You are on page 1of 10

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO.

4, OCTOBER 2009 2107

A New Proposal for Power Quality and Custom


Power Improvement: OPEN UPQC
Morris Brenna, Member, IEEE, Roberto Faranda, Member, IEEE, and Enrico Tironi

Abstract—Currently, the quality of supplied power is important


to several customers. Power quality (PQ) is a service and many cus-
tomers are ready to pay for it. In the future, distribution system op-
erators could decide, or could be obliged by authorities, to supply
their customers with different PQ levels and at different prices.
A new device that can fulfill this role is the OPEN unified power-
quality conditioner (UPQC), composed of a power-electronic series
main unit installed in the medium-voltage/low-voltage (LV) sub-
station, along with several power-electronic shunt units connected
close to the end users. The series and parallel units do not have a
common dc link, so their control strategies are different than tra-
ditional UPQC control techniques. This device can achieve general
improvement in PQ, reducing the most common disturbances for
all customers that are supplied by the mains (PQ) by using only the
series unit. Additional increments in PQ (i.e., mains power inter- Fig. 1. Chronology of voltage sags occurring in the Southeastern states of the
ruptions), can be provided to the customers who need it (custom U.S. on December 4 and 5, 2002.
power) by the shunt units. Therefore, this new solution combines
an improvement in PQ for all end users, with a cost reduction for configure their systems to keep their most important customers
those that need high quality power. The proposed solution has been
analyzed and described, and a model of a 400-kVA LV grid is con- on-line.
sidered a test network to evaluate the steady-state performance and Fig. 1 shows the chronology of voltage sags occurring in the
functioning limits. The results obtained under steady-state con- Southeastern states of the U.S. on December 4 and 5, 2002. As
ditions justify the configuration chosen and good device perfor- can be seen, most sags take place around the 10%–20% level.
mance. Various solutions are available to compensate for these distur-
Index Terms—Active power conditioner, custom power, interface bances. One solution involves increasing the short circuit level
devices, OPEN unified power-quality conditioner (UPQC), power of the distribution network, i.e., revamping all the LV distribu-
quality (PQ), unified power quality conditioner (UPQC).
tion cables or raising the power of the MV/LV substation trans-
former, thus increasing the power quality for all end users. In
I. INTRODUCTION this way, an incoming disturbance from a load (i.e., harmonics)
or from a fault in a line is reduced at the point of common
coupling (PCC). Therefore, this solution effectively reduces the
P OWER QUALITY (PQ) is very important to certain cus-
tomers. For this reason, many utilities could sell electrical
energy at different prices to their customers, depending on the
depth of the voltage variations, but does not protect the loads
against transients and short interruptions. A second solution that
quality of the delivered electric power. can compensate any kind of disturbance, including interrup-
Since most end users are connected to secondary distribution tions, is installation [2] of on-line, off-line, line interactive and
networks, at low voltage (LV), it could be important to monitor hybrid UPS systems. In all of these cases, only the end users
and compensate the main disturbances on the LV grid. Specif- that decide to install them are protected, while all of the other
ically, it has been reported in a survey [1] that, in the South- costumers do not receive any improvement in PQ.
eastern region of the U.S., most monitored industrial customers Often, these solutions cannot be adopted by the local utility
and main end users did not suffer long outages. Rather, they companies or by the end users, because they are too expensive
experienced numerous short duration voltage sags and momen- relative to the increase in power quality that they produce. How-
tary interruptions. Therefore, local utility companies had to re- ever, many cheaper solutions are available.
In particular, several electronic devices have been developed,
studied and proposed to the international scientific community
Manuscript received May 16, 2008; revised May 14, 2009. Current version with the goal of improving supplied power quality. In [3]–[10],
published September 23, 2009. Paper no. TPWRD-00364-2008. various single apparatus are analyzed. Different connection
M. Brenna and R. Faranda are with the Department of Energy, Po-
litecnico di Milano, Milan 20133, Italy (e-mail: morris.brenna@polimi.it;
topologies (series or shunt types) are used to realize these
roberto.faranda@polimi.it). devices. The series devices are connected upstream of the pro-
E. Tironi is with the Electrical Engineering Department, Politecnico di Mi- tected lines, while the shunt devices are connected in parallel
lano, Milan 20133, Italy (e-mail: tironi@polimi.it). to the sensitive loads. In general, both types of conditioning
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. devices increase the power quality level at the loads, as reported
Digital Object Identifier 10.1109/TPWRD.2009.2028791 in [3]–[7] for series devices and in [8]–[10] for shunt devices.
0885-8977/$26.00 © 2009 IEEE

Authorized licensed use limited to: Abdul Shaik. Downloaded on October 10, 2009 at 03:57 from IEEE Xplore. Restrictions apply.
2108 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009

