Professional Documents
Culture Documents
This specification has been revised as indicated below and described in the revision record on the following
page. Please destroy all previous revisions.
Lead Engineer
Engineering Manager:
Client Approval:
Record of Revisions
Revision Date Description
No.
TABLE OF CONTENTS
FOREWORD................................................................................................................................................. 4
1 Scope ............................................................................................................................................... 5
1.1 Alternative Designs .......................................................................................................................... 5
1.2 Conflicts ........................................................................................................................................... 5
2 References....................................................................................................................................... 5
2.2 Compliance ...................................................................................................................................... 5
3 Definitions ........................................................................................................................................ 5
4 Basic Design .................................................................................................................................... 6
4.1 General ............................................................................................................................................ 6
4.2 Pressure Casings............................................................................................................................. 6
4.3 Combustors and Fuel Nozzles ........................................................................................................ 9
4.4 Casing Connections ......................................................................................................................... 9
4.5 Rotating Elements............................................................................................................................ 9
4.7 Dynamics ...................................................................................................................................... 10
4.8 Bearings and Bearing Housings .................................................................................................... 10
4.9 Lubrication...................................................................................................................................... 10
4.10 Materials......................................................................................................................................... 11
5 Accessories.................................................................................................................................... 11
5.1 Starting and Helper Driver ............................................................................................................. 11
5.2 Gears, Couplings and Guards ....................................................................................................... 12
5.3 Mounting Plates ............................................................................................................................. 13
5.4 Controls and Instrumentation......................................................................................................... 14
5.5 Piping and Appurtenances............................................................................................................ 18
5.6 Inlet Coolers .................................................................................................................................. 21
5.7 Insulation, Weatherproofing, Fire Protection and Acoustical Treatment ....................................... 22
5.8 Fuel .......................................................................................................................................... 23
5.9 Special Tools ............................................................................................................................ 27
6 Inspection, Testing and Preparation for Shipment......................................................................... 27
6.1 General ......................................................................................................................................... 27
6.2 Inspection....................................................................................................................................... 27
6.3 Testing.. ......................................................................................................................................... 28
6.4 Preparation for Shipment.. ............................................................................................................. 30
7 Vendor’s data ................................................................................................................................. 30
7.2 Proposals ....................................................................................................................................... 30
7.3 Contract Data ................................................................................................................................ 31
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 4 of 31
Revision 1
FOREWORD
This specification is intended to supplement API Standard 616, 4th Edition, August 1998, which is part of
this specification. Paragraph numbers of this specification correspond to those in API 616 4th Edition.
Paragraph numbers not found in API 616 4th Edition are new paragraphs.
Paragraphs shall be highlighted as shown below to indicate the type of change from the API Standard:
The data sheet is an integral part of the specification. Bulleted items in the specification have been
addressed on the data sheets.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 5 of 31
Revision 1
1 Scope
(Addition) Gas Turbines units manufactured and packaged to this specification shall comply to
API 616, 4th Edition except as modified herein or as set forth in the Data Sheets or Project
Specifications or the Purchase Order.
(Addition) The gas turbine package shall be the Manufacturer’s standard design to the maximum
extent possible. The Vendor shall fully describe their exceptions to this Engineering Standard.
The Vendor may submit an alternative proposal incorporating the latest technology features for
evaluation by the Owner’s Engineer in accordance with Page 1, Paragraph 2.2 of this Standard.
1.2 Conflicts
(Modification) Should conflicts exist between this specification and other documents, the following
order of precedence shall govern:
a. Purchase Order
b. Data Sheets
c. Diagrams, Drawings and Schematics
d. This Specification
e. API 616 4th edition
f. Other Referenced Specifications
2 References
2.2 Compliance
(Modification) The equipment shall comply with the local codes and regulations for the Royal
Commission, Kingdom of Saudi Arabia.
3 Definitions
3.55 (Add) Base Load is the Vendor’s defined output limit required to achieve, as a minimum,
the operating life of 20 years and a Time Between Overhaul (TBO) of 48,000 fired hours.
3.56 (Add) Peak Load is the Vendor’s defined output limit required to achieve, as a minimum,
a TBO of 2000 fired hours.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 6 of 31
Revision 1
4 Basic Design
4.1 General
The two gas turbines shall have been in continuous operation for a minimum of 8,000
fired hours each and shall have performed satisfactorily throughout their operation. Major
damage to the compressor/turbine rotors or stationary parts in the combustion air/hot gas
path shall constitute cause for disqualification.
Proof of compliance with the above requirements shall be submitted to the Purchaser
with the equipment proposal for approval by the Owner’s Engineer.
Where the Vendor qualification requirements above prevents the application of the latest
technology, the Vendor shall submit a second alternative proposal incorporating the latest
technology features for evaluation by the Owner’s Engineer. This alternative proposal
shall specifically identify the undemonstrated by experience features and state their
advantages.
4.1.3 (Decision) The Purchaser will specify the normal duty dry bulb temperature, relative
humidity, and barometric pressure on Page 1, Lines 19, 20, and 21 respectively of the
Combustion Gas Turbine Data Sheets. Unless otherwise specified, the certified point on
Page 1, Line 30 of the Data Sheets shall be at normal duty.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 7 of 31
Revision 1
4.1.4 (Substitution) Gas turbine units shall be suitable for periods of idleness of several months
duration under the specified site conditions, without requiring any special maintenance
procedures.
