DETAIL NUMBER
2
SECTION LETTER
A
SCALE : NONE
(WALL TYPE)
(WALL TYPE)
LIMIT OF DEMOLITION
SCALE : NONE
SYMBOL IS MISSING)
VD
FD
FIRE DAMPER
BDD
SCALE : NONE
SCALE : NONE
[6.4x31.4mm]
IRON PIPE STRAP
EXTERIOR WALL
HIGH DENSITY
POLYETHYLENE (HDPE)
1/4"x1 1/4" SLEEVE WITH INTEGRAL
[6.4x31.4mm] HOLLOW MOLDED WATER
IRON PIPE
STOP RING 4" [100mm]
CLAMP LARGER THAN OUTSIDE
DIAMETER OF PIPE
[100mm]
5/8" [16mm]∅
4"
ROD
SCALE : NONE
REMOVABLE COVER
VARIES
SCALE : NONE
3/4"
SLOPE
TRENCH IN BUILDING
1. COORDINATE TRENCH DETAIL
GREATER THAN 24"[600mm]
WITH ARCHITECTURAL &
STRUCTURAL.
2 - SUPPORTS UP TO 24" [600mm] SPAN
2. REFER TO SPECIFICATION,
DESIGNER'S NOTE:
COORDINATE TRENCH DETAIL WITH ARCHITECTURAL & STRUCTURAL.
SD230511-27.DWG
STEAM LINE CONDENSATE
RETURN LINE
SCHEDULE
ANCHOR INSTALLATION
STEAM/CONDENSATE PIPING IN TRENCH
# NTS
SCALE : NONE
FLEXIBLE
MECHANICAL
COUPLING
ANCHOR (TYPICAL)
SEISMIC d
d
JOINT
DETAIL "A"
(STEEL PIPE FOR WATER/GLYCOL)
NOTE:
1. SEISMIC SEPARATION ASSEMBLY DETAIL SHOWN IN NFPA 13 (SPRINKLER PIPING),
UTILIZING FLEXIBLE MECHANICAL COUPLINGS, MAY BE USED IN LIEU OF PIPING DETAIL
SHOW ABOVE.
- - - - - - - - -
- - - - - - - - -
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION. THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
SCALE : NONE
RISE UP
12" [300mm]
MINIMUM
HANGER (CLOSE
TO ELBOW)
d ANCHOR ANCHOR
SEISMIC
JOINT
f f
DETAIL "B"
(PLASTIC PIPE FOR PRESSURIZED SYSTEMS)
- - - - - - -
- - - - - - -
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION. THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
SCALE : NONE
6" [150mm]
A
HANGER
d
ANCHOR
SEISMIC
JOINT
e
e
DETAIL "C"
(COPPER PIPE)
6" [150mm]
COPPER PIPE
4" [100mm]
MINIMUM RISE
FLEXIBLE HOSE
SECTION "A-A"
- - - - - - - -
- - - - - - - -
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION. THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
SCALE : NONE
HANGER
FLEXIBLE BALL
HANGER
c JOINT HANGER
SEISMIC
JOINT
d d
- - - - - - -
- - - - - - -
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION. THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
SCALE : NONE
HANGER
FLEXIBLE
b CONNECTOR
HANGER
c
HANGER
SEISMIC
JOINT
e
e
ANCHOR ANCHOR
DETAIL "E"
(STEEL PIPE FOR WATER)
- - - - - - - - -
- - - - - - - - -
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION. THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
SCALE : NONE
+My
STEAM NOZZLE
+Mz
+Mx
+Fx
+Fz
ISOMETRIC VIEW
BOILER NO. Fx Fy Fz Mx My Mz
BOILER Fx Fy Fz Mx My Mz
NO.
LB [Kg] LB [Kg] LB [Kg] FT LB [J] FT LB [J] FT LB [J]
------
--[--]--[--]--[--] --[--] --[--] --[--]
NOTES:
1. BOILERS SHALL BE DESIGNED TO WITHSTAND THE
FORCES AND MOMENTS SHOWN ABOVE.