Other studies have been carried out to consider combina-


tions of the previous single apparatus solutions (as UPS, UPLC,
UPQC, etc.). The unified power quality conditioner (UPQC)
compensator seems to be a particularly promising power con-
ditioner device. This apparatus is constituted of a series and a
shunt unit, with a common dc section through which power can
be exchanged. Its function is to improve the quality levels of
the current absorbed at the mains and the load supply voltage
[2], [11]. However, these devices do not allow local distribu-
tors to guarantee different quality demand levels to the final cus-
tomers, because they improve power quality for all the supplied
end users. The installation investments are also quite high rela-
tive to the power quality level obtained. A solution that has sim-
ilar performances and advantages, but also makes cost reduction
possible, is the proposed OPEN UPQC.
This new solution, analyzed in [12], [13], starts from the
Fig. 2. Example of distribution of voltage disturbances reported in the EPRI
UPQC configuration, removes the common dc connection and event coordination chart.
splits the shunt unit into several shunted devices. Therefore, the
control strategy is different than the traditional combined series
and shunt converters, but the improvements to load voltage and
network current quality are quite similar. Above all, the OPEN
UPQC can stabilize load voltage, increase the network power
factor, leading to keep load voltage and network current sinu-
soidal and balanced as well.
The series main unit is installed in the MV/LV substation. In
a grid connected configuration, it can stabilize load voltage at
the LV busbar (PCC) as the series devices analyzed in [3]–[7].
The shunt units do not affect the dynamic behavior of the series
unit, because their dynamic responses are very slow under these
operating conditions. In [6] and [7], the transient behavior of a
single dynamic voltage restorer) device was analyzed and simu-
lated, and its working limits were determined. In particular, the
device behavior in the presence of voltage sags (i.e. 10%–20%)
is described.
The several shunt units are connected near the end users that
need high power quality. If a storage system is present, they can
exchange active power and nonactive power with the electrical
system. Especially in a grid-connected configuration, nonactive Fig. 3. Multiwire power diagram of the new proposed solution.
power can be exchanged with the mains in order to enhance the
series unit performance and extend its working limits. Other-
wise, the users can disconnect themselves when the PCC voltage Each shunt unit is sized in relation to the supplied load power,
is out of the operating limits, and the load will be supplied in and can protect its sensitive load against interruptions. The shunt
back-up mode. unit’s function is similar to that of the UPS output stage [2],
[16], but is less expensive because it only has one conversion
II. THE OPEN UPQC stage and involves less power loss.
Most end user disturbances are characterized by short dura- Fig. 3 shows the multiwire power layout of the device in a
tion and small amplitude, though they can still cause interrup- three-phase, four-wire distribution network.
tions in production processes. As can be seen in Fig. 2, most The series unit consists of a coupling transformer (TR), with
voltage sags have small depth and short durations [14]. the primary circuit connected in series with the mains line and a
More than 95% of voltage sags can be compensated by in- secondary one supplying the reversible ac/dc power converter.
jecting a voltage of up to 60% of the nominal voltage, with a The output stage of the pulsewidth modulation (PWM) voltage
maximum duration of 30 cycles. This information is primarily controlled converter contains passive RC shunt filters, to com-
used to evaluate a suitable size for the OPEN UPQC. pensate for the harmonic currents at switching and multiple fre-
The series unit of the OPEN UPQC, sized to supply 60% quencies. Neglecting the active power to compensate the con-
of the LV network power and equipped with a small storage verter losses, the series unit is controlled to act as a purely re-
system, can compensate for most of the voltage disturbances active inductor when the supply voltage is within its operation
reported in Fig. 2. It has the same function as the DVR [6], [7], limits . This fact is of fundamental
[15]. importance, because in this range the loads must be supplied by

Authorized licensed use limited to: Abdul Shaik. Downloaded on October 10, 2009 at 03:57 from IEEE Xplore. Restrictions apply.
BRENNA et al.: NEW PROPOSAL FOR PQ AND CUSTOM POWER IMPROVEMENT: OPEN UPQC 2109

the mains 95% of the time, as established by the IEEE Std 1159
“IEEE Recommended Practice for Monitoring Electric Power
Quality” and European EN50160; therefore, the storage system
must not discharge itself. Outside of this range, active power
can be used to compensate the disturbances, in the same way as
the usual series compensation devices [6], [7], when a storage
system is present.
The shunt units consist of an ac/dc power converter, similar to
the one used in the series unit, connected to an energy storage
system and a set of static switches (SS) [17]. The shunt unit,
depending on the state of the network voltage, can supply either
the entire load, or a part of the load.
There are two different modes of OPEN UPQC operation:
• compensator: when the PCC voltage is within its operation
limits, the SS are closed, the series unit works as a three-
phase voltage generator and the shunt units work as current
generators;
• back-up: when the PCC voltage is outside of its operation
limits, the SS are open, decoupling the network and the
load-compensator system. Each sensitive load is supplied
by its shunt unit, which acts as a sinusoidal voltage gen-
erator, using the energy stored in the storage system as an
energy source.