4.1.5 (Addition) In sizing gas turbine drivers to drive generators the following practice shall be
applied:
a. The gas turbine vendor shall state their guaranteed generator terminal output site
rating of the turbine-gear (if required)-generator assembly based upon the following
conditions:
Note: It is a normal practice that Gas Turbine Vendors quote a guaranteed generator
terminal output site rating with all internal losses accounted for, including the driven
generator.
b. The gas turbine Vendor’s guaranteed generator terminal output site rating will be
further de-rated as follows:
(1) A de-rating of 2 percent (a 0.98 multiplier) shall be allowed when a gear box is
required.
(2) A de-rating of 2 percent (a 0.98 multiplier) shall be allowed for fouling and erosion of
the gas turbine compressor and the resulting loss in efficiency.
(3) A de-rating of 4 percent (a 0.96 multiplier) shall be allowed for long term gas turbine
deterioration.
The resulting de-rated generator terminal site rating in kWe will assure that the gas
turbine driver is capable of providing the necessary power to the generator until an
overhaul is required.
4.1.8 (Decision) The Vendor shall state in their proposal, the guaranteed maximum emission
levels of NOx, CO, and unburned hydrocarbons for both their standard combustion
system and their dry low NOx combustion system using the Purchaser supplied fuel gas
properties. The Vendor shall provide a cost adder for their dry low NOx combustion
system.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 8 of 31
Revision 1
4.1.9 (Decision) The design to permit steam or water injection is not required.
4.1.10 (Decision) The sound level within one meter of the combustion gas turbine package
boundary shall not exceed 85 dBA. See Page 1, Column 2, Lines 32 through 37 of the
Data Sheets.
4.1.11 (Substitution) Cooling water will not be available for equipment at the plant site.
4.1.12 (Addition) The Gas Turbine Supplier shall review and comment upon the proposed
arrangement of the installation, in particular the arrangement of the fuel gas supply piping
and appurtenances, the drive train and coupling arrangement, the inlet and exhaust
ducting lay-outs, the base plates and foundations, and the controls and instrumentation
provided.
4.1.14 (Decision) Unless otherwise specified, the equipment supplied shall be suitable for NEC
500 Class I, Group D, Division 2, Temperature Code T3 electrical area classification
(Page 1, Column 2, Lines 21, 22, and 23 of the Data Sheets).
4.1.19 (Substitution) Unless otherwise specified, the equipment including all auxiliaries shall be
designed for outdoor installation.
4.2.9 (Addition) Provisions for operational balancing of the coupling between the gas turbine
and load in the field shall be also provided. Field balancing by adding weights to
couplings is prohibited.
4.2.10 (Addition) Power turbine and exhaust gas diffuser turbine casing shall preferably be
horizontally –split design arranged to allow the removal of the upper casing and rotor
removal from above.
4.2.12 (New) The casing shall have valved connections to be used for injection and/or drainage
of liquid for on-line and off-line washing. Each drain shall be isolated by a flanged ball
valve, be accessible and terminate at the edge of the base plate.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 9 of 31
Revision 1
4.3.7 (Decision) Based upon the properties of the fuel gas specified, the Manufacturer shall
advise of the corresponding Modified Wobbe Index Number and the allowable variations
of the Modified Wobbe Index Number along with the corresponding temperatures.
4.3.8 (New) Removal of combustion liners (baskets) and transition pieces in heavy duty
industrial units shall not require disassembly of the combustion casing.
4.3.9 (New) An automatic drain valve shall be provided at the lowest point of the combustion
casing to drain any liquid that may enter the combustion casing when the unit is
shutdown. A manual valve shall also be provided in the drain line at a readily accessible
point. The drain line will be routed to a non-pressurized sewer.
4.4.1 (Decision) Unless otherwise specified, the air inlet and exhaust connections shall be
flanged and oriented vertically up (Page 5, Lines 57 and 58 of the Data Sheets).
4.4.5.4 (Addition) Mating flanges for non-standard flanges shall be supplied complete with
gasket, studs and nuts, and be shipped bolted to the casing connections.
4.4.7 (Addition) All drainage shall be through low point drains, terminated at skid edge with
valves and blind flanges.
4.5.1 Shafts
4.5.1.1 (Addition) In the event of an order for a number of gas turbines, all of the same rating, all
rotors shall be interchangeable.
4.5.3.3 (Decision) The Vendor shall provide Campbell and Goodman diagrams of the blading for
all turbine engine models being proposed having less than 50,000 fired hours of
operating experience.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 10 of 31
Revision 1
4.7 Dynamics
4.7.1.2 (Decision) Data and reports of rotor dynamic analysis and testing, following the
guidelines found in Paragraphs 4.7.1.2.1 through 4.7.1.2.3, shall be provided for
proposed turbine engines having less than 50,000 fired hours of operating experience.
4.7.3.5 (Decision) The Vendor having unit responsibility shall perform a torsional vibration
analysis of the complete coupled train and shall be responsible for directing and providing
the modifications necessary to meet the requirements of Paragraphs 4.7.4.1 through
4.7.4.4.
4.8.1 General
4.8.1.1 (Addition) Hydrodynamic bearings shall be equipped with temperature sensing devices.
4.9 Lubrication
4.9.2 (Decision) Synthetic lubrication oil shall be used for aeroderivative type gas turbines.
Mineral based lubricating oil shall be used for all industrial type gas turbines.
