19 February 2018

REQUEST FOR PROPOSAL

RFP#: 002

Project: Oakland Middle School


Rutherford County Board of Education
Murfreesboro, Tennessee
BGA Project No. 17004

To: RG Anderson Inc.


1801 West End Avenue, Suite 1800
Nashville, TN 37203

Please submit an itemized proposal for changes in the Contract Sum for proposed and/or
potential modifications to the Contract Documents described below. Also provide complete
backup from each subcontractor involved in this item(s). THIS IS NOT A CHANGE ORDER,
A CONSTRUCTION CHANGE DIRECTIVE, OR A DIRECTION TO PROCEED WITH THE
WORK DESCRIBED IN THE PROPOSED MODIFICATIONS.

Description:

Provide pricing deduct for labor, equipment, and materials to complete the changes described in
the attached drawings.

ARCHITECTURAL:

Sheet A101
1. Reconfigured Casework Layout in Science Labs 114 and 117.
2. Added Casework Elevation tag 18.
3. Removed sinks in Student Science Casework.
4. Additional Casework in Computer Lab 101.
5. Window Type A in Science Labs 114 and 117 changed to Window Type K

Sheet A102
1. Changed the name of Exploratory 234 to Stem 234.
2. Additional Casework in Exploratory 234.
3. Added Casework Elevation tag 19.
Sheet A104
1. Reconfigured Casework Layout in Science Labs 414 and 417.
2. Added Casework Elevation tag 18.
3. Removed sinks in Student Science Casework.
4. Additional Casework in Computer Lab 401.
5. Window Type A in Science Labs 414 and 417 changed to Window Type K

Sheet A202
1. Elevation D updated to reflect the addition of Window Type K.

Sheet A301
1. Window Type K note added at Wall Section D.

Sheet A602
1. Window Type K added.

Sheet A705
1. Reconfigured Casework Layout in Science Labs 114, 117, 414 and 417.
2. Removed sinks in Student Science Casework in Science Labs 114, 117, 414 and 417.
3. Removed sinks in elevations 3 and 4.

Sheet A801
1. Elevation 14 Typical Science Casework revised.
2. Elevation 8 Stem 234 revised.
3. Elevation 9 Stem 234 revised.
4. Casework Elevations 18 and 19 added.
5. Elevation 15 Computer Lab 101 and 401 Casework revised.

PLUMBING:
See attached Plumbing Notes – I.C. Thomasson Associates, Inc.

ELECTRICAL:
See attached Electrical Notes – I.C. Thomasson Associates, Inc.

Reference:

A101 – Binkley Garcia Architecture


A102 – Binkley Garcia Architecture
A104 – Binkley Garcia Architecture
A705 – Binkley Garcia Architecture
A801 – Binkley Garcia Architecture
2018-02-19 RFP-002 – I.C. Thomasson Associates, Inc.
E201 – I.C. Thomasson Associates, Inc.
E202 – I.C. Thomasson Associates, Inc.
E204 – I.C. Thomasson Associates, Inc.
E501 – I.C. Thomasson Associates, Inc.
E502 – I.C. Thomasson Associates, Inc.

Oakland Middle School


Binkley Garcia Architecture, LLC
E504 – I.C. Thomasson Associates, Inc.
E800 – I.C. Thomasson Associates, Inc.
P101 – I.C. Thomasson Associates, Inc.
P201 – I.C. Thomasson Associates, Inc.
P204 – I.C. Thomasson Associates, Inc.
P301 – I.C. Thomasson Associates, Inc.
P304 – I.C. Thomasson Associates, Inc.
P401 – I.C. Thomasson Associates, Inc.
P402 – I.C. Thomasson Associates, Inc.

Requested by:

BINKLEY GARCIA ARCHITECTURE, LLC

Joseph Binkley

xc: Trey Lee, Rutherford County Board of Education

Oakland Middle School


Binkley Garcia Architecture, LLC
RFP-002

FEBRUARY 19, 2018

OAKLAND MIDDLE SCHOOL - ANNEX


MURFREESBORO, TENNESSEE

ICT PROJECT NO. 170267

I. C. THOMASSON ASSOCIATES, INC.


2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TENNESSEE 37204

This information forms a part of the contract documents and modifies the original documents dated
October 6, 2017.

Changes to Drawings

ELECTRICAL

Sheet E201

1. Revised layout to accommodate updated architectural casework changes.

Sheet E202

1. Revised layout to accommodate updated architectural casework changes for STEM


classroom.

Sheet E204

1. Revised layout to accommodate updated architectural casework changes.

Sheet E302

1. Revised layout to accommodate updated architectural casework changes for STEM


classroom.

Sheet E501

1. Revised layout to accommodate updated architectural casework.

Page | 1
Sheet E504

1. Revised layout to accommodate updated architectural casework.

Sheet E800

1. Revised panel schedule.

PLUMBING

Sheet P101

1. Revised underground piping to accommodate updated architectural floor plan for science
classrooms.

Sheet P201

1. Revised domestic water piping to accommodate updated architectural floor plan for science
classrooms.

Sheet P204

1. Revised domestic water piping to accommodate updated architectural floor plan for science
classrooms.

Sheet P301

1. Revised sanitary waste piping to accommodate updated architectural floor plan for science
classrooms.

Sheet P304

1. Revised sanitary vent piping to accommodate updated architectural floor plan for science
classrooms.

Sheet P401

1. Revised riser diagrams.

Sheet P402

1. Revised riser diagrams.

END OF RFP-002

Page | 2
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
ICT Project No. 170267

4" SANITARY SEWER DRAWING KEYNOTES:


I.E.~ -3'-9" B.F.F.
(5'-0" OUTSIDE OF BUILDING) 1. 3" WASTE FROM ABOVE. PROVIDE CLEANOUT AT BASE OF STACK.
REFER TO CIVIL FOR CONTINUATION.
2. 4" WASTE FROM ABOVE. PROVIDE CLEANOUT AT BASE OF STACK.
NEW 3" DOMESTIC WATER
& 6" FIRE MAINS BELOW 3. 3" ACID WASTE FROM ABOVE
NEW 1" NATURAL GAS MAIN BELOW GRADE. REFER TO CIVIL FOR
GRADE. REFER TO CIVIL FOR CONTINUATION. CONTINUATION. 4. 3" ACID VENT UP

MATCH LIN
MATCH LIN
E.C.O. ACID NEUTRALIZATION BASIN. REFER
TO DETAIL & SPECIFICATION FOR
ADDITIONAL INFORMATION.

AW
E.C.O.

SAN

AV
3" RFP-002

NG
6"

CW
4" 3" 2
4"

F
4
4" 3

SPRINK. 3"

AW

SAN
1" NATURAL GAS LINE UP SAN 119
TO METER. 3" 3" 3"
4"
MECH.
4" 116
4"

SAN
SAN 3"
4" 4" 4" 4"

AW
3"
SAN SAN SAN SAN
MALE
1 TOIL.
MECHANICAL SCIENCE LAB 3" SCIENCE LAB 4"
243
118 117 114
4"

SAN PREP 4"


UP
4" ROOM
115 4" HANDWASH
2 242
SAN
1/2"
4"

HW

CW
SAN 1/2"

AW

AW
4"

CW
REF.
1/2"

HW
N.I.C.
STAIR 2 3" 3" 1/2"
121
ELECTRICAL FACULTY
120 4" TOIL.
244

SAN
2"
4"

SAN

RUTHERFORD COUNTY BOARD OF EDUCATION


CORRIDOR
108

4" 4" 3" 3"


SAN SAN SAN SAN
3"

SAN
SAN

SAN
3" F.C.O.
MECH. STORAGE COMM. MECH. MECH.
102 103 104 107 112
2" 3" 2"
3"

COMPUTER LAB STOR. STOR.


1
101 106 111

MURFREESBORO, TN
STAIR 3
201

CLASSROOM CLASSROOM CLASSROOM CLASSROOM


105 109 110 113

UP

MATCH LINE PART A


MATCH LINE PART B
10-06-2017 BID DOCUMENTS
02-19-2018 RFP-002

WALL LEGEND - SEPARATION REQUIREMENTS

NON-RATED WALL PLUMBING -


PLUMBING -
CMU SMOKE PARTITION UNDERGROUND FLOOR UNDERGROUND
1-HOUR RATED CMU FIRE BARRIER PLAN - NEW WORK - FLOOR PLAN - NEW
2-HOUR RATED CMU FIRE BARRIER PART A WORK - PART A

NOTE: C
SEE STRUCTURAL DRAWINGS FOR BEARING/NON LOAD BEARING WALLS.
SEE BUILDING CODE AND LIFE SAFETY INFORMATION A000 FOR
STRUCTURAL FIRE RATING REQUIREMENTS.
A B
0 4' 8' 16' 24'
P101
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
ICT Project No. 170267

DRAWING KEYNOTES: SCIENCE LAB NOTES:

1. 2-1/2" CW, 1-1/2" HW & 3/4" HWR UP. 1. 1/2" HW & CW AND 2" ACID WASTE TO SINK.
RFP-002 2. 1/2" CW & 1/2" HW DOWN TO BELOW. 2. 1/2" HW & CW AND 2" ACID WASTE TO TEACHERS TABLE.

3. 1-1/4" CW DOWN & 3/4" HWR UP FROM 3. 1-1/4" TEPID WATER TO OWNER FURNISHED EMERGENCY SHOWER/EYEWASH.
BELOW. 1" HW & CW TO MIXING VALVE BRADLEY MODEL NO. S19-2200 W/FAIL SAFE COLD
WATER BYPASS.
4. TRAP PRIMER.
4. 1/2" TEPID WATER TO OWNER FURNISHED EMERGENCY SHOWER/EYEWASH.
5. BALANCING VALVE SET @ 1 GPM. 1/2" HW & CW TO MIXING VALVE BRADLEY MODEL NO. S19-2100 W/FAIL SAFE
COLD WATER BYPASS.
6. 3" DOMESTIC WATER MAIN UP FROM BELOW
SLAB.

RFP-002

1" NATURAL GAS UP FROM


BELOW GRADE TO NEW
NATURAL GAS METER
RFP-002

P-19
6

CW SPRINK. P-1
NG
119
3/4" P-14 P-12
3/4" P-13
MECH. P-2
P-13 3" 116

CW
3/4"
P-2
1 P-12

NG
WS-1 MALE P-5
TOIL.
SCIENCE LAB SCIENCE LAB
243
118 117 114 P-4
CW
4

HWR
CW
1/2" 1/2"
2 2
UP P-13 PREP P-6
ROOM
CP-1 115 HANDWASH
4 242
4
WH-2 WH-1
1/2" 1/2"

CW

CW
REF. 1 P-7
N.I.C.
STAIR 2 2 1/2" 3/4"
1/2" 1/2"

CW
121
ELECTRICAL 3 3 FACULTY

HWR
120 TOIL.
P-21 P-21
2" 2 2 P-1
3/4" 2"

HW
3/4"
2 1/2" 2 1/2"
3/4" 2" 3/4" 3/4" 1 1/2"
CW
HW
HWR

RUTHERFORD COUNTY BOARD OF EDUCATION


CORRIDOR 1 1/2"
3/4"
108

1/2" 1/2" 3/4" 1/2"


1/2" 1/2"
1/2" 1/2"

MECH. STORAGE COMM. MECH. MECH.


P-10
102 P-14 103 104 107 112
P-10 P-10 P-10
P-14 P-14

COMPUTER LAB STOR. STOR.


101 106 111

MURFREESBORO, TN
CW
STAIR 3
201
3/4"

CLASSROOM CLASSROOM CLASSROOM CLASSROOM


105 109 110 113

UP

P-19

MATCH LINE PART A


MATCH LINE PART B
10-06-2017 BID DOCUMENTS
02-19-2018 RFP-002

WALL LEGEND - SEPARATION REQUIREMENTS

NON-RATED WALL

CMU SMOKE PARTITION PLUMBING - FIRST PLUMBING - FIRST


FLOOR PLAN - NEW
1-HOUR RATED CMU FIRE BARRIER FLOOR PLAN - NEW WORK - PART A
2-HOUR RATED CMU FIRE BARRIER WORK - PART A
NOTE: C
SEE STRUCTURAL DRAWINGS FOR BEARING/NON LOAD BEARING WALLS.
SEE BUILDING CODE AND LIFE SAFETY INFORMATION A000 FOR
STRUCTURAL FIRE RATING REQUIREMENTS.
A B
0 4' 8' 16' 24'
P201
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
ICT Project No. 170267

DRAWING KEYNOTES: SCIENCE LAB NOTES:

1. 2-1/2" CW, 1-1/2" HW & 3/4" HWR UP FROM 1. 1/2" HW & CW AND 2" ACID WASTE TO SINK.
BELOW.
2. 1/2" HW & CW AND 2" ACID WASTE TO TEACHERS TABLE.
2. TRAP PRIMER.
3. 1-1/4" TEPID WATER TO OWNER FURNISHED EMERGENCY SHOWER/EYEWASH.
1" HW & CW TO MIXING VALVE BRADLEY MODEL NO. S19-2200 W/FAIL SAFE COLD
WATER BYPASS.