SCALE : NONE
N
I VE EN
T
DR M
U IP
EQ
NUMBER OF ISOLATION
UNITS AS REQUIRED
TYPE"B"
WELDED STEEL BASE
SPRING
ISOLATOR
SECTION A-A
MO
T
SH OR
AF
T A
EN T
IV EN
DR M
U IP
EQ A
NUMBER OF ISOLATION
UNITS AS REQUIRED
TYPE "1"
CONCRETE INERTIA BASE
SCALE : NONE
FAN DISCHARGE
FLEXIBLE DUCT
CONNECTIONS
FAN SECTION
VIBRATORS ISOLATORS
AS SCHEDULED OR
SPECIFIED
COIL SECTION
OR DISCHARGE THRUST RESTRAINT
DUCT
TYPE "THR"
NOTES:
1. ATTACH THRUST RESTRAINTS SYMMETRICALLY ON BOTH SIDES OF THE FAN
DISCHARGE.
2. ADJUST RESTRAINT TO ALLOW 1/4" [6 mm] MOVEMENT OF FAN AT START
AND STOP.
DESIGNER'S NOTE:
ON THE VIBRATION ISOLATION SCHEDULE OR UNDER THE TITLE OF THIS DETAIL
DESIGNATE FANS REQUIRING RESTRAINT. THIS IS USUALLY SEPARATELY MOUNTED
FAN SECTIONS FOR STATIC PRESSURE OVER 4" [100 mm] AND POSSIBLY FOR
AXIAL FLOW FANS FOR STATIC PRESSURE OVER 4" [100 mm].
SCALE : NONE
[25mm]
1"
PIPE SLEEVE (5D, 3"
5D
A
[75mm] MIN.)
B B 2D
W
FLOOR
A
5D
CONCRETE BASE WELD HEAD TO PLATE
OR BEND OVER END 5D
PLAN
SECTION B-B
16"
[400mm]
[125mm]
5" MIN.
L/10
PROVIDE DOUBLE SLAB
REINFORCING IN BASE AREA
[125mm]
5" MIN.
L/10
DESIGNER'S NOTE:
THIS DETAIL IS PRIMARILY FOR PUMPS WITHOUT ISOLATORS. COORDINATE DETAIL
WITH ARCHITECTURAL AND STRUCTURAL.
SCALE : NONE
BONDED STEEL
CLAMP
PLATE
SCALE : NONE
LOCK
NUTS
FLOOR
(TYP)
EQUIPMENT WEIGHT
250 LBS. [114KG] OR
LESS
RESILIENT PAD
SD230541-04.DWG
STEEL EXPANSION SHIELD FOR EXISTING
CONSTRUCTION AND INSERTS FOR NEW
CONSTRICTION THIS TYPE SHALL BE
USED ONLY IN SLABS OR BEAMS OF 4"
[100mm] MIN DEPTH
CONCRETE
3/8" [10mm] MIN DIA EXPANSION
FLOOR SLAB BOLTS FOR EXISTING CONSTRUCTION
AND INSERTS FOR NEW CONSTRUCTION
CLIP
3/8" [10mm] MIN
ANGLE DIA INSERTS NEW
CONSTRUCTION ONLY.
SCALE : NONE
DUCT
CEILING DIFFUSER
OR REGISTER
SIDE VIEW END VIEW
COLLAR DIA.
WIDTH OR LENGTH
DUCT
CEILING DIFFUSER
OR REGISTER
SIDE VIEW END VIEW
DESIGNER NOTES:
1.SHOW LOCATION ON FLOOR PLANS
SCALE : NONE
DIFFERENTIAL PRESSURE
BLOWDOWN
ELEVATION
NOTES:
SCALE : NONE
CW OR
SW
N.C.
WATER METER
80 MESH
STRAINER
3'-6"
SUPPORT BRACKET
ANCHORED TO WALL OR
[1.1M]
FLOOR
COLUMN
ELEVATION
SCALE : NONE
RETURN
EXHAUST AIR RETURN FAN PSL AIR
AFMD
D-3 ZC
TT HT
VFD HS
ZC
SPD
PRESSURE SWITCH HIGH
D-4 SST TO DISABLE FAN WHEN HIGH PRESSURE
AIA
FT DPS
DPS DPS LIMIT SETPOINT IS REACHED SUPPLY AIR TO
MINIMUM DIFFUSER TERMINAL UNIT
OUTSIDE SECTION
COMM SD 10' MIN.
AIR
AFTER - FILTER
FINAL FILTER
COIL PREHEAT
PSH HT
SPS
OUTSIDE TT FT
SCALE : NONE
TT TSL TT TT
AIR T-1
T-5 TSL-1 T-3 T-6 SD
CS HHL
IT
D-1 SMOKE
2C
ZC SST DETECTOR
MPS VFD HS V-3
HOT GLYCOL V-2
TT WATER, HOT CHS ONLY WHERE REQUIRED STEAM HUMIDIFIER
V-1
WATER OR 2C V-4
T-2
ELECTRIC COILS
CHR VARIABLE FREQUENCY
ARE LPS
SPD
DRIVE, TYP.