4.9.5 (Decision) Industrial type gas turbine driven trains shall have an integrated combined
mineral oil based lubricating oil system. Compression trains shall use dry gas seals and
consequently seal oil systems will not be required. Aeroderivative type gas turbine driven
trains shall have separate synthetic and mineral oil based lubricating systems, with the
synthetic oil system lubricating the aeroderivative gas turbines and the mineral oil based
lubricating system lubricating the driven equipment.
4.9.6 (Substitution) The gas turbine shall be furnished with a complete system to provide
lubricating and control oil at pressure, for the gas turbine and driven equipment.
Lubrication systems shall generally in accordance with API Standard 614 Chapters 1 and
2, and the data sheets.
4.9.8 (Decision) Unless otherwise specified, the lubricating oil characteristics for the train shall
be in accordance with ISO Grade 32, as specified in ISO 3448 (Page 10, Column 2, Line
4 of Data Sheets).
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 11 of 31
Revision 1
4.10 Materials
4.10.1 General
4.10.1.1 (Addition) Copper and copper alloys are prohibited except for bearings pads only.
4.10.1.12(Addition) Materials for components in contact with gases containing hydrogen sulfide
shall conform to the requirements of NACE standard MR0175.
4.10.2 Castings
4.10.2.3 (Addition) Approval shall be obtained from the MARAFIQ before any major weld repair is
carried out. The Supplier's repair procedures shall be approved by the Contracting
Authority.
4.10.4 Welding
4.10.4.6.1(Decision) The Vendor shall use their standard inspection practice for welds. The
Vendor shall submit their standard practice for inspection of welds with their proposal
for review by the Purchaser.
4.10.5.3 (Decision) The minimum design metal temperature used to establish impact test
requirements shall be the site minimum temperature specified on Page 10, Line 34 of
the Data Sheets or –6.67°C (20°F), which ever is less.
5 Accessories
5.1.1 General
5.1.1.1 (Decision) Unless otherwise specified, the starting device shall be electrohydraulic. An
electric motor shall drive a hydraulic pump, which in turn will transmit hydraulic power to
start the combustion gas turbine. Helper drivers are not required.
5.1.1.5 (Decision) The starting motor’s starting torque requirements shall be met at 80 percent of
the normal voltage, specified on Page 5, Column 1, Line 19 of the Data Sheets.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 12 of 31
Revision 1
5.1.1.6 (Decision) The electric starting motor shall be provided per the MARAFIQ motor
specifications:
5.1.1.10 (Addition) Starting equipment located within the combustion air inlet plenum shall have
all bolts and fastenings wire-locked to prevent inadvertent loosening or detachment.
5.1.1.11 (New) The gas turbine shall be capable of an immediate hot start at anytime after trip for
three consecutive start attempts. If this can not be achieved, the Vendor shall specify,
with the proposal, the idle times required by the turbine due to the most severe operating
condition. The Client shall be consulted regarding any agreement related to restart
limitations.
5.1.2 Ratings
5.1.2.1 (Addition) Starting driver ratings shall allow the continuous cranking for crank-soak
washing of the gas turbine air compressor, followed by three consecutive starts.
5.1.3.1 (Decision) A turning gear or ratchet device shall be furnished by the Vendor where the
turbine shaft requires rotation to avoid shaft thermal distortion during startup or
immediately following a shutdown. When a turning gear is furnished, it shall be
automatically engaged. Unless otherwise specified, any turning equipment furnished
shall be driven by a DC electric motor.
5.2.1 Gears
5.2.1.1 (Decision) Any load gear to be mounted on the gas turbine base shall be provided by the
Turbine Vendor. Load gear to be mounted on the driven equipment base shall be
provided by the driven equipment Vendor. When the gas turbine base and the driven
equipment base is integral, the Vendor having unit responsibility shall provide any
required drive gear
5.2.1.4 (Addition) Auxiliary drives which are not part of a particular configuration shall be
removed from the gas turbine. Gears and bearings running unloaded while the gas
turbine is running are not permitted.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 13 of 31
Revision 1
5.2.2.3 (Addition) Coupling hubs shall be removable, tapered bore, and hydraulically fitted.
Keyed couplings are unacceptable.
5.2.2.5 (New) Couplings shall be dry flexible diaphragm type, type load couplings using hydraulic
fit of the hubs to tapered shaft ends is preferred, Lucas Bendix or Purchaser approved
equal. Alternatively couplings may be flange mounted.
5.2.2.6. (Addition) Spacers of adequate length shall be provided to allow the removal of coupling
hubs and driven equipment bearings and seals without disturbing the shafts.
(New) When required as a result of the dynamic analysis, reduced moment couplings
may be used.
5.2.2.8 (New) The coupling guards shall have an internal dam at the approximate axial mid point
of the guards with drains and sight glasses on each side of the dam. The drains may be
combined downstream of the two drain sight glasses. The drain size shall be 2NPS (50
mm) as a minimum.
5.2.2.9 (New) The fully enclosed coupling guards shall be furnished with a vent connection fitted
with the Vendor’s standard breather. The vent size shall be 2NPS (50mm) as a
minimum.
5.3.1 General
5.3.1.2.9(Substitution) The Vendor shall furnish AISI 316 stainless steel shim packs, 3 to 13
millimeters (1/8 to ½ inch) thick between the equipment feet and the mounting plates.
Laminated shim packs are unacceptable. All shim packs shall straddle the hold-down
bolts and vertical jackscrews and be at least 6 millimeters (¼ inch) larger on all sides
than the footprint of the equipment.