III. OPEN UPQC PERFORMANCE

This section is focused on understanding the OPEN UPQC


compensation limits. The analysis will be carried out under
steady state conditions, to evaluate the compensation capacity of Fig. 4. Voltage compensation, exchanging only nonactive power. Case (a1):
the device in normal operation mode . it is possible to obtain a power factor equal to 1 in s section in low-voltage
situations. Case (a2): the power factor is always less than 1.
It is important to remember that the power absorbed by the
loads and the shunt units influences the performance of the se-
ries unit, and therefore of the whole OPEN UPQC. Therefore,
when considering a particular set of load conditions, it is pos- A. Nonactive and Power Exchange
sible to find operating conditions for the shunt units that increase
the compensating limits of the series unit. The conditions under which all of the converters exchange
Depending on whether or not storage systems are present, the only nonactive power must be confirmed in situations when the
series and shunt units can exchange only nonactive power or system voltage is near the contractual limits (normal opera-
both nonactive power and active power with the mains. In the tion mode).
latter case, as will be shown in the following, the OPEN UPQC In normal operation mode, the maximum voltage drop in
can better compensate for short duration disturbances. the LV lines of the network must be less than 5% to maintain
In the following cases, all of the solutions will be analyzed low power loss. Therefore, if all the converter units are oper-
under the assumption that the voltages are sinusoidal and are ating to stabilize the voltage in the PCC at its nominal value
constituted of only the positive sequence component in the dif- (100%), the load voltage value will be at least 95% of the nom-
ferent network buses. inal voltage. This result allows an improvement of one of the
It is important to emphasize that suitably coordinating the var- aspects of the supply quality, the stability of the real value of the
ious units of the OPEN UPQC allows for a wide compensation supply voltage, for all customers. Therefore, the OPEN UPQC
range, comparable with the UPS, but more economical. This co- works to stabilize the nominal voltage at the PCC. The phasor
ordination requires a communication system (i.e., based on the diagram of the OPEN UPQC is shown in Fig. 4.
carrier waves) between the series unit and the shunt units, but In order to avoid active power injections, the series voltage
this system cannot be very fast. Moreover, in transient analysis, has to be in quadrature with the mains current . The
the communication between the series unit and the shunt units value is reported in (1), and the grey areas in Fig. 4 indicate the
cannot be included (the communication could be slow, could be field of possible values
out of order, etc.). Therefore, each unit necessarily works alone.
The dynamic behavior of each individual device is described in
(1)
[3]–[10], and [15].

Authorized licensed use limited to: Abdul Shaik. Downloaded on October 10, 2009 at 03:57 from IEEE Xplore. Restrictions apply.
2110 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009

The current is primarily composed of the current of unpro-


tected loads (whose phase difference with respect to
cannot be varied) and the current of protected loads (whose
phase difference with respect to can be changed by the
shunt units) as reported in (2), where and are the
active and reactive power of the equivalent load , respec-
tively, and are the active and reactive power lines
losses, respectively, and is the reactive power injected by all
the shunt units

(2)
Therefore, the angle can oscillate between the upper
and lower limits and , obtained when
and respectively, in the area highlighted Fig. 5. Compensation limits of the OPEN UPQC: with nonactive power ex-
in Fig. 4. The angle can be calculated by the equation shown at change only (light gray) and with also active power exchange (dark gray) by the
shunt units.
the bottom of the page.
The current phasor can move along the black dotted line,
varying the reactive power of the shunt units. In case (a1) the OPEN UPQC to stabilize the voltage at the PCC, maxi-
in particular, it is possible to obtain a power factor equal to mizing the power factor in normal operation conditions and in-
1 in the section in low voltage situations, because the line creasing its compensation limits outside of normal operation.
intercepts the black dotted line. In case (a2), the Obviously, in the case of large disturbances in that the se-
power factor is always less than 1. ries unit cannot compensate, each shunt unit can supply the load
The quantities and can be obtained with (4) in back-up mode.
and (5), as shown at the bottom of the page.
Assuming that , the range am- B. Nonactive and and Active Power Exchange
plitude can be obtained with (6) In this case, the series converter produces only nonactive
power, but the shunt units can exchange active and nonactive
(6) power with the mains. This condition could be represented as
an active network into which dispersed generations are inserted.
It can be seen that the compensating range amplitude Fig. 5 depicts the new phasor diagram of the OPEN UPQC
depends on the value that the series under the above operating conditions.
unit can inject, and on the nonactive power . The nonactive In order to avoid active power injections by the series unit,
power is susceptible to exchanges by the shunt units (length the voltage and the mains current have to be in quadrature
of the black dotted line, proportional to the loads apparent with each other. In Fig. 5, the light grey areas indicate the field in
power) and to the power factors of the equivalent loads and which can lay without active power exchanges by the shunt
. units, and the dark gray areas indicate the possible values of
In normal operation mode, the compensation strategy can be with active power exchanges by shunt units. In this case, the
implemented in various ways. For example, power factor maxi- compensating range amplitude is greater than
mization in the s section (corresponding to minimization of the without active power exchanges, but it is important to note that
current ) is a compensation strategy that can be implemented the difference is small. The phasor current can move inside of
by coordinating the series unit and the shunt ones. Therefore, the gray dotted circle, varying the active and nonactive power
communication between all the units is required. The simplest of the shunt units (movement on the black dotted line regards
solution is to employ a slow communication system that allows only nonactive power exchange).

