Professional Documents
Culture Documents
TRANSFORMER
MAINTENANCE
FACILITIES INSTRUCTIONS,
STANDARDS, AND TECHNIQUES
TRANSFORMER
MAINTENANCE
Acro n y m s a n d Abbre vi atio n s
A air
ANA self-cooled, nonventila ted kW kilow a tt
AN SI Ame rica n N a tion al St a n da rds IE EE Ins titu te of Elect rical a n d
I ns tit ute Elect ronic E ngineers
CEGB Cent r al Electric Gene ra ting M/DW moist ure by dry weigh t
Boa rd mg milligr a m
cfm cubic feet pe r min u te m va mega-volt-a mps
CH 4 meth a n e ND not de tected
C2 H 2 acetylene N2 nit rogen
C2 H 4 et hylene O oil
C2 H 6 et h a n e O2 oxygen
CO ca rbon monoxide OD ou ter dia meter
CO 2 ca rbon dioxide p pb pa r ts per billion
CT cu r ren t t r a n sformer ppm pa r ts per million
DBPC Diter tia ry Bu tyl P a r acresol p si pou nds per squ a re inch
DGA dissolved gas a n alysis R e cla m at io n Bu re a u of Recla m a tion
E HV ex tr a high volt age SCADA Supervisory Con trol a nd Da ta
FA forced air (fa n s) Acquisition
FO forced oil (pu mps) STP s ta nda r d temper a t ure a nd
G some type of ga s pressu re
GA ga s, self-cooled TDCG total dissolved comb ustible gas
gm gr a ms TOA Tr a n sformer Oil Analyst
GS U ge ner a tor step up TTR t r a n sfor mer t u r ns r a tio test
H2 hyd roge n TSC Technical Service Cen ter
ID in ner dia meter UV ult r aviolet
IFT in terfacial te nsion V volts
IEC In ter n a tion al Electrotech nical W wa ter/oil hea t exch a nger
Com mission
IR infr a red
J HA job h aza rd a n alysis
KOH pot assium hyd roxide
kV kilovolt
kVA kilovolt a mpere
Co n t e nt s
Page
v
Co n t e n ts (co nt.)
Page
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Table s
T able No. Page
Fig u res
Figure No. Page
vi
Co n t e n ts (co nt.)
vii
1. P U R P OS E
This docu men t is to p rovide guida nce to B u re a u of Recla m a tion (Recla m a tion) powerpla n t
pe rson nel in m ain t en a nce, diagnostics, a n d testing of t r a n sfor me rs a n d a ssocia ted
equip me n t.
Tra n sfor me rs r a ted 500 kilovolt a mperes (kVA) a n d a bove a re considered powe r
t r a nsform ers. Recla m a tion h a s h u n dreds of powe r t r a n sfor me rs wit h volt ages a s low a s
480 volts (V) a nd a s high a s 550 kilovolt s (kV).
All ge ner a tor s tep-up (GS U) t r a nsfor m ers, a nd m a ny st a tion service, a n d excit a tion
t r a nsform ers a re conside red power t ra nsfor mers beca use t hey a re r a ted 500 kVA or la rge r.
S t a nd a rds orga niza tion s such as Am erica n Na tion al S t a nd a rds Ins tit u te/In stit u te of
Elect rical a nd Elect ronic E nginee rs (ANSI/IE E E) consider aver age GS U t r a n sfor me r life to
be 20 to 25 yea rs. This estim a te is ba sed on con tin uous ope r a tion a t r a ted loa d a n d service
condition s wit h a n aver age a mbien t te m per a t u re of 40 °C (104 °F) a nd a te mper a t u re rise
of 65 °C. This estim a te is also ba sed on t he a ss u mp tion t h a t t r a nsform ers receive a dequ a t e
m ain t en a nce ove r t heir se rvice life [24]. Recla m a tion, Bon neville Power Adminis t r a tion,
a nd Weste r n Area Power Administ ra tion con duct regula r st u dies to dete rmine st a tistica l
equip me n t life. These s t udies show t h a t ave rage life of a Recla m a tion t r a nsform er is
40 yea rs. Recla m a tion ge ts longer service t h a n IE E E estim a tes beca use we oper a te a t
lower a mbie n t te m per a t u res a nd wit h lowe r loa ds. A significa n t n u mber of t r a nsform ers
we re p u rch a sed in t he 1940s, 1950s, a nd in to t he 1970s. Seve ral h ave been replaced, bu t
we h a ve m a ny t h a t a re ne a ring, or a re alrea dy well p a st, t heir a n ticip a ted se rvice life. We
s hould expect t r a n sfor me r replaceme n t a nd fa ilu res to increa se d ue to t his age factor.
Cu r ren t minim u m replace men t time is a rou nd 14 mon t hs; a more re alistic time m ay be
18 mon t hs to 2 yea rs. In t he fu t u re, le a d times m ay exte nd well beyon d wh a t t hey a re
today. The refore, high qu ality m ain te n a nce a nd accu r a te diagnostics a re im port a n t for all
t r a nsform ers, bu t absolu t ely esse n tia l for olde r ones—especially for critical t ra n sfor me rs
t h a t would ca u se loss of gene ra tion. It is also ve ry im por t a n t to consider providing spa res
for critical t r a nsform ers.
Hea t is one of t he mos t com mon des t royers of t ra nsfor mers. Oper a tion a t only 10 °C a bove
t he t r a nsfor mer r a ting will cu t t ra nsfor me r life by 50%. Hea t is ca used by in te rn al losses
d ue to loading, high a mbie n t t em per a t u re, a nd sola r ra dia tion. It is im por t a n t to u nder-
s t a nd how you r pa r ticula r t r a nsfor m ers a re cooled a nd how to detect p roble ms in t he
cooling sys tem s. ANSI a n d IE E E require t he cooling cla ss of each t r a nsfor mer to a ppea r on
its n a m epla te. Cooling cla ssifica tions, wit h short expla n a tions, a ppe a r in section s 3.1 a n d
3.2. The le t te rs of t he class design a te inside a t mosphere a nd type or types of cooling. In
some t r a nsform ers, more t h a n one cla ss of cooling a n d loa d r a ting a re indica ted. At each
1
DRY TYPE TRANSFORMER MAINTENANCE SUMMARY
When new after Do an infrared scan and compare with temperature gage, if any.
energizing and
allowing If transformer is gas filled (nitrogen [N2]), check pressure gage against data
temperature and sheets; never allow gas pressure to fall below 1 pound per square inch
loading to stabilize (psi).
After 1 week of Perform infrared scan and compare with temperature gage, if any.
operation at normal
loading Check temperature gage, if any, and compare with nameplate rating.
Check loading and compare with nameplate rating.
(Note: The time De-energize and remove panels for internal inspection.
between these
periodic inspections Use vacuum to remove as much dirt as possible.
may be increased if
the first internal After vacuuming, use low pressure dry air (20 to 25 psi) to blow off
inspection of remaining dirt. Caution: Make sure air is dry.
windings and
connections are Check for discolored copper and discolored insulation.
found clean and in
good condition and Check for corroded and loose connections.
if loading is at or
below nameplate Check for carbon tracking on insulation and insulators.
rating.)
Check for cracked, chipped, and loose insulators.
If windings are found dirty, add filter material to air intake ports.
2
s tep of addition al cooling, t he r a ting incre a ses to cor respon d wit h incre a sed cooling. Note
t h a t t he let ter “A” in dica tes air, “FA” in dica tes forced air (fa ns), “O” indica tes oil, “FO”
indica tes forced oil (pu mps), “G” indica tes some type of ga s, a nd “W” indica tes t here is a
wa te r/oil hea t exch a nge r.
3.1 D r y T y p e Tr a n sfo r m e r s
2. Cla ss AFA t r a nsform ers a re self-cooled (A) a nd a ddition a lly cooled by forced
circula tion of air (FA). This m ea ns t h a t t he re a re ven tila tion port s for fa n inlet s a n d
ou tlet s only. (Inlet s a re us u ally filtered.) Nor m ally, t he re a re no a ddition al
ve n tila tion port s for n a t u r al air circula tion.
3. Cla ss AA/FA t r a n sfor me rs a re ve n tila ted, self-cooled (sa me a s Cla ss AA in ite m 1).
In a ddition, t hey h ave a fa n or fa ns p roviding addition al forced-air cooling. F a n s m ay
be wired to s t a r t a u tom a tically when t he tem pe r a t u re reaches a p re-set value. These
t ra n sfor me rs gene r ally h ave a d u al loa d r a ting, one for AA (self-cooling n a t u r al air
flow) a nd a la rge r loa d r a ting for FA (forced air flow).
4. Cla ss ANV t r a n sfor me rs a re self-cooled (A), non-ve n tila ted (NV) u nit s. The
e nclosu re h a s no ve n tila tion por ts or fa ns a nd is not se aled to exclude migr a tion of
ou tside air, bu t t here a re no provisions to in te n tion ally allow ou t side air to en ter a nd
exit. Cooling is by n a t u r al circula tion of air a rou nd t he enclosu re. This t ra nsfor mer
m ay h ave som e type of fins a t t ached ou tside t he enclosu re to increa se su rface a re a for
a ddition al cooling.
3
t he e nclos u re. As dir t accu m ula tes on cooling su rfaces, it becomes more a nd more
difficult for air a rou n d t he t ra n sfor me r to re move hea t. As a result, ove r tim e, t he
t ra n sfor me r tem pe ra t u re slowly rises u n noticed, reducing service life.
Tr a nsfor me r room s a nd va ult s should be ven tila ted. Por t able fa n s (never wa t er)
m ay be u sed for a ddition al cooling if necess a ry. A fa n r a ted a t a bou t 100 cubic
fee t per min u te (cfm) per kilowa t t (kW) of t r a nsform er loss [5], loca ted ne a r t he
top of t he room to remove hot air, will s uffice. These room s/va ults should not be
u sed a s s tor age.
Afte r de-e nergizing t he t r a nsform er, re move access p a nels a n d in spect windings
for dir t- a nd he a t-discolored ins ula tion a n d st r uct u re problem s [14]. It is
im port a n t t h a t dir t not be allowed to accu m ula te on windings beca use it im pedes
he a t removal a nd reduces win ding life. A vacu u m should be u sed for t he initial
winding clea ning, followed by com pressed air [7]. Ca re m ust be t a ken to e ns u re
t he com p ressed air is dry to avoid blowing mois t u re in to win dings. Air press u re
should not be gre a ter t h a n 20 to 25 psi to avoid imbedding s m all p a rticles in to
in sula tion. After cle a ning, look for discolored copper a n d in sula tion, which
in dica tes ove rhe a ting. If discolora tion is fou n d, check for loose con nection s. If
t here a re no loose con nections, check t he cooling p a t hs ve ry ca refully a n d check for
ove rloa ding afte r t he t r a nsfor m er h a s been re-e nergized. Look for ca rbon t r acking
a nd cr acked, chipped, or loose ins ula tors. Look for a n d repair loose cla m ps, coil
sp acers, dete riora ted ba r rie rs, a nd cor roded or loose con nection s.
Check fa ns for p rope r ope r a tion inclu ding con t rols, te m per a t u re switches, a n d
ala r ms. Clea n fa n bla des a nd filters if needed. A dir ty fa n bla de or filt er red uces
cooling air flow over t he win dings a nd reduces service life. If ven tila tion por ts do
not h ave filters, t hey m ay be fa brica ted from hom e-fu r n ace filte r m a te rial. Adding
filte rs is only necess a ry if t he win dings a re dir ty u pon ye a rly inspections.
4
OIL-FILLED TRANSFORMER MAINTENANCE SUMMARY
Before energizing,
inspect and test all
controls, wiring, fans
alarms, and gages.
Indepth inspection of Oil pumps load current, oil Oil pumps load current, oil flow Check diaphragm or
transformer and flow indicators, fans, etc. indicators, fans etc, see 3.2.5, bladder for leaks if you
cooling system, See 3.2.5, 3.2.6, and 4.1. 3.2.6 and 4.1 have conservator. See
check for leaks and Thermometers 4.1.2 and 3. Thermometers 4.1.2 and 3, 4.2.2.
proper operation. Heat exchangers. heat exchangers
Transformer tank 4.1.1. Transformer tank 4.1.1
Do a DGA. Oil level gages 4.1.4. Oil level gages 4.1.4
Pressure relief 4.1.5. Pressure relief 4.1.5
Do a DGA. Do a DGA
Test all controls, See 3.2.5, 4.1.4, 4.1.5. See 3.2.5 Thermometers. See 4.1.3.
relays, gages; test Inspect pressure relief for leaks Oil level gages 4.1.4.
alarms and and indication for operation Inspect pressure relief
annunciator points. (rod extension) see 4.1.5 4.1.5.
Sudden pressure relay
4.1.6.