5.3.2.1 (Decision) The gas turbine unit, including starting equipment, lubrication system, and
other auxiliaries shall be furnished on one integral base plate as a minimum. The gas
turbine unit, including starting equipment, lubrication system, other auxiliaries, and the
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 14 of 31
Revision 1
driven equipment may be integrated on one single integrated base plate. When multi-
section base plates are supplied for drivers and driven equipment, they shall have
machined and doweled mating surfaces to ensure accurate field assembly.
5.3.2.3 (Substitution) Machined pads shall be provided on all base plates to facilitate the use of
either laser and or other optical alignment tools. The machined pads shall be protected
with removable covers.
5.3.2.4 (Decision / Add) The base plate shall be suitable for column mounting. Aeroderivative
gas turbines shall be three point mounted on the base plate.
5.3.2.7 (Substitution) The mounting pads on the bottom of the base plate shall be in one plane to
permit the use of a single-level foundation. When imbedded subplates are recommended
by the Vendor, the Vendor shall provide the subplates. When the Vendor’s recommended
method of mounting is the grouting of the single mounting pads (not with the matching
subplates) on the bottom of the base plate, the subplates are not required and will not be
supplied by either the Vendor or Purchaser.
5.3.2.12 (Addition) All equipment supports and pedestals shall be fitted with horizontal jacking
screws and vertical leveling screws to facilitate alignment.
5.4.1 General
5.4.1.1 (Addition) All controls and instrumentation, including alarm and shutdown sensing
devices, shall be installed with sufficient valving for isolation to permit testing and removal
with the system in operation.
5.4.1.5 (Submission) The control system shall be electronic, microprocessor based. When
possible, the gas turbine control shall be integral with and common to the driven
equipment load control. The Vendor’s proposal shall state the degree of redundancy of
their standard control system.
5.4.1.6 (Decision) The control system shall be designed to maintain normal turbine operation and
protection in the event AC power is interrupted.
5.4.1.7 (New) A bypass shall be provided to allow maintenance of single unspared items, such
as control valves and traps, without interrupting operation. The fuel governor, starting,
and shutoff valves shall not be bypassed.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 15 of 31
Revision 1
5.4.1.8 (Addition) The complete control program shall be available to Purchaser. It shall be field
reprogrammable, except for certain critical functions that may be protected by the
Supplier with the agreement of MARAFIQ.
5.4.2.1 (Substitution) The normal starting sequence shall be automatic. The turbine control
system shall be configured for remote and local starting.
5.4.2.2 (Substitution) The control system shall provide air path purging in accordance with the
following:
a. For simple cycle systems, the purge period shall be sufficient to displace the volume
of the exhaust system (turbine, exhaust duct, and exhaust stack) a minimum of six
times before firing the unit.
b. For exhaust heat recovery systems, the purge period shall be adjusted to satisfy the
Vendor specified purge requirements for the waste heat recovery device. In no case
shall the purge period be less than is sufficient to displace the volume of the exhaust
system (turbine, exhaust duct, waste recovery device, and exhaust stack) a minimum
of six times before firing the unit.
5.4.3.1 (Addition) Electronic governors shall be provided. The electronic governors shall have
triple input sensors, triple processor redundancy, and use 2 out of 3 voting logic.
5.4.3.6 (Addition) The governor system shall prevent a turbine speed increase beyond the
specified over speed limit (5.4.4.6 Add) upon load coupling failure.
5.4.4.2.a (Addition) The normal shutdown sequence shall be fully automatic. However, it shall be
possible to stop the unit manually, if required.
5.4.4.3 (Addition) Fuel shutoff valves shall have a remote shutdown actuator device and a partial
stroke feature to permit checking the operability of the shutoff valve during normal
operation of the gas turbine.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 16 of 31
Revision 1
5.4.4.4 (Addition) The vent from this valve shall not be connected to any other venting or blow-
down system.
5.4.4.6 (Addition) The over speed trip system shall be independent of the governor system. A
triple redundant electronic over speed trip system with three shaft probes and two out of
three voting logic shall be provided. In the case of multiple shafts, each shaft shall have
its’ own over speed trip protection system. The over speed trip system shall allow on-line
testing without over speeding the turbine. Over speed alarm and trip speeds shall be
specified by the Vendor.
5.4.4.9 (Substitution) All instruments and controls, including alarm and shutdown sensing
devices, shall be installed with sufficient valving for isolation to permit testing and removal
while the turbine is operating. The Vendor shall provide a means of locking the valves in
the open position.
5.4.5.1 (Substitution) Each gas turbine driver shall be controlled from its own dedicated gas
turbine control panel which will be located by others in an air conditioned room. Each
gas turbine package shall be suitable for remote, unattended operation. The control panel
shall include the operating parameters of all the equipment train components including
the driven equipment and common lubrication system.
5.4.5.4 (New) The arrangement, grouping, and number of instrumentation and control panels
shall be in accordance with the Vendor’s standard. However, the installation of these
panels shall be in a remote air conditioned cabin located in the vicinity of the unit.
Instrumentation and controls for the driven equipment shall also be installed in the same
air conditioned cabin. The Vendor shall provide a detailed description or listing of all
instruments and controls required.
5.4.6.1 (Decision) Auxiliary motors shall be 480 Volts AC, 3-Phase, 60 HZ in accordance with the
MARAFIQ Motor specification. Lube oil heaters of 1 kW or larger shall be 480 Volts AC,
3-Phase, 60 HZ. Lube oil heaters of less than 1 kW shall be 120 Volts AC, 1-Phase, 60
HZ. Motor space heaters shall be 120 Volts AC, 1-Phase, 60 HZ. All motor space
heaters shall be rated at 240 Volts AC but sized for 120 Volts AC operating voltage.