(3)

(4)

(5)

Authorized licensed use limited to: Abdul Shaik. Downloaded on October 10, 2009 at 03:57 from IEEE Xplore. Restrictions apply.
BRENNA et al.: NEW PROPOSAL FOR PQ AND CUSTOM POWER IMPROVEMENT: OPEN UPQC 2111

The dynamic response during transient events has not been


considered in this work, because it is described in detail in [15],
[17]. For example, considering the dynamic behavior of the se-
ries unit, it can be seen that the series unit cannot be affected by
the shunt units during a transient event. This is due to the fact
that the communication system between them is slow, and does
not allow a fast coordinated control strategy.
In order to compensate for the voltages in normal operation,
the strategy that maximizes the power factor (corre-
sponding to the current minimization) can be chosen. With
this choice, it is possible to minimize the apparent power re-
quired by the mains.
The mains current is reported in (2), and the compensated
voltage is
Fig. 6. Compensation limits of the OPEN UPQC: with nonactive power ex- (7)
change only (light gray) and with also active power exchange (dark gray) by the
series unit.
Neglecting power losses and considering that the voltage
C. Noncctive and and Active Power Exchange has to be in quadrature with the current , it is possible to write
the following relation:
In order to exchange active power with the mains, a storage
system connected to the dc section of the series unit is needed. (8)
The storage system size does not need to be very large, be-
cause little energy is required to compensate most of the dis- where is the equivalent reactance of the series unit, giving a
turbances For example, to compensate most of the voltage vari- voltage proportional to . Solving (7) and (8) is not mathemat-
ations reported in Fig. 2 (voltage sag 60% deep for 30 cycle) ically easy due to the nonlinearity of the problem, and imple-
for a 400-kW load, an energy equal to 120 kJ is needed, cor- menting them into a controller is not useful.
responding to a battery capacity of about 0.4 Ah at 96 V or a It is more convenient to implement two PI controllers: one to
capacitor or supercapacitor bank of about 1.5 F at 400 V. evaluate the voltage of the series unit, and another to evaluate
Given a storage system with twice the abovementioned ca- a signal related to the nonactive power that all of the
pacity, in order to allow bidirectional energy exchange with the shunt units have to inject.
mains, it is possible to compensate voltage disturbances in The conditions under which the series unit can exchange only
that are outside of the contractual limits. nonactive power can be obtained by applying the Park transform
In the case of mains interruptions lasting longer than 30 cy- to the three phase currents , and , and calculating
cles, the SS of the shunt units switch off, and the loads are sup- the two components and in a rotating reference frame,
plied in back-up mode. as reported in (9)
Considering compensation of transient disturbances, such as
voltage sags, swells, etc., various compensation strategies are
available for the OPEN UPQC, including minimizing the energy
required by the storage system of the series unit. The new phasor
diagram of the OPEN UPQC operation is shown in Fig. 6. In the (9)
light gray areas, the series voltage and the mains current
have to be in quadrature with each other, because active power
exchanges by the series unit are not allowed. In these areas, the where the angle is equal to and is the mains
behavior of the OPEN UPQC is the same as that of the cases frequency. Consequently, the components of the injected
described previously. voltage have to be proportional to the components of
In the case of transient disturbances, the series unit can com- the current , as follows:
pensate the voltage over a very large range (the compensating
range amplitude is ) compared with all the
cases previously analyzed. Indeed, the series unit can exchange (10)
active power with the mains in the dark gray areas, but this is For the constant to be independent of the load condi-
only possible for transient disturbances due to the small size of tions, the previous expressions must be normalized with respect
the series unit storage system. to the load current module
IV. CONTROL STRATEGY
The following describes a control strategy that can be em-
ployed in normal operation mode ,
under steady state conditions, and elucidates the device perfor- (11)
mance.

