceeded.
The pressure in the agent cylinder is significantly affected by fill density and temperature.
At elevated temperatures, the rate of increase in pressure is very sensitive to fill density.
If the maximum fill density is exceeded, the pressure will increase rapidly with tempera-
ture increase so as to present a hazard to personnel and property. Adherence to the limits
on fill density and pressurization levels will prevent excessively high pressures from oc-
curring if the agent cylinder is exposed to elevated temperature, minimizing the possibil-
ity of an inadvertent discharge of agent through the pressure relief device.
Note: To change the agent supply container (Item 1) close container valve (Items 3) and
valve (Item 9). Disconnect filling line from agent supply container. Position new agent
supply container in place. Connect filling line to the new agent supply container. Open
valves (Items 3 and 9).
Clamp agent cylinder securely in place. The clamping device and supports must
be capable of withstanding a thrust force of 1800 lbf (8000 N). This
WARNING approximates the thrust force generated out of the agent cylinder valve outlet
on a full, wide open discharge.
1. Warm up the leak detector for 30 minutes before proceeding with Step 2.
2. Calibrate the detector against the LS-20 leak standard by holding the probe about 1/8-inch
(3 mm) away, and noting the meter deflection for the leakage allowance of the standard.
Maximum allowable leak rates are shown in Table 6-11.
lb lb oz/yr
3. Remove the safety cap from the discharge outlet. Blow nitrogen on the surface where the
plug was removed.
4. Move probe back and forth slowly approximately 1/8-inch (3 mm) away from all potential
leak points (discharge outlet area, pilot check, valve bonnet, safety outlet, liquid level in-
dicator, valve-to-cylinder connections, gauge and container welds). If the meter deflections
are greater than those that occurred during calibration, the cylinder/valve assembly has
failed the leaked test.
5. Replace the safety cap immediately after the test.
6. If the assembly failed the leak test in Step 4, salvage the agent, perform the required main-
tenance on the container, and recharge.
7. After the leak test is complete, reassemble the protection cap to the actuation port of valve
assembly. Unclamp the cylinder.
When removing a pressurized cylinder due to pressure loss, the control head
must be in the SET position with the safety pin installed. A control head in the
released position will cause the remaining contents of cylinder to discharge
WARNING resulting in a system activation which can cause death, personal injury and/or
property damage.
Replace the nitrogen pilot cylinder when expended or when loss of pressure occurs as follows:
1. Remove the control head from the nitrogen driver cylinder valve.
2. Immediately install the protection cap on the nitrogen pilot cylinder actuation port.
3. Remove discharge head from cylinder valve.
4. Remove 1-inch nitrogen transfer hose from the agent cylinder.
5. Remove clamps and hardware securing nitrogen pilot cylinder to the mounting bracket.
6. Allow the cylinder to cool to ambient temperature and recheck the nitrogen pilot cylinder
indicated pressure.
7. Open valve and add additional nitrogen as needed to obtain full cylinder charge at ambient
temperature (1800 PSIG at 70°F [124 bar gauge at 21°C]).
8. Close the valve and remove the supply hose and charging adapter from the pilot cylinder.
9. Check the nitrogen driver cylinder valve for leakage using a soap solution. Bubbles appear-
ing in the soap solution indicate leakage and shall be cause for rejection of cylinder.
10. After the leak test is completed, clean and dry the cylinder valve.
11. Ensure the cylinder valve control head port is clean and dry.
12. Immediately install the protective cap to the actuation port of the cylinder valve.
13. Install the charged cylinder as directed in Table 5-7.
2000
1900
1800 U RE
PRESSURE PSIG
E SS E
PR SUR
1700
AL R ES
M
IN L EP
1600 NO WAB
L O
AL
1500 M UM
NI
MI
1400
RECHARGE
1300
1200
-40° -20° 0° 20° 40° 60° 80° 100° 120° 140°
TEMPERATURE °F
CHAPTER 7
PARTS LIST
Cylinder/Valve Assemblies
2300 cu. in. Nitrogen Driver Cylinder/Valve Assembly with pressure gauge for use with 200 45-502300-001
lb. agent cylinders
2300 cu. in. Nitrogen Driver Cylinder/Valve Assembly with en.Gauge® supervisory pressure 45-502300-101
gauge for use with 200 lb. agent cylinders
4070 cu. in. Nitrogen Driver Cylinder/Valve Assembly with pressure gauge for use with 350 45-504070-001
lb. and 600 lb. agent cylinders
Note: The 600 lb. agent cylinders require either one or two drivers, depending on the flow
calculations. For more information, see Section 4-2.3.1.