Buchholz relay 4.1.7.
Test alarms, fan and
pump controls, etc. See
3.2.6.
Inspect transformer Check with binoculars for check with binoculars for
bushings. cracks and chips; look for cracks and chips, look carefully
oil leaks and check oil for oil leaks and check oil
levels. levels IR Scan See 4.1.8
IR scan. See 4.1.8.
Doble test Doble test transformer and See 4.1.8 and 4.7.
transformer and bushings before
bushings. energizing. See 4.1.8, 4.7.
5
Check pressu re gages by looking a t t he weekly d a t a sheet s; if press u re neve r va ries
wit h tem pe r a t u re ch a nges, t he ga ge is defective. Never allow t he pressu re to go below
a bou t 1 psi du ring cold wea t he r. Add nit roge n to bring t he pressu re up to 2½ to 3 psi
to in su re t h a t moist air will not be p ulled in.
3.2.1 Liq u i d-Im m e r s e d, Air-Co ol e d. There a re t h ree cla sses in t his ca tegory.
1. Cla ss OA: Oil-im mersed, self-cooled. Tra nsfor mer win dings a nd core a re
im me rsed in some type of oil a nd a re self-cooled by n a t u r al circula tion of air
a rou n d t he ou tside enclosu re. Fins or ra dia tors m ay be a t t ached to t he e nclos u re
to aid in cooling.
6
3.2.2 Liq u i d-Im m e r s e d, Air-Co ol e d/F o r c e d Liq u i d-Co ol e d. The re a re two
cla sses in t his grou p.
1. Cla ss OW: Tra n sfor me r coil a nd core a re im me rsed in oil. Typically a oil/wa te r
he a t exch a nger (r a dia tor) is a t t ached to t he ou t side of t he t a n k. Cooling wa te r is
pu m ped t h rough t he hea t exch a nge r, bu t t he oil flows only by n a t u r al circula tion.
As oil is he a ted by t he win dings, it rises to t he top a nd exit s t h rough piping to t he
r a dia tor. As it is cooled, t he oil descen ds t h rough t he r a dia tor a n d re-e n ters t he
t ra n sfor me r t a n k a t t he bot tom.
1. Cla ss FOA: Liquid-im me rsed, forced liquid-cooled wit h forced air-cooled. This
t ra n sfor me r nor m a lly h a s only one r a ting. The t r a n sfor me r is cooled by p u m ping
oil (forced oil) t h rough a r a dia tor nor m a lly a t t ached to t he ou t side of t he t a n k.
Also, air is forced by fa n s ove r t he cooling su rface.
7
3.2.5 P o t e n ti al P r o bl e m s a n d R e m e d i al Ac ti o n s for Liq u id F ill e d
Tr a n sfor m e r Co ol i n g S y s te m s.
If plugged r a dia tors a re discove red, t hey need to be cor rect ed a s soon a s possible.
Some r adia tors a re a t t ached to t he m ain t a n k wit h fla nges a nd h ave isola ting
valves. These m ay be removed for clea ning a n d/or le a k repair wit hou t d raining oil
from t he t ra nsfor mer. If ra dia tors a re a t t ached directly to t he m ain t a n k, oil m u st
be dr ained before cle a ning t he m. If ra dia tors a re plugged wit h sludge, ch a nces
a re t he t r a n sfor me r is slu dged u p also. In t his ca se, t he oil s hould be reprocessed
a nd t he t ra nsfor mer cle a ned in ter n ally. Compe ten t con t r actors s hould be
obt ained if t his is necessa ry.
8
V a l v e P r o b le m s. If you r t r a n sfor me r h a s isola ting valves for r a dia tors, check to
m a ke su re t hey a re fully open on bot h top a nd bot tom of t he r a dia tors. A broke n
valve ste m m ay ca use t he valve to be fully or p a rtially closed, bu t it will a ppea r
t h a t t he valve is ope n.
Aft e r 1 m o n t h of s e r v i c e a n d y e a rly, i n s p e c t a n d t e s t th e o il p u m p s.
In spect piping a nd con nections for lea ks. Ove rride t he te m per a t u re con t roller so
t h a t t he pu m p st a r ts. Check t he oil pu m p motor cu r ren t on all t h ree p h a ses wit h
a n accu r a te a m me ter; t his will give a n indica tion if oil flow is cor rect a nd if
u n us u al we a r is ca using a ddition al motor loa ding. Record t his infor m a tion for
la te r com pa rison, especially if t he re is no oil flow in dica tor. If th e m ot or l o a d
c u rr e n t i s l o w , s o m e t h i n g i s c a u si n g lo w o il fl o w. C a refully inspect all
valves to m a ke s u re t hey a re fully ope n. A valve st em m a y brea k a n d le ave t he
valve pa r tially or fully closed, even t hough t he valve h a n dle indica tes t he valve is
fully ope n. P u m p im pelle rs h ave been fou nd loose on t he sh aft, red ucing oil flow.
Slu dge buildup or debris in lines ca n also ca u se low oil flow. If m o to r l o a d
c u rr e n t i s h i g h , t h i s m a y i n d i c a t e i m p e d e d p u m p r o ta ti o n. Lis ten for
u n us u al noises. Th ru st be a ring we a r result s in t he im pelle r a dva ncing on t he
housing. An im peller touching t he housing m a kes a r ubbing sou nd which is
diffe re n t from t he sou nd of a failing motor be a ring. If t his is he a rd, remove t he
pu m p motor from t he hou sing a n d check im pelle r cle a ra nce. Replace t he t h r us t
bea ring if needed, a nd replace t he motor bea rings if t he s h aft h a s too m uch play or
if noise is u n usu al.
9
Th ree ph ase pu m ps will r u n a nd pu m p some oil eve n when t hey a re r u n ning
backwa rds. Va ne type oil-flow m ete rs will indica te flow on t his low a mou n t. The
best indica tion of t his is t h a t sometimes t he pu m p will be very noisy. The motor
loa d cu r re n t m ay also be lowe r t h a n for full load. If t his is su spected d ue to t he
ext r a noise a nd highe r t r a nsfor m er te mper a t u re, t he pu mp s hould be checked for
prope r rot a tion. Reverse two ph a se le a ds if t his is e ncou n te red.[4]
P u m p s c a n p u ll air i n t h r o u g h g a s k e ts o n t h e s u c ti o n si d e of t h e p u m p s.
The suction (vacu u m) on t he in t a ke side of t he p u m p ca n pull air t h rough gasket s
t h a t a re not tigh t. P u m p suction h a s also been known to pull air t h rough p acking
a rou n d valve ste ms, in t he s uction side piping. This ca n result in da nge rous
bubbles in t he t r a n sfor me r oil a n d m ay ca use t he ga s detector or Buch holz relay to
oper a te. Dissolved gas a n alysis will show a big incre ase in oxygen a nd nit rogen
con ten t [4]. High oxygen a n d nit rogen con ten t ca n also be ca u sed by ga sket le a ks
elsewhe re.
10
4.1 Oil-F ill e d Tra n sfor m e rs
Aft e r 1 m o n t h of s e r v i c e a n d o n c e e a c h y e ar, m a k e a n i n d e p t h i n s p e c ti o n of
o il-fill e d tr a n sfor m e r s. Before begin ning, look ca refully a t t em per a t u re a n d oil level
da t a s heet s. If tem pe ra t u re, p ressu re, or oil level gages never ch a nge, even wit h
sea son al te mper a t u re a nd loa ding ch a nges, som et hing is wrong. The gage m ay be
st uck or da t a s heet s m ay h ave bee n filled in incor rectly. Exa mine t he DGA’s for
evidence of le a ks, etc.
4.1.1 Tra n sfor m e r Ta n k. Check for excessive cor rosion a nd oil lea ks. P a y
special a t ten tion to fla nges a nd ga skets (bus hings, valves, a nd r a dia tors) a nd
lower section of t he m a in t a n k. Report oil le a ks to m ain t en a nce, a nd pay special
a t te n tion to t he oil level indica tor if lea ks a re fou nd. Seve rely cor roded spots
should be wire bru shed a n d p ain ted wit h a r ust in hibitor.
Winding te mper a t u re t her mome ters work t he s a me a s t he top oil t her mome ter
(4.1.2) a bove, excep t t h a t t he bulb is in a sepa r a te t her mome ter well nea r t he top
of t he t a n k. A wire-type hea te r coil is eit her in ser ted in to or wra pped a rou n d t he
t her momet er well which su r rou n ds t he te mpe r a t u re sensitive bulb. In some
t ra n sfor me rs, a cu rren t t ra nsfor me r (CT) is a rou n d one of t he t h ree winding lea ds
a nd p rovides cu r ren t directly to t he hea te r coil in propor tion to win ding cu rren t.
In ot her t r a nsfor mers, t he CT su pplies cu r re n t to a n a u to-t r a nsform er t h a t
supplies cu r ren t to t he he a te r coil. The he a ter wa rm s t he bulb a nd t he dial
in dica tes a te m per a t u re, bu t it is not t he t rue hot test-spot te m per a t u re.
11
These devices a re calibra ted a t t he factory by ch a nging t aps eit he r on t he CT or on
t he a u tot r a nsform er, or by a dju sting t he calibr a tion resistors in t he con t rol
ca binet. They nor m ally ca n not be field calibr a t ed or test ed, ot her t h a n testing t he
t her momet er, as m en tioned. The calibr a tion resistors ca n be a dju sted in t he field
if t he m a n ufact u rer p rovides calibra tion cu rves for t he t r a n sfor me r. In p ractice,
mos t winding te m per a t u re indica tors a re ou t of ca libr a tion, a nd t heir re a dings a re
m ea ningless. These te mpe r a t u re in dica tions s hould not be relied upon for loa ding
oper a tion s or m ain t en a nce decisions.
Ther mome ters ca n be removed wit hou t lowe ring t he t r a nsform er oil if t hey a re in
a t her mome ter well. Check you r t r a nsfor me r ins t r uction m a n u al. Look ca refully
a t t he ca pilla ry t ubing betwee n t he t her mome ter well a n d dial indica tor. If t he
t ubing h a s been pinched or acciden tly st ruck, it m ay be res t rict ed. This is not a n
obviou s defect, a nd it ca n ca u se t he dia l poin ter to lock in one position. If t his
defect is fou nd, t he whole gage m us t be re t u r ned to t he factory for rep air or
replace men t; it ca n not be repaired in t he field. Look for a le a k in t he t ubing
syst em; t he gage will be re a ding ve ry low a nd m u st be replaced if a lea k is
discove red. Ther mome ters s hould be re moved a nd tested every 3 to 5 ye a rs a s
described below.
T h e r m o m e t e r Te s t i n g. E v e r y 3 to 5 y e a r s, a n d if tr o u bl e i s s u s p e c t e d, d o a
t h e r m o m e t e r t e s ti n g. S uspen d t he indica tor bulb a n d a n accu r a te m ercu ry
t her momet er in a n oil ba t h. Do not allow eit her to touch t he side or bot tom of t he
con t ainer. Hea t t he oil on a hotpla te while stirring a n d com p a re t he two
t her momet ers while t he te m per a t u re incre ases. If a m agne tic s tir ring/he a ting
pla te is available, it is more effective t h a n h a nd stirring. P ay p a r ticula r a t te n tion
to t he u ppe r te mpe r a t u re r a nge a t which you r t r a n sfor me rs nor m ally oper a te
(50 °C to 80 °C). An oh m me ter should also be used to check switch oper a tion s. If
eit her dial in dica tor is more t h a n 5 °C diffe re n t t h a n t he mercu ry t he r mom ete r, it
should be replaced wit h a sp a re. A n u m ber of sp a res should be kept, ba sed on t he
qu a n tity of t r a n sfor me rs a t t he pla n t. Oil ba t h test kit s a re ava ila ble from t he
Qu alit rol Com pa ny. Afte r calling for Qu alit rol a u t horiza tion a t 716-586-1515, you
ca n ship defective dial t he r momete rs for repair a nd calibr a tion to: Qu alit rol Co.,
1387 F airport Rd., F airpor t, NY 14450.
The ala r m s a n d ot her fu nctions s hould also be tes ted to see if t he cor rect
a n n u ncia tor poin ts activa te, p u mps/fa n s ope ra te, e tc.
12
pu m p-t u r n-on se t tings by t his s a m e correction factor. Since t hese a re pressu re-
filled syst em s, t he indica tor will typically re ad low if it is ou t of calibr a tion. Field
tes ting h a s s hown som e of t hese gages re ading 15 °C to 20 °C lowe r t h a n act u al
te m per a t u re. This is h az a rdous for t r a nsfor mers beca use it will allow t hem to
con tin uou sly ru n hot ter t h a n in t ended, d ue to delayed ala rm s a nd cooling
activa tion. If t he rmom ete rs a re not tes ted a nd er rors corrected, t r a nsform er
service life m ay be shorte ned or prem a t u re failu re m ay occu r.