Authorized licensed use limited to: Abdul Shaik. Downloaded on October 10, 2009 at 03:57 from IEEE Xplore. Restrictions apply.
2112 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009

Fig. 8. System compensation structure.

TABLE I
MV/LV TRANSFORMER PARAMETERS

Fig. 7. Voltage control loop of the series unit and nonactive power control loop
of the shunt units in the OPEN UPQC system.

TABLE II
The constant is obtained by a PI controller that keeps LV CABLE PARAMETERS
the voltage at the output of the series unit equal to the
rated value , as reported in the block diagram of Fig. 7.
The second control loop acts to minimize the angle
between the voltage and the current downstream of the
MV/LV transformer, in order to maximize the power factor ab-
sorption in the section. In this case, the PI controller produces
a signal , which varies from 0 to 1, and is equal to the ratio
between the desired nonactive power injectable by the shunt
units and the maximum injectable nonactive power. This signal
is sent to all shunt units by the communication system. Thus,
the injected nonactive power of the th shunt unit is equal
to

(12) The protected loads are grouped into the equivalent load ,
so all of the shunt units are represented by means of an equiv-
where is the unit’s rated power. The total nonactive power alent unit. In the same way, all of the unprotected loads are
injected by all the shunt units is grouped in the equivalent load .
All of the parameters of the three-phase MV/LV transformer
used for the simulations are reported in Table I.
(13)
The LV cables used for the following analysis, with different
power factors and loads and , are reported in Table II.
Obviously, this compensation strategy, which is useful for its In each analysis, the correct 200-m cable is chosen as a func-
fast series unit response, requires nonactive power injection by tion of the current needed to supply the equivalent load with a
the shunt units to be capable of achieving a wide compensation voltage drop of less than 3%, without considering the OPEN
range. To enhance the entire system’s performance, the power UPQC. In this way, it is possible to neglect power loss and the
losses and the voltage drops in the LV lines generally must in- voltage drop on the LV grid.
crease. However, if the power factor at the is kept high In this study, all of the converters are represented as ideal
( 0.8), these increments are negligible. Moreover, this incre- controlled voltage or current sources. Moreover, the series unit
ment can be reduced by sending a different signal to each is not equipped with a storage system. For these reasons, the
shunt unit. This allows the closest shunt units to be used to inject OPEN UPQC limits are evaluated mainly in the normal oper-
more nonactive power, avoiding useless nonactive power flows. ation mode in the following. Therefore, the series unit cannot
exchange active power with the mains.
The following figures and tables report the power factor
V. TEST NETWORK AND EVALUATION OF OPERATION LIMITS
and the mains current in the section as functions
Fig. 8 shows a simplified 400-kVA LV grid, used to validate of the network voltage . Each diagram is represented for a
the OPEN UPQC. fixed load power factor and , and is parametric in . This

Authorized licensed use limited to: Abdul Shaik. Downloaded on October 10, 2009 at 03:57 from IEEE Xplore. Restrictions apply.
BRENNA et al.: NEW PROPOSAL FOR PQ AND CUSTOM POWER IMPROVEMENT: OPEN UPQC 2113

Fig. 9. Power factors of the system and maximum line currents in case 1, for Fig. 10. Power factors of the system and maximum line currents in case 2 for
different values. The maximum voltage of the series unit is equal to 0.6 p.u. different values. The maximum voltage of the series unit is equal to 0.6 p.u.

In the following, the maximum nonactive power injected by


parameter indicates the ratio between the apparent powers of
all the shunt units can reach the apparent power .
the total loads of shunt units and the total apparent power
In this case, if the control strategy can keep the voltage
of loads
equal to the nominal value, then these relations have to be true

(14) (16)

With a fixed , and therefore fixed , it is possible to calcu-


late as a function of the power factors of the loads
and
(17)

(15) The operation limits given by (16) and (17) were obtained by
The reference current is expressed in per unit (p.u.), as the using (3) and (15).
ratio between the power reference and the voltage refer- The figures reveal that:
ence. 1) the OPEN UPQC is well-adapted when the power factor
Since the network cables are correctly designed and their of the load is low. Fig. 9 shows the interval that can be
parameters are constant, the voltage drop variation when the compensated by exchanging only nonactive power when
OPEN UPQC is present can be neglected under maximum load the power factor of the load is equal to 0.8. In this case,
conditions when the load power factor is equal to 0.9 and it is the OPEN UPQC produces excellent voltage stabilization,
connected at the end of the line. especially when the parameter is greater than 0.4;
The operation limits reported in Figs. 9 and 10, which allow 2) the OPEN UPQC is not well-adapted when the power
the voltage to be fixed at the nominal value, were obtained factor of the load is high. Fig. 10 shows the interval
by assuming the above hypothesis and that the maximum in- that can be compensated by exchanging only nonactive
jectable voltage by the series unit is equal to 0.6 p.u.. power when the power factor of the load is equal to
The following results for the proposed solution were obtained 1. In this case, the OPEN UPQC does not produce good
by converting the vector diagrams of Fig. 4 into geometrical voltage stabilization, because it is too limited. It is possible
equations. to obtain voltage stabilization in normal operation mode