4070 cu. in. Nitrogen Driver Cylinder/Valve Assembly with en.Gauge supervisory pressure 45-504070-101
gauge for use with 350 lb. and 600 lb. agent cylinders
Note: The 600 lb. agent cylinders require either one or two drivers, depending on the flow
calculations. For more information, see Section 4-2.3.1.
4890 cu. in. Nitrogen Driver Cylinder/Valve Assembly with pressure gauge for use with 900 45-504890-001
lb. agent cylinders
Note: The 900 lb. agent cylinders require either one or two drivers, depending on the flow
calculations. For more information, see Section 4-2.3.1.
4890 cu. in. Nitrogen Driver Cylinder/Valve Assembly with en.Gauge supervisory pressure 45-504890-101
gauge for use with 900 lb. agent cylinders
Note: The 900 lb. agent cylinders require either one or two drivers, depending on the flow
calculations. For more information, see Section 4-2.3.1.
Vertical Mount Only- Kidde ECS ADS Series Cylinder and Valve Assemblies
200 lb. Capacity Cylinder and Valve Assembly with LLI 45-500201-001
350 lb. Capacity Cylinder and Valve Assembly with LLI 45-500351-001
600 lb. Capacity Cylinder and Valve Assembly with LLI 45-500601-001
900 lb. Capacity Cylinder and Valve Assembly with LLI 45-500901-001
Actuation Assemblies
Actuation Assembly (for use with 200 lb. or 350 lb. systems) 06-129882-001
Actuation Assembly (for use with 600 lb. or 900 lb. systems) 06-129985-001
Orifice Fitting, 0.107” Diameter 85-194129-107
Orifice Fitting, 0.111” Diameter 85-194129-111
Orifice Fitting, 0.116” Diameter 85-194129-116
Orifice Fitting, 0.120” Diameter 85-194129-120
Orifice Fitting, 0.129” Diameter 85-194129-129
Orifice Fitting, 0.136” Diameter 85-194129-136
Orifice Fitting, 0.234” Diameter 85-194129-234
Orifice Fitting, 0.261” Diameter 85-194129-261
Orifice Fitting, 0.281” Diameter 85-194129-281
Orifice Fitting, 0.316” Diameter 85-194129-316
Orifice Fitting, 0.348” Diameter 85-194129-348
Orifice Fitting, 0.391” Diameter 85-194129-391
Orifice Fitting, 0.438” Diameter 85-194129-438
Orifice Fitting, 0.484” Diameter 85-194129-484
Cylinder Straps
Cradles
Front Clamps
Control Heads
Auxiliary Equipment
Check Valves
Name Plate
“Main” WK-310330-000
“Reserve” WK-310340-000
“Warning 3M™ Novec™ 1230 Fire Protection Fluid” 06-231866-760
Escutcheon Plates
0.0460 85-194423-201
0.0475 85-194423-202
0.0491 85-194423-203
0.0519 85-194423-204
0.0535 85-194423-205
0.0554 85-194423-206
0.0603 85-194423-207
0.0620 85-194423-208
0.0661 85-194423-209
0.0716 85-194423-210
0.0767 85-194423-211
0.0784 85-194423-212
0.0845 85-194423-213
0.0866 85-194423-214
0.0928 85-194423-215
0.0951 85-194423-216
0.1014 85-194423-217
0.1064 85-194423-218
0.1116 85-194423-219 85-194424-219
0.1170 85-194423-220 85-194424-220
0.1238 85-194423-221 85-194424-221
0.1296 85-194423-222 85-194424-222
0.1340 85-194423-223 85-194424-223
0.1398 85-194423-224 85-194424-224
0.1503 85-194423-225 85-194424-225
0.1612 85-194423-226 85-194424-226
0.1726 85-194423-227 85-194424-227
0.1843 85-194423-228 85-194424-228 85-194425-228
0.1963 85-194423-229 85-194424-229 85-194425-229
0.2088 85-194423-230 85-194424-230 85-194425-230
0.2216 85-194423-231 85-194424-231 85-194425-231
0.2349 85-194423-232 85-194424-232 85-194425-232
0.0460 85-194413-201
0.0475 85-194413-202
0.0491 85-194413-203
0.0519 85-194413-204
0.0535 85-194413-205
0.0554 85-194413-206
0.0603 85-194413-207
0.0620 85-194413-208
0.0661 85-194413-209
0.0716 85-194413-210
0.0767 85-194413-211
0.0784 85-194413-212
0.0845 85-194413-213
0.0866 85-194413-214
0.0928 85-194413-215
0.0951 85-194413-216