4. 1/2" TEPID WATER TO OWNER FURNISHED EMERGENCY SHOWER/EYEWASH.


1/2" HW & CW TO MIXING VALVE BRADLEY MODEL NO. S19-2100 W/FAIL SAFE
COLD WATER BYPASS.

5. 1/2" HW & CW AND 2" ACID WASTE TO STUDENT'S TABLE.

RFP-002

P-1

P-14 P-12
ELEC. MECH.
420 416
P-2
1
P-2
P-12
P-13
MALE P-5
TOIL.
DN
2 1/2" 526
P-4

CW
HWR
SCIENCE LAB PREP SCIENCE LAB
417 2 ROOM 2 414

HW
3/4" 2 415 P-6
HANDWASH
1 1/2" 525
4 4

CW
MECH. STOR.
419 418

HW
P-13
STAIR 2 REF. 1 P-7
421 N.I.C.

3 3 FACULTY
P-21 P-21 TOIL.
527 2"
P-1 3/4"
2 1/2" 2 1/2" 2"
CW CW
HW HW
HWR HWR
3/4" 1 1/2" 3/4" 1 1/2" 1 1/4"
CORRIDOR
409
1/2" 1/2"
1/2" 1/2" 1/2" 1/2" 1/2"
1/2"

RUTHERFORD COUNTY BOARD OF EDUCATION


MECH. STORAGE COMM. MECH. MECH. STAIR 3
402 403 404 407 412 501
P-10 P-10 P-10 P-10
P-14
P-14 P-14 DN

STOR. STOR.
406 411

MURFREESBORO, TN
COMPUTER LAB
401 CLASSROOM CLASSROOM CLASSROOM CLASSROOM S
405 408 410 413 5

MATCH LINE PART D


MATCH LINE PART E
10-06-2017 BID DOCUMENTS
02-19-2018 RFP-002

WALL LEGEND - SEPARATION REQUIREMENTS

NON-RATED WALL

CMU SMOKE PARTITION PLUMBING - SECOND PLUMBING -


SECOND FLOOR
1-HOUR RATED CMU FIRE BARRIER
FLOOR PLAN - NEW PLAN - NEW WORK -
2-HOUR RATED CMU FIRE BARRIER
WORK - PART D PART D

NOTE:
SEE STRUCTURAL DRAWINGS FOR BEARING/NON LOAD BEARING WALLS.
SEE BUILDING CODE AND LIFE SAFETY INFORMATION A000 FOR
STRUCTURAL FIRE RATING REQUIREMENTS.
D E
0 4' 8' 16' 24'
P204
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
ICT Project No. 170267

MATCH LIN
MATCH LIN
E.C.O.

RFP-002
E.C.O.
7 4
6 3"

SPRINK. AV
119
4"

V
3"

V
V
MECH. AW

SAN
3" 3" 116

AV
3" 3" 1
4" 3 3"

V
SAN 3" C.O. SAN

AW
MALE
8
TOIL.
MECHANICAL SCIENCE LAB SCIENCE LAB

V
3"

AW
2 243
118 117 114
5 3" 5
2"

V
4"

AV
SAN
UP PREP
ROOM
115 HANDWASH
4" 2"
4 242

AW
AW

SAN
4"
C.O.

V
3"
REF.
AV N.I.C. AV
STAIR 2

AV
121 3"
ELECTRICAL 3" FACULTY
TOIL. 4"
120
244 SAN
3" V
4"

RUTHERFORD COUNTY BOARD OF EDUCATION


CORRIDOR
108

C.O.
F.C.O.
3 2" 3" 3" 2"
MECH. 3" STORAGE COMM. MECH. MECH.
SAN SAN
102 103 104 107 112
3" V V V
2" 3" 3" 3" 3"

1 1
COMPUTER LAB STOR. 3 STOR.
101 106 111

MURFREESBORO, TN
STAIR 3
201

CLASSROOM CLASSROOM CLASSROOM CLASSROOM


105 109 110 113

UP

MATCH LINE PART A


MATCH LINE PART B
DRAWING KEYNOTES:

1. 3" VENT UP

2. 4" VENT UP

3. 3" WASTE DOWN. PROVIDE CLEANOUT AT BASE OF STACK.

4. 4" WASTE DOWN. PROVIDE CLEANOUT AT BASE OF STACK.

5. LOOP VENT (TYPICAL)

6. 3" ACID WASTE DOWN

7. 3" ACID VENT UP FROM BELOW

8. 3" ACID VENT UP

10-06-2017 BID DOCUMENTS


02-19-2018 RFP-002

WALL LEGEND - SEPARATION REQUIREMENTS

NON-RATED WALL

CMU SMOKE PARTITION


SANITARY - FIRST SANITARY - FIRST
FLOOR PLAN - NEW FLOOR PLAN - NEW
1-HOUR RATED CMU FIRE BARRIER WORK - PART A
2-HOUR RATED CMU FIRE BARRIER
WORK - PART A
NOTE: C
SEE STRUCTURAL DRAWINGS FOR BEARING/NON LOAD BEARING WALLS.
SEE BUILDING CODE AND LIFE SAFETY INFORMATION A000 FOR
STRUCTURAL FIRE RATING REQUIREMENTS.
A B
0 4' 8' 16' 24'
P301
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
ICT Project No. 170267

RFP-002

3"
ELEC. 4"
MECH.

V
420 416

V
4 2
3"
V
V V
MALE
4" 4" TOIL.

V
DN 3" 526
1 3 3

AV
SCIENCE LAB PREP SCIENCE LAB
417 ROOM 414

V
415
4" HANDWASH
525
MECH. STOR. 2"

AV
419 418
4"

V
3" 3"

V
STAIR 2 REF.
421 AV N.I.C. AV

3" FACULTY
3" TOIL.
527
V V
4" 3"
1

RUTHERFORD COUNTY BOARD OF EDUCATION


CORRIDOR
409

MECH. STORAGE COMM. MECH. MECH. STAIR 3


402 403 404 407 412 2" 501
2"
V V V DN
3" 3"
2

STOR. 2 STOR.
406 411

MURFREESBORO, TN
COMPUTER LAB
401 CLASSROOM CLASSROOM CLASSROOM CLASSROOM S
405 408 410 413 5

MATCH LINE PART D


MATCH LINE PART E
DRAWING KEYNOTES:

1. 4" VENT FROM BELOW UP TO 4" V.T.R.

2. 3" VENT FROM BELOW UP TO 4" V.T.R.

3. LOOP VENT (TYPICAL)

4. 3" ACID VENT FORM BELOW UP TO 4" ACID V.T.R.

10-06-2017 BID DOCUMENTS


02-19-2018 RFP-002

WALL LEGEND - SEPARATION REQUIREMENTS

NON-RATED WALL

CMU SMOKE PARTITION


SANITARY - SECOND SANITARY -
FLOOR PLAN - NEW SECOND FLOOR
1-HOUR RATED CMU FIRE BARRIER PLAN - NEW WORK -
2-HOUR RATED CMU FIRE BARRIER
WORK - PART D PART D

NOTE:
SEE STRUCTURAL DRAWINGS FOR BEARING/NON LOAD BEARING WALLS.
SEE BUILDING CODE AND LIFE SAFETY INFORMATION A000 FOR
STRUCTURAL FIRE RATING REQUIREMENTS.
D E
0 4' 8' 16' 24'
P304
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
ICT Project No. 170267

2-1/2" CW, 1-1/2" HW & 3/4"


HWR UP TO FLOOR ABOVE

1 1/2"
2 1/2"
3"
CP-1 CW
P-19
3"
WH-2
CW 3"
WS-1
WH-1

HW 2 1/2"
R

1/2" CW &
2"
HW UP

RFP-002
2 1/2"
1/2"

2" 1/2" 1/2" 1/2" CW &


CW HW UP
1/2" 1/2"
1/2" 3/4" 2"
1/2" 1/2"
1/2" 1/2" 3/4"
1/2" CW
1/2" 1/2"
P-10
1/2" 2" 1/2" HW
3/4"
1 1/2" R
P-10 1 1/2" HW 1 1/2"
3/4"
1/2" 2 1/2" 1/2"
1/2" 1 1/4"
3/4" 1 1/4"
1/2"
P-1
1 1/4"
2" 1/2" P-22 P-1
P-2
1 1/2" 1/2" P-2
3/4" P-1
1/2" P-5 1/2"
1/2" P-24
P-7
P-4 P-2
2"
P-10 P-7
1/2" P-2
1 1/4" 1"
1/2" 2" 1/2" P-6 P-2 P-1
1/2" P-2
3/4" CW P-1 P-7 1/2" P-5
P-10
3/4"
CW
2 1/2" P-19
1 1/2" 3/4"
P-22 3/4"
P-11 P-3 3/4"
1/2" 1/2"
1/2"
1/2" 1"
P-19 P-3 P-3
1/2" P-3
P-10 2"
P-1
P-7
P-10 1 1/2" P-4
1/2" P-5 P-24 1/2"
P-7 R 1/2"
1/2" 3/4" CW HW P-22
1 1/4" 2"
1/2" HW
P-10 3/4"
2 1/2" 3/4"
1/2" P-28
1 1/2"
P-24 1 1/4"
2" HW 3/4" P-1
1/2" CW 2" P-7
1 1/4" 1/2" 3/4" HW 1/2"
P-1
HW R 1/2" 2"
P-10 P-2
1 1/4" 3/4"
CW WR 3/4" 3/4" P-7
H P-11 P-4
1 1/4" P-5
P-7
1/2"
1/2" P-1
P-7
P-7 P-1
P-1
1/2"
1/2"
P-10

RUTHERFORD COUNTY BOARD OF EDUCATION


4" WASTE
FROM ABOVE 4" SANITARY SEWER
I.E.~ -3'-9" B.F.F.
4" VENT UP E.C.O. (5'-0" OUTSIDE OF BUILDING)
4" REFER TO CIVIL FOR CONTINUATION.
SAN

4" 2"
V

P-13 V N 3" ACID VENT UP


W.C.O. SA P-13
V

3" VENT UP 3" ACID WASTE


4" SA FROM ABOVE
3" WASTE P-13 2" N 3"
FROM ABOVE 3" WASTE
SA 4" SA FROM ABOVE
V

N
V

N
3"
2" 3" VENT UP
4"
P-14 W.C.O. 4"
AV
3"
AV
E.C.O.
RFP-002 WATER RISER - FIRST FLOOR
N ACID
SA 4" SAN
V
NEUTRALIZATION
SA

MURFREESBORO, TN
N 3" 4"
BASIN
2"
AW 3"
3" WASTE AV 2" 3"
A V
SA FROM ABOVE 3" V
N 4"
P-14
AV

4" 3" VENT UP W.C.O.


AW 3" 3"
2" SA AW
AV N
3"
AW 4"
P-10
1 1/2" V 3" P-10 4" V.T.R.
4" 4"
P-14 3" 4" WASTE
FROM ABOVE V

V
P-10
2" AW 3" 4" 2"
V

V
SA
SAN

N V P-1
N N
W.C.O. SA P-12 SA 4" W.C.O.
3" P-1 P-22
3" 4" VENT UP W.C.O.
V 4" 2" 4"
P-12 P-2 V P-7
P-2 P-2
P-1 4" SANITARY SEWER
2" P-5
P-12 I.E.~ -3'-9" B.F.F. N
V 4" P-4 (5'-0" OUTSIDE OF BUILDING) SA
P-10 1 1/2" P-2 2"
2" REFER TO CIVIL FOR CONTINUATION. 4" SANITARY SEWER P-22
SA P-2 4"

V
3" N F.C.O. 2" P-7 I.E.~ -3'-0" B.F.F.
P-14 SA P-6 P-2 SAN P-12 2"
P-1 N (5'-0" OUTSIDE OF BUILDING) P-1 2" P-7
4" P-2
3" REFER TO CIVIL FOR CONTINUATION. E.C.O.
4"
P-10 4" 4" SANITARY SEWER
E.C.O. I.E.~ -2'-3" B.F.F. P-5
P-22 S 2"
4" AN (5'-0" OUTSIDE OF BUILDING)
P-22 V 3" REFER TO CIVIL FOR CONTINUATION.
4" 4"
4"
P-11 N 4"
4" WASTE N SA E.C.O.
FROM ABOVE 4" SA V 4"
SA 2" 4" V V
P-3
P-10 N 3"
V P-3 P-12 2"
N P-3
W.C.O. 4" SA
V

P-3
2" P-3 P-1 V V
P-14 2" 3" P-7 P-28
P-3 4" V.T.R.
P-10 P-4 P-7
N
4" 2" SA P-12 P-5 P-22
3" P-7
P-22 2"
2" 2" P-7 V
4" P-7
V

SA 4" P-10 P-7


N SA
N
3" WASTE 4" VENT UP
FROM ABOVE P-7 P-28 2"
4" 2" SA
P-1 N
1 1/2" 4" VENT UP P-11 W.C.O.
3" WASTE V P-2
FROM ABOVE 2"
SA P-1 3"
V N 4"
V P-7 N P-2 10-06-2017 BID DOCUMENTS
2" 3" SA N
P-10 P-7 SA P-4
SAN

SA
N 4" P-5 02-19-2018 RFP-002
3"
P-1 SA
2" N P-1
2" P-1
4" P-7
P-7
V W.C.O.