To check t he level in dica tor, you ca n remove t he ou t side mech a nism for tes ting
wit hou t lowe ring t r a nsform er oil. After removing t he gage, hold a m agnet on t he
back of t he dial a n d rot a te t he m agnet; t he dial indica tor should also rot a te. If it
fails to respon d or if it dr ags or sticks, replace it. As m en tioned a bove, defective
u nits ca n be sen t to t he factory for rep air.
There m ay also be elect rical switches for ala r m s a n d possibly t ripping off t he
t ra nsfor me r on falling t a nk level. These s hould be checked wit h a n oh m me ter for
p rope r ope r a tion. The ala r m/t ripping circuits s hould also be tes ted to see if t he
cor rect a n n u ncia tor poin t s a n d relays respon d. See t he t r a nsform er in st ruction
book for inform a tion on you r specific in dica tor.
13
If oil h as h a d to be lowered in t he t r a nsform er or conse rva tor for ot he r rea sons
(e.g., inspections), check t he oil level floa t mech a nism. Rot a te t he floa t
m ech a nis m by h a n d to check for free move me n t. Check t he floa t visu ally to m a ke
su re it is secu re to t he a r m a nd t h a t t he a r m is in t he proper s h a pe. Some a r ms
a re form ed (not s t r aigh t).
14
Ca u ti o n: Bolt s t h a t hold t he device to t he t a n k m ay be loosened safely, bu t never
loose n screws which hold t he cove r to t he fla nge wit hou t refe rring to t he
in st r uction m a n u al a nd using grea t ca re. Sp rings t h a t oppose t a n k p ress u re a re
held in com pression by t hese screws, a n d t heir stored e nergy could be h aza rdous.
The relief pin dete rmines ope ra ting pressu re; a n u mber, which is t he oper a ting
pressu re, nor m ally a ppe a rs on top of t he pin. Check you r specific t r a n sfor me r
in st r uction m a n u al for p rope r ca t alog n u mbe rs. Do not a ssu me you h ave t he righ t
pa rt s, or t h a t cor rect pa r ts h ave been p reviously ins t alled—look it up. If t he
oper a ting pressu re is too high, a ca t a st rophic t a nk failu re could result.
On olde r u nit s, a sh aft rot a tes, ope r a tes ala r m/t rip switches, a nd r aises a s m a ll
red flag when t he u nit relea ses pressu re. If u nit s h ave been pa in ted or a re more
t h a n 30 yea rs old, t hey s hould be replaced wit h t he new model a s soon a s it is
possible to h ave a t r a nsfor mer ou t age.
15
Once e ach ye a r a nd a s soon a s possible after a t h rough-fa ult or in te rn a l fa ult,
exa mine t he indica tor fla g to see if t he device h a s oper a ted. They m us t be
exa mined from a high-lift bucke t if t he t r a nsform er is ene rgized. A clea r a nce
m us t be obt ained to test, rep air, or reset t he device. See t he ins t r uction m a n u al
for you r specific t r a nsform er. Tes t ala r m/t rip circuits by oper a ting t he switch
byh a nd. C heck to m a ke s u re t he cor rect a n n u ncia tor poin t activa tes.
E v e r y 3 to 5 y e a rs, whe n doing ot he r m ain te n a nce or tes ting, exa mine t he top of
t he t r a n sfor me r t a n k a rou nd t he press u re relief device. If t he t r a nsfor m er h a s a
con serva tor a n d oil is visible, t he device is le a king, eit he r a rou nd t he t a n k ga ske t
or relief dia ph r agm. The ga ske t a nd/or device m us t be replaced. Ta ke ca re t h a t
t he new device will fit t he sa me t a n k opening prior to ordering. Mos t of t he m a re
m a de by t he Qu alit rol Comp a ny; con t act t he m a n ufact u rer to obt ain a cor rect
replace men t.
Moder n su dde n pressu re relays con sis t of t h ree bellows (see figu re 4) wit h silicone
sealed inside. Ch a nges in pressu re in t he t r a n sfor me r deflect t he m ain sensing
bellows. Silicone inside act s on two con t rol bellows a r r a nged like a bala nce be a m,
one on each side. One bellows senses p ress u re ch a nges t h rough a sm all orifice.
The ope ning is a u tom a tically ch a nged by a bime t allic s t rip to a djus t for nor m a l
te m per a t u re
ch a nges of t he oil. BIMETAL TEMPERATURE COMPENSATOR CONTROL ORIFICE
ch a nges a nd is
affected m uch more
TRANSFORMER OIL
quickly. P ressu re
diffe re nce tilts t he
bala nce bea m a nd ELECTRICAL CONNECTOR
1/8" DIAMETER DRAIN HOLE
activa tes t he switch. SILICONE SENSING FLUID MANIFOLD HOUSING CONTROL BELLOWS
This type relay
a u tom a tically reset s F i g u r e 4.—S u d d e n P r e s s u r e R e la y.
16
when t he two bellows a gain reach pressu re equilibriu m. If t his relay oper a tes, do
not re-e ne rgize t he t r a nsfor me r u n til you h ave dete rmined t he exact ca u se a n d
cor rected t he proble m.
Old style s udden p ress u re relays h ave only one bellows. A s udden excessive
pressu re wit hin t he t r a n sfor me r t a n k exer ts p ress u re directly on t he bellows,
which moves a sp ring-loaded oper a ting pin. The pin ope ra tes a switch which
provides ala r m a n d brea ke r t rip. Aft er t he relay h a s oper a ted, t he ca p m ust be
removed a nd t he switch rese t to nor m al by dep ressing t he reset bu t ton.
17
floa t. These con t acts a re typically con nected to ca use t he t r a n sfor me r to t rip.
This relay also serves a t hird fu nction, simila r to t he su dde n pressu re relay. A
m agnetically held pa ddle a t t ached to t he bot tom floa t is positioned in t he oil-flow
st rea m be tween t he conserva tor a nd t r a nsform er t a n k. Nor m al flows resulting
from te mper a t u re ch a nges a re sm all a n d byp a ss below t he pa ddle. If a fa ult
occu rs in t he t r a n sfor me r, a pressu re wave (su rge) is crea ted in t he oil. This s u rge
t ra vels t h rough t he pipe a nd displaces t he pa ddle. The pa ddle activa tes t he sa me
m agnetic switch a s t he bot tom floa t m en tioned a bove, t ripping t he t r a n sfor me r.
The flow r a te a t which t he p addle activa tes t he relay is nor m ally a dju st a ble. See
you r specific t r a nsform er in st r uction m a n u al for de t ails.
Ca u ti o n: Do not t es t a bus hing while it’s in its wood s hipping cr a te, or while it is
lying on wood. Wood is not a s good a n ins ula tor a s porcelain a n d will ca use t he
rea dings to be in accu ra te. Keep t he test results a s a ba seline record to com pa re
wit h fu t u re tes ts.
Look ca refully for oil lea ks. Check t he bus hing oil level by viewing t he oil-sigh t
gla ss or t he oil level gage. When t he bus hing h a s a gage wit h a poin te r, look
ca refully, beca use t he oil level s hould va ry a lit tle wit h tem per a t u re ch a nges. If
t he poin t er neve r ch a nges, eve n wit h wide a mbie n t tem per a t u re a nd loa d ch a nges,
18
t he gage should be checked a t t he next ou t age. A s t uck gage poin te r coupled wit h
a sm all oil le a k ca n ca use explosive failu re of a bushing, da m aging t he
t ra n sfor me r a n d ot he r switchya rd equipme n t. A cos tly exte nded ou t age is t he
result.
If t he oil level is low a n d t here is a n exter n al oil lea k, check t he bolts for prope r
torque a nd t he ga sket for proper com pression. If torque a nd com pression a re
cor rect, t he bus hing m us t be replaced wit h a spa re. Follow ins t r uction s in t he
t ra n sfor me r m a n u al ca refully. It is ve ry im por t a n t t h a t t he cor rect type ga sket be
in st a lled a nd t he cor rect comp ression be a pplied. A lea ky ga ske t is probably also
le a king wa ter a nd air in to t he t r a nsfor mer, so check t he most rece n t t r a nsfor m er
DGA for high moist u re a nd oxygen.
Abou t 90% of all preven t able bus hing failu res a re ca used by moist u re en te ring
t h rough le a ky ga skets, cr acks, or se als. In te r n al moist u re ca n be detected by
Doble tes ting. See F IST 3-2 [9] a nd Doble B ushing Field Test Guide [8] for
t roubles a nd corrective actions. In te r n al moist u re ca uses dete rior a tion of t he
in sula tion of t he bu shing a nd ca n result in explosive failu re, ca using exte nsive
t ra n sfor me r a n d ot he r equipm en t d a m age, a s well a s h aza rds to wor ke rs.
19
bus hings. In conditions t h a t produce deposits, a ligh t a pplica tion of Dow Cor ning
grea se DC-5 or GE In sulgel will help reduce risk of exte rn al flas hover. The
downside of t his t re a t me n t is t h a t a gre ase buildup m ay occu r. In high h u midity
a nd wet a rea s, a be t ter choice m ay be a high qu ality silicone pa st e wax a pplied to
t he porcelain, which will reduce t he risk of fla s hover. A sp r ay-on wa x con t aining
silicone, s uch a s Tu r tle Wax br a n d, h a s been fou nd to be very u seful for cle a ning
a nd waxing in one ope ra tion, providing t he deposit s a re not too h a rd. Wax will
ca use wa ter to for m be a ds r a t her t h a n a con tin uous sheet, which red uces
fla s hover risk. Clea ning m ay involve ju st spr aying wit h Tu r tle W ax a n d wiping
wit h a soft clot h. A lim e re moval product, such as “Lim e Away,” also m ay be
u seful. More st ubborn con t a min a tes m ay require solven t s, st eel wool, a n d
br us hes. A high press u re wa ter s t rea m m ay be required to remove salt a nd ot he r
wa ter soluble deposits. Limestone powde r blas ting wit h d ry air will safely remove
m et a llic oxides, che micals, s alt-ca ke, a n d a lmos t a ny h a rd con t a min a te. Ot he r
m a terials, s uch a s pot te rs clay, waln u t or peca n s hells, or cru shed cocon u t shells,
a re a lso u sed for h a rd con t a min a tes. Ca rbon dioxide (CO 2) pelle t bla sting is more
expen sive bu t vir t u ally elimin a tes cle a n up beca u se it eva por a t es. Grou n d up
cor n-cob bla sting will remove soft pollu t a n ts s uch a s old coa tings of built-up
grea se. A com pe ten t experienced con t r actor should be em ployed a nd a t horough
writ te n job h aza rd a n alysis (J HA) perfor med whe n a ny of t hese t rea t me n t s a re
u sed.
20
in sula tor h a s a la rge chip t h a t reduces t he fla s hover dist a nce or h as a la rge cr ack
tot ally t h rough t he in sula tor, t he bus hing m us t be replaced. Some m a n ufact u re rs
offer repair se rvice to da m aged bu shings t h a t ca n not be rep aired in t he field.
Con t act t he m a n ufact u re r for you r pa r ticula r bushings if you h ave rep air
questions.
The pu rpose of se aling sys tem s is to preve n t a ir a nd mois t u re from con t a min a ting oil
a nd cellulose ins ula tion. Se aling syste ms a re designed to preven t oil inside t he
t ra n sfor me r from coming in to con t act wit h air. Air con t ains moist u re, which ca u ses
sludging a nd a n a bu nd a n t s upply of oxyge n. Oxyge n in combin a tion wit h moist u re
ca uses gre a tly accele r a ted de terior a tion of t he cellulose. This oxyge n-moist u re
com bin a tion will gre a tly reduce se rvice life of t he t r a nsform er.
Se aling system s on m a ny existing Recla m a tion power t r a nsfor mers a re of t he iner t gas
(nit roge n) p ressu re design; however, we h ave m a ny ot her design s. Cu rren t p r actice is
to buy only con serva tor designs wit h bla dders for t r a nsform er volt ages 115 kV a nd
a bove a n d ca pacities above 10 mega-volt-
a m ps (mva). Below t hese values, we buy
only ine rt ga s pressu re system
t ra n sfor me rs, a s depict ed in figu re 8.
4.2.1 S e a li n g S y s t e m s T y p e s.
Fr ee B r e a t h i n g. Se aling syste ms
h ave progressed from e a rly designs
of “free bre a t hing” t a nks, in which F i g u r e 6.—F r e e B r e at h i n g
a n air sp ace on top of t he oil is Tr a n sfor m e r.
21
ven ted to a t mosphere t h rough a bre a t her pipe. The pipe typically is screened to
keep ou t in sects a nd rode n t s a nd t u rned down to preven t r ain from en t ering.
