Qu. 1 Stairs:
Qu. 3 Light
• Window area of 10% (min) of room floor area (NA for bathroom/storeroom)
Qu. 4 Ventilation
• Window openable area of 5% (min) of room floor area (NA for rooms + private lift
2
lobby less than 6m )
• Window openable area of 10% (min) stair floor area (for fire exit stairs)
S/N ITEM
1:10 (50-200mm)
1:5 (15-50mm)
1:2 (0-15mm)
• Handrail shall extend horizontally = 300mm or more beyond the top and bottom of the
ramp to provide support for persons who may need help to negotiate the ramp
• Ramps & landings not adjacent to a wall shall have an edge protection such as
A raised barrier with its lower edge not more than 75mm from the ramp or landing
surface
A rail with the bottom edge not more than 75mm from the ramp or landing surface
S/N ITEM
• The doorway of a one-way swing door the manoeuvring spaces on both sides for
wheelchairs
On the pull side, a minimum space of 460mm (unit entrance) / 610mm (common
area) adjacent to the leading edge of the door (450/600 absolute minimum) with a
minimum clear floor space of 1500mm wide by 1500mm deep
On the push side, a minimum space of 310mm adjacent to the leading edge of the
door (300mm absolute minimum) with a minimum clear floor space of 1200mm wide
by 1200mm deep
The leading edge of the door leaf shall not be set more than 150mm away from the
wall surface
The difference in levels between the floor of the entrance to the unit and the abutting
common area shall not be more than 40mm: 50mm absolute minimum & floor
slope/laid to fall considered
• The doorway of the bathroom and the clear space in front of the doorway shall
comply with the dimensions
900mm 1000mm
850mm 1100mm
800mm 1200mm
• There shall be an unobstructed passageway of not less than 1000mm leading from
the doorway to the water closet, and a clear 1m x 1m space at the front edge of the
water closet
• The change in level of the floor surface at the way of bathroom shall be not more
than 20mm (25mm absolute maximum)
S/N ITEM
• Call button to be placed between = 900mm (min) and 1200mm (max), with side
wall/obstruction at 350mm (min) away
Qu. 7 Safety