0.1014 85-194413-217
0.1064 85-194413-218
0.1116 85-194413-219 85-194414-219
0.1170 85-194413-220 85-194414-220
0.1238 85-194413-221 85-194414-221
0.1296 85-194413-222 85-194414-222
0.1340 85-194413-223 85-194414-223
0.1398 85-194413-224 85-194414-224
0.1503 85-194413-225 85-194414-225
0.1612 85-194413-226 85-194414-226
0.1726 85-194413-227 85-194414-227
0.1843 85-194413-228 85-194414-228 85-194415-228
0.1963 85-194413-229 85-194414-229 85-194415-229
0.2088 85-194413-230 85-194414-230 85-194415-230
0.2216 85-194413-231 85-194414-231 85-194415-231
0.2349 85-194413-232 85-194414-232 85-194415-232
0.2485 85-194414-233 85-194415-233
0.2625 85-194414-234 85-194415-234
0.2769 85-194414-235 85-194415-235
0.2917 85-194414-236 85-194415-236
1.9175 85-194418-274
2.0739 85-194418-275
2.2365 85-194418-276
2.4053 85-194418-277
2.5802 85-194418-278
2. HAZARDS IDENTIFICATION
EU Main Hazards
R36 Irritating to eyes.
Routes of Entry
Eye contact - Inhalation - Skin contact - Ingestion
Carcinogenic Status
Not considered carcinogenic by NTP, IARC, and OSHA.
Target Organs
Eyes - Respiratory system
Health Effects - Eyes
Contact may cause slight irritation.
Health Effects - Skin
Not expected to cause irritation.
Health Effects - Ingestion
Not a likely route of exposure. No adverse effects are expected.
Health Effects - Inhalation
If thermal decomposition occurs, may be harmful if inhaled.
3. COMPOSITION/INFORMATION ON INGREDIENTS
Eyes
Immediately flood the eye with plenty of water for at least 15 minutes, holding the eye open. Obtain
medical attention if soreness or redness persists.
Skin
Flush with water. Obtain medical attention if symptoms persist.
Ingestion
Ingestion is not considered a potential route of exposure.
Inhalation
Remove from exposure. If there is difficulty in breathing, give oxygen. Obtain medical attention
immediately.
Advice to Physicians
Treat symptomatically.
Extinguishing Media
TM TM
3M Novec 1230 is used as an extinguishing agent and therefore is not a problem when trying to
control a blaze. Use extinguishing agent appropriate to other materials involved. Keep containers and
surroundings cool with water spray as containers may rupture or burst in the heat of a fire.
Unusual Fire and Explosion Hazards
Containers may explode in heat of fire. Predominant decomposition product is hydrogen fluoride in fire
situations. By -products are irritating and potentially toxic.
Protective Equipment for Fire-Fighting
Wear full protective clothing and self-contained breathing apparatus as appropriate for specific fire
conditions.
Wear full protective clothing. Remove leaking cylinder to a well ventilated area. Contain and absorb
using earth, sand or other inert material. Transfer into suitable containers for recovery or disposal.
Containers should be properly stored and secured to prevent falling or being knocked over. Do not
drag, slide or roll containers. Do not drop containers or permit them to strike against each other. Never
apply flame or localized heat directly to any part of the container. Store away from sources of heat or
ignition. Storage area should be: - cool - dry - well ventilated - under cover - out of direct sunlight -
away from incompatible materials (see Section 10)
Respiratory Protection
Not normally required. If thermal decomposition occurs, use a self contained breathing apparatus.
Hand Protection
Protective Gloves
Eye Protection
Chemical goggles or safety glasses with side shields.
Body Protection
Normal work wear.
Stability
Stable under normal conditions.