Brea t hing is ca used by expa nsion a n d con t r action of t he oil a s te mper a t u re
ch a nges. These ea rlie r design s did not use a n air drye r, a nd con den sa tion from
mois t u re form ed on inside walls a nd t a n k top. Moist u re, oxyge n, a n d nit roge n
would also dissolve directly in to oil from t he air. This wa s not t he bes t design. As
m en tioned before, a combin a tion of oxygen a n d mois t u re acceler a tes dete rior a tion
of cellulose ins ula tion. Moist u re also decre a ses dielect ric s t rengt h, des t roying
in sula ting qu ality of t he oil, a n d ca uses for m a tion of slu dge. If you h ave one or
more of t hese ea rlie r design t r a nsform ers, it is recom m en ded t h a t a desicca n t type
air d rye r be a dded to t he bre a t her pipe.
S e a le d or P r e ss u r i z e d
B re a t h i n g. This design is
simila r to t he free bre a t hing
one wit h a ddition of a
pressu re/vacu u m bleeder
valve. When t he
t ra nsfor me r wa s ins t alled,
pressu rized dry air or
nit rogen wa s placed on top of
t he oil. The bleeder valve is
designed to hold p ressu re
in side to a pproxim a tely plus
or min u s 5 psi (figu re7). The Fi g u r e 7.—P r e s s u r iz e d Br e a th i n g
sa me problem s wit h Tr a n sfo r m e r.
mois t u re a n d oxyge n occu r
a s p reviously described. P roblem s a re not a s severe beca u se “bre a t hing” is limited
by t he bleeder valve. Air or N 2 is exh a us ted to t he ou t side a t mosp here when a
positive pressu re more t h a n 5 psi occu rs inside t he t a n k. This process does not
a dd moist u re a nd oxyge n to t he t a n k. However, whe n cooling, t he oil con t r act s
a nd, if pressu re falls 5 psi below t he ou tside a t mosphere, t he valve allows ou tside
air in to t he t a nk, which pulls in mois t u re a n d oxygen.
22
con nected to rea d low p ress u re ga s
in side t he t a n k. This gage m ay be
loca ted on t he t r a n sfor me r a nd
nor m ally h a s high a n d low pressu re
ala r m con t acts. See section 4.2.2
which follows.
Ca u ti o n: Wh e n r e p l a c i n g n i tr o g e n
c yl i n d e r s, d o n ot ju s t or d e r a
“n itr o g e n c yli n d e r” fr o m th e l o c a l
w e ld i n g s u p p li e r. N i tr o g e n fo r
tra n sfor m e rs s h o u ld m e e t AS TM
D-1933 Ty p e III w it h - 59 °C d e w
p o i n t a s s p e c ifi e d i n IEE E
C-57.12.00-1993, p ar a gr a p h 6.6.3
[27, 2].
F ig u r e 8.—P r e s s u riz e d In e rt Ga s
4.2.2 Ga s P r e s s u r e Co n tr ol
Tra n sfor m e r.
Co m p o n e n ts. Aft e r 1 m o n t h of
s e r v i c e a n d y e arl y, i n s p e c t th e g a s p r e s s u r e c o n tr ol c o m p o n e n t s. The re is
nor m ally a n a djus t able, t h ree-ele men t p ress u re con t rol syst em for ine rt ga s,
which m ain t ains a p ressu re ra nge of 0.5 to 5 psi in t he t r a n sfor me r t a n k. The re is
also a bleeder valve t h a t exh a us ts ga s to a t mosp here whe n p ress u re exceeds relief
pressu re of t he valve, nor m a lly 5 to 8 psi.
Ca u ti o n: The
com ponen t p a r t
descrip tion s below a re
for t he typical t h ree-
st age pressu re
regula ting equip men t
supplying iner t ga s to
t he t r a n sfor me r. You r
pa rticula r u nit m ay be
diffe re n t, so check you r
t ra n sfor me r inst r uction
m a n u al.
H i g h P r e ss u r e G a g e.
The high pressu re gage
is a t t ached be twee n t he
nit rogen cylin der a nd
high p ress u re regula tor
t h a t in dica tes cylinde r Front View Side View
pressu re. When t he
cylinder is full, t he gage Fi g u r e 9.—G a s P r e s s u r e Co n tr ol
will rea d a pproxim a tely Co m p o n e n t s.
23
2,400 psi. Nor m ally, t he gage will be equipped wit h a low pressu re ala r m t h a t
activa tes when t he cylinde r is ge t ting low (a rou nd 500 psi). However, ga s will s till
be su pplied, a nd t he regula ting equipm en t will con tin ue to fu nction u n til t he
cylinder is em pty. Refe r to figu re 9 for t he following descriptions.
By p a s s V a l v e As se m b ly. The bypa ss valve a sse mbly open s a byp a ss line a rou nd
t he low pressu re regula tor a n d allows t he second s t age of t he high p ressu re
regula tor to fu r nish ga s directly to t he t r a n sfor me r. The pu rpose of t his a sse mbly
is to allow m uch fa st er filling/pu rging of t he ga s sp ace du ring initial in st alla tion
or if t he t r a nsform er t a n k h as to be refilled afte r being opened for inspection.
24
gage on t he t r a n sfor me r or t he low pressu re gage in t he nit rogen cabinet, just to
be su re, before re moving t he dr ain plug.
S h u t off V a l v es. The sh u toff valves a re loca ted ne a r t he top of t he ca binet for t he
pu rpose of isola ting t he t r a nsfor m er t a n k for s hipping or m ain t en a nce. These
valves a re norm ally of double-sea t con st ruction a n d s hould be fully opened agains t
t he stop to preven t ga s le a k age a rou n d t he ste m. A sh u toff valve is also p rovided
for t he pu rpose of sh u t ting off t he nit roge n flow to t he t ra nsfor mer t a nk. This
sh u toff valve m ust be closed p rior to ch a nging cylinde rs to keep t he ga s in t he
t ra n sfor me r t a n k from bleeding off.
Fr ee B r e a t h i n g C on se r v a t o r. This
design a dds a n expa nsion t a n k
(con serva tor) a bove t he t r a n sfor me r so
t h a t t he m ain t a n k m ay be com ple tely
filled wit h oil. Oil expa nsion a nd air
exch a nge wit h t he a t mosphe re (bre a t hing)
occu rs a wa y from t he oil in t he
t ra n sfor me r. This design red uces oxygen
a nd mois t u re con t a min a tion beca use only
a sm all portion of oil is exch a nged be twee n
t he m ain t a n k a nd con serva tor. An oil/air
in terface still exis ts in t he conse rva tor,
exposing t he oil to air. Eve n t u ally, oil in F i g u r e 10.—Fr e e Br e a th i n g
t he conse rva tor is exch a nged wit h oil in Co n s e r v a to r.
t he m ain t a n k, a n d oxyge n a nd ot her
con t a min a tes gain access to t he ins ula tion.
25
con t r act s wit h t he oil a n d isola tes it from t he
a t mosphe re. The in side of t he bla dde r or top
of t he dia p h r agm is open to a t mosp heric
pressu re t h rough a desicca n t air d rye r. As
oil exp a n ds a nd con t r acts a nd a s
a t mosphe ric pressu re ch a nges, t he bla dder
or dia p h r agm “bre a t hes” air in a n d ou t.
This keeps air a n d t r a n sfor me r oil
essen tially a t a t mospheric p ressu re. The oil
level gage on t he con serva tor typically is F i g u r e 11.—Co n s e r v a to r
m agnetic, like t hose me n tioned e a rlie r, w it h B la d d e r.
except t he floa t is positioned nea r t he cen te r
of t he u n d e r s id e of t he bla dder. Wit h a dia p h r agm, t he level in dica tor a r m rides
o n t o p of t he dia p h r agm. Exa mine t he air d ryer periodically a n d ch a nge t he
desicca n t whe n approxim a t ely one-t hird of t he m a terial ch a nges color.
F i g u r e 12.—B la d d e r F a il u r e R e la y.
26
Ca u ti o n: Neve r ope n t he ve n t of t he bla dde r failu re relay u nless you h ave
vacu u m or pressu re equipm en t available. The oil will fall in side t he relay a n d
con serva tor a n d p ull in air from t he ou t side. You will h ave to recom mission t he
relay by valving off t he conse rva tor a nd pressu rizing t he bla dder or by placing a
vacu u m on t he relay. See you r specific t r a nsfor mer in st ruction m a n u al for det a ils.
E v e r y 3 to 5 y e a rs, (if t he conserva tor h a s a dia ph r agm) remove t he conse rva tor
in spection fla nge a nd look in side wit h a flas hligh t. If t he re is a lea k, oil will be on
top of t he dia ph r agm, a nd it m us t be replaced. The new dia p h r agm m a te rial
should be nit rile. If t he conse rva tor h a s a bla dder a n d a bla dder failu re relay, t he
relay will ala r m if t he bla dde r develops a le a k. If t he con se rva tor h a s a bla dder
a nd does not h ave a bladde r failu re relay, in spect t he bla dder by removing t he
mou n ting fla nge a n d look inside wit h a fla shligh t. If t here is oil in t he bot tom of
t he bla dder, a failu re h a s definitely occu r red, a n d t he bla dder m us t be replaced.
Follow proced u res in t he specific t r a n sfor me r ins t r uction m a n u a l for dr aining t he
con serva tor a n d replace men t; designs a nd procedu res va ry a n d will not be covered
he re.
A u xi l i a r y T a n k S e a l i n g
S ys t e m . The a uxilia ry t a n k
sealing sys tem incorpor a tes
a n ext r a t a n k be tween t he
m ain t ra nsfor mer t a nk a n d
t he con serva tor t a nk. Ine r t
ga s (nor m ally nit rogen) is
placed above oil in bot h t he
m ain a nd middle t a n ks.
Only oil in t he top
con serva tor t a n k is exposed
to air. A desicca n t air dryer
m ay or m ay not be inclu ded
on t he brea t her. As oil in
t he m ain t a n k expa nds a n d
con t r act s wit h tem pe r a t u re,
ga s press u re va ries above
t he oil in bot h (figu re 13). Fi g u r e 13.—Au x ili a ry S e ali n g S y s t e m.
27
Ch a nges in ga s press u re ca uses oil to go back a n d fort h betwee n t he middle t a nk
a nd t he con serva tor. Air con t aining oxygen a nd moist u re is not in con t act wit h oil
in t he m ain t r a nsform er t a n k. Oxygen a nd moist u re a re a bsorbed by oil in t he
con serva tor t a n k a n d in t erch a nged wit h oil in t he middle one. Howeve r, since ga s
in t he middle t a n k in t erch a nges wit h ga s in t he m ain t a n k, sm all a mou n ts of
oxyge n a nd moist u re ca rried by ga s s till m a ke t heir way in to t he t ra nsfor mer.
Wit h t his a r r a nge men t, t he conse rva tor does not h ave to be loca t ed above t he
m ain t a n k, which reduces t he ove r all heigh t. If you h ave one or more of t hese type
t ra n sfor me rs wit hou t desicca n t air dryers, t hey should be ins t alled.
4.3 Ga s k e t s
Ga ske ts h a ve seve ral impor t a n t jobs in sealing syste m s [6]. A ga sket m ust cre a t e a
seal a nd hold it ove r a long period of time. It m u st be im perviou s a n d not con t a min a te
t he in sula ting fluid or ga s above t he fluid. It should be ea sily removed a nd replaced.
It m ust be ela stic e nough to flow in to im perfection s on t he sealing su rfaces. It m us t
wit h st a nd high a nd low tem pe r a t u res a nd re m ain resilien t enough to hold t he se al
eve n wit h join t moveme n t from expa nsion, con t r action, a nd vibra tion. It m u st be
resilien t enough to not t a ke a “se t” even t hough exposed for a long time to p ress u re
a pplied wit h bolt torque a nd te mper a t u re ch a nges. It m u st h ave sufficie n t st re ngt h to
resis t cr us hing u n der applied loa d a nd resist blowou t u nder syste m pressu re or
vacu u m. It m us t m ain t ain its in tegrity while being h a ndled or ins t alled. If a ga sket
fails to mee t a ny of t hese criteria, a le a k will result. Ga sket lea ks res ult from
im proper torque, choosing t he wrong type gasket m a t erial, or t he wrong size ga sket.
Im p roper sealing su rface p repa r a tion or t he ga ske t t a king a “se t” (becoming h a rd a nd
losing its resilie nce a n d elas ticity) will also ca use a le a k. Us u ally, ga sket s t a ke a set
a s a res ult of te mper a t u re ext re mes a n d age.
