ARCUBE
MONOBLOCK LIFT CONTROL UNIT
PARAMETER MANUAL
ARCUBE Parameter Manual Versiyon : V1.0
E-mail: info@arkel.com.tr
www.arkel.com.tr
This document has been created to be a guide for Arkel customers. Reproduction, transfer, distribution or storage of part or all
of the contents in this document in any form without the prior written permission of Arkel is prohibited. Arkel reserves the
right to make changes and improvements to any of the products described in this document without prior notice.
Arkel is not responsible for those mistakes that may be found in this manual and for the damages that they may cause.
ARCUBE Parameter Manual Versiyon : V1.0
Table of contents
PUBLISHER ........................................................................................................................................................................ 2
2. BASIC SETTINGS ..................................................................................................................................................... 6
2.1. LISAN/LANGUAGE ........................................................................................................................................... 6
2.2. OPERATION MODE........................................................................................................................................... 6
2.3. NUMBER OF FLOORS ....................................................................................................................................... 6
2.4. SHAFT POSITION SYSTEM .............................................................................................................................. 6
2.5. MOTOR DIRECTION ......................................................................................................................................... 6
2.6. LOP WIRING SYSTEM ...................................................................................................................................... 6
2.7. COLLECTION TYPE .......................................................................................................................................... 6
2.8. MAXIMUM TRAVEL TIME BETWEEN FLOORS .......................................................................................... 6
2.9. PIT INSPECTION TERMINAL .......................................................................................................................... 6
2.10. OSG COIL CONTROL ........................................................................................................................................ 6
2.11. CAR LIGHT OFF DELAY .................................................................................................................................. 6
2.12. CAR FAN OFF DELAY ...................................................................................................................................... 6
2.13. PARKING FUNCTION ....................................................................................................................................... 6
2.14. PARKING FLOOR .............................................................................................................................................. 6
2.15. PARKING TIME ................................................................................................................................................. 7
2.16. FIRE EVACUATION FUNCTION ..................................................................................................................... 7
2.17. FIRE EVACUATION MAIN FLOOR ................................................................................................................. 7
2.18. FIRE EVACUATION ALTERNATE FLOOR .................................................................................................... 7
2.19. FIREFIGHTER FUNCTION ............................................................................................................................... 7
2.20. ON INSPECTION LIMITS .................................................................................................................................. 7
2.21. GROUP IDENTITY ............................................................................................................................................. 7
2.22. BOTTOM MISSING FLOORS ............................................................................................................................ 7
2.23. TOP MISSING FLOORS ..................................................................................................................................... 7
2.24. PANIC EVACUATION FUNCTION .................................................................................................................. 7
2.25. PANIC EVACUATION FLOOR ......................................................................................................................... 7
2.26. ATTENDANT SERVICE MODE ........................................................................................................................ 7
2.27. WELCOME & GOODBYE ANNOUNCE-1 ....................................................................................................... 7
2.28. ANNOUNCE-1 FLOOR ...................................................................................................................................... 7
2.29. WELCOME & GOODBYE ANNOUNCE-2 ....................................................................................................... 7
2.30. ANNOUNCE-2 FLOOR ...................................................................................................................................... 7
2.31. MAINS FREQUENCY ........................................................................................................................................ 7
2.32. PHASE ORDER CONTROL ............................................................................................................................... 7
2.33. MONO PHASE REDUCED SPEED MODE ....................................................................................................... 8
2.34. CANCELLING COP CALL ON SECOND PRESS ............................................................................................. 8
2.35. POSITION RESET AFTER POWER DOWN ..................................................................................................... 8
2.36. PASSWORD ........................................................................................................................................................ 8
2.37. LCD CONTRAST ................................................................................................................................................ 8
2.38. CAR FAN CONTROL ......................................................................................................................................... 8
3. SHAFT SETTINGS .................................................................................................................................................. 8
3.1. SHAFT LEARNING DONE ................................................................................................................................ 8
3.2. DOOR ZONE MAGNET LENGTH..................................................................................................................... 8
3.3. DISTANCE BETWEEN ML1-ML2 MAGNETS ................................................................................................ 8
3.10. 817 SIGNAL POSITION ..................................................................................................................................... 8
3.11. 817 SIGNAL POSITION ..................................................................................................................................... 8
4. TRAVEL SPEED CURVE SETTINGS.................................................................................................................... 8
4.1. HIGH SPEED [V_MAX] ..................................................................................................................................... 8
4.3. LOW SPEED [V_MIN]........................................................................................................................................ 8
4.4. INSPECTION SPEED [V_INSP]......................................................................................................................... 8
4.5. RECALLL SPEED [V_RCL] ............................................................................................................................... 9
ARCUBE Parameter Manual Versiyon : V1.0
Motors are sensitive devices to connection order of 3 require new shaft learning than this parameter should be
phase alternative current supply lines. If any problem in set to “No”.