Authorized licensed use limited to: Abdul Shaik. Downloaded on October 10, 2009 at 03:57 from IEEE Xplore. Restrictions apply.
2114 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009

TABLE III TABLE IV


MAXIMUM AND MINIMUM MAINS VOLTAGE RANGE VARIATION THAT THE MAXIMUM AND MINIMUM MAINS VOLTAGE RANGE VARIATION THAT THE
SYSTEM CAN COMPENSATE, AS A FUNCTION OF THE MAXIMUM NONACTIVE SYSTEM CAN COMPENSATE, AS A FUNCTION OF THE MAXIMUM NONACTIVE
POWER THAT THE SHUNT UNIT CAN INJECT, WITHOUT CONSIDERING THE POWER THAT THE SHUNT UNIT CAN INJECT TO KEEP THE MAINS POWER
MAINS POWER FACTOR FACTOR BETWEEN 0.9 AND 1 (LIMITATIONS OF THE VOLTAGE DROP
IN THE LINE)

range (between 0.9 p.u. and 1.1 p.u.) only with a high
value.
From Figs. 9 and 10, it is possible to estimate the power of
the series unit, given the maximum current value. This value disturbances and network interruptions, while the ones that be-
is equal to the product between the maximum injectable voltage long to set only require general improvement of the power
(equal to 0.6 p.u.) and the maximum line current (equal to 1.1 quality.
p.u. when and as shown in Fig. 9). There- Several solutions are available for compensating each load
fore, with slight over-sizing of the series unit, good stabilization . In the following description, only two possible solutions are
of the mains voltage is possible. The usual working conditions considered. The first solution consists of the installation of an
present an interesting case, when the power factor of load is UPS for each end user, while the second one is the installation
between 0.9 and 1, and the mains voltage is inside of the con- of a shunt unit for each load.
tractual limits (normal operation). The distribution power losses Instead, in order to obtain general power quality improvement
should be estimated, in order to understand the energy cost as- for all loads, it is possible to rebuild the LV distribution system
sociated with this solution. to increase the short circuit level in the load connection point
Under these conditions, it is always possible to compensate or to install a series unit in the MV/LV substation. Therefore,
the voltage , without considering the power factor in section three different methods for improving the power quality have
, if is greater than or equal to 0.5, as reported in Table III. been considered:
In the case of smaller spread among the shunt units • installation of a UPS for each end user. In this case, it is
, it is always possible to compensate for the voltage by not possible to improve the power quality of the distribu-
decreasing the power factor in the section. However, the power tion network. However, it is possible to compensate for all
factor will always be greater than 0.8. When the power voltage disturbances for the end users;
factor of the load is equal to one, the power factor in the • revamping of all of the LV distribution cables. In this case,
section is always close to one, and the compensation limits it is not possible to compensate for all voltage disturbances;
previously mentioned can be maintained. • installation of an OPEN UPQC. In this case, it is possible
The mains voltage limits reported in Table III change to those to compensate for most of the voltage disturbances.
reported in Table IV when it is important to keep the mains The last solution consists of the installation of a series unit
power factor between 0.9 and 1. sized for 66% of the total power loads supplied (264 kVA), while
each shunt unit has an assumed size of 5 kVA. Moreover, each
VI. COST EVALUATION UPS is assumed to have the same power, and the input stage of
each UPS is composed of PFC rectifiers.
To evaluate the costs of power quality improvement and the It is important to clarify that the storage systems cost for
economic convenience of the proposed solution, an analysis of UPS and OPEN UPQC solutions in this analysis is not consid-
the 400-kVA LV distribution network has been carried out. ered, because it primarily depends on the technologies and au-
It was supposed that the line represents an equivalent line tonomies required. The revamping cost considered here can be
in which all of the sensitive loads that make up the OPEN found in the economical analysis carried out in [17].
UPQC are connected, while the line represents an equiva- The total cost for each solution is reported in Fig. 11. They
lent line that supplies only the nonsensitive loads . Therefore, include only the devices and various materials; the installation
each load that belongs to the set needs to be protected against cost is assumed to be 50% of the device cost.