1 1/2" 3"
P-10
N
SA 3"

2" 2" N
SA 3" PLUMBING - RISERS -
FIRST FLOOR PLAN
F.C.O.
3" WASTE RISER - FIRST FLOOR

P401
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
3/4" PHONE (615) 346-3400
R HW 1 1/2" FAX (615) 346-3550
HW W
C 1 1/2" 2 1/2" www.icthomasson.com
3/4"
ICT Project No. 170267
2 1/2"

2-1/2" CW, 1-1/2" HW


& 3/4" HWR UP FROM
FLOOR BELOW

C
HW W
R H
W

2 1/2"
1 1/2" RFP-002

3/4"
1/2"
1/2" CW &
1/2" HW DOWN
1/2"
1/2" 1/2"
1/2" 1/2"

P-10 1/2"
1/2" 2 1/2"
1/2"
1 1/2" 1/2"
3/4" 1/2"
P-10 1/2"
1/2"
HW C 1/2" CW &
W HW DOWN
HW
R
2" P-1 1 1/4"
1/2" 2"
1 1/4" P-2
2" 1/2" P-1
1/2" P-5
1/2"
1/2" P-4
1 1/4" P-2
P-10 3/4" P-7 3/4"
1/2" P-2
1/2"
1 1/4"
1/2" 2" P-2
1/2" P-6
1/2" P-2

P-10 P-1

P-22

P-11
1/2" 1/2"

1 1/4" 1/2"
3/4"
P-10
1/2" 1 1/4"
1/2" 1/2"
P-10
P-10
HW C
W
HW
R

1/2" 1"
1" 1/2"
1/2"
3/4"
1/2"

4" 1/2"
V V 4" P-10

4" V.T.R.
P-10
1/2"
V

4" 1/2" 1/2" 1/2"


2" P-13 1/2"
W
P-13 P-10 3/4" HW C
N 4" P-10
4" V.T.R. SA 4" 1/2"
V

1/2" 3/4"
1/2" P-10
4" VENT
FROM BELOW
4" WASTE
V

DOWN 4" ACID V.T.R.


2" P-10
V

P-14 3"
3" 4" V.T.R.

RUTHERFORD COUNTY BOARD OF EDUCATION


LOOP VENT RFP-002
2"
(TYPICAL)
3" 2"
V
AV

3" ACID
AV P-14 WASTE DOWN
3" VENT 3" WASTE AV 3"
FROM BELOW DOWN 2" 3" ACID VENT UP
V
3" FROM BELOW
AW
AV

2" 4" V.T.R. 2"


AV

AW 3"
AV 3"
2"
2"
AW
P-10 V 3" N
3" 3" SA AW 3"
V

2" P-14
3" VENT WATER RISER - SECOND FLOOR
P-10 AW 3" FROM BELOW
4"

MURFREESBORO, TN
V 3" 2" 3" WASTE DOWN V
3" WASTE 2"
SA 2"
DOWN N 3" 4"
4" V.T.R. P-1
V

3" VENT 2" V


FROM BELOW P-2
1 1/2" P-2 P-1
4" 3" P-5
4" V
3" P-4
V

SA P-10 1 1/2" P-2


N 4" WASTE
V

P-2
V

P-7 3" P-6 DOWN


P-1 2" P-2 SA 3"
2" V N
P-14 P-2
2"
P-10

3" 4" VENT SA 4" 3"


FROM BELOW N
P-11

4" WASTE 3" 1 1/2"


DOWN
V

SA 3"
N P-10
2" V
2"

P-14
P-10
SA
3" N
P-10 2"
3"
P-14 V 3"
V

2" N 2"
SA

2"
P-10 1 1/2"
4" V.T.R.
V

SA 3"
N
V 3" 4" V.T.R. 3" 2"
P-10 1 1/2" V
2" N
SA P-14 V
3" 2"
V SA 1 1/2"
N
P-10
P-10 1 1/2" 2"
4"
V
V

SA 3" P-10
N 3" SA 10-06-2017 BID DOCUMENTS
V
V

N
P-14
4" N
SA 2" 02-19-2018 RFP-002
P-10
P-14
2" 3" WASTE
DOWN
3" WASTE 4" VENT
DOWN FROM BELOW

4" VENT
FROM BELOW

PLUMBING - RISERS -
SECOND FLOOR
PLAN
WASTE RISER - SECOND FLOOR

P402
I.C. Thomasson Associates, Inc.
MEC CONSULTING ENGINEERS
112 2950 KRAFT DRIVE, SUITE 500
GFI NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
CKT #1 ICT Project No. 170267

STO
111

3
USB MH1 CH1
USB

MSB-B

2 USB ELECTRICAL
CKT #2 120
T-CL1 FACP
USB CL1 (HUNG)

1
USB

ENLARGED ELECTRICAL
CLASSROOM
110 ROOM 120
CKT #3 USB

CKT #4

USB

2 2

CL1-45

WP/GFI

ENLARGED TYPICAL 5 5 5 USB


USB
3 5 5 5
SPRINK. USB
CLASSROOM 119
J J J
3
USB
J J J
5
USB USB 6
6 6 6 MECH. 6 6 6
J J
5 6 116

5 6 6 5
2 2 MALE
J SCIENCE CLASSROOM CIRCUITS SCIENCE CLASSROOM CIRCUITS J TOIL.
MECHANICAL SCIENCE LAB SCIENCE LAB
243
118 CL1-73 CKT 117
#1 CL1-66 CKT #7 4 USB USB 4 CL1-83 CKT #1 CL1-77
114 CKT #7
CL1-70 CKT #2 CL1-67 CKT #8 J J CL1-80 CKT #2 CL1-74 CKT #8
1 1
CL1-62 CKT #3 CL1-32 CKT #9 CL1-81 CKT #3 CL1-34 CKT #9
UP PREP
5 6 CL1-71 CL1-65 ROOM CL1-78 CL1-75 5
CKT #4 CKT #10 CKT #4 CKT #10 6
J 115 J HANDWASH
CL1-68 CKT #5 CL1-64 CKT #11 CL1-58 CL1-79 CKT #5 CL1-72 CKT #11 242
5 5 5
CL1-69 CKT #6 CL1-94 CKT #12 CL1-76 CKT #6 CL1-97 CKT #12
USB
SEE ENLARGED TYPICAL SCIENCE CLASSROOM, SEE ENLARGED TYPICAL SCIENCE CLASSROOM,
3 E201 FOR ADDITIONAL INFORMATION. E201 FOR ADDITIONAL INFORMATION.
CL1-19
USB CKT #7
REF.
CH1 N.I.C.
STAIR 2 MH1 CL1-104
J J CKT #6 J CKT #5 6 6
121 CL1-35
6 6 6 MSB-B ELECTRICAL CL1-131 J J J 6 J 6 FACULTY
USB 3 3
120 TOIL.

FACP
6 USB GFI GFI 244
CL1 T-CL1 USB
J USB 5
5 5 5 USB

WP/GFI
4
E201
CKT #3 CORRIDOR
108

CL1-24

RUTHERFORD COUNTY BOARD OF EDUCATION


2 CONTINUE TO
CL1-40 CL1-61 SHEET E201
J CL1-41
CKT #9
SCIENCE LAB 6
5

114 CKT #2 MECH. STORAGE COMM. MECH.


107
MECH.
112
102 103 104
4 GFI GFI GFI GFI
J
CKT #10
1 USB USB CL1-100
COMPUTER LAB STOR. STOR.
1
101 2 106 111
CLASSROOM CIRCUITS 3 CLASSROOM CIRCUITS CLASSROOM CIRCUITS 3 CLASSROOM CIRCUITS
CL1-85 CL1-82
CKT #11 J CL1-43 CL1-101 CL1-98 CL1-99 CL1-96
CKT #1 CKT #1 CKT #1 CKT #1
6 USB USB USB USB
CL1-38 CKT #2 USB USB CL1-39 CKT #2 CL1-36 CKT #2 USB USB CL1-37 CKT #2
5
CKT #1 CL1-121 CKT #3 3 CL1-118 CKT #3 CL1-119 CKT #3 3 CL1-116 CKT #3 STAIR 3
2 2

MURFREESBORO, TN
2 USB USB 2 USB USB
CL1-112 CKT #4 CL1-113 CKT #4 CL1-110 CKT #4 CL1-111 CKT #4 201
CL1-84 CL1-6 USB USB
USB SEE ENLARGED TYPICAL SEE ENLARGED TYPICAL USB SEE ENLARGED TYPICAL SEE ENLARGED TYPICAL
CLASSROOM, E201 FOR CLASSROOM, E201 FOR CLASSROOM, E201 FOR CLASSROOM, E201 FOR
1 ADDITIONAL INFORMATION ADDITIONAL INFORMATION ADDITIONAL INFORMATION ADDITIONAL INFORMATION
USB USB 1 1 USB USB 1

CL1-87 CLASSROOM CLASSROOM CLASSROOM CLASSROOM


CL1-86
105 109 110 113
CKT #8 CKT #4 2 USB USB USB USB

CL1-18
CKT #12
USB USB USB USB UP
J 6 J 6 USB USB USB USB
3

3
USB
5 5 USB

ENLARGED TYPICAL

MATCH LINE PART A


MATCH LINE PART B
SCIENCE CLASSROOM

10-06-2017 BID DOCUMENTS


02-19-2018 RFP-002

GENERAL NOTES: NOTES: WALL LEGEND - SEPARATION REQUIREMENTS


A. ALL RECEPTACLES IN AREAS ACCESSIBLE TO STUDENTS SHALL BE TAMPER 1. RECEPTACLE FOR SHORT THROW, WALL MOUNTED, PROJECTOR. REFER TO
RESISTANT/SAFETY TYPE. ARCHITECTURAL ELEVATION BEFORE ROUGH-IN.

B. OUTLET BOXES IN WALLS SHALL NOT BE MOUNTED BACK TO BACK. WHERE


2. RECEPTACLE FOR SMART BOARD. REFER TO ARCHITECTURAL ELEVATION
BEFORE ROUGH-IN
NON-RATED WALL POWER - FIRST FLOOR
DRAWINGS SHOW OUTLETS ON BOTH SIDES OF THE SAME WALL, THE BOXES
POWER - FIRST
SHALL BE STAGGERED SIDEWAYS AND CONNECTED WITH SHORT NIPPLES
TO PREVENT PASSAGE OF SOUND. WHERE OUTLETS ARE MOUNTED ON BOTH
3. RECEPTACLE MOUNTED INSIDE CASEWORK. REFER TO ARCHITECTURAL
ELEVATION BEFORE ROUGH-IN.
CMU SMOKE PARTITION PLAN - NEW WORK - FLOOR PLAN - NEW
SIDES OF SAME FIRE WALL THEY ARE TO BE STAGGERED A MINIMUM OF 24
INCHES TO MAINTAIN THE RATINGS OF THE WALL. WHERE 24 INCHES IS NOT
POSSIBLE UTILIZE FIRE RATED PUTTY PAD SYSTEM TO MAINTAIN FIRE
4. PROVIDE CONNECTION TO DUPLEX RECEPTACLE MOUNTED IN SCIENCE
CASEWORK TO BE PROVIDED BY CASEWORK VENDOR. VERIFY EXACT
1-HOUR RATED CMU FIRE BARRIER PART A WORK - PART A
RATING. UTILIZE UL 1479 RATED M3 FIRE BARRIER PUTTY MODEL MPP+ OR REQUIREMENTS WITH VENDOR DRAWINGS.
EQUAL. REFER TO ARCHITECTURAL PLANS FOR WALL RATINGS. 2-HOUR RATED CMU FIRE BARRIER
5. GFI WALL OUTLET PROVIDED BY CONTRACTOR.