order is detected, motor is not powered anymore.
3.2. DOOR ZONE MAGNET LENGTH
2.33. MONO PHASE REDUCED SPEED [ 10.00, 70.00] Default: 30.00 CM
MODE In ARCUBE system door zones are determined by long
- DISABLED (Default) magnets. Lengths of door zone magnets are important
- ENABLED because any length in the shaft based on door zone
magnet length. If door zone magnet length is entered
2.34. CANCELLING COP CALL ON incorrect way, all lengths in the shaft will be calculated
SECOND PRESS as wrong.
- DISABLED (Default)
3.3. DISTANCE BETWEEN ML1-ML2
- ENABLED
This parameter enables cancelling of car command by MAGNETS
pressing to the same button for twice. [ 5.00, 10.00] Default: 5.00 CM
Distance between ML1 and ML2 magnets can be varies
2.35. POSITION RESET AFTER POWER from this parameter.
DOWN
3.10. 817 SIGNAL POSITION
- DISABLED
- ENABLED (Default) [ -100.00, 20000.00] Default: 0.00 CM
The ARCUBE remembers the last position at any mains After shaft learning 817 pre-limiter position is calculated
power failure, and it can reset its position after a mains and saved to this parameter.
failure. If this parameter is enable.
3.11. 817 SIGNAL POSITION
2.36. PASSWORD [ -100.00, 20000.00] Default: 0.00 CM
[ 0, 999999] Default: 0 After shaft learning 818 pre-limiter position is calculated
This parameter is used to set access password. It can be 6 and saved to this parameter.
digits number.
4. TRAVEL SPEED CURVE SETTINGS
2.37. LCD CONTRAST
4.1. HIGH SPEED [V_MAX]
[ 0, 9] Default: 2
LCD’s contrast level can be adjusted from this parameter. [ 0.10, 1.75] Default: 1.00 m/s
This is the maximum speed that the car will move in
2.38. CAR FAN CONTROL normal operation mode. This value should be entered the
same as nominal car speed.
-BY FAN BUTTON
-AUTOMATIC
4.3. LOW SPEED [V_MIN]
This parameter is used to change car fan control type.
[ 0.05, 0.30] Default: 0.13 m/s
3. SHAFT SETTINGS This is the minimum speed that the car will move in
normal operation mode.
3.1. SHAFT LEARNING DONE
4.4. INSPECTION SPEED [V_INSP]
- NO (Default)
- YES [ 0.10, 0.63] Default: 0.30 m/s
If the shaft learning is done and the results are saved, this Car speed in the inspection mode can be adjusted with
parameter automatically set to “YES”. If elevator system this parameter.
ARCUBE Parameter Manual Versiyon : V1.0
4.5. RECALLL SPEED [V_RCL] travel duration shorten. This parameter enables only
[ 0.10, 0.30] Default: 0.30 m/s when the “Comfort Level Parameter” adjusted as “User
Car speed in the recall mode can be adjusted with this defined”.
parameter.
4.11. DECCELERATION [NA]
4.6. RELEVEL SPEED [V_RLVL] [ 0.10, 1.00] Default: 0.50 m/s2
[ 0.01, 0.15] Default: 0.05 m/s This parameter is used to adjust acceleration of speed
Car speed during relevelling the car can be adjusted from down when car approaching to its stop level. High
this parameter. deceleration value can be uncomfortable for some
passengers while it makes the travel duration shorten.
4.7. SLOWING DISTANCE [XSLW] This parameter enables only when the “Comfort Level
Parameter” adjusted as “User defined”.)