Ca u ti o n: T a k e e x tr a c a r e th a t r u s t a n d d ir t p arti c l e s n e v e r fall i n to t h e
tra n sfor m e r. T h e r e s u lts c o u ld b e c at a s tr o p h i c, w h e n t h e tra n sfor m e r i s
e n e r g iz e d.
Afte r r us t a nd scale h ave been removed, m et al su rfaces should be coa ted wit h Loctite
Ma s ter ga sket No. 518. This m a terial will cu re afte r you bolt up t he ga sket, so
a ddition al glue is not necess a ry. If t he te m per a t u re is 50 °F or more, you ca n bolt up
t he ga sket im media tely. This m a te rial comes in a kit (p a r t No. 22424) wit h prime r, a
t ube of m a terial, a n d inst ructions. If t hese ins t r uction s a re followed, t he seal will la s t
m a ny yea rs, a nd t he ga ske t will be ea sy to re move la ter if necessa ry. If t he
te m per a t u re is u nde r 50 °F, wait abou t ½ to 1 hou r after a pplying t he m a te rial to
su rfaces before bolting. If you a re u sing cork-nit rile or cork-neoprene, you ca n also
28
seal ga sket su rfaces (including t he edge of t he ga ske t) wit h t his s a me m a te rial.
Loctite m a kes ot her sealers t h a t ca n be u sed to se al ga ske ts s uch a s “Hi-t ack.”
GE glyp tol No. 1201B-red ca n also be u sed to p ain t ga sket a n d met al su rfaces, bu t it
t a kes more time a n d you m us t be more ca u tious a bou t tem pe ra t u re. If possible, t his
wor k should be done in te m per a t u res a bove 70 °F to speed pain t cu ring. Allow t he
pain t to com ple tely dry before a pplying glue or t he new ga sket. It is not necessa ry to
remove old glyptol or ot her prime r or old glue if t he su rface is fairly smoot h a nd
u nifor m.
Ca u ti o n: Mos t syn t he tic rubber com pou nds, including nit rile (Bu n a N), con t ain some
ca rbon, which m a kes it semi-conductive. Ta ke ext ra ca re a nd n e v e r drop a ga sket or
pieces of gasket in to a t ra n sfor me r t a n k. The results could be ca t a s t rophic whe n t he
t ra n sfor me r is e nergized.
C hoose t he correct replaceme n t gaske t. The m ain influe nces on gaske t m a t erial
selection a re design of t he ga ske t join t, m axim u m a nd minim u m oper a ting
te m per a t u re, type of fluid con t ained, a n d in ter n al p ressu re of t he t r a nsfor mer.
Cor k-n itril e s hould be u sed if t he join t does n ot h ave grooves or limit s. This
m a terial pe rform s be t te r t h a n cork-neopre ne beca u se it does not t a ke a set a s ea sily
a nd confor m s be t te r to m a ting su rfaces. It also pe rform s be t te r a t highe r
te m per a t u res. Be ext r a ca reful whe n you s tore t his m a t erial beca u se it looks like
cor k-neop re ne (described below), a nd t hey ea sily a re mist a ken for each ot her.
Comp ression is t he s a m e a s for cor k-neop rene, abou t 45%. Cor k-nit rile s hould recover
80% of its t hick ness wit h com pression of 400 psi in accorda nce wit h ASTM F 36.
H a rdness should be 60 to 75 du rom ete r in accorda nce wit h ASTM D2240. (See
published specifica tions for E-98 by m a n ufact u rer Dodge-Regu pol Inc., La nca ste r, PA.)
Ca u ti o n: Co r k-n i tr il e h a s a s h e lf life of o n ly a b o u t 2 y e ar s, s o d o n o t or d e r
a n d s t o c k m or e t h a n c a n b e u s e d d u ri n g t h i s ti m e.
Cor k-N e o pr e n e mixt u re (called coroprene) ca n also be u sed; however, it does not
perfor m a s well a s cor k-nit rile. This m a te rial t a kes a set whe n it is com pressed a n d
should only be used whe n t he re a re no exp a nsion limiting grooves. Using cork-
neop re ne in grooves ca n res ult in le a ks from expa nsion a nd con t raction of m a ting
su rfaces. The m a terial is very porou s a n d s hould be se aled on bot h sides a n d edges
wit h a t hin coa t of Glyptol No. 1201B red or simila r se ale r before in st alling. Glyptol
No. 1201B is a slow d rying pain t used to se al met al fla nges a n d ga sket s, a nd t he p ain t
should be allowed to dry tot ally before in st alla tion. Once com pressed, t his ga sket
should never be re used. These ga sket s should be kept a bove 35 °F before in st a lla tion
to p reve n t t he m from becoming h a rd. Ga sket s should be cu t a n d sealed (pa in ted)
in doors a t tem pe ra t u res above 70 °F for e a se of h a n dling a n d to red uce p ain t cu ring
time. Inst alling neoprene-cor k ga ske ts when tem pe ra t u res a re a t or ne a r freezing
should be avoided beca use t he ga sket could be da m aged a nd lea k. Cork-neopre ne
ga sket s m us t be evenly comp ressed a bou t 43 to 45%. For exa m ple, if t he ga sket is
¼-inch t hick, 0.43 x 0.25 = 0.10. When t he ga ske t is torqued down, it s hould be
29
com pressed abou t 0.10 inch. Or you m ay subt r act 0.1 from ¼ inch to calcula te t he
t hick ness of t he ga sket after it is com pressed. In t his ca se, ¼ = 0.25 so 0.25 min us
0.10 = 0.15 inch would be t he fin al dis t a nce bet wee n t he m a ting su rfaces afte r t he
ga sket is com pressed. In a n em ergency, if comp ression limit s a re required on t his
ga sket, split lock was hers m ay be used. Be nd t he wa she rs u n til t hey a re fla t a n d
in st all e nough of t hem (miniu m of t h ree), eve nly spaced, in t he cen te r of t he ga sket
cross section to preven t excessive comp ression. The t hick ness of t he wa she rs should
be such t h a t t he ga ske t com pression is limited to a pproxim a t ely 43%, as explained
a bove.
Ca u ti o n: Do not confuse t his m a te rial wit h Bu tyl Rubber. B u tyl is not a sa tisfactory
m a terial for t ra nsfor me r gasket s. The te rm s Bu tyl a n d B u n a a re e asily confused, a n d
ca re m us t be t a ken to m a ke s u re Nit rile (Bu n a N) is always used a nd never B u tyl.
Viton should be used only for ga ske ts a nd O-rings in tem pe ra t u res higher t h a n 65 °C
or for a pplica tions requiring motion (sh aft se als, etc.). Viton is ve ry tough a nd we a r
resis t a n t; however, it is ve ry expe nsive ($1,000+ pe r s heet) a n d should not be u sed
u nless it is needed for high wea r or high te mper a t u re a pplica tion s. Viton should only
be used wit h com pression limiter grooves a nd recesses. Ca re s hould be t a ken to store
Nit rile a nd Viton sep a ra tely, or order t hem in differen t colors; t he m a terials look alike
a nd ca n be e a sily confu sed, a nd a m uch more expe nsive ga sket ca n be ins t alled
u n necessa rily. Com pression a nd fill requirem en t s for Viton a re t he a s s a m e as t hose
for nit rile, ou tlined above a nd s hown in t a ble 1.
Ga ske t t hick ness is dete rmined by groove dept h a nd s t a nda rd gas ke t t hick ness.
C hoose t he shee t t hick ness so t h a t one-fou r t h to one-t hird of t he ga ske t will p rot r ude
a bove t he groove; t his is t he a mou n t availa ble to be comp ressed. (See t able 2.) Ga sket
shee ts come in st a n da rd t hick nesses in 1/16-inch increm en t s. Choose one t h a t allows
one-t hird of t he ga sket to s tick ou t above t he groove if you ca n, bu t never choose a
30
Table 1.—Transformer Gasket Application Summary
Best Percent
Gasket Temperature Compres Compatible UV Best
Material Range -sion Fluids Resist Applications
Neoprene -54 to 60 °C 30 Askarels and Yes Use only with
(use Nitrile except (-65 to 140 °F) to hydrocarbon fluids compression limits or
where there is not good with 33 recesses and use only if
ultraviolet [UV] temp. swings UV resistance is needed
exposure) or use Viton
Note: Viton O-rings are best for wear resistance and tolerating temperature variations. Nitrile (Buna N) can also
be used in low wear applications and temperatures less than 65 °C.
31
t hick ness t h a t allows less t h a n one-fou r t h or a s m uch a s one-h alf to prot ru de above
t he groove. Do not t ry to remove old prim er from t he groove.
Horizon t al groove fill is dete r mined by how wide t he groove is. The groove widt h is
equ al to t he ou te r dia me ter (OD) min us t he in ner dia me ter (ID) divided by two:
OD ID
2
. Or ju st me a su re t he groove widt h wit h a n accu r a te caliper.
The widt h of t he groove min us t he widt h of t he gasket is t he room left for t he ga sket to
expa nd while being comp ressed. For nit rile, t he a mou n t of horizon t al room needed is
a bou t 15 to 25%. Therefore, you need to cu t t he ga sket cross section so t h a t it fills
a bou t 75 to 85% of t he widt h of t he groove.
8 6
For exa m ple, a n 8-inch OD groove wit h a 6-inch ID, OD ID is 2 = 1 inch. The refore,
2
t he wid t h of t he groove is 1 inch. Beca u se we h ave to le ave 25% expa nsion sp ace, t he
wid t h of t he ga ske t is 75% of 1 inch, or ¾ inch. So t h a t t he ga sket ca n exp a nd equ ally
towa rd t he cen te r a nd towa rd t he ou tside, you s hould leave one-h alf t he expa nsion
sp ace a t t he in ne r dia m ete r of t he groove a nd one-h alf a t t he ou te r. In t his exa mple,
t here should be a
tot al sp ace of
25% of 1 inch or
(¼ inch) for
expa nsion after
t he ga sket is
in ser ted, so you
should le ave
-inch sp ace a t
t he OD a nd
-inch sp ace a t CROSS SECTION OF CIRCULAR GASKET IN GROOVE
t he ID. See
figu re 14. Fi g u r e 14.—Cr o s s S e c ti o n of Cir c u la r G a s k e t i n Gr o o v e.
To check you rself, subt ract t he in ner r a dius from t he ou ter to m a ke su re you ge t t he
sa me ga ske t wid t h calcula ted a bove. In t his exa m ple, 3 -inches (ou ter ra dius, ½ of
7¾), min us 3 inches (in ner ra dius, ½ of 6¼), is ¾ inch, which is t he cor rect ga sket
wid t h.
32
a d hesive (s upe r glue). There a re m a ny types of t his glue; only a few of t hem work well
wit h nit rile, a nd t hey all h ave a ve ry limited shelf life. Re mem ber to always keep
t hem refrige r a ted to exten d shelf life. The one proven to st a n d u p best to tem per a t u re
ch a nges a nd com pression is Lawson R ubbe r Bon der No. 92081. The Lawson p a rt
n u mber is 90286, a nd it is available from La wson P roduct s Co. in Reno, Neva da,
(702-856-1381). Loctite 404 is com monly a vailable a t NAPA a u to pa r ts s tores a nd
wor ks also bu t does not s u rvive te mpe r a t u re va ria tions a s well. S helf life is critical. A
new su pply s hould al w a y s be obt ained whe n a ga sketing job is st a r ted; n e v e r u se a n
old bot tle t h a t h a s bee n on t he s helf since t he la st job.
When bonding t he e nds of ribbon toget her, e nds should be cu t a t a n a ngle (sca rfed) a t
a bou t 15 degrees. The best bon d occu rs whe n t he le ngt h of t he a ngle cu t is a bou t
fou r times t he t hick ness of t he ga sket. Wit h pr actice, a craftspe rson ca n cu t 15-degree
sca rfs wit h a u tility knife. A jig ca n also be m a de from wood to hold t he ga ske t a t a
15-degree a ngle for cu t ting a n d sa nding. The en ds m ay be fu r t he r fine-sa nded or
grou n d on a fine bench grin der wheel to m a tch pe rfectly before a pplying glue. A jig
ca n be fabrica ted to hold t he ga sket a t 15 degrees while cu t ting, sa nding, or grinding.
Ca u ti o n: Nit rile (Bu n a N) is a syn t he tic r ubbe r com pou n d a n d, a s cove r bolts a re
tigh tened, t he ga sket is comp ressed. Thickness of t he ga ske t is decrea sed a n d t he
33
wid t h is increa sed. If a ga ske t is too la rge,
r ubber will be pressed in to t he void
betwee n t he cove r a n d t he se aling su rface.