E201
6. PROVIDE CONNECTION TO TWO DUPLEX RECEPTACLES MOUNTED IN SCIENCE NOTE: C
CASEWORK TO BE PROVIDED BY CASEWORK VENDOR. VERIFY EXACT SEE STRUCTURAL DRAWINGS FOR BEARING/NON LOAD BEARING WALLS.
REQUIREMETS WITH VENDOR DRAWINGS. SEE BUILDING CODE AND LIFE SAFETY INFORMATION A000 FOR 0 4' 8' 16' 24'
STRUCTURAL FIRE RATING REQUIREMENTS.
A B
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
ICT Project No. 170267

MATCH LINE PART C MATCH LINE PART C


MATCH LINE PART B MATCH LINE PART B

WP/GFI CL1-10

GIRLS
LOCKER ROOM CL1-59 CL1-13
CONCESSIONS
226 225
CL1-54

GIRLS
TOILET/SHOWER
227 GFI
CL1-28

GFI

CL1-120,122,124
COMM. CL1-30
MATCH LINE PART A
MATCH LINE PART B

224
CL1-31 WP/GFI /WR 8

J J J
BOYS 5
TOILET/SHOWER 6 STORAGE
CL1-52
229 223
CL1-44
CL1-46 CL1-22
5
BOYS
MECH. LOCKER ROOM
245 228
CL1-9
1/2

5 4
GFI GFI
GFI FEMALE
5 USB USB USB TOILET
6
6 230 CORRIDOR CL1-48
229
USB USB CL1-60 USB
CLASSROOM CLASSROOM STEM CL1-134 USB
239 236 234 3
USB CL1-51
6 5 USB USB
MALE FEMALE CLASSROOM CIRCUITS CLASSROOM CIRCUITS USB
1 3
TOIL. TOIL.
243 241 1 CL1-88 CKT #1 CL1-91 CKT #1 1
4 4
1/2
CL1-27 USB USB CL1-26 USB
CKT #2 3 3 CKT #2
USB USB USB USB
J CL1-114 CKT #3 CL1-117 CKT #3 2 3
2 USB USB 2 MALE
5 CL1-107 CKT #4 CL1-106 CKT #4
2 TOILET
6
HANDWASH USB USB J
CL1-3 SEE ENLARGED TYPICAL SEE ENLARGED TYPICAL CL1-29 CL1-132 231 5
242 CLASSROOM, E201 FOR CLASSROOM, E201 FOR J CL1-11
GFI GFI
ADDITIONAL INFORMATION ADDITIONAL INFORMATION
USB
STOR.
238

CUST. CL1-90
CL1-136 CL1-109
240 CUST. TOIL.
233 232 7
CL1-89 GFI MECH. GFI USB GFI
6 FACULTY GFI
3 TOIL. 237 USB USB USB
USB USB GYMNASIUM
244 USB USB USB 221
5 1/2

3 3 3

CONTINUE TO
SHEET E202
CORRIDOR
235
CL1-115 CL1-103

CL1-20 CL1-21

RUTHERFORD COUNTY BOARD OF EDUCATION


COPIER
N.I.C.
ELEV. GFI USB USB
GFI____ CLINIC 1/2
210 TOIL.
CL1-33 CL1-17 CL1-55
211 CL1-93
CL1-16 GFI GFI STAIR 1
T.W.A.
COPIER

RECEP. 220
N.I.C.

SUMP 206 218


TV CL1-56
PUMP 4 4
WAITING CL1-125
CORR. CL1-127 CL1-14
205 RECORDS TOIL.
COMMONS 212 215
202 CL1-95 214 REF.
GFI GFI GFI
N.I.C.
CL1-57
UP
CL1-15 CL1-50
STAIR 3
201 MECH.
CORRIDOR
208 219 1/2
4
CL1-102

MURFREESBORO, TN
TV

CLASSROOM
TV
113
CL1-63 CL1-92 CL1-105 OFFICE CL1-53
CL1-108 SECRETARY CONFERENCE GUIDANCE OFFICE CL1-23
207 209
TV 213 216 217
SRO CONTROL
203 VESTIBULE 18" BELOW CL1-47 STORAGE
UP 204 CEILING 5
222 CL1-5
CL1-12
6
CL1-49
J J J 5

WP/GFI
WP/GFI/WR
WP/GFI/WR
GYM SOUND RACK
CL1-42
MATCH LINE PART A
MATCH LINE PART B

GENERAL NOTES: NOTES:


10-06-2017 BID DOCUMENTS
A. ALL RECEPTACLES IN AREAS ACCESSIBLE TO STUDENTS SHALL BE TAMPER 1. RECEPTACLE FOR SHORT THROW, WALL MOUNTED, PROJECTOR. REFER TO 02-19-2018 RFP-002
RESISTANT/SAFETY TYPE. ARCHITECTURAL ELEVATION BEFORE ROUGH-IN.

B. OUTLET BOXES IN WALLS SHALL NOT BE MOUNTED BACK TO BACK. WHERE 2. RECEPTACLE FOR SMART BOARD. REFER TO ARCHITECTURAL ELEVATION
DRAWINGS SHOW OUTLETS ON BOTH SIDES OF THE SAME WALL, THE BEFORE ROUGH-IN
BOXES SHALL BE STAGGERED SIDEWAYS AND CONNECTED WITH SHORT
NIPPLES TO PREVENT PASSAGE OF SOUND. WHERE OUTLETS ARE 3. RECEPTACLE MOUNTED INSIDE CASEWORK. REFER TO ARCHITECTURAL
WALL LEGEND - SEPARATION REQUIREMENTS
MOUNTED ON BOTH SIDES OF SAME FIRE WALL THEY ARE TO BE ELEVATION BEFORE ROUGH-IN.
STAGGERED A MINIMUM OF 24 INCHES TO MAINTAIN THE RATINGS OF THE
WALL. WHERE 24 INCHES IS NOT POSSIBLE UTILIZE FIRE RATED PUTTY 4. PROVIDE NEMA L14-20R RECEPTACLE FOR CONNECTION TO BASKETBALL
PAD SYSTEM TO MAINTAIN FIRE RATING. UTILIZE UL 1479 RATED M3 FIRE GOAL WINCH. COORDINATE EXACT REQUIREMENTS WITH BLEACHER VENDOR NON-RATED WALL
BARRIER PUTTY MODEL MPP+ OR EQUAL. REFER TO ARCHITECTURAL
PLANS FOR WALL RATINGS.
PRIOR TO ROUGH-IN. USE 3#12, 1#12G., 3/4"C.
POWER - FIRST FLOOR POWER - FIRST
5. BASKETBALL GOAL CONTROLLER. COORDINATE REQUIREMENTS WITH CMU SMOKE PARTITION
VENDOR PRIOR TO ROUGH-IN. PLAN - NEW WORK - FLOOR PLAN - NEW
6. JUNCTION BOX FOR CONNECTION OF SCOREBOARD AND JUNCTON BOX FOR
CONNECTION TO SCOREBOARD CONTROL WIRES. COORDINATE MOUNTING
1-HOUR RATED CMU FIRE BARRIER
PART B WORK - PART B
HEIGHTS AND LOCATIONS WITH ARCHITECT/VENDOR.
2-HOUR RATED CMU FIRE BARRIER
7. PROVIDE 3-GANG OUTLET BOX. BOX TO CONTAIN (1) 20-AMP DUPLEX
RECEPTACLE, (1) MICROPHONE OUTLET, AND (1) CONDUIT FOR

E202
SCOREBOARD CONTROLS. BOXES TO BE LOCATED IN FACE OF BLEACHERS. NOTE: C
COORDINATE. SEE STRUCTURAL DRAWINGS FOR BEARING/NON LOAD BEARING WALLS.
EXACT REQUIREMENTS WITH VENDOR. SEE BUILDING CODE AND LIFE SAFETY INFORMATION A000 FOR 0 4' 8' 16' 24'
8. STRUCTURAL FIRE RATING REQUIREMENTS.
20A/3P/NF/208V. DISCONNECT FOR CONNECTION OF MOTORIZED BLEACHERS. A B
COORDINATE EXACT REQUIREMENTS WITH BLEACHER VENDOR PRIOR TO
ROUGH-IN. USE 2#10, 1#12G.,3/4''C.
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
ICT Project No. 170267

T-CL2

ELEC.
420 CL2

MH2 CH2

2 ENLARGED ELECTRICAL ROOM 420


E204 E204
1/4" = 1'-0"

2
2

5 5 5 USB 5 5 5
T-CL2 USB 3
3 USB
USB
ELEC. J J J J J J
USB MECH. USB 6 5
420 CL2 6 6 6 416 6 6 6
J J
2 5 6
E204
MH2 CH2
SCIENCE CLASSROOM CIRCUITS SCIENCE CLASSROOM CIRCUITS
5 6 6 5
CL2-57 2 2 CL2-62 MALE
J
CKT #1 CL2-51 CKT #7 CKT #1 CL2-56 CKT #7
J TOIL.
DN
CL2-59 CKT #2 CL2-53 CKT #8 CL2-64 CKT #2 CL2-58 CKT #8 526
4 USB USB 4
CL2-50 CKT #3 CL2-35 CKT #9 CL2-66 CKT #3 CL2-31 CKT #9
SCIENCE LAB J PREP J SCIENCE LAB
CL2-52 417CKT #4 CL2-44 CKT #10 1 ROOM 1 CL2-61 CKT #4
414 CL2-60 CKT #10

6 CL2-54 CKT #5 CL2-46 CKT #11 415 CL2-63 CKT #5 CL2-55 CKT #11
5 6 5
J J HANDWASH
CL2-49 CKT #6 CL2-75 CKT #12 CL2-65 CKT #6 CL2-73 CKT #12
CL2-43 525
SEE ENLARGED TYPICAL SCIENCE CLASSROOM, SEE ENLARGED TYPICAL SCIENCE CLASSROOM,
MECH. STOR. E201 FOR ADDITIONAL INFORMATION. E201 FOR ADDITIONAL INFORMATION.
419 418

CL2-13
STAIR 2 REF.
421 N.I.C.

6 6 CL2-33
CL2-113 J J J 6 J 6 FACULTY
3 3 TOIL.
USB GFI GFI 527
USB 5 5 5
5

RUTHERFORD COUNTY BOARD OF EDUCATION


CORRIDOR
409
CL2-24
CL2-79
CL2-39 CL2-48
CL2-37

MECH. STORAGE COMM. MECH. MECH. STAIR 3


402 403 404 407 412 501
GFI GFI GFI GFI DN

USB USB
STOR. STOR.
1 2 CL2-81 406 411

MURFREESBORO, TN
CLASSROOM CIRCUITS 3 CLASSROOM CIRCUITS CLASSROOM CIRCUITS 3 CLASSROOM CIRCUITS
CL2-67 CL2-42 CL2-68 CL2-83 CKT #1 USB USB CL2-74 CKT #1 CL2-76 CKT #1 USB USB CL2-78 CKT #1
CL2-41 CKT #2 USB USB CL2-32 CKT #2 CL2-34 CKT #2 USB USB CL2-36 CKT #2
3 3
2 CL2-112 CKT #3 USB USB CL2-114 CKT #3 2 2 CL2-109 CKT #3 USB USB CL2-111 CKT #3 2
CL2-72 CL2-71 CL2-4 CKT #4 CL2-6 CKT #4 CL2-104 CKT #4 CL2-106 CKT #4
USB USB USB USB
SEE ENLARGED TYPICAL SEE ENLARGED TYPICAL SEE ENLARGED TYPICAL SEE ENLARGED TYPICAL
CLASSROOM, E201 FOR CLASSROOM, E201 FOR CLASSROOM, E201 FOR CLASSROOM, E201 FOR
1 ADDITIONAL INFORMATION USB USB ADDITIONAL INFORMATION 1 ADDITIONAL INFORMATION USB USB ADDITIONAL INFORMATION
1 1
CL2-70 COMPUTER LAB
CL2-69 CLASSROOM CLASSROOM CLASSROOM CLASSROOM S
401
405 408 410 413 5
2 USB USB USB USB

CL2-3
USB USB USB USB
USB USB USB USB

MATCH LINE PART D


MATCH LINE PART E
GENERAL NOTES: NOTES: 10-06-2017 BID DOCUMENTS

A. ALL RECEPTACLES IN AREAS ACCESSIBLE TO STUDENTS SHALL BE TAMPER 1. RECEPTACLE FOR SHORT THROW, WALL MOUNTED, PROJECTOR. REFER TO
02-19-2018 RFP-002
RESISTANT/SAFETY TYPE. ARCHITECTURAL ELEVATION BEFORE ROUGH-IN.