[ 10, 500] Default: 150 CM
This parameter is used to adjust the distance at which car
4.12. RAMP SOFTEN S1
is starting to be slowing.
[ 0.10, 1.00] Default: 0.50 m/s3
4.8. STOPING DISTANCE [XSTP]
4.13. RAMP SOFTEN S2
[ 1, 50] Default: 7 CM
This parameter is used to adjust the distance at which car [ 0.10, 1.00] Default: 0.50 m/s3
is starting to be stopping.
4.14. RAMP SOFTEN S3
4.9. COMFORT LEVEL [ 0.10, 1.00] Default: 0.50 m/s3
- USER DEFINED
- COMFORT:1 PERFORMANCE:5 4.15. RAMP SOFTEN S4
- COMFORT:2 PERFORMANCE:4 [ 0.10, 1.00] Default: 0.50 m/s3
- COMFORT:3 PERFORMANCE:3 (Default)
- COMFORT:4 PERFORMANCE:2 5. MOTOR PARAMETERS
- COMFORT:5 PERFORMANCE:1
This parameter determines the acceleration and jerk 5.1. MOTOR AUTO-TUNING DONE
values used in calculation of the travel speed curves. - NO (Default)
There are 5 preset values in the form "Comfort:X / - YES
Performance: Y". If the motor auto-tuning is done and the results are saved
Comfort and performance are two contradicting criteria this parameter automatically set to “YES”. If elevator
that must be considered when choosing the value of this system requires to be auto-tuned from the beginning than
parameter. To increase travel comfort, the accelerations this parameter should be set to “NO”.)
during travel will need be decreased which will in turn
lengthen the travel times. If shorter travel times are 5.2. MOTOR TYPE
desired, accelerations will need to be increased which
- INDUCTION (Default)
will in turn result in travels with less comfort.
- SYNCHRONOUS
Although not necessary in most cases, the "User defined"
This parameter informs the ARCUBE about used type of
option can also be selected to have fine control on every
motor.
aspect of the travel curve.
5.3. MOTOR CONTROL TYPE
4.10. ACCELERATION [PA]
- OPEN LOOP (Default)
[ 0.10, 1.00] Default: 0.50 m/s2
- CLOSED LOOP
This parameter is used to adjust acceleration of speed up
when car started to move. High acceleration value can be
uncomfortable for some passengers while it makes the
ARCUBE Parameter Manual Versiyon : V1.0
This parameter is used to choose the motor control type. the auto tune procedure and it is not recommended to
The control of the motor can be in open loop mode or in change automatically set value.
closed loop mode.
5.10. MOTOR VOLTAGE
5.4. NOMINAL CAR SPEED [ 150, 500] Default: 380 VOLT
[ 0.20, 2.00] Default: 1.00 m/s Nominal motor voltage is defined with this parameter.
Nominal speed of the elevator machine is defined with This value is given by the motor manufacturer and shown
this parameter. This value is given by the motor on the machine plate.
manufacturer and shown on the machine plate.
5.11. MOTOR CURRENT
5.5. MOTOR ENCODER TYPE [ 5.00, 80.00] Default: 17.00 Ampere
- ENDAT-SIN COS 2048 (Default) Nominal motor current is defined with this parameter.
- SSI GRAY-SINCOS 2048 This value is given by the motor manufacturer and shown
- SSI GRAY-SINCOS 1024 on the machine plate.
- BISS BINARY SINCOS 2048
- BISS GRAY SINCOS 2048 5.12. MOTOR FREQUENCY
- SINCOS 2048 SINCOS 2048 [ 10.00, 200.00] Default: 50.00 Hz
Motor encoder type can be adjusted with this parameter Nominal motor supply frequency is defined with this
which is activated only for synchronous motors. Most of parameter. This value is given by the motor manufacturer
the absolute encoder protocols are supported and can be and shown on the machine plate.
pick up from the menu.