This will p reve n t a me t al-to-me t al seal,
a n d a le a k will res ult. It is bes t if t he cross
section al a re a of t he ga sket is a lit tle
sm alle r t h a n t he groove cross section al
a rea. As cover bolt s a re tigh te ned, t he
t hick ness of t he gasket decre a ses bu t t he
wid t h increa ses so t h a t cross section al a re a
(t hick ness tim es t he widt h) re m a in s t he
sa me. C a re m u st be t a ke n to e nsu re t h a t
t he ga sket cross section al a re a is e q u al to
o r s li g h tly s m all e r (neve r la rge r) t h a n
t he groove cross section al a re a. This will
provide space for t he rubber to expa nd in
t he groove so t h a t it will not be forced ou t
in to t he met al-to-met al con t act a re a. (See
figu re 15.) If it is forced ou t in to t he
“me t al-to-me t al” seal a rea, a le a k gene r ally
will be t he result. W hen t his h a ppen s, ou r
firs t response is to tigh te n t he bolts, which
ben ds t he cover a rou n d t he ga sket m a te rial
in t he me t al-to-me t al con t act a re a. The
le a k m ay stop (or more ofte n not); bu t t he F i g u r e 15.—Cr o s s S e c ti o n of G a s k e t
next time t he cover is removed, ge t ting a R e m ai n s Co n s ta n t B efor e Ti g h t e n i n g
prope r se al is almost impossible beca use a n d Afte r. w x d = g w x g t
t he cove r is be n t. Ta ke ext r a ca re sizing
t he ga sket, a n d t hese p roble ms won’t occu r.
Thin me t al cond uctive shim s tock m ay be folded over t he ou ter perime ter a rou n d
a pproxim a t ely one-h alf t he circu mference. These pieces of shim stock s hould be evenly
sp aced a rou nd t he circu mference a nd stick fa r enough in towa rd t he cen ter so t h a t
t hey will be held when t he bolts a re tigh tened. As a n exa mple, if t he ga ske t is
8 inches in dia me ter, t he circu mfe re nce would be D or 3.1416 times 8 inches =
25.13 inches in circu mference. Fifty percen t of 25.13 is abou t 12½ inches. C u t
12 s t rips 1-inch wide a nd long enough to be cla m ped by t he fla nge top a nd bot tom
34
when tigh te ned. Fold t he m ove r t he ou tside edge of t he ga sket leaving a lit tle more
t h a n 1-inch space bet wee n, so t h a t t he s him stock pieces will be more or less evenly
sp aced a rou nd t he circu mference.
N o t e: F ailu re to provide a pa t h for st a tic elect ric ch a rges to ge t to grou nd will result
in coron a disch a rges be tween t he grou nd sleeve a n d t he bu shing fla nge. The ga sket
will be r apidly dest royed, a n d a le a k will be t he result.
B olti n g s e q u e n c e s to a v o i d s e a li n g
p r o bl e m s: If prope r bolt tigh tening
sequences a re not followed or im proper
torque a pplied to t he bolt s, se aling
proble m s will result. The res ulting
proble m is illus t r a t ed in figu re 16. A
sligh t bow in t he fla nge or lid top
(exagger a ted for illu st r a tion) occu rs, which
a pplies u neven pressu re to t he ga ske t.
This bow com promises t he se al, a nd t he F i g u r e 16.—B o w i n g a t Fl a n g e s.
ga sket will even t u ally lea k.
P rope r bolting seque nces a re illus t r a ted for va rious type fla nges/covers in figu re 17.
Bolt n u mbers s how t he cor rect tigh tening seque nces.
4.4.2 D i s s o lv e d Ga s An al y s i s. Aft e r 1 m o n th of s e r v i c e a n d o n c e e a c h
y e ar, a n d more oft en if a problem is e ncou n te red, do a DGA. This is by fa r t he
mos t im port a n t tool for de ter mining t he he alt h of a t r a nsfor me r.
35
F i g u r e 17.—B o lt Ti g h t e n i n g S e q u e n c e s.
The pu rpose of t his section is to provide guida nce in in te rpre ting DGA a n d to
sugges t action s ba sed on t he a n alysis. The re a re no “quick a nd su re” ea sy
a nswe rs when de aling wit h t r a n sfor me rs. Tr a n sfor me rs a re ve ry complex, ve ry
expen sive, a nd ve ry im por t a n t to Recla m a tion; a n d e ach one is differen t.
Decisions m ust be ba sed on experienced judgm en t fou nded on all availa ble da t a
a nd con sult a tion wit h expe rie nced people. Along wit h t horough periodic
in spection s cove red e a rlier, t he most im por t a n t key to t r a nsform er life is pe riodic
DGA a nd proper in terpret a tion. E ach DGA m us t be comp a red to p rior DGAs so
t h a t t re nds ca n be recognized a nd r a tes of ga s gene r a tion est ablis hed.
36
Alt h o u g h e x a m p l e s w ill b e p r e s e n t e d la t e r, t h e r e i s n o u n i v e r s all y
a c c e p t e d m e a n s for i n t e r p r e ti n g DGA [15]. Tr a n sfor me rs a re ve ry complex.
Aging, chemical actions a nd re actions, elect ric fields, m a gne tic fields, t he rm al
con t r action a nd exp a n sion, loa d va ria tions, gr avity, a nd ot he r forces all in ter act
in side t he t a n k. Exte rn ally, t h rough-fa ult s, volt age su rges, wide a m bie n t
te m per a t u re ch a nges, a nd ot he r forces such a s t he e a rt h’s m agnetic field a nd
gr avity affect t he t ra n sfor me r. The re a re few if a ny “cu t a nd d ried” DGA
in terpret a tions; eve n exper t s dis agree. Cons ult a tion wit h ot he rs, expe rie nce,
st u dy, comp a ring e a rlie r DGA’s, keeping accu r a te records of a t r a nsform er’s
history, a nd noting infor m a tion fou nd whe n a t r a n sfor me r is disa ssem bled will
increa se exper tise a n d p rovide life extension to t his critical equip men t.
Co n d iti o n 1: Tot al dissolved combus tible ga s (TDCG) below t his level indica tes
t he t r a n sfor me r is ope r a ting s a tisfactorily. Any individ u al combu stible ga s
exceeding specified levels in t a ble 4 should h ave a ddition al inves tiga tion.
37
Table 4.—Dissolved Key Gas Concentration Limits in Parts Per Million (ppm)
1
CO2 is not included in adding the numbers for TDCG because it is not a combustible gas.
Co n d iti o n 2: TDCG wit hin t his r a nge indica tes gre a te r t h a n nor m al combus tible
ga s level. Any individu a l combus tible ga s exceeding specified levels in t able 4
should h ave a ddition al inves tiga tion. A fa ult m ay be p rese n t. Ta ke DGA s a mples
a t lea st ofte n enough to calcula te t he a mou n t of gas gene r a tion per day for each
ga s. (See t able 5 for recom men ded sa mpling frequency a n d action s.)
Co n d iti o n 3: TDCG wit hin t his r a nge indica tes a high level of decomposition of
cellulose ins ula tion a nd/or oil. Any individu a l combus tible ga s exceeding specified
levels in t able 4 should h ave a ddition al investiga tion. A fa ult or fa ults a re
probably prese n t. Ta ke DGA sa m ples a t le a st often enough to calcula t e t he
a mou n t of ga s gene ra tion pe r d ay for each ga s. (See t a ble 5.)
A s u d d e n i n c r e a s e i n k e y g a s e s a n d th e r a te of g a s p r o d u c ti o n i s m or e
i m p o rt a n t i n e v a l u ati n g a tr a n sfor m e r t h a n t h e a m o u n t of g a s. One
exception is ace tylene (C 2 H 2). The gene r a tion of a ny a mou n t of t his ga s a bove a
few ppm in dica tes high energy a rcing. Trace a mou n t s (a few pp m) ca n be
gene r a t ed by a very hot t her m al fa ult (500 °C). A one-time a rc ca u sed by a ne a rby
ligh t ning st rike or a high-volt age su rge ca n ge ner a te acetyle ne. If C 2 H 2 is fou nd in
t he DGA, oil s a mples should be t a ken weekly to dete rmine if a ddition al acetyle ne
is being gene r a ted. If no addition al ace tylene is fou n d a n d t he level is below t he
IE E E Condition 4, t he t r a nsform er m ay con tin ue in se rvice. Howeve r, if
acetyle ne con tin ues to increa se, t he t r a nsfor me r h a s a n active high ene rgy
38
Table 5.—Actions Based on Dissolved Combustible Gas
NOTES: 1. Either the Highest Condition Based on Individual Gas or Total Dissolved Combustible Gas can
determine the condition (1,2,3, or 4) of the transformer [11]. For example, if the TDCG is between 1,941 ppm and
2,630 ppm, this indicates Condition 3. However ,if hydrogen is greater than 1,800 ppm, the transformer is in
Condition 4, as shown in table 4..
2. When the table says “determine load dependence,” this means, if possible, find out if the gas generation rate in
ppm/day goes up and down with load. Perhaps the transformer is overloaded. Take oil samples every time the load
changes; if load changes are too frequent, this may not be possible.
3. To get TDCG generation rate, divide the change in TDCG by the number of days between samples that the
transformer has been loaded. Down-days should not be included. The individual gas generation rate ppm/day is
determined by the same method.
39
Fi g u r e 18.—Co m b u s tib l e G a s Ge n e r ati o n Ve r s u s T e m p e r at u r e.
41
spect rome ter. This ch a rt wa s u sed by R.R. Rogers of t he Ce n t r al Elect ric
Gene ra ting Boa rd (C EGB) of E ngla nd to develop t he “Rogers Ra tio Met hod” of
a n alyzing t r a nsfor m ers (discu ssed la ter).
42
to becom e loose a nd fall a nd become u ngrou n ded. S t a tic ca n t hen build up a nd
disch a rge to a grou nded su rface a nd prod uce “hot me t al” ga ses. An u nin ten tion al
core grou nd wit h circula ting cu r ren t s ca n also prod uce t hese ga ses. There a re
m a ny ot her exa m ples.
Notice t h a t bot h type fa ult s (t her m al a n d elect rical) m ay be occu r ring a t once, a nd
one m ay ca u se t he ot he r. The a ssocia tions do not me n tion m agne tic fa ults;
howeve r, m agne tic fa ult s (s uch a s s t r ay m agnetic flux im pinging t he steel t a nk or
ot her m agnetic st r uct u res) also ca use hot spots.
If one or more com bustible ga s ge ner a tion r a tes a re equ al to or exceed G2 limit s
(50% of L1 limits pe r mon t h), t his t r a n sfor me r should be con side red in critical
con dition. You m ay wa n t to reduce sa m ple in te rvals to mon t hly or weekly, pla n
a n ou t age, pla n to rebuild or replace t he t r a nsfor me r, e tc. If a n active a rc is
43
Table 6.—TOA L1 Limits and Generation Rate Per Month Alarm Limits
G1 Limits G2 Limits
GAS L1 Limits (ppm per month) (ppm per month)
H2 100 10 50
CH4 75 8 38
C2H2 3 3 3
C2H4 75 8 38
C2 H6 75 8 38
CO 700 70 350
prese n t (C 2 H 2 ge ner a tion), or if ot he r hea t ga ses a re high (above Con dition 4 limits
in t a ble 4), a n d G2 limit s a re exceeded, t he t r a nsform er should be re moved from
service.
2. Ope ra ting t r a nsform ers a t s us t ained overloa d will gene ra te combu stible ga ses.
4. A blocked oil duct inside t he t r a nsform er ca n ca use local ove rhe a ting,
gene r a ting ga ses.
6. Oil circula ting p u m p proble m s (bea ring wea r, im pelle r loose or wor n) ca n ca use
t ra n sfor me r cooling proble m s.
7. Oil level is too low; t his will not be obvious if t he level indica tor is inoper a tive.
8. Slu dge in t he t r a nsfor mer a n d cooling syste m. (See “3. Tr a n sfor me r Cooling
Me t hods.”)
44
Table 7.—Fault Types
H2, possible trace of CH4 and Partial discharges (corona) Weakened insulation from aging
and electrical stress.
C2H6. Possible CO.
H2, CH4, (some CO if discharges Low energy discharges Pinhole punctures in paper
involve paper insulation). (sparking). insulation with carbon and
Possible trace amounts of C2 carbon tracking. Possible
H6. (May be static discharges) carbon particles in oil. Possible
loose shield, poor grounding of
metal objects
H2, CH4, C2 H6, C2H4, and the High energy discharges Metal fusion, (poor contacts in
key gas for arcing C2 H2 will be tap changer or lead
present perhaps in large (arcing) connections). Weakened
amounts. If C2 H2 is being insulation, from aging and
generated, arcing is still going electrical stress. Carbonized oil.
on. CO will be present if paper is Paper destruction if it is in the
being heated. arc path or overheated.
H2, CO, CH4, C2H6, C2 H4. Thermal fault between 300 °C Paper insulation destroyed. Oil
and 700 °C heavily carbonized.