B. OUTLET BOXES IN WALLS SHALL NOT BE MOUNTED BACK TO BACK. WHERE 2. RECEPTACLE FOR SMART BOARD. REFER TO ARCHITECTURAL ELEVATION
DRAWINGS SHOW OUTLETS ON BOTH SIDES OF THE SAME WALL, THE BOXES
SHALL BE STAGGERED SIDEWAYS AND CONNECTED WITH SHORT NIPPLES TO
BEFORE ROUGH-IN WALL LEGEND - SEPARATION REQUIREMENTS
PREVENT PASSAGE OF SOUND. WHERE OUTLETS ARE MOUNTED ON BOTH 3. RECEPTACLE MOUNTED INSIDE CASEWORK. REFER TO ARCHITECTURAL
SIDES OF SAME FIRE WALL THEY ARE TO BE STAGGERED A MINIMUM OF 24 ELEVATION BEFORE ROUGH-IN.
INCHES TO MAINTAIN THE RATINGS OF THE WALL. WHERE 24 INCHES IS NOT
POSSIBLE UTILIZE FIRE RATED PUTTY PAD SYSTEM TO MAINTAIN FIRE RATING. 4. PROVIDE CONNECTION TO DUPLEX RECEPTACLE MOUNTED IN SCIENCE
UTILIZE UL 1479 RATED M3 FIRE BARRIER PUTTY MODEL MPP+ OR EQUAL. REFER CASEWORK TO BE PROVIDED BY CASEWORK VENDOR. VERIFY EXACT
NON-RATED WALL
TO ARCHITECTURAL PLANS FOR WALL RATINGS. REQUIREMENTS WITH VENDOR DRAWINGS.
CMU SMOKE PARTITION
POWER - SECOND POWER - SECOND
5. WALL OUTLET PROVIDED BY CONTRACTOR.
FLOOR PLAN - NEW FLOOR PLAN - NEW
WORK - PART D
6. PROVIDE CONNECTION TO TWO DUPLEX RECEPTACLES MOUNTED IN SCIENCE 1-HOUR RATED CMU FIRE BARRIER
CASEWORK TO BE PROVIDED BY CASEWORK VENDOR. VERIFY EXACT
REQUIREMETS WITH VENDOR DRAWINGS.
2-HOUR RATED CMU FIRE BARRIER
WORK - PART D

E204
NOTE:
SEE STRUCTURAL DRAWINGS FOR BEARING/NON LOAD BEARING WALLS.
SEE BUILDING CODE AND LIFE SAFETY INFORMATION A000 FOR 0 4' 8' 16' 24'
STRUCTURAL FIRE RATING REQUIREMENTS.
D E
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
ICT Project No. 170267

55'-7%%130"

MATCH LINE PART B


MATCH LINE PART A
49'-7%%130"

1"
SPRINK.
119

MECH.
3 3
116

S S

P P
MALE
1 1 TOIL.
MECHANICAL SCIENCE LAB 1" SCIENCE LAB
243
118 117 114
2 2

UP PREP
ROOM
115 HANDWASH
242
6 6
S
TS TS
1" REF. 1" 1"
N.I.C.
STAIR 2
121
ELECTRICAL C C FACULTY
120 TOIL.
1" 2" 244

3" 3" 3" 3"

RUTHERFORD COUNTY BOARD OF EDUCATION


CORRIDOR
(3)4"C TO 108
FLOOR
S ABOVE S S S S S

(3)4" CABLE TRAY


(TYP.)

C C C C
MECH. STORAGE COMM. MECH. MECH.
2" 107 1" 2" 2" 112 1" 2" 1"
102 1" 103 1" S 4 104

C
P
3"
3"
COMPUTER
1 LAB
2 3 STOR. STOR.
101 106 S 111 S

MURFREESBORO, TN
3/4" 3/4" 3/4" 3/4"

5 5 P P P P
1 1 1 1 STAIR 3
TS TS TS TS 201
S
TS
2 2 2 2
5 5

CLASSROOM CLASSROOM CLASSROOM CLASSROOM


105 109 110 113
5 5

2
3 3 3 3
UP

MATCH LINE PART A


MATCH LINE PART B
#6
10-06-2017 BID DOCUMENTS
TO NOTES: GENERAL NOTES: 02-19-2018 RFP-002
NEAREST
ELECTRICAL
PANEL 1. PROVIDE ROUGH-IN AND 1-1/4'' CONDUIT STUBBED UP ABOVE CEILING FOR A. PROVIDE CABLE TRAY IN COMMUNICATIONS CLOSETS. COORDINATE EXACT
GROUND WALL MOUNTED SHORT THROW PROJECTOR. COORDINATE EXACT LOCATION REQUIREMENTS WITH OWNER/LOW VOLTAGE VENDOR.
BUS REQUIREMENTS WITH AUDIO/VISUAL VENDOR AND OWNER PRIOR TO ROUGH-
IN. B. CABLE TRAY IN CORRIDORS TO BE LOCATED ON THE SAME SIDE AS
WALL LEGEND - SEPARATION REQUIREMENTS
COMMUNICATIONS CLOSET. COORDINATE WITH OTHER TRADES. WHERE CABLE
2. PROVIDE 1-1/4" CONDUIT STUBBED UP ABOVE CEILING FOR A/V ROUGH-IN AS TRAY MUST BE LOCATED ELSEWHERE, CABLE TRAY MUST BE PROVIDED ACROSS
REQUIRED. CORRIDOR.
GROUNDING BAR
NON-RATED WALL
TO BUILDING STEEL
TO BE PROVIDED
BY ELECTRICAL
CONTRACTOR
3. PROVIDE (2) 1-1/4" CONDUITS STUBBED UP ABOVE CEILING FOR RAPID RUN,
ETC. TYPICAL. PROVIDE (2) SINGLE GANG BOXES.
C. PROVIDE GROUNDING BAR IN ALL COMMUNICATIONS CLOSETS FOR GROUNDING
OF ALL I.T. AND CABLE TRAY EQUIPMENT. GROUND BAR SHALL BE CONNECTED TO
TELECOMMUNICATIONS TELECOMMUNICATIONS
GROUND BUS OF MSB-B WITH A #6G. CMU SMOKE PARTITION
4. COMPLETELY COVER WALL WITH 2/4" PLYWOOD BACKBOARD PAINTED FIRE
RETARDANT BLACK. D. COORDINATE WITH OWNER PROVIDE TECHNOLOGY FOR CABLE MANAGEMENT IN
- FIRST FLOOR PLAN - - FIRST FLOOR PLAN
5. PROVIDE (1) 1-1/4" CONDUIT STUBBED UP ABOVE CEILING AND PROVIDE 2" X 4''
MDF AND ALL IT CLOSETS. 1-HOUR RATED CMU FIRE BARRIER
NEW WORK - PART A - NEW WORK -
SINGLE GANG BOX. E. OUTLET BOXES IN WALLS SHALL NOT BE MOUNTED BACK TO BACK. WHERE
DRAWINGS SHOW OUTLETS ON BOTH SIDES OF THE SAME WALL, THE BOXES 2-HOUR RATED CMU FIRE BARRIER PART A
6. PROVIDE CONNECTION TO DATA RECEPTACLES MOUNTED IN SCIENCE SHALL BE STAGGERED SIDEWAYS AND CONNECTED WITH SHORT NIPPLES TO
TYPICAL COMMUNICATIONS CLOSET CASEWORK TO BE PROVIDED BY CASEWORK VENDOR. VERIFY EXACT PREVENT PASSAGE OF SOUND. WHERE OUTLETS ARE MOUNTED ON BOTH SIDES

E501
REQUIREMENTS WITH VENDOR DRAWINGS. OF SAME FIRE WALL THEY ARE TO BE STAGGERED A MINIMUM OF 24 INCHES TO NOTE: C
MAINTAIN THE RATINGS OF THE WALL. WHERE 24 INCHES IS NOT POSSIBLE SEE STRUCTURAL DRAWINGS FOR BEARING/NON LOAD BEARING WALLS.
GROUNDING DETAIL UTILIZE FIRE RATED PUTTY PAD SYSTEM TO MAINTAIN FIRE RATING. UTILIZE UL
1479 RATED M3 FIRE BARRIER PUTTY MODEL MPP+ OR EQUAL. REFER TO
SEE BUILDING CODE AND LIFE SAFETY INFORMATION A000 FOR 0 4' 8' 16' 24'
STRUCTURAL FIRE RATING REQUIREMENTS.
ARCHITECTURAL PLANS FOR WALL RATINGS. A B
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
ICT Project No. 170267

MATCH LINE PART C MATCH LINE PART C


MATCH LINE PART B MATCH LINE PART B

WP S

GIRLS
LOCKER ROOM S CONCESSIONS
226 225

S
GIRLS
TOILET/SHOWER
227
1"
3/4"

(2)4"C STUBBED OUT FROM


S EXISTING BUILDING
(3)4"
COMM.
MATCH LINE PART A
MATCH LINE PART B

224 GYM SOUND RACK


4 WP
S

WG
S
1" J
BOYS WG
TOILET/SHOWER STORAGE
4"
229 5 8 223
S

BOYS J

MECH. LOCKER ROOM S 1"


245 228
S

1"
FEMALE
3 3 TOILET
3 CORRIDOR
230
229
S S
CLASSROOM CLASSROOM TS STEM
239 236 234

MALE FEMALE
TOIL. TOIL.
243 241
2
TS TS
2 2
1
P 2 MALE
1 1
TOILET S
HANDWASH P P
231
242
9
(2)4"
STOR.S
238 S
S CUST. 3/4" 3/4"
240 CUST. TOIL.
2" 233 232
FACULTY 1" MECH. WG
C

S
TOIL. 2" 237 2" 1"
GYMNASIUM 6
244 7 WG
221

S
C C
J
6
J
1" 1"
J 1"

CORRIDOR J
235

RUTHERFORD COUNTY BOARD OF EDUCATION


S S S S S S 1"
5

(3)4"
ALL DEVICES ON
GYMNASIUM WALLS
ARE TO BE PROVIDED
(3)4" WITH WIRE GUARDS
COPIER
N.I.C.
ELEV. 1"
____ 1" CLINIC
210 1" TOIL.
211
S STAIR 1
T.W.A.
COPIER

TV RECEP. 220
N.I.C.

206 2" 218


S
S
WAITING
205 RECORDS CORR. 1"
S COMMONS S TOIL. 215
1" 1" 212 214 1" REF.
202 N.I.C.

UP

MURFREESBORO, TN
2"
STAIR 3
201 S MECH.
CORRIDOR
208 2" S 1" (3)4" 219
1"

TV V
TV 1"
ROOM
1"

S 1" SECRETARY CONFERENCE OFFICE GUIDANCE OFFICE


TV
207 209 213 216 217 2"
SRO CONTROL S
S VESTIBULE
203 STORAGE
204 S
UP 222 GYM SOUND RACK
5
S
WG WG
S J

J S
S
WP
WP
4
MATCH LINE PART A
MATCH LINE PART B

#6
10-06-2017 BID DOCUMENTS
NOTES: GENERAL NOTES: 02-19-2018 RFP-002
TO
NEAREST
1. PROVIDE ROUGH-IN AND 1-1/4'' CONDUIT STUBBED UP ABOVE CEILING FOR WALL A. PROVIDE CABLE TRAY IN COMMUNICATIONS CLOSETS. COORDINATE EXACT
ELECTRICAL
MOUNTED SHORT THROW PROJECTOR. COORDINATE EXACT LOCATION REQUIREMENTS WITH OWNER/LOW VOLTAGE VENDOR.
PANEL
GROUND
REQUIREMENTS WITH AUDIO/VISUAL VENDOR AND OWNER PRIOR TO ROUGH-IN. WALL LEGEND - SEPARATION REQUIREMENTS
B. CABLE TRAY IN CORRIDORS TO BE LOCATED ON THE SAME SIDE AS
BUS
2. PROVIDE 1-1/4" CONDUIT STUBBED UP ABOVE CEILING FOR A/V ROUGH-IN AS COMMUNICATIONS CLOSET. COORDINATE WITH OTHER TRADES. WHERE CABLE
REQUIRED. TRAY MUST BE LOCATED ELSEWHERE, CABLE TRAY MUST BE PROVIDED
ACROSS CORRIDOR.
3. PROVIDE (2) 1-1/4" CONDUITS STUBBED UP ABOVE CEILING FOR RAPID RUN, ETC. NON-RATED WALL
GROUNDING BAR
TO BE PROVIDED
TYPICAL. PROVIDE (2) SINGLE GANG BOXES. C. PROVIDE GROUNDING BAR IN ALL COMMUNICATIONS CLOSETS FOR GROUNDING
OF ALL I.T. AND CABLE TRAY EQUIPMENT. GROUND BAR SHALL BE CONNECTED
TELECOMMUNICATIONS TELECOMMUNICATIONS
TO BUILDING STEEL BY ELECTRICAL
CONTRACTOR
4. COMPLETELY COVER WALL WITH 2/4" PLYWOOD BACKBOARD PAINTED FIRE
RETARDANT BLACK.
D.
TO GROUND BUS OF MSB WITH A #6G.