5.4.6.2 (Decision) Electrical equipment on the turbine and in the turbine enclosure if provided,
shall be suitable for NEC Class I, Group D, Division 2, Temperature Code T3 electrical
area classification. Arcing and sparking devices, including equipment such as switches,
relays, solenoid valves, alarm horn, and tachometer, shall be as follows:
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 17 of 31
Revision 1
5.4.6.6 (Decision) Electrical materials shall be protected from fungus attack and unpainted
surfaces protected from corrosion in accordance with Paragraphs 5.4.6.6.1 and 5.4.6.6.2.
5.4.7 Instrumentation
5.4.7.2.2 (Decision) The tachometer shall be electronic digital display type, Liquid Crystal Display
(LCD) with background illumination or similar.
(Addition) Over temperature protection shall be independent from the turbine combustion
temperature control. Six thermocouples per gas turbine engine shall be placed around
the turbine exhaust gas frame to measure exhaust gas temperatures. Alarm and trip
exhaust temperature settings for the average exhaust gas temperatures sensed by the
thermocouples shall be specified by the Vendor. Any chromel-alumel thermocouples
used for actuation of exhaust temperature shutdowns shall be pre-aged. Thermocouple
heads and leads shall not be exposed to temperatures greater than 50°C.
(Addition) Heavy duty industrial turbines engines shall have two wheel space
thermocouples per wheel space. The thermocouples shall be replaceable during
operation. The alarm setting for the maximum allowable wheel space temperature shall
be specified by the Vendor.
(Addition) Aeroderivative turbine engines shall have two wheel space thermocouples
located downstream of the last turbine wheel. The thermocouples and conduits shall be
as small as possible. They shall use the turbine exhaust casing struts for assembly and
mounting. Disturbance of the air and hot gas flow due to this installation shall be
insignificant.
(Addition) For heavy duty industrial gas turbine engines, bearing lubricating oil drain
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 18 of 31
Revision 1
thermocouples shall be provided for each bearing drain. Lubricating oil drain
thermocouples shall be used for alarm and emergency shutdown. Hydrodynamic thrust
and radial bearings shall have a replaceable RTD installed in the pad that is expected to
carry the greatest load.
5.4.7.8.1 (Addition) Vibration measurement and monitoring of heavy duty industrial gas turbine
engines shall be provided on the bearings, providing the operating temperature does not
exceed instrumentation operating limits. The following instrumentation shall be provided:
5.4.7.8.2 (Decision) Vibration and axial position monitors shall be supplied and installed in
accordance with API Standard 670.
5.5.2.3 (Addition) All oil supply and return piping shall be seamless type 304L stainless steel.
All pipe fittings, oil tanks and appurtenances, excluding the filter bodies, filter change over
valve bodies, and the bodies of isolation and control valves, shall be type 304L stainless
steel.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 19 of 31
Revision 1
5.5.3.1 (Decision) See Paragraph 5.5.4.1 for the decision on the type of filter.
5.5.3.3 (Decision) The inlet system shall be designed for a maximum pressure drop of 100 mm
water column with a dirty filter at 110 percent of the air flow at site rated power. The
exhaust system shall be designed for a maximum pressure drop of 100 mm water column
for a simple cycle system and a maximum pressure drop of 300 mm water column for
exhaust systems recovering exhaust heat.
5.5.3.4 (Decision) The Purchaser will specify the normal dust loading, wind design velocity, and
seismic zone on Page 9, Column 1, Lines 15, 16, and 18 of the Data Sheets respectively.
The Purchaser will specify any unusual conditions such as dust, fumes, and corrosive
agents on Page 1, Column 2, Lines 29 through 32 of the Data Sheets
5.5.3.9 (Decision) When a single unique gas turbine package is being purchased, the Vendor
shall supply a fixed integral-to-package compressor cleaning system. When multiple
units are being purchased, the Vendor shall supply a single portable compressor cleaning
system that may be used to clean any of the compressors within the purchased lot. The
Vendor shall describe the compressor cleaning system being supplied in their proposal,
along with the cleaning fluid specification, the amount of fluid required to clean the
compressors, and cost data per compressor cleaning operation.
(Addition) Water wash equipment shall be supplied and designed for both on-line and off-
line crank washing. The necessary equipment safeguards shall be incorporated into the
unit controls where feasible (e.g. temperature limits on washing and control over the
duration/quantity of wash fluids injected).
5.5.4.1 (Decision) The air inlet filtration system shall be the Supplier's standard design for
prevailing site conditions, and shall incorporate a self cleaning facility using pulse air. The
filter media shall be adapted to site conditions (onshore, desert conditions). Compressed
air shall be supplied from the air compressor section of the gas turbine, including
associated equipment, piping and controls (Page 9, Column 1, Lines 9, 12 and 13 of the
Data Sheets).
5.5.4.2 (Decision) A mist eliminator is not required and shall not be furnished.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 20 of 31
Revision 1
5.5.4.5 (Decision) Implosion doors are not deemed to be necessary for the self-cleaning air inlet
filter design. Supplier design shall address the safety from implosion risk using redundant
instrumentation shutdowns.
5.5.4.6 (Decision) When practical, the filter house shall be mounted on top of the gas turbine
enclosure with the enclosure and framing providing support for the filter house. When the
above is not practical, the Purchaser will provide the required independent supporting
steel work.