All the above gases and High energy electrical arcing Same as above with metal
acetylene in large amounts. discoloration. Arcing may have
700 °C and above. caused a thermal fault.
10. An u nin te n tion al core grou n d m ay ca u se hea ting by providing a p a t h for st ray
cu r ren t s.
12. A hot-spot m ay also be ca u sed by disch a rges of st a tic elect rical ch a rges t h a t
build u p on s hields or core a n d s t r uct u res which a re not properly grou nded.
13. Hot-spots m ay be ca u sed by elect rica l a rcing betwee n windings a n d grou nd,
betwee n windings of diffe re n t pote n tial, or in a rea s of differen t poten tial on t he
sa me win ding, d ue to dete riora ted or d a m aged insula tion.
45
wedges. The res ult m ay be a rcing in t he t r a nsfor m er, begin ning a t t he time of t he
fa ult, or t he insula tion m ay be wea ke ned a nd a rcing develop la te r.
15. Ins ula tion ca n also be d a m aged by a volt a ge su rge such a s a nea rby ligh t ning
st rike or switching su rge or closing ou t of step, which m ay result in im media te
a rcing or a rcing t h a t develops la t er.
16. Ins ula tion m a y be de terior a ted from age a nd simply wor n ou t. Clea r a nces
a nd dielect ric s t rengt h a re red uced, allowing p a rtial disch a rges a n d a rcing to
develop. This ca n also reduce physical st re ngt h allowing wedging a n d windings to
move exten sively du ring a t h rough-fa ult, ca u sing tot al mech a nical a nd elect rical
failu re.
46
F rom t he solubility t able 8 below, comp a ring hydrogen wit h a solubility of 7% a n d
acetyle ne wit h solubility of 400%, you ca n see t h a t t r a nsfor m er oil h a s a m uch
grea te r ca p acity for dissolving acetyle ne. However, 7% hyd roge n by volu me
represe n ts 70,000 pp m, a nd 400% acetyle ne represe n t s 4,000,000 pp m. You will
probably neve r see a DGA wit h n u m be rs t his high. Nit rogen ca n a pproach
m axim u m level if t he re is a pressu rized nit rogen bla n ket above t he oil. Ta ble 8
shows t he m a x i m u m a mou n t of e ach ga s t h a t t he oil is ca pa ble of dissolving a t
st a nd a rd te mper a t u re a nd p ressu re. At t hese levels, t he oil is said to be
sa t u r a ted.
Table 8.—Dissolved Gas Solubility in Transformer Oil Accurate Only at STP, 25 °C (77 °F)
and 14.7 psi (29.93 inches of mercury)
Solubility in
Transformer Oil Equivalent
Dissolved Gas Formula (% by Volume) (ppm by Volume) Primary Causes/Sources
Overheated cellulose,
Carbon Dioxide CO 2 120.0 1,200,00
atmosphere
47
t ra n sfor me r’s service life to est ablis h a ba seline DGA; t h e n t a k e s a m p l e s a t l e a s t
a n n u ally. The nit roge n a nd oxygen ca n be com pa red wit h e a rlier DGAs; a nd if t hey
increa se, it is a good indica tion of a le a k. If t he t r a n sfor me r oil h a s eve r been de-
ga ssed, nit rogen a nd oxyge n should be low in t he DGA. It is ext re mely impor t a n t to
keep accu ra te records ove r a t r a nsform er’s life; whe n a proble m occu rs, recorded
inform a tion helps gre a tly in t roubles hooting.
D i s sol v e d G a s A n a ly s i s De t ec t i o n L i m i t s.
When a fa ult occu rs in side a t ra nsfor mer, t he re is no problem wit h miniu m gas
a mou n t s a t which t he r a tio a re valid. The re will be more t h a n e nough ga s prese n t.
48
If a t r a nsfor me r h a s been ope r a ting nor m ally for some tim e a n d a DGA s hows a
sudden increa se in t he a mou n t of gas, t he firs t t hing to do is t a ke a second sa m ple to
verify t here is a problem. Oil sa m ples a re e a sily con t a min a ted du ring sa m pling or a t
t he la b. If t he next DGA s hows ga ses to be more in line wit h prior DGAs, t he ea rlier
oil s a m ple wa s con t a min a ted, a nd t here is no fu rt her ca use for conce rn. If t he
secon d s a mple also s hows incre a ses in ga ses, t he problem is real. To apply R a tio
Me t hods, it helps to subt ract ga ses t h a t we re p resen t prior to s udden gas increa ses.
This t a kes ou t ga ses t h a t h ave bee n ge ner a ted up to t his poin t d ue to nor m al aging
a nd from prior problem s. This is especially t r ue for ra tios using H 2 a nd t he cellulose
in sula tion ga ses CO a n d CO 2 [12]. These a re gene ra ted by nor m al aging.
C 2 H 2 /C 2 H 4 , CH 4/H 2, C 2 H 4/C 2 H 6
49
Table 9.—Rogers Ratios for Key Gases
Code range of ratios C 2H2 CH4 C2H4 Detection limits and 10 x detection limits are shown below:
C2H4 H2 C2H6 C2H2 1 ppm 10 ppm
C2H4 1 ppm 10 ppm
<0.1 0 1 0 CH4 1 ppm 10 ppm
0.1-1 1 0 0 H2 5 ppm 50 ppm
1-3 1 2 1 C2H6 1 ppm 10 ppm
>3 2 2 2
Case Fault Type Problems Found
0 No fault 0 0 0 Normal aging
1 Low energy partial 1 1 0 Electric discharges in bubbles, caused by insulation voids or super
discharge gas saturation in oil or cavitation (from pumps) or high moisture in
oil (water vapor bubbles).
2 High energy 1 1 0 Same as above but leading to tracking or perforation of solid
partial discharge cellulose insulation by sparking, or arcing; this generally produces
CO and CO2.
3 Low energy 1-2 0 1-2 Continuous sparking in oil between bad connections of different
discharges, potential or to floating potential (poorly grounded shield etc);
sparking, arcing breakdown of oil dielectric between solid insulation materials.
4 High energy 1 0 2 Discharges (arcing ) with power follow through; arcing breakdown of
discharges, arcing oil between windings or coils, or between coils and ground, or load
tap changer arcing across the contacts during switching with the oil
leaking into the main tank.
5 Thermal fault less 0 0 1 Insulated conductor overheating; this generally produces CO and
than 150 °C CO2 because this type of fault generally involves cellulose
(see note 2) insulation.
6 Thermal fault 0 2 0 Spot overheating in the core due to flux concentrations.
temp. range Items below are in order of increasing temperatures of hot spots.
150-300 °C Small hot spots in core. Shorted laminations in core. Overheating
(see note 3) of copper conductor from eddy currents. Bad connection on
winding to incoming lead, or bad contacts on load or no-load tap
7 Thermal fault 0 2 1 changer. Circulating currents in core; this could be an extra core
temp. range ground, (circulating currents in the tank and core); this could also
300-700 °C mean stray flux in the tank.
8 Thermal fault 0 2 2 These problems may involve cellulose insulation which will produce
temp. range over CO and CO2.
700 °C
(see note 4)
Notes: 1. There will be a tendency for ratio C2H2 /C2H4 to rise from 0.1 to above 3 and the ratio C2H4 /C2H6 to rise from 1-3 to above 3
as the spark increases in intensity. The code at the beginning stage will then be 1 0 1.
2. These gases come mainly from the decomposition of the cellulose which explains the zeros in this code.
3. This fault condition is normally indicated by increasing gas concentrations. CH4 /H2 is normally about 1, the actual value above or
below 1, is dependent on many factors such as the oil preservation system (conservator, N2 blanket, etc.), the oil temperature, and oil
quality.
4. Increasing values of C2H2 (more than trace amounts), generally indicates a hot spot higher than 700 °C. This generally indicates
arcing in the transformer. If acetylene is increasing and especially if the generation rate is increasing, the transformer should be de-
energized, further operation is extremely hazardous.
1. Values quoted for ratios should be regarded as typical (not absolute). This means that the ratio numbers are not “carved in stone”;
there may be transformers with the same problems whose ratio numbers fall outside the ratios shown at the top of the table.
2. Combinations of ratios not included in the above codes may occur in the field. If this occurs, the Rogers Ratio Method will not work
for analyzing these cases.
3. Transformers with on-load tap changers may indicate faults of code type 2 0 2 or 1 0 2 depending on the amount of oil interchange
between the tap changer tank and the main tank.
50
Exa mple 1
Example 2
Ethylene (C2H4) 25 4 17
Acetylene (C2H2) 2 0 0
51
Rogers Ratio Analysis Based on Latest DGA:
Codes
The t r a nsfor m er in t his exa m ple is one of t h ree sis ter t ra nsfor mers t h a t h ave h a d
increa sed cooling inst alled a n d a re ru n ning highe r loa ds due to a ge ner a tor
u pgr a de seve ral ye a rs ago. Tr a n sfor me r sou nd level (h u m) is m a rkedly highe r
t h a n for t he t wo siste r t r a nsform ers. The u nit bre a ker experienced a fa ult some
ye a rs ago, which placed high mech a nical s t resses on t he t ra nsfor me r. This
ge ne r ally me a n s loose windings, which ca n gene ra te ga s due to friction (called a
t her m al fa ult) by Rogers Ra tios. Comp a rison wit h siste r u nit s reve als a lmos t
t riple t he e t h a ne a s t he ot he r two, a nd it is a bove t he IE E E Condition 4.Ga ses a re
increa sing slowly; t here h as been no su dde n r a te incre a se in com bustible ga s
production. Notice t he la rge incre ase in O 2 a nd N 2 be tween t he first a nd second
DGA a nd t he la rge decre ase be twee n t he secon d a n d t hird. This p roba bly me a ns
t h a t t he oil s a m ple wa s exposed to air (a t mosp here) a nd t h a t t hese two ga ses a re
in accu r a t e in t he middle sa mple.
For m a tion of CO 2 a n d CO from t he degr a d a tion of oil im p regn a ted pa pe r increa ses
r a pidly wit h tem pe ra t u re. CO 2 /CO r a tios less t h a n t h ree a re ge ner ally conside red
a n indica tion of probable pa pe r involve men t in a n elect rical fa ult (a rcing or
sp a r king), along wit h some ca rboniza tion of p a per. Norm al CO 2 /CO ra tios a re
typically a rou nd seve n. Ra tios a bove 10 gene r ally indica te a t he rm al fa ult wit h
t he involveme n t of cellulose. T h i s i s o n l y tr u e if th e CO 2 c a m e fr o m w it h i n
t h e tr a n sfo r m e r (n o l e a k s), a n d t h e s e r a ti o s ar e o n l y m e a n i n gfu l if t h e r e
i s a s ig n ific a n t a m o u n t of b ot h g a s e s. C a u tion m u st be em ployed beca use oil
52
degr a da tion also produces t hese ga ses, a nd CO 2 ca n also be dissolved in t he oil
from a t mosphe ric le a ks. The oil sa m ple ca n also pick up CO 2 a nd O 2 if it is
exposed to air du ring sa m pling or h a ndling a t t he lab. If a fa ult is s uspected, look
ca refully to see if CO is incre a sing. If CO is incre a sing a rou n d 70 ppm or more pe r
mon t h (gene ra tion limit from IEC 60599), t he re is p robably a fa ult. It is a good
idea to s ubt r act t he a mou n t of CO a nd CO 2 s hown before t he incre a se in CO a n d
CO 2 bega n, so t h a t only ga ses ca used by t he presen t fa ult a re u sed in t he r a tio.
This will elimin a te CO a nd CO 2 gene ra ted by nor m al aging a n d ot her sou rces.
When excessive cellulose degr a da tion is s uspected (CO 2 /CO r a tios less t h a n 3, or
grea te r t h a n 10), it m ay be a dvis able to a sk for a fu r a n a n alysis wit h t he next
DGA. This will give a n in dica tion of u seful life left in t he pa pe r insula tion [12].
You ca n not de-ene rgize a t ra nsfor me r ba sed on fu ra n a n alysis alone. All t his tes t
does is g i v e a n i n d i c a tio n of t he he alt h of t he p a per; it is not a su re t hing. B u t
fu r a n a n alysis is recom me nded by m a ny exper t s to give a n indica tion of re m a ining
life whe n t he CO 2 /CO r a tio is less t h a n 3 or grea te r t h a n 10. Som e oil
la bor a tories do t his tes t on a rou tine basis, a nd some ch a rge ext r a for it.
Ta ble 10 is a da p ted from IEC 60599 Appe ndix A.1.1 [12]. Some of t he wording
h as been ch a nged to reflect Am erica n la ngu age u sage r a t he r t h a n E u rope a n.