COORDINATE WITH OWNER PROVIDE TECHNOLOGY FOR CABLE MANAGEMENT IN


CMU SMOKE PARTITION
- FIRST FLOOR PLAN - - FIRST FLOOR PLAN
5. CONNECTION AS REQUIRED FOR MOBILE MIXING UNIT. PROVIDE 3/4" CONDUIT TO
GYM SOUND RACK.
MDF AND ALL IT CLOSETS. 1-HOUR RATED CMU FIRE BARRIER
NEW WORK - PART B - NEW WORK -
6. PROVIDE 3/4" CONDUIT TO GYM SOUND RACK.
E. OUTLET BOXES IN WALLS SHALL NOT BE MOUNTED BACK TO BACK. WHERE
DRAWINGS SHOW OUTLETS ON BOTH SIDES OF THE SAME WALL, THE BOXES 2-HOUR RATED CMU FIRE BARRIER PART B
SHALL BE STAGGERED SIDEWAYS AND CONNECTED WITH SHORT NIPPLES TO
7. GYM SOUND SYSTEM SPEAKER CLUSTER. REFER TO SPECIFICATIONS. PREVENT PASSAGE OF SOUND. WHERE OUTLETS ARE MOUNTED ON BOTH SIDES

E502
C
TYPICAL COMMUNICATIONS CLOSET 8. JUNCTION BOX FOR CONNECTION TO WIRELESS MICROPHONE RECIEVER. MOUNT
OF SAME FIRE WALL THEY ARE TO BE STAGGERED A MINIMUM OF 24 INCHES TO
MAINTAIN THE RATINGS OF THE WALL. WHERE 24 INCHES IS NOT POSSIBLE
NOTE:
SEE STRUCTURAL DRAWINGS FOR BEARING/NON LOAD BEARING WALLS.
AT 12' A.F.F. UTILIZE FIRE RATED PUTTY PAD SYSTEM TO MAINTAIN FIRE RATING. UTILIZE UL SEE BUILDING CODE AND LIFE SAFETY INFORMATION A000 FOR 0 4' 8' 16' 24'
GROUNDING DETAIL 9. PROVIDE 100' OF CONDUIT FOR LOW VOLTAGE ACCESS TO RAFTERS. LOCATIONS
1479 RATED M3 FIRE BARRIER PUTTY MODEL MPP+ OR EQUAL. REFER TO
ARCHITECTURAL PLANS FOR WALL RATINGS.
STRUCTURAL FIRE RATING REQUIREMENTS.
A B
TO BE COORDINATED WITH CONTRACTOR/OWNER.
I.C. Thomasson Associates, Inc.
CONSULTING ENGINEERS
2950 KRAFT DRIVE, SUITE 500
NASHVILLE, TN. 37204
PHONE (615) 346-3400
FAX (615) 346-3550
www.icthomasson.com
ICT Project No. 170267

MATCH LINE PART E


MATCH LINE PART D
2

1" ELEC. MECH.


420 416
3 3

P P
MALE
1 1 TOIL.
DN
1" 526
S TS 2 2
SCIENCE LAB PREP SCIENCE LAB
417 ROOM 414
415
S HANDWASH
525
MECH. STOR. 6 6
419 418 S
1"
STAIR 2 REF.
1" 1" TS
421 N.I.C.

C C FACULTY
TOIL.
527

3" 3" 3" 3"

1" 3" 1"

RUTHERFORD COUNTY BOARD OF EDUCATION


S S S S CORRIDOR
S S
(3)4"C TO
409
FLOOR
BELOW

(3)4"

C C C C
MECH. STORAGE COMM. MECH. MECH. STAIR 3
1" 1" 2" 407 2" 2" 412 2" 501
402 403 404
S 4 1" 1" 1"
DN
C
P
3/4" 3/4"
3" 3"
3/4" 3/4"
3 2 1 STOR. STOR.
406 S 411 S

MURFREESBORO, TN
5 5 P P P P
1 1 1 1
TS TS TS TS
TS S
2 2 2 2
5 5

COMPUTER LAB
401 CLASSROOM CLASSROOM CLASSROOM CLASSROOM S
405 408 410 413 5
5 5

2
3 3 3 3

MATCH LINE PART D


MATCH LINE PART E
#6
10-06-2017 BID DOCUMENTS
TO NOTES: GENERAL NOTES: 02-19-2018 RFP-002
NEAREST
ELECTRICAL
1. PROVIDE ROUGH-IN AND 1-1/4'' CONDUIT STUBBED UP ABOVE CEILING FOR A. PROVIDE CABLE TRAY IN COMMUNICATIONS CLOSETS. COORDINATE EXACT
PANEL
WALL MOUNTED SHORT THROW PROJECTOR. COORDINATE EXACT LOCATION REQUIREMENTS WITH OWNER/LOW VOLTAGE VENDOR.
GROUND
BUS
REQUIREMENTS WITH AUDIO/VISUAL VENDOR AND OWNER PRIOR TO ROUGH-
IN. B. CABLE TRAY IN CORRIDORS TO BE LOCATED ON THE SAME SIDE AS
WALL LEGEND - SEPARATION REQUIREMENTS
COMMUNICATIONS CLOSET. COORDINATE WITH OTHER TRADES. WHERE CABLE
2. PROVIDE 1-1/4" CONDUIT STUBBED UP ABOVE CEILING FOR A/V ROUGH-IN AS TRAY MUST BE LOCATED ELSEWHERE, CABLE TRAY MUST BE PROVIDED ACROSS
REQUIRED. CORRIDOR.
GROUNDING BAR
TO BE PROVIDED 3. PROVIDE (2) 1-1/4" CONDUITS STUBBED UP ABOVE CEILING FOR RAPID RUN, C. PROVIDE GROUNDING BAR IN ALL COMMUNICATIONS CLOSETS FOR GROUNDING
NON-RATED WALL
TO BUILDING STEEL BY ELECTRICAL
CONTRACTOR
ETC. TYPICAL. PROVIDE (2) SINGLE GANG BOXES. OF ALL I.T. AND CABLE TRAY EQUIPMENT. GROUND BAR SHALL BE CONNECTED TO
GROUND BUS OF MSB-B WITH A #6G. CMU SMOKE PARTITION
TELECOMMUNICATIONS TELECOMMUNICATIONS
4. COMPLETELY COVER WALL WITH 2/4" PLYWOOD BACKBOARD PAINTED FIRE
RETARDANT BLACK. D. COORDINATE WITH OWNER PROVIDE TECHNOLOGY FOR CABLE MANAGEMENT IN - SECOND FLOOR PLAN - - SECOND FLOOR
MDF AND ALL IT CLOSETS. 1-HOUR RATED CMU FIRE BARRIER
NEW WORK - PART D PLAN - NEW WORK
- PART D
5. PROVIDE (1) 1-1/4" CONDUIT STUBBED UP ABOVE CEILING AND PROVIDE 2" X E. OUTLET BOXES IN WALLS SHALL NOT BE MOUNTED BACK TO BACK. WHERE
4'' SINGLE GANG BOX. DRAWINGS SHOW OUTLETS ON BOTH SIDES OF THE SAME WALL, THE BOXES 2-HOUR RATED CMU FIRE BARRIER
SHALL BE STAGGERED SIDEWAYS AND CONNECTED WITH SHORT NIPPLES TO
TYPICAL COMMUNICATIONS CLOSET 6. PROVIDE CONNECTION TO DATA RECEPTACLES MOUNTED IN SCIENCE PREVENT PASSAGE OF SOUND. WHERE OUTLETS ARE MOUNTED ON BOTH SIDES