5.5.4.8a.(Addition) The inlet filter house shall be constructed from 316 Stainless Steel materials
with a minimum Molybdenum content of 2.5 percent. Coating of the inlet filter house is
not required.
5.5.5.1.4 (Substitution) Inlet silencer perforated plate elements shall be constructed of 316
stainless Steel with a 2.5 percent minimum Molybdenum content, except for use in
corrosive environments that may promote stress corrosion cracking. When perforated
plate elements are exposed to corrosive environments, the Vendor shall recommend and
supply upgraded materials which meet the design life criteria.
5.5.5.2.3 (Decision) When the exhaust silencer perforated plates or sheets are exposed to
corrosive environments, the Vendor shall recommend and supply upgraded materials
which meet the 20 year life criteria.
5.5.5.2.5 (Decision) Supporting lugs for the exhaust stack shall be provided near the exit side of
the exhaust silencer and/or the waste heat recovery unit by the Vendor. These support
locations will be determined during detailed engineering and will be depicted on the
drawings during the approval stage by the Design Contractor. Lifting lugs for the
exhaust silencer and/or the waste heat recovery unit shall be provided by the Vendor
and located on the approval drawings.
5.5.6 Ducting
5.5.6.8 (Decision) An atmospheric relief device shall be provided in the exhaust duct upstream of
any isolation damper or any diverter valve used to modulate waste heat recovery.
Routing of the atmospheric relief device discharge shall be to a safe area not normally
accessible to personnel.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 21 of 31
Revision 1
5.5.6.10(Decision) Emissions sampling ports shall be provided in the exhaust ducting along with
necessary access ladders and platforms.
5.5.6.11(New) The exhaust stack provided by the Vendor shall be covered with insulation and
liquid tight metal jacketing to limit the skin surface temperature to 230°C. The Vendor
shall also supply any required extensions to the supporting structure and safety
provisions for personnel protection. The turbine casing and exhaust ducting shall be
insulated for personnel protection to the 74°C surface temperature limitation in
accordance with Paragraph 5.7.1.1.
5.5.6.12 (New) The exhaust plenum and exhaust silencer shall be made of 309 Stainless Steel or
better materials.
5.5.6.13 (New) Thermal insulation shall be installed inside the exhaust plenum walls to maximize
plenum life.
5.5.6.14 (New) The exhaust plenum shall be provided with an access door to facilitate inspection.
5.5.6.15 (New) The exhaust plenum shall have a connection, with double block valves, for
sampling exhaust gas.
5.5.6.16 (New) A pressure indicator shall be provided to measure pressure at the turbine exhaust
plenum.
5.6.1.1 (Decision) Evaporative coolers are not required and shall not be supplied.
5.6.1.5 (Decision) Since evaporative coolers are not required, the walkways, hand rails, and
access ladders required to service the evaporative coolers are not required.
5.6.2.1 (Decision) Liquid-to-air heat exchangers to cool the inlet air for engine performance
enhancement are not required and shall not be supplied.
5.6.2.3 (Delete) (Comment: Since inlet air cooler heat exchangers are not required, the
referenced paragraph is not applicable.)
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 22 of 31
Revision 1
5.7.1 Insulation
5.7.1.2 (Decision) Insulation for heat conservation is not required and shall not be supplied.
5.7.2 Weather-proofing
5.7.2.1 (Addition) The gas turbine shall be provided with a weather-proof positively pressurized
enclosure designed to meet the prevailing site ambient conditions, noise attenuation
requirements and hazardous area classification.
The enclosure(s) shall be constructed from carbon steel and painted. All associated
fittings (internal and external) shall be manufactured from type 316L stainless steel.
Fuel gas piping within the enclosure shall, as far as practicable, be of all welded
construction.
The enclosure shall be furnished with all necessary lifting equipment to facilitate routine
maintenance of the equipment, including items used outside the enclosure.
The Supplier shall furnish with the bid details of the analyses and acceptance testing
(including acceptance criteria) carried out to verify the ventilation air flow within the
enclosure.
5.7.3.1 (Addition) A fixed fire suppression system shall be provided for the enclosure. The fire
suppression system shall be based on a carbon dioxide (C02) total flooding system and
or an alternate medium such as water mist. It shall be designed in accordance with NFPA
12. The Supplier shall be responsible for the entire system design.
5.7.4.1 (Substitute) The package noise levels shall not exceed the limits specified on the
Equipment Noise Data Sheet with the plant operating at rated speed and output power,
and also under turndown conditions with the driven equipment on continuous recycle.
The Supplier shall provide with the bid expected and guaranteed sound pressure level
and sound power level data (both overall and octave band) at 1 m distance and an
elevation of 1.5 m above walk-ways, access ladders and platforms in free-field
conditions. Data shall be provided for the complete package.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 23 of 31
Revision 1
5.7.4.2 (Decision) Special “far field” or neighborhood sound restrictions are not applicable.
5.7.5 Enclosures
5.7.5.1 (Decision) Suitable enclosure(s) shall be provided to meet the Purchaser specified
acoustical, weatherproofing, safety, and fire protection requirements.
5.7.5.6 (Decision) The enclosure ventilation system shall be designed to generate a negative
pressure within the enclosure when located within a safe area or a positive pressure
when located within a hazardous area. The system shall include two each 100 percent
size ventilation fans with controls that automatically start the standby fan after failure of
the running fan. Fan motors shall be suitable for hazardous area operation and shall be
located to provide ease of access for maintenance or replacement.