LOCATE SENSOR PERMISSIBLE
OUTSIDE UNDER SUBSTITUTES
SHIELD
VARIABLE AIR VOLUME AIR HANDLING UNIT WITH MINIMUM OUTSIDE AIR CONTROL DIAGRAM
# NTS
ROOM ELECTRIC
EXHAUST FAN UNIT HEATER
D1 PLENUM INTAKE
T T T LOUVER
EMERGENCY
GENERATOR
ACD
NOTES:
1. EMERGENCY GENERATOR SHALL BE INTERLOCKED WITH D3. WHEN EMERGENCY
GENERATOR IS ENERGIZED D3 SHALL OPEN. WHEN EMERGENCY GENERATOR IS
DE-ENERGIZED D3 SHALL CLOSE, PROVIDED ROOM EXHAUST FAN IS OFF.
2. ROOM EXHAUST FAN SHALL BE INTERLOCKED WITH D3 & ROOM THERMOSTAT T1.
WHEN ROOM THERMOSTAT RISES ABOVE 85°F [29°C] ROOM EXHAUST FAN SHALL RUN
& D3 SHALL OPEN. WHEN ROOM THERMOSTAT DROPS BELOW 80°F [27 C] ROOM
EXHAUST FAN SHALL STOP & D3 SHALL CLOSE, PROVIDED EMERGENCY GENERATOR
IS DE-ENERGIZED.
45°F [7.2°C]. ON A DROP IN ROOM TEMPERATURE BELOW 43°F [6.1°C] ELECTRIC UNIT
HEATER SHALL BE ENERGIZED & ON A RISE IN ROOM TEMPERATURE ABOVE 47°F [8.3°C].
DESIGNER'S NOTES:
1. IF THE PROJECT INVOLVES MULTIPLE EMERGENCY GENERATORS, EACH GENERATOR
SHALL HAVE A DEDICATED SECTION OF THE OUTSIDE AIR INTAKE LOUVER & DAMPER
2. WHEN THE ROOM EXHAUST FAN IS RUNNING ALONE, WITHOUT ANY EMERGENCY
GENERATOR, ONLY A DESIGNATED PORTION OF THE OUTSIDE AIR INTAKE LOUVER
SHALL OPEN. THE DESIGNER SHALL SHOW THIS SECTION ON THE FLOOR PLANS.
SCALE : NONE
M
HOIST WAY VENT DAMPER
TWO POSITION, N.O.
TO LOCAL 120 V
POWER
SPACE SMOKE
DETECTOR*
LOCATED AT TOP TO FIRE ALARM CONTROL
OF HOISTWAY PANEL (FACP)*
SD TO FIRE ALARM* &
INITIATE PHASE 1 RECALL
*BY ELECTRICAL
ECC
NOTES:
1. THE DAMPER SHALL REMAIN CLOSED DURING NORMAL OPERATION AND OPEN UPON
LOSS OF POWER FROM A SIGNAL FROM THE SMOKE DETECTOR, LOCATED AT THE
TOP OF THE HOISTWAY. COORDINATE NUMBER OF CONTACTS WITH THE ELECTRICAL
AND FIRE PROTECTION DESIGNS.
DESIGNER'S NOTES:
1. THE AREA OF VENTS SHALL NOT BE LESS THAN 3.0% OF THE TOTAL HOISTWAY
AREA OR 3 SQUARE FEET (0.28 SQUARE METERS) FOR EACH ELEVATOR CAR,
WHICHEVER IS GREATER.
SCALE : NONE
DUCT TRANSITION
SMOKE DAMPER (N.C.)
AS REQUIRED SEE SCHEDULE
AIR
SD AIRFLOW DUCT
AD
TO FIRE
ALARM CONTROL PSH
PANEL (FACP)
120V
ZS M ELECTRICAL
2 POSITION POWER
BINARY POINT
PRESSURE SWITCH HIGH
TO SHUT DOWN FAN UPON
DAMPER POSITION
REACHING HIGH PRESSURE
FEEDBACK TO
SETPOINT
ECC
NOTE:
UPON DETECTION OF SMOKE BY THE SMOKE DETECTOR, THE SMOKE DAMPER SHALL
CLOSE & SEND AN ALARM TO THE ECC.