5.13. ROTOR SLIP FREQENCY
5.6. ENCODER RESOLUTION
[ 0.50, 8.00] Default: 2.3 Hz
[ 100, 9999] Default: 1024 PULSE/REV Nominal slip frequency of the motor is defined with this
This parameter defines how many pulses are generated in parameter. This value is given by the motor manufacturer
one turn of the motor rotor. 100 pulses/rev to 10000 and shown on the machine plate. This parameter is only
pulses/rev encoders can be used. This parameter requires available if the Motor Type is selected as Asynchronous.
only for asynchronous motors.
5.14. MOTOR NO LOAD CURRENT
5.7. ENCODER DIRECTION
[ 20, 60] Default: 40 %
- CLOCKWISE (Default) No-load current of the motor is defined with this
In some case it is required to change encoder direction parameter. This value is given by the motor manufacturer
which has reverse direction according to the motor rotate. and shown on the machine plate.
Clockwise or counterclockwise can be adjusted.
5.15. MOTOR TIME CONSTANT
5.8. ENCODER FILTER
[ 50, 500] Default: 200 ms
[ 1, 4] Default: 2 Time constant for motor rotor, dependence of the inverter
The filter applied to the encoder value to this parameter is reduced, do not change this parameter
1]2ms, 2]4ms, 3]8ms, 4]16ms if not necessary. This value may be get from the motor
it is recommended to set this parameter to 2 for closed manufacturer. This parameter is needed for vector
loop asynchronous motors and to 2 or 3 for synchronous control.
motors.
5.16. MOTOR V/F MIDDLE FREQUENCY
5.9. ENCODER OFFSET ANGLE
[ 2.00, 10.00] Default: 5.00 Hz
[ 0, 360] Default: 0 This parameter determines approximately middle point
For synchronous motors this is very important parameter frequency of the voltage- frequency table.
for good drive. This value can be set automatically with
ARCUBE Parameter Manual Versiyon : V1.0
5.17. MOTOR V/F MIDDLE VOLTAGE Setting this parameter too short will cause the motor to
[ 5, 100] Default: 40 VOLT release the car before brakes could lock the car in
This parameter determines approximately middle point position. In this case, the car will start to move freely in
voltage of the voltage- frequency table. the heavy direction until the brakes close.
Setting this parameter too long will cause unnecessary
5.18. MOTOR V/F MINIMUM delays before opening the doors at the end of travels.
FREQUENCY
5.23. MECHANICAL BRAKE
[ 0.50, 10.00] Default: 0.50 Hz
MONITORING
This parameter determines approximately minimum
point frequency of the voltage- frequency table. - DISABLED (Default)
- MONITORING WITH ONE INPUT
5.19. MOTOR V/F MINIMUM VOLTAGE - MONITORING WITH TWO INPUTS
Every drop or release of brake operation is verified with
[ 5, 100] Default: 10 VOLT
brake micro switches which are located on brake. This
This parameter determines approximately minimum
parameter is used to enable/disable mechanical brake
point voltage of the voltage- frequency table.
monitoring by one or two inputs.
with the movement of the cabinet. While changing those with the movement of the cabinet. While changing those
values take the required precaution to prevent hazardous values take the required precaution to prevent hazardous
movement. movement.
7.5. LOADING / UNLOADING TIME door (car command or hall call, door open button,
[ 3, 90] Default: 5 Seconds photocell or overload signals) it waits with doors closed.
After landing on a floor, the door will open. After the Note: This parameter is only available for full automatic
door is fully opened, an internal timer will be set to the doors. Even this choice is selected, semi- automatic doors
value entered in this parameter. The door stays opened always wait doors opened.
until the internal timer is expired. When the timer - WAITS WITH DOOR OPEN
expires, the door will close or stay opened depending on The door is opened after the car landed on the target floor.
the option selected on parameter AUTO DOOR STATE When the door was opened fully, door close timer is set
WHEN IDLE ON FLOOR”. to “LOADING / UNLOADING TIME”. After this timer
expired, if there is no call from any floor the door
7.6. DOOR DELAY TIME AFTER continues to wait with doors opened. Unless the door
close timer expired, the door is not closed even if there is
PHOTOCELL
a call from any floor.
[ 1, 90] Default: 3 Seconds
The door will stay opened during the value set in this 7.20. DOOR BRIDGING CIRCUIT
parameter when one of the following events occur:
- DISABLED (Default)
1.Photocell (light-curtain) interruption of the related door
- ENABLED
2.Pressing the car command button of the current floor
The door safety circuit is bridging with this parameter
and related door-side
and only used in EN 81-20.
