Compensation matrices for transformer


differential protection
 Apply one for each winding of the transformer
 Typical usage is:

 IA.sec_cor   IA_Primary 
  1  
 IB.sec_cor  = MATcorrection   IB_Primary 
TapHV CTRHV
I  I 
 C.sec_cor   C_Primary 

 Matrices for commonly used transformer connections in the North America

- Standard Y Connected winding (Y0 using IEC clock position notation):

 1 0 0 
MAT0   0 1 0 
0 0 1 
 

- Δ connected winding, DAB (D1 using IEC clock position notation):


 1 1 0 
1 
MAT1    0 1 1 
3  
 1 0 1 
- Δ connected winding, DAC (D11 using IEC clock position notation):

 1 0 1 
1 
MAT11    1 1 0 
3  
 0 1 1 
- Zero sequence removal matrix:

 2 1 1 
1 
MAT12    1 2 1 
3  
 1 1 2 