DESIGNER'S NOTE:
PROVIDE A DAMPER AND DETECTOR ONLY FOR PARTIALLY SPRINKLERED BUILDINGS
WHEN EITHER SIDE OF SMOKE PARTITION IS NOT SPRINKLED AND PROTECTED BY
QUICK RESPONSE SPRINKLER HEADS.
SCALE : NONE
GRAVEL (ALL
AROUND) 3" [75mm]
CONCRETE #4 REBAR TOP
AND BOTTOM
(SQUARE)
ACCESS COVER INTEGRAL DRAIN VALVE WITH
FILL BOX -
GRADE COMPRESSED
V
FOAM BOARD
TANK
FOR TYPICAL PIPE
SCALE : NONE
HOLD-DOWN
STRAPS
HANGER SOUNDING ROD
OVERFILL
PREVENT ON
GAGE
12" VALVE
FOR
FILL
FOS
TURN-BUCKLE
THICK, 12"
[304mm] SQ 6"
12" STEEL (TYP.)
[150mm]
[300mm]
STORAGE TANK
# NTS
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
ELEVATION ELEVATION
THREADED PIPING WELDED PIPING
MV
AIR VENT OR
1/4" [8mm]
AV
ELEVATION
NOTES:
TYPICAL MANUAL AIR VENT
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
(HYDRONIC SYSTEMS)
SCALE : NONE
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
A
DRAIN
PAN
[25mm]
B
1"
DIELECTRIC
FITTING
FLOOR SINK
UNIT TYPE A B
SCALE : NONE
(TYPICAL)
(TYPICAL)
H
SUPPLY
PLAN
EXPANSION LOOP
LOOP NO. W H
SCALE : NONE
(TYP.) MV
WATER RETURN
COIL
WATER SUPPLY
DESIGNER'S NOTE:
1. THIS DETAIL IS APPLICABLE TO: 2-PIPE FAN COIL UNITS (CHILLED OR HOT WATER)
○ VAV/CV AIR TERMINAL UNITS ( REHEAT COIL)
○ DUCT-MOUNTED REHEAT COIL
○ CABINET UNIT HEATERS
SCALE : NONE
1 1/2" [40mm]
FULL PORT BALL
VALVE
1 1/2"∅x2" LONG
[40x50mm] PIPE
1 1/2" [40mm]
9
0
°
PLUG
WELD (TYP)
NOTE:
DESIGNER'S NOTE:
SCALE : NONE
PRESSURE GAGE
1/2" [15mm]
BALANCING
DEVICE
FLEXIBLE STRAINER
CONNECTION
BALL OR
BUTTERFLY
TYP.
NOTES:
DESIGNER'S NOTE:
1. CHECK VALVE IS OPTIONAL FOR SINGLE PUMP, EXCEPT FOR COOLING TOWER PUMP.
2. ELIMINATE BALANCING DEVICE WHEN PUMP CONTROLLED BY VARIABLE SPEED DRIVE.
SCALE : NONE
BUTTERFLY OR BALL
INSTALL HANGER AS CLOSE
TO PIPE ELBOW AS POSSIBLE SHUT OFF VALVE, TYP.
(TYPICAL)
OPTIONAL STRAINER
PRESSURE GAUGE
CHECK VALVE
DRAIN
VIBRATION ISOLATOR
CONCRETE INERTIA
(TYPICAL)
BASE 1" [25mm] MIN.
DIA. PIPE STAND
NOTES:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION
DESIGNER'S NOTE:
CHECK VALVE IS OPTIONAL FOR SINGLE PUMP, EXCEPT FOR COOLING TOWER PUMP.
SCALE : NONE
HANGER HANGER
BUTTERFLY OR BALL
INSTALL HANGER AS CLOSE
SHUT OFF VALVE, TYP.
TO PIPE ELBOW AS
PRESSURE
GAGE
1/2" [15mm]
1/2" [15mm]
SUCTION DIFFUSER
FLOOR DRAIN
CONCRETE BASE
(SEE DETAIL)
NOTES:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION
DESIGNER'S NOTE:
1. CHECK VALVE IS OPTIONAL FOR SINGLE PUMP, EXCEPT FOR COOLING TOWER
PUMP. USE THIS DETAIL ONLY FOR PUMPS IN A MECHANICAL BUILDING WHERE
POSSIBLE VIBRATION WILL NOT BE OBJECTIONABLE AND WHERE APPROVED BY VA.
SCALE : NONE