E504
CASEWORK TO BE PROVIDED BY CASEWORK VENDOR. VERIFY EXACT OF SAME FIRE WALL THEY ARE TO BE STAGGERED A MINIMUM OF 24 INCHES TO NOTE:
REQUIREMENTS WITH VENDOR DRAWINGS. MAINTAIN THE RATINGS OF THE WALL. WHERE 24 INCHES IS NOT POSSIBLE SEE STRUCTURAL DRAWINGS FOR BEARING/NON LOAD BEARING WALLS.
GROUNDING DETAIL UTILIZE FIRE RATED PUTTY PAD SYSTEM TO MAINTAIN FIRE RATING. UTILIZE UL
1479 RATED M3 FIRE BARRIER PUTTY MODEL MPP+ OR EQUAL. REFER TO
SEE BUILDING CODE AND LIFE SAFETY INFORMATION A000 FOR 0 4' 8' 16' 24'
STRUCTURAL FIRE RATING REQUIREMENTS.
ARCHITECTURAL PLANS FOR WALL RATINGS. D E
Branch Panel: CL1
Location: ELEC. RM. 120 Volts: 120/208 Wye A.I.C. Rating: 10,000
Switchboard: MSB-B Supply From: T-CL1 Phases: 3 Mains Type: M.C.B.
Location: ELEC. RM. 120 Volts: 480/277 Wye A.I.C. Rating: 65,000 Mounting: Surface Wires: 4 Mains Rating: 250 A
Supply From: EXISTING MSB Phases: 3 Mains Type: M.C.B. Enclosure: Type 1 MCB Rating: 250 A
Mounting: Surface Wires: 4 Mains Rating: 1200 A
Enclosure: Type 1 MCB Rating: 1200 A Notes:
I.C. Thomasson Associates, Inc.
Notes:
PROVIDE M.C.B. WITH GFI PROTECTION CONSULTING ENGINEERS
PROVIDE WITH TVSS SIZED PER MANUFACTURER'S SUGGESTION
Demand A B C Demand
2950 KRAFT DRIVE, SUITE 500
CKT Circuit Description Code TRIP P P TRIP Code Circuit Description CKT NASHVILLE, TN. 37204
Load 1 FIRST FLOOR DOORS Equip... 20 A 1 100... 200... 1 20 A Equip... EMS CONTROL PANEL - ROOM 118 2 PHONE (615) 346-3400
CKT Circuit Description # of Poles Trip Rating Remarks 3 HANDWASH ROOM 242 Equip... 20 A 1 300... 4 FAX (615) 346-3550
1 MH1 3 600 A 274421 VA 5 GYM SOUND RACK Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 101 6 www.icthomasson.com
2 CH1 3 250 A 115424 VA 7 EMS CONTROL PANEL - ROOM 219 Equip... 20 A 1 200... 1080... 1 20 A Recept... REC-CORRIDOR 208,215 8 ICT Project No. 170267
3 MH2 3 600 A 252311 VA 9 REC-GYMNASIUM 221 Recept... 20 A 1 540... 180... 1 20 A Recept... REC-ROOM 225 10
4 CH2 3 250 A 106207 VA 11 SCOREBOARD CONTROLS Recept... 20 A 1 180... 180... 1 20 A Recept... REC-ROOM 222 12
5
6
ELEVATOR (SHUNT TRIP)
Spare
3
3
70 A
400 A
22000 VA
0 VA
13 REC-ROOM 225 Recept... 20 A 1 180... 180... 1 20 A Recept... REC-ROOM 218 REFRIGERATOR 14 Branch Panel: CH2
15 REC-ROOM 219 Recept... 20 A 1 180... 180... 1 20 A Recept... REC-ROOM 206 COPIER 16
7 Spare 3 200 A 0 VA
Location: ELEC. RM. 420 Volts: 480/277 Wye A.I.C. Rating: 42,000
17 REC-ROOM 218 COPIER Recept... 20 A 1 180... 360... 1 20 A Recept... REC-ROOM 101 18
8 Spare 3 200 A 0 VA
Supply From: MSB-B Phases: 3 Mains Type: M.L.O.
19 REC-ROOM 115 REFRIGERATOR Recept... 20 A 1 180... 180... 1 20 A Recept... REC-ELEVATOR 20
9 Space -- -- 0 VA --
Mounting: Surface Wires: 4 Mains Rating: 250 A
21 REC-ELEVATOR SUMP PUMP Recept... 20 A 1 1680... 180... 1 20 A Equip... BASKETBALL SCOREBOARD 22
Enclosure: Type 1
10 TVSS 3 60 A 0 VA SIZED PER MANUFACTURER 23 BASKETBALL SCOREBOARD Equip... 20 A 1 180... 360... 1 20 A Recept... REC-ROOMS 102,103 24
772029 VA 25 BASKETBALL GOAL CONTROLLER Equip... 20 A 1 180... 360... 1 20 A Recept... REC-ROOM 236 26
Notes:
929 A 27 REC-ROOM 239 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 225 (POWER DOOR) 28
Legend: 29 REC-ROOM 234 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 224 30
31 REC-ROOM 224 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 117 32
33 REC-ROOM 210 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 114 34
Demand A B C Demand
35 REC-ROOM 115 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 110 36
CKT Circuit Description Code TRIP P P TRIP Code Circuit Description CKT
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals 37 REC-ROOM 113 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 105 38
1 T-CL2 Recept... 20 A 3 28960 880 1 20 A Lighting LTS - ROOMS 401-404 2
Existing Load 0 VA 0.00% 0 VA 39 REC-ROOM 109 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 104 40
3 -- -- -- -- 28358 2122 1 20 A Lighting LTS - ROOMS 405-408, 410-413 4
Equipment 78186 VA 80.00% 62549 VA Total Conn. Load: 772029 VA 41 REC-ROOM 104 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-OUTDOOR RECEPTACLES 42
5 -- -- -- -- 28018 2738 1 20 A Lighting LTS - ROOMS 414-420 6
Kitchen 0 VA 0.00% 0 VA Total Est. Demand: 599509 VA 43 REC-ROOM 101 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-GYMNASIUM 223 44
7 LTS - ROOMS 501-507, 509-512 Lighting 20 A 1 2458 3497 1 20 A Lighting LTS - ROOMS 514-527 8
Lighting 51676 VA 100.00% 51676 VA Total Conn. Current: 929 A 45 REC-OUTDOOR RECEPTACLE Recept... 20 A 1 360... 360... 1 20 A Recept... REC-GYMNASIUM 221 46
9 LTS - GYMNASIUM Lighting 20 A 1 3304 3304 1 20 A Lighting LTS - GYMNASIUM 10
Motor 425126 VA 80.00% 340101 VA Total Est. Demand Current: 721 A 47 REC-GYMNASIUM 221 (SCOREBOARD) Recept... 20 A 1 360... 360... 1 20 A Equip... BASKETBALL GOAL CONTROLLER 48
11 LTS-CORRIDOR 409, 508 Lighting 20 A 1 3328 112 1 20 A Lighting LTS - ELEVATOR 12
Receptacle 153420 VA 53.26% 81710 VA 49 REC-GYM OUTDOOR RECEPTACLES Recept... 20 A 1 360... 360... 1 20 A Equip... BASKETBALL GOAL CONTROLLER 50
13 Spare -- 20 A 1 0 0 1 20 A -- Spare 14
Heating 41000 VA 100.00% 41000 VA 51 BASKETBALL GOAL CONTROLLER Equip... 20 A 1 360... 360... 1 20 A Equip... BASKETBALL GOAL CONTROLLER 52
15 Spare -- 20 A 1 0 0 1 20 A -- Spare 16
Elevator 22000 VA 100.00% 22000 VA 53 BASKETBALL GOAL CONTROLLER Equip... 20 A 1 360... 540... 1 20 A Recept... REC-ROOM 225 54
17 Spare -- 20 A 1 0 0 1 20 A -- Spare 18
55 BASKETBALL GOAL CONTROLLER Equip... 20 A 1 360... 540... 1 20 A Recept... REC-ROOM 202 56
19 Spare -- 20 A 1 0 0 1 20 A -- Spare 20
Notes: 57 REC-ROOM 210 Recept... 20 A 1 540... 720... 1 20 A Recept... REC-ROOMS 115,116 58
21 Spare -- 20 A 1 0 0 1 20 A -- Spare 22
59 REC-ROOMS 226,228,233,245 Recept... 20 A 1 720... 900... 1 20 A Recept... REC-ROOM 234 60
23 Spare -- 20 A 1 0 0 1 20 A -- Spare 24
61 REC-ROOMS 106,107,111,112 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 117 62
25 Spare -- 20 A 1 0 0 1 20 A -- Spare 26
63 REC-ROOM 207 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 117 64
27 Spare -- 20 A 1 0 0 1 20 A -- Spare 28
65 REC-ROOM 117 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 117 66
29 Spare -- 20 A 1 0 0 1 20 A -- Spare 30
67 REC-ROOM 117 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 117 68
Total Load: 35794 VA 37088 VA 34196 VA
69 REC-ROOM 117 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 117 70
Total Amps: 130 A 135 A 123 A
71 REC-ROOM 117 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 114 72
Branch Panel: MH1 73 REC-ROOM 117 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 114 74
Legend:
Location: ELEC. RM. 120 Volts: 480/277 Wye A.I.C. Rating: 42,000 75 REC-ROOM 114 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 114 76
Supply From: MSB-B Phases: 3 Mains Type: M.L.O. 77 REC-ROOM 114 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 114 78
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Mounting: Surface Wires: 4 Mains Rating: 600 A 79 REC-ROOM 114 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 114 80
Lighting 21741 VA 100.00% 21741 VA
Enclosure: Type 1 81 REC-ROOM 114 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 101 82
Equipment 7396 VA 80.00% 5917 VA Total Conn. Load: 107077 VA
83 REC-ROOM 114 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 101 84
Receptacle 77940 VA 56.42% 43970 VA Total Est. Demand: 71628 VA
Notes: 85 REC-ROOM 101 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 101 86
Total Conn. Current: 129 A
87 REC-ROOM 101 Recept... 20 A 1 720... 900... 1 20 A Recept... REC-ROOM 239 88
Total Est. Demand Current: 86 A
89 REC-ROOMS 237,238,240,242 Recept... 20 A 1 900... 900... 1 20 A Recept... REC-ROOM 234 90
91 REC-ROOM 236 Recept... 20 A 1 900... 900... 1 20 A Recept... REC-ROOM 209 92
Demand A B C Demand 93 REC-ROOM 218 Recept... 20 A 1 720... 900... 1 20 A Recept... REC-ROOM 117 94
Notes:
CKT Circuit Description Code TRIP P P TRIP Code Circuit Description CKT 95 REC-ROOM 206 Recept... 20 A 1 900... 900... 1 20 A Recept... REC-ROOM 113 96
1 ELECTRIC UNIT HEATER EUH-C - ROOM 119 Heating 25 A 1 3000 5000 1 20 A Heating ELECTRIC DUCT HEATER EDH-1 2 97 REC-ROOM 114 Recept... 20 A 1 900... 900... 1 20 A Recept... REC-ROOM 109 98
3 ELECTRIC UNIT HEATER EUH-D - STAIR 201 Heating 25 A 1 3000 5000 1 25 A Heating ELECTRIC UNIT HEATER EUH-A - CORRIDOR... 4 99 REC-ROOM 110 Recept... 20 A 1 900... 900... 1 20 A Recept... REC-ROOM 101 100
5 ELECTRIC UNIT HEATER EUH-A - STAIR 220 Heating 25 A 1 5000 5000 1 25 A Heating ELECTRIC UNIT HEATER EUH-B - CORRIDOR... 6 101 REC-ROOM 105 Recept... 20 A 1 900... 1080... 1 20 A Recept... REC-ROOMS 216,217 102
7 ELECTRIC DUCT HEATER EDH-2 Heating 20 A 1 5000 2522 3 15 A Motor HEAT PUMP- MECH. ROOM 107 8 103 REC-CORRIDOR 229 Recept... 20 A 1 900... 1080... 1 20 A Recept... REC-ROOMS 118,119,120 104
9 ELECTRIC UNIT HEATER EUH-A - STAIR 121 Heating 25 A 1 5000 2522 -- -- -- -- 10 105 REC-ROOMS 213,216 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 236 106
11 ELECTRIC UNIT HEATER EUH-B - ROOM 204 Heating 20 A 1 5000 2522 -- -- -- -- 12 107 REC-ROOM 239 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 203 108
13 HEAT PUMP- MECH. ROOM 107 Motor 15 A 3 2522 2522 3 15 A Motor HEAT PUMP- MECH. ROOM 112 14 109 REC-ROOM 234 Recept... 20 A 1 540... 1080... 1 20 A Recept... REC-ROOM 110 110 Branch Panel: CL2
15 -- -- -- -- 2522 2522 -- -- -- -- 16 111 REC-ROOM 113 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 105 112 Location: ELEC. RM. 420 Volts: 120/208 Wye A.I.C. Rating: 10,000
17 -- -- -- -- 2522 2522 -- -- -- -- 18 113 REC-ROOM 109 Recept... 20 A 1 1080... 1260... 1 20 A Recept... REC-ROOM 239 114 Supply From: T-CL2 Phases: 3 Mains Type: M.C.B.
19 HEAT PUMP- MECH. ROOM 112 Motor 15 A 3 2522 2522 3 15 A Motor HEAT PUMP- MECH. ROOM 237 20 115 REC-CORRIDOR 108,235 Recept... 20 A 1 1080... 1260... 1 20 A Recept... REC-ROOM 113 116 Mounting: Surface Wires: 4 Mains Rating: 250 A
21 -- -- -- -- 2522 2522 -- -- -- -- 22 117 REC-ROOM 236 Recept... 20 A 1 1260... 1260... 1 20 A Recept... REC-ROOM 109 118 Enclosure: Type 1 MCB Rating: 250 A
23 -- -- -- -- 2522 2522 -- -- -- -- 24 119 REC-ROOM 110 Recept... 20 A 1 1260... 1441... 3 20 A Motor BLEACHERS 120
25 HEAT PUMP- MECH. ROOM 237 Motor 15 A 3 2522 2910 3 15 A Motor HEAT PUMP- MECH. ROOM 219 26 121 REC-ROOM 105 Recept... 20 A 1 1260... 1441... -- -- -- -- 122 Notes:
27 -- -- -- -- 2522 2910 -- -- -- -- 28 123 WATER HEATER WH-2 Equip... 20 A 1 300... 1441... -- -- -- -- 124
29 -- -- -- -- 2522 2910 -- -- -- -- 30 125 REC-ROOM 218 Recept... 20 A 1 180... 300... 1 20 A Equip... WATER HEATER WH-1 126
31 HEAT PUMP- MECH. ROOM 102 Motor 20 A 3 4074 4074 3 20 A Motor HEAT PUMP- MECH. ROOM 116 32 127 REC-ROOM 218 Recept... 20 A 1 180... 791... 2 20 A Motor CIRCULATING PUMP CP-1 128
33 -- -- -- -- 4074 4074 -- -- -- -- 34 129 Civil Hot Box Equip... 20 A 1 180... 791... -- -- -- -- 130 2
Demand A B C Demand
35 -- -- -- -- 4074 4074 -- -- -- -- 36 131 FIRE ALARM CONTROL PANEL - ROOM 120 General 20 A 1 500... 720... 1 20 A Recept... REC-ROOM 234 132 CKT Circuit Description Code TRIP P P TRIP Code Circuit Description CKT
37 HEAT PUMP- MECH. ROOM 245 Motor 20 A 3 4074 4351 3 25 A Motor HEAT PUMP- MECH. ROOM 116 38 133 Spare -- 20 A 1 0 VA 1080... 1 20 A Recept... REC-ROOM 234 134 1 ELEVATOR CONTROLS (SHUNT TRIP) Equip... 20 A 1 0 VA 180... 1 20 A Recept... REC-ROOFTOP 2
39 -- -- -- -- 4074 4351 -- -- -- -- 40 135 Spare -- 20 A 1 0 VA 1080... 1 20 A Recept... REC-ROOM 234 136 3 REC-ROOM 401 Recept... 20 A 1 360... 1080... 1 20 A Recept... REC-ROOM 405 4
41 -- -- -- -- 4074 4351 -- -- -- -- 42 137 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 138 5 CONTROLS-OAU-3 Equip... 20 A 1 200... 1080... 1 20 A Recept... REC-ROOM 408 6
43 HEAT PUMP- MECH. ROOM 219 Motor 25 A 3 4351 4351 3 25 A Motor HEAT PUMP- MECH. ROOM 219 44 139 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 140 7 REC-ROOM 525 (HANDWASH) Equip... 20 A 1 3000... 180... 1 20 A Recept... REC-ROOM 514 8
45 -- -- -- -- 4351 4351 -- -- -- -- 46 141 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 142 9 A/C-1 ROOFTOP Equip... 25 A 2 1498... 180... 1 20 A Recept... REC-ROOM 514 10
47 -- -- -- -- 4351 4351 -- -- -- -- 48 143 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 144 11 -- -- -- -- 1498... 180... 1 20 A Recept... REC-ROOM ELEVATOR 12
49 HEAT PUMP- MECH. ROOM 118 Motor 25 A 3 4628 7693 3 45 A Motor OUTSIDE AIR UNIT - OAU-1 - ROOM 118 50 145 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 146 13 REC-ROOM 415 REFRIGERATOR Recept... 20 A 1 180... 200... 1 20 A Equip... LTS-OAU-3 14
51 -- -- -- -- 4628 7693 -- -- -- -- 52 147 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 148 15 REC-ROOM 506 Recept... 20 A 1 180... 200... 1 20 A Equip... LTS-RTU-1 16
53 -- -- -- -- 4628 7693 -- -- -- -- 54 149 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 150 17 REC-ROOM 507 Recept... 20 A 1 180... 200... 1 20 A Equip... LTS-RTU-2 18
55 PUMP LWP-1 - ROOM 118 Equip... 100 A 3 11085 11085 3 100 A Equip... PUMP LWP-2 - ROOM 118 56 151 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 152 19 CONTROLS-RTU-1 Equip... 20 A 1 200... 360... 1 20 A Recept... REC-ROOM 519 20
57 -- -- -- -- 11085 11085 -- -- -- -- 58 153 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 154 21 CONTROLS-RTU-2 Equip... 20 A 1 200... 360... 1 20 A Recept... REC-ROOM 522 22
59 -- -- -- -- 11085 11085 -- -- -- -- 60 155 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 156 23 EMS CONTROL PANEL-ROOM 419 Equip... 20 A 1 200... 360... 1 20 A Recept... REC-ROOMS 402,403 24
61 Spare -- 15 A 3 0 0 1 20 A -- Spare 62 157 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 158 25 REC-ROOM 512 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 503 26