5.7.5.6.3 (Decision) Ventilation and purging flow shall enter and exit the enclosure via port(s).
Each port shall be equipped with a back draft damper and a fire suppression medium
damper. Additional ventilation ducting is not required.
5.8.1 General
5.8.1.1 The Purchaser will provide the fuel gas composition, range of heating values,
temperatures, delivery pressure, and contaminant levels on Page 2, Lines 13 through 48
of the Data Sheets.
5.8.1.2.1a. (Addition) A fuel gas strainer and a blow-down pipe connection to the flare shall be
provided upstream of the gas supply connection to the turbine. The Y-type strainer shall
be purchased with the combustion gas turbine from the turbine manufacturer. The
internals of this strainer shall be stainless steel. The blow-down pipe shall be provided
with a manual valve.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 24 of 31
Revision 1
5.8.1.2.1d.(Addition) A safety shutdown valve shall be installed in the gas supply line at the plot
limit. Multiple supply branches shall each be equipped with a safety shutdown valve.
The plot limit valve shall automatically trip on primary gas knockout drum high high liquid
level, preceded by a high level alarm, and shall also be capable of being manually
tripped. The valve shall be operated by means of an electric motor or by air and shall be
of the “Fail Safe” design.
5.8.1.2.1h.(New) A Purchaser supplied primary knockout drum will be provided for the maximum
expected gas consumption of the plant. The knockout drum shall be installed
downstream of the safety shut-down valve and the plant pressure control valve, except
where there are two or more branches having differing pressure requirements. Each
branch shall be equipped with a safety shutdown valve, a control valve, and a knockout
drum. A high high liquid level shutdown signal shall be provided for the safety shutdown
valve and shall be preceded by a high level alarm.
5.8.1.2.1i.(New) In order to prevent a condensate mist carryover or hydrate formation, a fuel gas
super heater shall be supplied and designed to deliver 40°C (72°F) superheated fuel gas
to the turbine gas distribution system. The super heater shall be sized for the total
maximum expected gas consumption of the plant or the branch. Heat may be obtained
from gas, steam, or electricity, depending upon economics, reliability, and available plant
facilities. Normally, the super heater shall be located downstream of the separator.
5.8.1.2.1j.(New) A particle filter and coalescing filter/separator shall be installed close to the gas
turbine, downstream of the pressure control valve. The filters shall be of the Vendor’s
proven design and shall be Pall or Purchaser approved equal. Screw type mounting of
the particle or coalescing cartridges is unacceptable. The filters shall be vertical to
minimize plot space required near the turbine. Block and bypass valves shall be
provided for the filters.
The particle filter shall have the following particle removal efficiency as a minimum:
a. 100 percent removal efficiency for particle sizes of 3.0 microns and larger.
b. 99 percent removal efficiency for particle sizes in the range of 0.5 to 3.0 microns.
5.8.1.2.1k.(New) Horizontal piping sections shall be installed sloped towards the knockout drums
or filters/separators to allow drainage. All low points shall be provided with valved
drain connections and all high points shall have valved vent connections.
5.8.1.2.2 (Decision) Any fuel gas compression system required to meet the fuel gas pressure
required by the Vendor will be provided by the Purchaser.
5.8.1.2.5 (Decision) A fuel gas bypass valve and vent valve for purging the fuel gas line prior to
light off shall be supplied.
5.8.2.1 Composition
(Decision/ Addition) The Purchaser will specify the composition and characteristics of the
fuel gas on Page 2, Lines 10 through 34, of the Data Sheets. The fuel gas will be
superheated a minimum of 10°C, unless the Vendor requires a greater superheat.
Note: Modified Wobbe Index variations in excess of five percent may require dual fuel
manifolds and fuel nozzles. Every effort should be made to maintain the Modified Wobbe
Index within the allowable ± 5 percent band to avoid the more complex and consequently
less reliable fuel control system. The Modified Wobbe Index is affected by fuel temperature
variations, specific gravity of the fuel with respect to air at ISO conditions (varies with
composition), and the Lower Heating Value (LHV) of the fuel (varies with composition). The
mathematical definition of the Modified Wobbe Index is as follows:
LHV
ModifiedWobbeIndex
TSG
or
LHV
ModifiedWobbeIndex
TM
28.96
Where: LHV = Lower Heating Value of the Gas Fuel (kcal/Nm3 or Btu/SCF),
SG = Specific Gravity of the Fuel Gas relative to Air,
M = Molecular Weight of the Fuel Gas,
T = Absolute Temperature of the Fuel Gas (Celsius or Rankine), and
28.96 = Molecular Weight of Dry Air.
5.8.2.2 Contaminants
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 26 of 31
Revision 1
5.8.2.2.1(Decision) The Purchaser will specify the concentration of contaminants in the fuel gas
on Page 2, Line 40, of the Data Sheets.
(Decision) The Purchaser will specify the concentration of corrosive agents in the fuel gas
on Page 2, Line 39, of the Data Sheets.
(Decision) The Purchaser will specify the Lower Heating Value (LHV) of the normal fuel
gas, the starting fuel gas, and the range of fuel gas characteristics (considering the
extreme variations) on Page 2, Line 41, of the Data Sheets.
5.8.4.1 (Decision) ___________ equipment for emission suppression ______ (Page 9, Column
2, Lines 33, __
5.8.4.2b.(Decision) The power output load range for which the specified emission levels are
acceptable are from 65 percent to maximum continuous power.
