10—Adjustments to Flammable Consequence for Mitigation


Systems
Consequence Area
Mitigation System
Reduction Factor, mit fact

Inventory blowdown, coupled with isolation system classification B


0.25
or higher Note #1
Fire water deluge system and monitors 0.2
Fire water monitors only 0.05
Foam spray system 0.15
Not Applicable 0
Note #1
Isolation system classification
B- Isolation or shutdown systems activated by operators in the
control room or other suitable locations remote from the leak.
A-Isolation or shutdown systems activated directly from process
instrumentation or
detectors, with no operator intervention.