RUTHERFORD COUNTY BOARD OF EDUCATION


63 -- -- -- -- 0 0 1 20 A -- Spare 64 159 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 160 27 REC-ROOM 515 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 507 28
65 -- -- -- -- 0 0 1 20 A -- Spare 66 161 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 162 29 REC-ROOM 518 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 509 30
67 Spare -- 20 A 3 0 0 3 30 A -- Spare 68 163 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 164 31 REC-ROOM 414 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 408 32
69 -- -- -- -- 0 0 -- -- -- -- 70 165 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 166 33 REC-ROOM 415 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 410 34
71 -- -- -- -- 0 0 -- -- -- -- 72 167 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 168 35 REC-ROOM 417 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 413 36
73 Space -- -- -- 0 0 -- -- -- Space 74 Total Load: 28112 VA 29532 VA 28521 VA 37 REC-ROOM 404 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOF OUTLETS 38
75 Space -- -- -- 0 0 -- -- -- Space 76 Total Amps: 234 A 247 A 238 A 39 REC-ROOM 404 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOFTOP 40
77 Space -- -- -- 0 0 -- -- -- Space 78 Load Classification Connected Load Demand Factor Estimated Demand Panel Totals 41 REC-ROOM 405 Recept... 20 A 1 360... 360... 1 20 A Recept... REC-ROOM 401 42
79 Space -- -- -- 0 0 -- -- -- Space 80 Motor 5904 VA 80.00% 4723 VA 43 REC-ROOMS 415,416 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 417 44
81 Space -- -- -- 0 0 -- -- -- Space 82 Equipment 4280 VA 80.00% 3424 VA Total Conn. Load: 86164 VA 45 REC-ROOMS 504,505,510,511 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 417 46
83 Space -- -- -- 0 0 -- -- -- Space 84 Receptacle 75480 VA 56.62% 42740 VA Total Est. Demand: 51312 VA 47 REC-ROOMS 516,517,520,521 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOMS 406,407,411,412 48
Total Load: 90807 VA 90807 VA 92807 VA General 500 VA 85.00% 425 VA Total Conn. Current: 239 A 49 REC-ROOM 417 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 417 50
Total Amps: 328 A 328 A 335 A Total Est. Demand Current: 142 A 51 REC-ROOM 417 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 417 52
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals 53 REC-ROOM 417 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 417 54
Motor 166911 VA 80.00% 133529 VA 55 REC-ROOM 414 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 414 56
Heating 41000 VA 100.00% 41000 VA Total Conn. Load: 274421 VA

MURFREESBORO, TN
57 REC-ROOM 417 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 414 58
Equipment 66510 VA 80.00% 53208 VA Total Est. Demand: 227737 VA
Total Conn. Current: 330 A Branch Panel: MH2 59
61
REC-ROOM 417
REC-ROOM 414
Recept... 20 A 1
Recept... 20 A 1 720... 720...
720... 720... 1
1
20 A
20 A
Recept...
Recept...
REC-ROOM 414
REC-ROOM 414
60
62
Total Est. Demand Current: 274 A Location: ELEC. RM. 420 Volts: 480/277 Wye A.I.C. Rating: 42,000 63 REC-ROOM 414 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 414 64
Supply From: MSB-B Phases: 3 Mains Type: M.L.O. 65 REC-ROOM 414 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 414 66
Mounting: Surface Wires: 4 Mains Rating: 600 A 67 REC-ROOM 401 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 401 68
Enclosure: Type 1 69 REC-ROOM 401 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 401 70
71 REC-ROOM 401 Recept... 20 A 1 720... 720... 1 20 A Recept... REC-ROOM 401 72
Branch Panel: CH1 Notes: 73 REC-ROOM 414 Recept... 20 A 1 900... 900... 1 20 A Recept... REC-ROOM 408 74
Location: ELEC. RM. 120 Volts: 480/277 Wye A.I.C. Rating: 42,000 75 REC-ROOM 417 Recept... 20 A 1 900... 900... 1 20 A Recept... REC-ROOM 410 76
Supply From: MSB-B Phases: 3 Mains Type: M.L.O. 77 REC-ROOMS 502,523,525 Recept... 20 A 1 900... 900... 1 20 A Recept... REC-ROOM 413 78
Mounting: Surface Wires: 4 Mains Rating: 250 A 79 REC-CORRIDOR 409 Recept... 20 A 1 900... 1080... 1 20 A Recept... REC-ROOM 522 80
Demand A B C Demand 81 REC-ROOM 401 Recept... 20 A 1 900... 1080... 1 20 A Recept... REC-ROOM 522 82
Enclosure: Type 1
CKT Circuit Description Code TRIP P P TRIP Code Circuit Description CKT 83 REC-ROOM 405 Recept... 20 A 1 900... 900... 1 20 A Recept... REC-ROOMS 514,514B 84
1 HEAT PUMP- MECH. ROOM 402 Motor 20 A 3 4074 2522 3 15 A Motor HEAT PUMP- MECH. ROOM 407 2 85 REC-ROOM 519 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 518 86
Notes:
3 -- -- -- -- 4074 2522 -- -- -- -- 4 87 REC-ROOM 519 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 518 88
5 -- -- -- -- 4074 2522 -- -- -- -- 6 89 REC-ROOM 522 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 519 90
7 HEAT PUMP- MECH. ROOM 407 Motor 15 A 3 2522 4351 3 25 A Motor HEAT PUMP- MECH. ROOM 416 8 91 REC-ROOM 515 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 512 92
9 -- -- -- -- 2522 4351 -- -- -- -- 10 93 REC-ROOM 515 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 512 94
Demand A B C Demand 11 -- -- -- -- 2522 4351 -- -- -- -- 12 95 REC-ROOM 518 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 515 96
CKT Circuit Description Code TRIP P P TRIP Code Circuit Description CKT
13 HEAT PUMP- MECH. ROOM 416 Motor 20 A 3 4074 2522 3 15 A Motor HEAT PUMP- MECH. ROOM 412 14 97 REC-ROOM 509 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 507 98
1 LTS - ROOMS 101-104 Lighting 20 A 1 880 1331 1 20 A Lighting LTS - CORRIDOR 229, STAIR 1 220 2
15 -- -- -- -- 4074 2522 -- -- -- -- 16 99 REC-ROOM 509 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 507 100
3 LTS - OUTSIDE LIGHTING Lighting 20 A 1 900 840 1 20 A Lighting LTS - PARKING LOT 4
17 -- -- -- -- 4074 2522 -- -- -- -- 18 101 REC-ROOM 512 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 509 102
5 LTS - ROOMS 201-204, Elevator Lighting 20 A 1 1078 1680 1 20 A Lighting LTS - PARKING LOT 6
19 HEAT PUMP- MECH. ROOM 412 Motor 15 A 3 2522 2522 3 15 A Motor HEAT PUMP- MECH. ROOM 505 20 103 REC-ROOM 503 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 410 104
7 LTS - ROOMS 105-107, 109-113 Lighting 20 A 1 2122 741 1 20 A Lightin... LTS - OUTSIDE LIGHTING 8
21 -- -- -- -- 2522 2522 -- -- -- -- 22 105 REC-ROOM 503 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 413 106
9 LTS - CORRIDOR 108, STAIR 2 121 Lightin... 20 A 1 2486 2626 1 20 A Lighting LTS - ROOMS 114-120 10
23 -- -- -- -- 2522 2522 -- -- -- -- 24 107 REC-ROOM 507 Recept... 20 A 1 1080... 1080... 1 20 A Recept... REC-ROOM 503 108
11 LTS - ROOMS 236-244 Lighting 20 A 1 2181 3570 1 20 A Lighting LTS - PARKING LOT 12
25 HEAT PUMP- MECH. ROOM 505 Motor 15 A 3 2522 2522 3 15 A Motor HEAT PUMP- MECH. ROOM 521 26 109 REC-ROOM 410 Recept... 20 A 1 1260... 1260... 1 20 A Recept... REC-CORRIDOR 508 110
13 LTS - ROOMS 205-219 Lighting 20 A 1 3478 1114 1 20 A Lightin... LTS - OUTSIDE LIGHTING 14
27 -- -- -- -- 2522 2522 -- -- -- -- 28 111 REC-ROOM 413 Recept... 20 A 1 1260... 1260... 1 20 A Recept... REC-ROOM 405 112
15 LTS - PARKING LOT Lighting 20 A 1 2310 28112 3 20 A Motor;... T-CL1 16
29 -- -- -- -- 2522 2522 -- -- -- -- 30 113 REC-ROOMS 418,419,420 Recept... 20 A 1 1260... 1260... 1 20 A Recept... REC-ROOM 408 114
17 LTS - ROOMS 221-234, 245 Lighting 20 A 1 2705 29532 -- -- -- -- 18
31 HEAT PUMP- MECH. ROOM 521 Motor 15 A 3 2522 2522 3 15 A Motor HEAT PUMP- MECH. ROOM 511 32 115 REC-ROOM 514 Recept... 20 A 1 180... 180... 1 20 A Recept... REC-ROOM 514 116
19 Spare -- 20 A 1 0 28521 -- -- -- -- 20
33 -- -- -- -- 2522 2522 -- -- -- -- 34 117 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 118
21 Spare -- 20 A 1 0 0 1 20 A -- Spare 22
35 -- -- -- -- 2522 2522 -- -- -- -- 36 119 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 120
23 Spare -- 20 A 1 0 0 1 20 A -- Spare 24
37 HEAT PUMP- MECH. ROOM 511 Motor 15 A 3 2522 2522 3 15 A Motor HEAT PUMP- MECH. ROOM 517 38 121 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 122
25 Spare -- 20 A 1 0 0 1 20 A -- Spare 26
39 -- -- -- -- 2522 2522 -- -- -- -- 40 123 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 124
27 Spare -- 20 A 1 0 0 1 20 A -- Spare 28
41 -- -- -- -- 2522 2522 -- -- -- -- 42 125 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 126
29 Spare -- 20 A 1 0 0 1 20 A -- Spare 30
43 HEAT PUMP- MECH. ROOM 517 Motor 15 A 3 2522 2493 1 15 A Motor HEAT PUMP- MECH. ROOM 514B 44 127 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 128
Total Load: 38186 VA 37273 VA 40745 VA
45 -- -- -- -- 2522 0 1 20 A -- Spare 46 129 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 130
Total Amps: 138 A 135 A 148 A
47 -- -- -- -- 2522 0 1 20 A -- Spare 48 131 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 132
Legend:
49 OUTSIDE AIR UNIT - OAU-2 - ROOM 419 Motor 45 A 3 8203 6125 3 20 A Motor HEAT PUMP- MECH. ROOM 419 50 133 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 134
51 -- -- -- -- 8203 6125 -- -- -- -- 52 135 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 136
53 -- -- -- -- 8203 6125 -- -- -- -- 54 137 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 138
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
55 ROOFTOP UNIT - RTU - 1 Motor 125 A 3 18401 7782 3 45 A Motor OUTSIDE AIR UNIT - OAU-3 56 139 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 140
Lighting 29935 VA 100.00% 29935 VA
57 -- -- -- -- 18401 7782 -- -- -- -- 58 141 Space -- -- -- 0 VA 0 VA -- -- -- Space 142
Motor 5904 VA 80.00% 4723 VA Total Conn. Load: 116220 VA
59 -- -- -- -- 18401 7782 -- -- -- -- 60
Equipment 4280 VA 80.00% 3424 VA Total Est. Demand: 81296 VA
143 Space -- -- -- 0 VA 0 VA -- -- -- Space 144 10-06-2017 BID DOCUMENTS
61 Spare -- 20 A 3 0 0 3 15 A -- Spare 62 145 Space -- -- -- 0 VA 0 VA -- -- -- Space 146
Receptacle 75480 VA 56.62% 42740 VA Total Conn. Current: 140 A
63 -- -- -- -- 0 0 -- -- -- -- 64 147 Space -- -- -- 0 VA 0 VA -- -- -- Space 148
02-19-2018 RFP-002
General 500 VA 85.00% 425 VA Total Est. Demand Current: 98 A
65 -- -- -- -- 0 0 -- -- -- -- 66 149 Space -- -- -- 0 VA 0 VA -- -- -- Space 150
67 Spare -- 30 A 3 0 0 3 45 A -- Spare 68 151 Space -- -- -- 0 VA 0 VA -- -- -- Space 152
69 -- -- -- -- 0 0 -- -- -- -- 70 153 Space -- -- -- 0 VA 0 VA -- -- -- Space 154
Notes:
71 -- -- -- -- 0 0 -- -- -- -- 72 155 Space -- -- -- 0 VA 0 VA -- -- -- Space 156
73 Space -- -- -- 0 0 -- -- -- Space 74 157 Space -- -- -- 0 VA 0 VA -- -- -- Space 158
75 Space -- -- -- 0 0 -- -- -- Space 76 159 Space -- -- -- 0 VA 0 VA -- -- -- Space 160
77 Space -- -- -- 0 0 -- -- -- Space 78 161 Space -- -- -- 0 VA 0 VA -- -- -- Space 162
79 Space -- -- -- 0 0 -- -- -- Space 80 163 Space -- -- -- 0 VA 0 VA -- -- -- Space 164
81 Space -- -- -- 0 0 -- -- -- Space 82 165 Space -- -- -- 0 VA 0 VA -- -- -- Space 166 ELECTRICAL - PANEL
83 Space -- -- --
Total Load: 85766 VA 83273 VA
0
83273 VA
0 -- -- -- Space 84 167 Space -- -- --
Total Load: 28960 VA 28358 VA
0 VA 0 VA
28018 VA
-- -- -- Space 168
SCHEDULES
Total Amps: 310 A 301 A 301 A Total Amps: 242 A 237 A 233 A
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Motor 252311 VA 80.00% 201849 VA Equipment 7396 VA 80.00% 5917 VA
Total Conn. Load: 252311 VA Receptacle 77940 VA 56.42% 43970 VA Total Conn. Load: 85336 VA

E800
Total Est. Demand: 201849 VA Total Est. Demand: 49887 VA
Total Conn. Current: 303 A Total Conn. Current: 237 A
Total Est. Demand Current: 243 A Total Est. Demand Current: 138 A