5.8.4.2c.(Decision) When emission suppression systems are required, they shall be dry type
(Page 9, Column 2, Line 37 of the Data Sheets).
5.9.1 (Addition) The Vendor shall provide one set of special tools for each group of three or
less identical combustion gas turbines installed in one location. Where identical
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 27 of 31
Revision 1
combustion gas turbines are installed in different locations, a minimum of one set of
special tools shall be provided for each location.
5.9.2 (New) Special tools shall be packaged in separate, rugged metal boxes and marked
“Special Tools for (tag/item number)”. Each tool shall be stamped or tagged to indicate
its’ intended use.
6.1 General
6.1.1 (Decision) The Purchaser will specify the extent of their participation in inspection and
testing on Page 10, Column 1, Lines 9 through 40 of the Data Sheets.
6.1.2 (Decision) The Purchaser’s and Vendor’s representative shall indicate compliance in
accordance with the inspector’s checklist found in API 616, Appendix B, by initialing and
dating the checklist and the Vendor submitting the completed checklist to the Purchaser
before shipment.
6.2 Inspection
6.2.1 General
6.2.1.1 (Decision) The Vendor shall maintain the data outlined in Paragraphs 6.2.1.1a., 6.2.1.1b.,
6.2.1.1c., and 6.2.1.1d. for a minimum of 20 years.
6.2.2.1 General
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 28 of 31
Revision 1
(New) All longitudinal and circumferential pressure-containing casing butt welds shall be
100% radiographed. All other welds shall be either magnetic particle or liquid penetrant
examined over 100% of their length. All forgings shall be 100% ultrasonic examined
after rough machining prior to further fabrication.
6.2.3.3 (Decision) The Purchaser will inspect for cleanliness the equipment and all piping and
appurtenances furnished by or through the Vendor before heads are welded to vessels,
openings in vessels or exchangers are closed, or piping is finally assembled.
6.2.3.4 (Decision) The hardness of parts, welds, and heat-affected zones shall be verified as
being within the allowable values by testing of the parts, welds, or heat-affected zones.
6.3 Testing
6.3.2.2 (Addition) to this clause: The water used for hydrostatic testing shall be fresh and
clean, and shall include a, suitable wetting agent.
6.3.2.5 (New) Hydrostatic tests shall be maintained for a sufficient period of time to complete
examination of all parts under pressure. The hydrostatic test shall be considered
satisfactory when no leaks are observed for a minimum of 30 minutes. Large and heavy
casings may require a testing period greater than 30 minutes, which shall be agreed to by
the Purchaser and Vendor. All hydrostatic testing shall be witnessed.
6.3.3.1.13 (New) During the run test, the gas turbine shall run for at least 30 minutes at the
minimum lubricating oil temperature and for 30 minutes at the maximum lubricating oil
temperature as dictated by the specified climatic conditions. During the tests, the
performance of the gas turbine shall be monitored, especially for vibration and
maintenance of the specified lubricating oil pressures and temperatures.
6.3.3.3.2 (Addition) The vibration amplitude and frequency sweep shall also be conducted at
minimum governor speed.
6.3.3.3.4 (Decision) Plots showing synchronous vibration amplitude and phase angle versus
speed for deceleration shall be made before and after the 4 hour mechanical running
test. Data shall be furnished in polar form.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-M-4026
Project Name: MARAFIQ SPEC DEVELOPMENT Date: 28 Feb 2011
Contract Number: A5MU Page 29 of 31
Revision 1
6.3.3.3.6 (Substitution) this paragraph by: Tape recordings shall be made of all real-time vibration
data and shall be kept by the Supplier and be available to the CA for a minimum of 5
years.
6.3.3.7 (Addition) The gas turbine need not be dismantled after the mechanical running test,
unless it has failed to meet the specified performance. Flexible fibre optics shall be used
as much as practicable for inspection after tests and photographic records shall be made
where applicable.
(Addition) Auxiliary equipment/system testing shall include, but not necessarily be limited
to, the following witnessed tests:
(Decision /Addition) Post-Test inspection shall be performed. All main casings, bearings,
and burners shall be opened for inspection following the first mechanical run or
performance tests. Bore scope videos of main casing internals shall be produced.
(Decision) The coupling hub/shaft fit inspection shall be performed. Minimum acceptance
criteria shall be 85 percent contact.
(Decision) The tests required by Paragraphs 6.3.4.8.1 and 6.3.4.8.2 shall be performed.
6.4.1 (Decision) The gas turbine units shall be prepared for export boxing and storage for a
minimum of 6 months.
7.2 Proposals
7.2.1 General
(Decision) The Vendor shall forward the original and four (4) copies of the proposal to the
Purchaser.
7.2.3p. (New) The Vendor shall furnish the Purchaser all necessary data for a turbine lateral and
torsional analysis by the Owner’s Engineer.
7.2.3q. (New) Any alternative proposal provided by the Vendor shall be in accordance with
Paragraph 1.1 and shall identify the undemonstrated features and their advantages.
7.2.3 (f) (Modification) The Supplier shall provide a list for the following categories of spare parts
with the bid:
7.2.4 Curves
(Decision) The curves described in 7.2.4a., 7.2.4c., and 7.2.4d. shall be furnished. The
curves described in 7.2.4b. are not required as neither steam or water are to be injected.
(Decision) A Technical data manual shall be provided within 4 weeks of shipment of the
gas turbine unit.