Conditions to Avoid
Exposure to direct sunlight - ultraviolet light
Materials to Avoid
Strong bases – amines - alcohols
Hazardous Polymerization
Will not occur.
Hazardous Decomposition Products
Oxides of carbon - hydrogen fluoride
Acute Toxicity
NOAEL for cardiac sensitization: 10% v/v
Inhalation Study: No signs of acute toxicity were observed during a 4-hr acute inhalation study (rat) at
10%, a 2-hr. acute inhalation study (rat) at 10% and a 28 day acute inhalation study (rat) at 2.0%.
Chronic Toxicity/Carcinogenicity
This product is not expected to cause long term adverse health effects.
Genotoxicity
Not mutagenic in Ames assay.
Reproductive/Developmental Toxicity
This product is not expected to cause adverse reproductive effects.
Mobility
Product is highly insoluble in water and volatile.
Persistence/Degradability
Photolytic half-life: 3 - 5 days
Persistent Photolytic degradation product: trifluoroacetic acid.
Bio-accumulation
No data available.
Ecotoxicity
No data available.
13. DISPOSAL CONSIDERATIONS
Dispose of container in accordance with all applicable local and national regulations. Do not cut,
puncture or weld on or near the container. If spilled, contents will vaporize to the atmosphere.
DOT CFR 172.101 Data Compressed Gases, n.o.s. (C-6 Perfluoroketone), 2.2, UN1956
UN Proper Shipping Name Compressed Gases, n.o.s. (C-6 Perfluoroketone)
UN Class (2.2) Non-Flammable Gas
UN Number UN1956
UN Packaging Group Not applicable
EU Label Information
Classification and labelling have been performed according to EU directives 67/548/EEC and 99/45/EC
including amendments(2001/60/EC and 2006/8/EC)
EU Hazard Symbol and Indication of Danger.
Xi - Irritant
R phrases
R36 Irritating to eyes.
S phrases
S26 In case of contact with eyes, rinse immediately with plenty of water and seek medical advice.
S36/37/39 Wear suitable protective clothing, gloves and eye/face protection.
NFPA Ratings
NFPA Code for Health - 3
NFPA Code for Flammability - 0
NFPA Code for Reactivity - 1
NFPA Code for Special Hazards – None
HMIS Ratings
HMIS Code for Health - 0
HMIS Code for Flammability - 0
HMIS Code for Reactivity - 1
HMIS Code for Personal Protection - See Section 8
Abbreviations
N/A: Denotes no applicable information found or available
CAS#: Chemical Abstracts Service Number
ACGIH: American Conference of Governmental Industrial Hygienists
OSHA: Occupational Safety and Health Administration
TLV: Threshold Limit Value
PEL: Permissible Exposure Limit
STEL: Short Term Exposure Limit
NTP: National Toxicology Program
IARC: International Agency for Research on Cancer
R: Risk
S: Safety
NOAEL: No Observed Adverse Effect Level
Prepared By: EnviroNet LLC.
The information contained herein is based on data believed to be accurate. However, no
representation, warranty, or guarantee is made to its accuracy, reliability or completeness. It is the
user's responsibility to satisfy himself as to the suitability and completeness of such information for its
own particular use. Kidde Fire Systems assumes no responsibility for personal injury or property
damage resulting from use, handling or from contact with this product.
Nitrogen (Expellant)
2. HAZARDS IDENTIFICATION
EU Main Hazards
Non Flammable Gas
Routes of Entry
Eye contact - Inhalation - Skin contact
Carcinogenic Status
Not considered carcinogenic by NTP, IARC, and OSHA.
Target Organs
Respiratory System
Health Effects - Eyes
Non-irritating gas
Health Effects - Skin
Non-irritating gas
Health Effects - Ingestion
Ingestion is not a possible route of exposure.
Health Effects - Inhalation
Avoid direct inhalation of undiluted gas. Can cause suffocation by reducing oxygen available for
breathing. Breathing very high concentrations can cause dizziness, shortness of breath,
unconsciousness or asphyxiation.
3. COMPOSITION/INFORMATION ON INGREDIENTS
Nitrogen (Expellant)
Eyes
No specific measures.
Skin
No specific measures.
Ingestion
Ingestion is not considered a potential route of exposure.
Inhalation
Remove from exposure. If there is difficulty in breathing, give oxygen. Obtain medical attention
immediately.