3.Pressing the landing call button of the current floor and
related door-side
7.21. DOOR PREOPENING
4.Activation of overload signal
5.Switching from inspection or recall to normal operation - DISABLED (Default)
- ENABLED
7.7. DOOR OPEN ERROR This parameter is used to enable/disable door pre-
opening function. It can be used when article 7.20 is
- DISABLED (Default)
activated.
- ENABLED
This parameter adjusts the speed of colour change on the - (PAN) PANIC BUTTON
displays. Speed parameter can be very slow, slow, - (DEP) EARTHQUAKE DETECTION SIGNAL
normal, fast and very fast. - (FES) FIRE EVACUATION SIGNAL
- (FES2) FIRE EVACUATION SIGNAL-2
9.28. DIRECTION ARROW SLIDING - (FFK) FIREFIGHTER KEY
SPEED - (ATSM) ATTENDANT SERVICE MODE KEY
- VERY SLOW The programmable input terminals PI$ on the LCB Board
- SLOW is assigned to input functions by these parameters.
- NORMAL (Default)
- FAST 10.2. FX-CUBE PI$
- VERY FAST $ = Input [ 1, 3]
This parameter adjusts the speed of sliding direction Number of inputs can be changed by left or right button.
arrow on the displays. Speed parameter can be very slow, Input can be one of the following:
slow, normal, fast and very fast. - <UNDEFINED> (Default)
- (141) DOWN DIRECTIONMAGNET SIGNAL
9.29. FLOOR TEXT SLIDING DIRECTION - (142) UP DIRECTION MGNET SIGNAL
- MOVEMENT DIRECTION - (VAT) COP PRIORITY OPERATION KEY
- OPPOSITE OF MOVEMENT DIRECTION - (PAN) PANIC BUTTON
(Default) - (DEP) EARTHQUAKE DETECTION SIGNAL
This parameter adjusts the direction of sliding floor - (FES) FIRE EVACUATION SIGNAL
number on the displays. - (FES2) FIRE EVACUATION SIGNAL-2
- (FFK) FIREFIGHTER KEY
9.30. CHARACTER SLIDING SPEED - (ATSM) ATTENDANT SERVICE MODE KEY
The programmable input terminals PI$ on the FX-CUBE
- VERY SLOW
Board is assigned to input functions by these parameters.
- SLOW
- NORMAL (Default)
10.3. LCB PD$
- FAST
- VERY FAST $ = Input [ 1, 2]
This parameter adjusts the speed of sliding character on Number of inputs can be changed by left or right button.
the displays. Speed parameter can be very slow, slow, Input can be one of the following:
normal, fast and very fast. - <UNDEFINED> (Default)
- (141) DOWN DIRECTIONMAGNET SIGNAL
9.31. CHARACTER FONT TYPE - (142) UP DIRECTION MGNET SIGNAL
- (VAT) COP PRIORITY OPERATION KEY
- NORMAL (Default)
- (PAN) PANIC BUTTON
- BOLD
- (DEP) EARTHQUAKE DETECTION SIGNAL
By using this parameter, User can be change FONT type.
- (FES) FIRE EVACUATION SIGNAL
- (FES2) FIRE EVACUATION SIGNAL-2
10. PROGRAMMABLE INPUTS
- (FFK) FIREFIGHTER KEY
- (ATSM) ATTENDANT SERVICE MODE KEY
10.1. LCB PI$
The programmable input terminals PD$ on the LCB
$ = Input [ 1, 4] Board is assigned to input functions by these parameters.
Number of inputs can be changed by left or right button.
Input can be one of the following: 11. PROGRAMMABLE OUTPUTS
- <UNDEFINED> (Default)
- (141) DOWN DIRECTIONMAGNET SIGNAL 11.1. LCB PR1
- (142) UP DIRECTION MGNET SIGNAL
- <UNDEFINED> (Default)
- (VAT) COP PRIORITY OPERATION KEY
- (K5) DOOR OPEN COMMAND
ARCUBE Parameter Manual Versiyon : V1.0