Authorized licensed use limited to: Abdul Shaik. Downloaded on October 10, 2009 at 03:57 from IEEE Xplore. Restrictions apply.
BRENNA et al.: NEW PROPOSAL FOR PQ AND CUSTOM POWER IMPROVEMENT: OPEN UPQC 2115

TABLE V
OPEN UPQC UNITS ACTIONS

the P injection is possible only for few time and if necessary.

Fig. 11. Comparison between installation costs of a new line, of the OPEN
UPQC and of the UPS, as functions of the compensated sensitive loads power. availability of electrical distribution operators for an infield test
will be required.

Fig. 11 shows that to compensate for most of the disturbances ACKNOWLEDGMENT


in the whole network, installing the series unit only is a better The authors would like to thank the referees for their useful
solution than revamping all of the LV distribution system. To remarks, which helped to improve the paper.
compensate for the loads , it is necessary to install a UPS or
a shunt unit close to them, which increases the total cost as a REFERENCES
function of their power. [1] D. M. Divan, W. E. Brumsickle, G. A. Luckjiff, J. W. Freeborg, and
R. L. Hayes, “Realizing a nation-wide power quality and reliability
Referring to Fig. 11, it can be seen that the UPSs are a good monitoring system,” 2003. [Online]. Available: http://www.softswitch.
solution if only a few sensitive loads are present. However, if it com/docs/Realizing%20a%20Nationwide%20System%202003.pdf
is necessary to improve the power quality of the whole network, [2] J. M. Guerrero, L. Garcia de Vicuna, and J. Uceda, “Uninterruptible
power supply systems provide protection,” IEEE Ind. Electron. Mag.,
they become too expensive to use. They can only be more con- vol. 1, no. 1, pp. 28–38, Spring, 2007.
venient than the proposed OPEN UPQC if the total power of the [3] B. Wang, G. Venkataramanan, and M. Illindala, “Operation and control
sensitive loads is lower than about 80 kVA (20% of the total of a dynamic voltage restorer using transformer coupled H-bridge con-
verters,” IEEE Trans. Power. Electron., vol. 21, no. 4, pp. 1053–1061,
load) when, and only when, it is not necessary to increase the Jul. 2006.
PQ of the network. [4] D. M. Vilathgamuwa, H. M. Wijekoon, and S. S. Choi, “A novel
technique to compensate voltage sags in multiline distribution
VII. CONCLUSION system—The interline dynamic voltage restorer,” IEEE Trans. Ind.
Electron., vol. 53, no. 5, pp. 1603–1611, Oct. 2006.
The OPEN UPQC apparatus is a good compensation system [5] C. N. M. Ho and H. S. H. Chung, “Fast transient control of single-
if wide installation of shunt units is needed. An increase in the phase Dynamic Voltage Restorer (DVR) without external DC source,”
in Proc. 37th IEEE Power Electronics Specialists Conf., Jeju, Korea,
percentage of the protected load enhances the voltage stabi- Jun. 18–22, 2006, pp. 2105–2111.
lization interval over which the OPEN UPQC can significantly [6] M. R. Banaei, S. H. Hosseini, and M. D. Khajee, “Mitigation of voltage
improve the power quality, especially if the load power factor sag using adaptive neural network with dynamic voltage restorer,” in
Proc. 5th Int. CES/IEEE Power Electronics and Motion Control Conf.,
takes a high value. If the power factor of load is less than one, Shanghai, China, Aug. 14–16, 2006, vol. 2, pp. 1–5.
the power factor in section increases, to avoid nonactive power [7] A. Ghosh and G. Ledwich, “Compensation of distribution system
absorption from the mains. voltage using DVR,” IEEE Trans. Power Del., vol. 17, no. 4, pp.
1030–1036, Oct. 2002.
For low values of the parameter, the OPEN UPQC be- [8] M. K. Mishra, K. Karthikeyan, and P. K. Linash, “A development and
comes expensive if there are few shunt units. In this case, it is implementation of DSP based DSTATCOM to compensate unbalanced
better to install other compensation device typologies (as UPS, nonlinear loads,” presented at the IEEE Power India Conf., New Delhi,
India, Apr. 10–12, 2006.
UPQC, etc.) near the sensitive loads, and a nonactive compen- [9] B. Singh, A. Adya, A. P. Mittal, and J. R. P. Gupta, “Analysis, sim-
sator system near the nonsensitive loads if necessary. ulation and control of DSTATCOM in three-phase, four-wire isolated
It is possible to conclude that installation of the series unit is a distribution systems,” presented at the IEEE Power India Conf., New
Delhi, India, Apr. 10–12, 2006.
cost-effective way for distributors to improve the power quality [10] A. Ghosh and R. Gupta, “Frequency-domain characterization of sliding
level in the distribution networks in order to achieve the stan- mode control of an inverter used in DSTATCOM application,” IEEE
dards imposed by the authorities. Compensation improvement Trans. Circuits Syst. I, vol. 53, no. 3, pp. 662–676, Mar. 2006.
[11] G. Jianjun, X. Dianguo, L. Hankui, and G. Maozhong, “Unified power
for the sensitive end users can be achieved by installing a quality conditioner (UPQC): The principle, control and application,” in
shunt unit near them, instead of the more expensive UPS device. Proc. Power Conversion Conf. (PCC), Osaka, Japan, 2002, vol. 1, pp.
The OPEN UPQC working conditions are reported in Table V. 80–85.
[12] R. Faranda, E. Tironi, I. Valadè, and D. Zaninelli, “Power quality im-
At this moment, the OPEN UPQC study is still under investi- provement using series electronic reactor and shunt power conditioner,”
gation. The dynamic behavior, considering changing operating in Proc. Int. Symp. and Exhib. Electric Power Engineering at the Be-
modes, of a 5 kW prototype shunt unit is developed and experi- ginning of the Third Millennium, Capri, Italy, May 12–18, 2000.
[13] M. Brenna, R. Faranda, and E. Tironi, “OPEN UPQC able to improve
mental results are presented in [18]. As shown in Fig. 11, large power quality of network and loads,” in Proc. Int. Congr. Electricity
investments are needed to analyze the completed solution, and Distribution, Buenos Aires, Argentina, Nov. 27–29, 2006.