Advice to Physicians
Treat symptomatically.
Extinguishing Media
All known extinguishing media can be used. Use extinguishing media appropriate for containers in the
area.
Unusual Fire and Explosion Hazards
Containers may explode in heat of fire.
Protective Equipment for Fire-Fighting
Wear full protective clothing and self-contained breathing apparatus as appropriate for specific fire
conditions.
Material is a normal atmospheric gas. Remove leaking cylinder to a safe place. Ventilate the area.
Wear self contained breathing apparatus when entering confined spaces unless atmosphere is proven
to be safe.
Cylinders should be properly stored and secured to prevent falling or being knocked over. Do not drag,
slide or roll cylinders. Do not drop cylinders or permit them to strike against each other. Never apply
flame or localized heat directly to any part of the cylinder. Store away from sources of heat or ignition.
Storage area should be: - cool - dry - well ventilated - under cover - out of direct sunlight
Nitrogen (Expellant)
Respiratory Protection
Not normally required. In oxygen deficient atmospheres, use a self contained breathing apparatus, as
an air purifying respirator will not provide protection.
Hand Protection
Use leather or sturdy work gloves when handling cylinders.
Eye Protection
Chemical goggles or safety glasses with side shields.
Body Protection
Normal work wear.
Stability
Stable under normal conditions.
Conditions to Avoid
Extremely high temperatures - flames
Materials to Avoid
None known
Hazardous Polymerization
Will not occur.
Hazardous Decomposition Products
None
Acute Toxicity
Simple asphyxiant.
Chronic Toxicity/Carcinogenicity
This product is not expected to cause long term adverse health effects.
Nitrogen (Expellant)
Genotoxicity
This product is not expected to cause any mutagenic effects.
Reproductive/Developmental Toxicity
This product is not expected to cause adverse reproductive effects.
Mobility
Nitrogen occurs naturally in the atmosphere.
Persistence/Degradability
Nitrogen occurs naturally in the atmosphere.
Bio-accumulation
Nitrogen occurs naturally in the atmosphere.
Ecotoxicity
No data available
Dispose of container in accordance with all applicable local and national regulations. Do not cut,
puncture or weld on or near to the container. If spilled, contents will vaporize to the atmosphere.
EU Label Information
Classification and labelling have been performed according to EU directives 67/548/EEC and 99/45/EC
including amendments(2001/60/EC and 2006/8/EC)
EU Hazard Symbol and Indication of Danger.
Non Flammable Gas
R phrases
None
S phrases
S9 Keep container in a well ventilated place.
Nitrogen (Expellant)
NFPA Ratings
NFPA Code for Health - 0
NFPA Code for Flammability - 0
NFPA Code for Reactivity - 0
NFPA Code for Special Hazards – None
Nitrogen (Expellant)
HMIS Ratings
HMIS Code for Health - 0
HMIS Code for Flammability - 0
HMIS Code for Reactivity - 0
HMIS Code for Personal Protection - See Section 8
Abbreviations
N/A: Denotes no applicable information found or available
CAS#: Chemical Abstracts Service Number
ACGIH: American Conference of Governmental Industrial Hygienists
OSHA: Occupational Safety and Health Administration
TLV: Threshold Limit Value
PEL: Permissible Exposure Limit
STEL: Short Term Exposure Limit
NTP: National Toxicology Program
IARC: International Agency for Research on Cancer
R: Risk
S: Safety
Prepared By: EnviroNet LLC.
The information contained herein is based on data believed to be accurate. However, no
representation, warranty, or guarantee is made to its accuracy, reliability or completeness. It is the
user's responsibility to satisfy himself as to the suitability and completeness of such information for its
own particular use. Kidde Fire Systems assumes no responsibility for personal injury or property
damage resulting from use, handling or from contact with this product.
These instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection with
installation, operation and maintenance. All specifications subject to change without no-
tice. Should further information be desired or should particular problems arise which are
400 Main Street not covered sufficiently for the purchaser’s purposes, the matter should be referred to
Ashland,MA 01721 KIDDE-FENWAL INC., Ashland, MA 01721.
Ph:(508)881-2000
Fax:(508)881-8920 06-237256-001 Rev. AA ©2014 Kidde-Fenwal, Inc. All Rights Reserved.
http://www.kiddefiresystems.com