You are on page 1of 2

900VPR-2 Voltage Protection Relay

Features :
! 3Ø - 3 Wire, 3Ø - 4 Wire Input
! Monitors Under Voltage, Over Voltage, Under Frequency, Over
Frequency, Phase Asymmetry, Phase Failure and Phase Sequence
! True RMS Measurement
! Power ON Delay, Trip Time Delay and Recovery Time Delay
! Adjustable Switching Hysteresis
! Two Separate Alarm Relays
! DIN Rail Mount

DIN 35mm
Certifications :

Display Specifications
Trip Time Settings
Type Digital Power ON Delay 2 - 99.9sec
Display Liquid Crystal Display Trip Time Delay 0 - 99.9sec
No. of LED 3 Recovery Time Delay 0 - 99.9sec
No. of Push Button 3 Response Time < 200ms
Hysteresis
LED Indication Chart Voltage 1.0 - 99.9V
Frequency 0.2 - 2Hz
Condition 'ON' LED 'R1' LED 'R2' LED Asymmetry 2 - 20%
Nominal Condition ON OFF OFF Resolution
Fault Condition If Programming Relay1 ON ON OFF Voltage 1V
Fault Condition If Programming Relay2 ON OFF ON Frequency 0.1Hz
Fault Condition (If Programming
ON ON ON Accuracy
For Both Relay)
Voltage ±1% of set value
Frequency ±0.3Hz
Input Specifications

Functions
Output Specifications
Measurements Under voltage, Over voltage, Under
frequency, Over frequency, Phase No. of Relays 2
asymmetry, Phase failure and Phase Type of Output (Relay1) 1 C/O (SPDT)
sequence
Type of Output (Relay2) 1 C/O (SPDT)
Time Setting Power ON delay, Trip time delay and
Recovery time delay Relay Rating NO / 5A@250V AC
NC / 3A@250V AC (res)
Alarm Indications Trip
Latching Selectable
Reset Auto / Manual Auxiliary Supply Specifications
Electrical Connection 3Ø - 3 wire, 3Ø - 4 wire Supply Voltage Self powered
Measuring Range Operating Range 280 to 520V AC (L - L)
(RMS Value) 280 to 520V AC (L - L) 160 to 300V AC (L - N)
160 to 300V AC (L - N) ` Power Consumption 50VA max
Trip Settings Frequency 45 / 65Hz

Under Voltage 280 to 520V AC (L - L) [for 3Ø - 3 wire]


160 to 300V AC (L - N) [for 3Ø - 4 wire] Environmental Specifications
Over Voltage 280 to 520V AC (L - L) [for 3Ø - 3 wire]
Temperature Operating Temperature : 00 to 550C
160 to 300V AC (L - N) [for 3Ø - 4 wire] Storage Temperature : -200 to 700C
Under Frequency 45 / 65Hz Humidity (non-condensing) 95% RH
Over Frequency 45 / 65Hz Pollution Degree
Phase Failure Yes For PCB 2
Phase Sequence Yes For Product 3
Phase Asymmetry 5.0 - 99.9% Degree of Protection Devices IP20

www.selec.com 1
900VPR-2 Voltage Protection Relay

Mechanical Specifications Timing Diagram


Monitored Over trip
Mounting DIN Rail
~
3 Supply } Hysteresis
Weight 135g Phases reversed
L1, L2
L2, L3
Screw Tightening Torque 0.5 NM L3, L1 Phase failure

N
} Hysteresis
Under trip
Dimensions
Output

35mm
Td T t T t tr t T t tr
Td = Power on delay
T = Trip time delay + Response time (tr)
tr = Response time
t = Recovery delay
67.50mm
90mm

45mm
90mm

Compliance

Applicable EMI / EMC Standards


Product Standard : IEC 60947-2
70.50mm Category Reference Standards Testing Level
Electrostatic Discharge IEC 61000-4-2 Level-3
Terminal Connection Electrical Fast Transient / Brust IEC 61000-4-4 Level-3

Electromagnetic Field IEC 61000-4-3 Level-3


RELAY 1

15 18 16 Surge IEC 61000-4-5 Level-3


COM1 NO1 NC1 Conducted RF IEC 61000-4-6 Level-2

Rated Power Frequency IEC 61000-4-8 Level-4


RELAY 2 Voltage Dip / Short Interruptions IEC 61000-4-11 Level-3
26 28 25
Conducted Emissions CISPR-11 Class-B
NC2 NO2 COM2
Radiated Emissions CISPR-11 Class-A

Emission & Immunity IEC 61326-1


Safety IEC 61010-1
L2 L3

Ordering Information
N L1 Product Code Operating Range Certification
900VPR-2-280/520V-CE 280 to 520V AC
900VPR-2-280/520V-CU-RoHS 280 to 520V AC

www.selec.com 2