Authorized licensed use limited to: Abdul Shaik. Downloaded on October 10, 2009 at 03:57 from IEEE Xplore. Restrictions apply.
2116 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009

[14] M. Buschmann, G. Linhofer, P. Maibach, and O. Suter, “Voltage source Roberto Faranda (M’06) received the Ph.D. degree in electrical engineering
converter based power quality solutions,” in Proc. Asia Pacific Regional from the Politecnico di Milano, Milan, Italy, in 1998.
Power Quality Seminar, Putrajaya, Malaysia, Mar. 28–31, 2005. He is an Assistant Professor with the Department of Energy, Politecnico di
[15] F. Blaabjerg, M. Newman, H. Nielsen, and J. G. Nielsen, “Control and Milano. His areas of research include power electronics, power system har-
testing of a dynamic voltage restorer (DVR) at medium voltage level,” monics, power quality, power system analysis, and distributed generation.
IEEE Trans. Power Electron., vol. 19, no. 3, pp. 806–813, May 2004. Dr. Faranda is a member of the Italian Standard Authority (CEI), the Italian
[16] K. N. Choma and M. Etezadi-Amoli, “The application of a Electrical Association (AEI), and the Italian National Research Council (CNR)
DSTATCOM to an industrial facility,” in Proc. IEEE Power Eng. Group of the Electrical Power System.
Soc. Winter Meeting, Jan. 27–31, 2002, vol. 2, pp. 725–728.
[17] A. Agustoni, E. Borioli, M. Brenna, G. Simioli, E. Tironi, and G.
Ubezio, “LV DC distribution network with distributed energy re-
sources: Analysis of possible structures,” presented at the 18th Int. Enrico Tironi received the M.S. degree in electrical engineering from the Po-
Conf. Electricity Distribution CIRED 2005, Turin, Italy, Jun. 6–9, litecnico di Milano, Milan, Italy, in 1972.
2005. He then joined the Dipartimento di Elettrotecnica, Politecnico di Milano,
[18] R. Faranda, F. Castelli Dezza, I. Mazzucco, P. Redi, and E. Tironi, where he is a Full Professor. His areas of research include power electronics,
“An interface converter for DG/storage system able to improve power power quality, and distributed generation.
quality of the load,” presented at the IEEE Power Eng. Soc., Montreal, Dr. Tironi is a member of the Italian Standard Authority (CEI), the Italian
QC, Canada, Jun. 18–22, 2006. Electrical Association (AEI), and the Italian National Research Council (CNR)
group of the Electrical Power System.
Morris Brenna (M’06) received the M.S. and Ph.D. degrees in electrical engi-
neering from the Politecnico di Milano, Milan, Italy, in 1999 and 2003, respec-
tively.
Currently, he is an Assistant Professor with the Department of Energy, Po-
litecnico di Milano. His research interests include power electronics, distributed
generation, traction systems, and electromagnetic compatibility.
Dr. Brenna is a member of the Italian Electrical Association (AEIT) and
Italian Railways Engineering Association (CIFI).

Authorized licensed use limited to: Abdul Shaik. Downloaded on October 10, 2009 at 03:57 from IEEE Xplore. Restrictions apply.

You might also like