4.5 Mo i s tu r e P r ob l e m s
Moist u re, especially in t he prese nce of oxygen, is ext rem ely h aza rdou s to t ra nsfor mer
in sula tion. E ach DGA a nd Doble t es t res ult should be exa mined ca refully to see if
wa ter is increa sing a nd to de ter mine t he mois t u re by dry weigh t (M/DW) or pe rcen t
sa t u r a tion t h a t is in t he pa per insula tion. W hen 2% M/DW is re ached, pla n s should be
m a de for a d ry ou t. Never allow t he M/DW to go above 2.5% in t he p aper or 30% oil
sa t u r a tion wit hou t d rying ou t t he t r a nsform er. E ach tim e t he moist u re is doubled in a
t ra nsfor me r, t he life of t he in sula tion is cu t by one-h alf. Keep in mind t h a t t he life of
t he t r a n sfor me r is t he life of t he pa pe r, a n d t he pu rpose of t he pa per is to keep ou t
mois t u re a n d oxyge n. For se rvice-aged t r a nsform ers r a t ed less t h a n 69 kV, result s of
u p to 35 ppm a re con side red accep t a ble. For 69 kV t h rough 288 kV, t he DGA tes t
result of 25 ppm is conside red accep t able. For gre a t er t h a n 288 kV, moist u re s hould
not exceed 20 pp m. Howeve r, t he u se of a bsolu te values for wa te r does not always
gu a r a n tee s afe conditions, a n d t he percen t by dry weigh t s hould be dete r mined. See
t able 12, “Doble Limits for In-Se rvice Oils,” in section 4.6.5. If va lues a re higher, t he
oil s hould be processed. If t he t r a n sfor me r is kept a s dry a nd free of oxyge n a s
possible, t r a nsform er life will be exte nded.
Recla m a tion specifies t h a t m a n ufact u rers dry new t r a nsform ers to no more t h a n 0.5%
M/DW du ring com missioning. In a t r a nsform er h aving 10,000 pou nds of p a per
in sula tion, t his me a ns t h a t 10,000 x 0.005 = 50 pou n ds of wa ter (a bou t 6 gallons) is in
t he pa pe r. This is not e nough moist u re to be de t rime n t al to elect rica l in tegrity. When
t he t r a n sfor me r is new, t his wa te r is dist ribu ted equ ally t h rough t he t r a nsform er. It
is ext re mely im por t a n t to re move a s m uch wa te r a s possible.
53
Table 10.—Typical Faults in Power Transformers [12]
Fault Examples
Discharges of Sparking or arcing between bad connections of different floating potential, from
low energy shielding rings, toroids, adjacent discs or conductors of different windings,
broken brazing, closed loops in the core. Additional core grounds. Discharges
between clamping parts, bushing and tank, high voltage and ground, within
windings. Tracking in wood blocks, glue of insulating beam, winding spacers.
Dielectric breakdown of oil, load tap changer breaking contact.
Discharges of Flashover, tracking or arcing of high local energy or with power follow-through.
high energy Short circuits between low voltage and ground, connectors, windings, bushings,
and tank, windings and core, copper bus and tank, in oil duct. Closed loops
between two adjacent conductors around the main magnetic flux, insulated bolts
of core, metal rings holding core legs.
Overheating less Overloading the transformer in emergency situations. Blocked or restricted oil
than 300 °C flow in windings. Other cooling problem, pumps valves, etc. See the “Cooling”
section in this document. Stray flux in damping beams of yoke.
Overheating Defective contacts at bolted connections (especially busbar), contacts within tap
changer, connections between cable and draw-rod of bushings.
300 to 700 °C Circulating currents between yoke clamps and bolts, clamps and laminations, in
ground wiring, bad welds or clamps in magnetic shields.
Abraded insulation between adjacent parallel conductors in windings.
Overheating Large circulating currents in tank and core. Minor currents in tank walls created
over 700 °C by high uncompensated magnetic field. Shorted core laminations.
Notes:
1. X wax formation comes from Paraffinic oils (paraffin based). These are not used in transformers at present
in the United States but are predominate in Europe.
2. The last overheating problem in the table says over 700 °C.” Recent laboratory discoveries have found
that acetylene can be produced in trace amounts at 500 °C, which is not reflected in this table. We have several
transformers that show trace amounts of acetylene that are probably not active arcing but are the result of high-
temperature thermal faults as in the example. It may also be the result of one arc, due to a nearby lightning strike or
voltage surge.
3. A bad connection at the bottom of a bushing can be confirmed by comparing infrared scans of the top of the
bushing with a sister bushing. When loaded, heat from a poor connection at the bottom will migrate to the top of the
bushing, which will display a markedly higher temperature. If the top connection is checked and found tight, the
problem is probably a bad connection at the bottom of the bushing.
54
When t he t r a nsfor mer is e nergized, wa te r begins to migr a te to t he cooles t pa rt of t he
t ra n sfor me r a n d t he site of t he gre a test elect rical st ress. This loca tion is norm ally t he
in sula tion in t he lower one-t hird of t he winding [5]. P a pe r ins ula tion h a s a m uch
grea te r affinity for wa te r t h a n does t he oil. The wa te r will dist ribu te itself u nequ ally,
wit h m uch more wa t er being in t he p a per t h a n in t he oil. The pa pe r will p a r tially d ry
t he oil by a bsorbing wa ter ou t of t he oil. Tem pe ra t u re is also a big factor in how t he
wa ter dis t ribu tes it self bet wee n t he oil a nd p aper. See t a ble 11 below for com p a rison.
The t a ble a bove shows t he t re men dou s a t t r action t h a t p a per in sula tion h a s for wa ter.
The ppm of wa ter in oil shown in t he DGA is only a s m all p a r t of t he wa ter in t he
t ra n sfor me r. It is im port a n t t h a t, whe n a n oil s a m ple is t a ke n, you record t he oil
te m per a t u re from t he top oil tem per a t u re gage.
Some labora tories give pe rce n t M/DW of t he ins ula tion in t he DGA. Ot hers give
perce n t oil sa t u r a tion, a nd some give only t he ppm of wa te r in t he oil. If you h ave a n
accu r a te te mper a t u re of t he oil a n d t he pp m of wa te r, t he Nomogra p h (figu re 23,
section 4.5.2) will give percen t M/DW of t he insula tion a n d t he perce n t oil sa t u r a tion.
55
in side t he st r uct u re, ca using t r a nsform er cooling to be less efficien t, a nd slowly over
time tem pe ra t u re rises. (This wa s discu ssed ea rlie r in “3. Tr a nsform er Cooling
Me t hods.”) Acids ca use a n increa se in t he r a te of decay, which for ms more acid,
sludge, a n d mois t u re a t a fa ste r r a t e [20]. This is a viciou s cycle of increa sing speed
for ming more acid a n d ca using more decay. The a nswe r is to keep t he t r a n sfor me r a s
d ry a s possible a nd a s free of oxyge n a s possible. In addition, oxygen in hibitor should
be wa tched in t he DGA testing. The t r a nsform er oil s hould be dried whe n mois t u re
reaches t he values according to t able 12. In hibitor should be a dded (0.3% by weigh t
ASTM D-3787) when t he oil is processed.
56
cools, dissolved moist u re for m s a n em ulsion [20]. A wa te r/oil e m ulsion ca uses dr a stic
reduction in dielect ric st rengt h.
How m uch moist u re in insula tion is too m uch? Whe n t he in sula tion get s to 2.5%
M/DW or 30% oil s a t u r a tion (give n on some DGAs), t he t r a n sfor me r should h ave a dry
ou t wit h vacu u m if t he t a n k is r a ted for vacu u m. If t he t r a nsform er is old, pulling a
vacu u m ca n do more h a r m t h a n good. In t his ca se, it is be t te r to do rou nd-t he-clock re-
circula tion wit h a Bowser d rying t he oil a s m uch a s possible, which will p ull wa t er ou t
of t he pa pe r. At 2.5% M/DW, t he pa per insula tion is degr a ding m uch fa s ter t h a n
nor m al [5]. As t he pa pe r is degr aded, more wa ter is prod uced from t he decay
product s, a nd t he t r a nsform er becom es even we t te r a nd decays even fas ter. When a
t ra n sfor me r ge ts a bove 4% M/DW, it is in d a nge r of fla shover if t he t em per a t u re rises
to 90 °C.
F i g u r e 20.—Tr a n sfo r m e r Oi l P e r c e n t S a t u r a ti o n Cu r v e s.
57
estim a te t he pe rcen t s a t u r a tion ba sed on whe re t he poin t is loca ted. For exa mple, if
t he wa ter is 30 ppm a nd t he te m per a t u re is 40 °C, you ca n see on t he cu rves t h a t t his
poin t of in tersection falls a bou t h alfway betwee n t he 20% cu rve a nd t he 30% cu rve.
This m ea ns t h a t t he oil is approxim a tely 25% s a t u r a ted. Cu rves s hown on figu re 20
a re from IE E E 62-1995 [19].
Ca u ti o n: B e lo w 30 °C, t h e c u r v e s ar e n o t v e r y a c c u r a t e.
F a il u r e s d u e to m o i s tu r e ar e
t h e m o s t c o m m o n c a u s e of
tr a n sfor m e r fa il u r e s [5].
Wit hou t a n accu r a te oil
te m per a t u re, it is impossible for
la bor a tories to p rovide accu r a te
inform a tion abou t t he M/DW or
perce n t sa t u ra tion. It will also
be impossible for you to
calcula te t his infor m a tion
accu r a tely.
58
keep in min d t h a t t he life of t he t ra n sfor me r is t he life of t he ins ula tion. The
in sula tion is quickly degr a ded by excess mois t u re a n d t he prese nce of oxyge n.
B ase a ny decisions on sever al DGAs ove r a pe riod of tim e a n d est a blis h a t ren d of
increa sing mois t u re.
If t he lab does not provide t he percen t M/DW, IE E E 62-1995 [19] gives a m et hod.
F rom t he cu rve (figu re 22), fin d te m per a t u re of t he b o tt o m oil s a m p l e a n d a d d
5 °C. Do not use t he top oil te m per a t u re. This a pproxim a tes tem pe ra t u re of t he
bot tom t hird (coolest pa r t) of t he winding, where most of t he wa ter is loca ted.
F rom t his t em per a t u re, move u p ve rtica lly to t he cu rve. F rom t his poin t on t he
cu rve, move horizon t ally to t he left a n d find t he Myers Multiplier n u mbe r. Ta ke
t his n u m be r a nd m ultiply t he pp m of wa t er s hown on t he DGA. The res ult is
perce n t M/DW in t he u ppe r p a r t of t he in sula tion. This me t hod gives less a mou n t
of wa te r t h a n t he Ge ner al Elect ric nomogr a ph on t he following p age.
Fi g u r e 22.—M y e r s M u lti p li e r Ve r s u s T e m p e r a tu r e.
59
This nomogr a ph,
published by Ge ner al
Elect ric in 1974 (figu re
23), gives t he pe rcen t
sa t u r a tion of oil a nd
perce n t M/DW of
in sula tion. Use t he
nomogr a p h to check
you rself afte r you h ave
com ple ted t he m et hod
illu st ra ted in figu re 22.
The nomogr a ph in
figu re 23 will show
more moist u re t h a n t he
IE E E m et hod.
60
t he % M/DW a t a bou t 3.75%. The coole r t he oil, t he highe r t he moist u re
perce n t age for t he s a m e pp m of wa te r in t he oil.
Do not m a ke a decision on dryou t ba sed on only one DGA a n d one calcula tion; it
should be ba sed on t ren ds over a period of time. Ta ke a ddition al s a m ples a n d
sen d t hem for a n alysis. Ta k e e xtr a c ar e to m a k e s u r e th e o il te m p e r at u r e i s
c or r e c t. You ca n see by t he nomogr a ph t h a t moist u re con te n t va ries
dr a m a tically wit h te m per a t u re. Ta ke e x tra c a r e t h a t t he s a m ple is not exposed
to air. If after u sing t he more conserva tive IE E E me t hod a n d again s ubseque n t
sa mples s how M/DW is 2.5% or more a nd t he oil is 30% s a t u r a ted or more, t he
t ra n sfor me r should be d ried a s soon a s possible. Check t he nomogr a ph a n d cu rves
a bove to dete r mine t he pe rce n t sa t u r a tion of t he oil. The in sula tion is degr a ding
m uch fa s ter t h a n nor m al due to t he high moist u re con te n t. Drying ca n be a n
expen sive process; it is pr uden t to cons ult wit h ot he rs before m a king a fin al
decision to do dryou t. Howeve r, it is m uch less expe nsive to pe rform a dryou t
t h a n to allow a t r a nsfor mer to degr a de fas ter t h a n nor m al, subs t a n tially
shor te ning t ra n sfor me r life.
61
As t he oil ages, it is con t a min a ted by tiny p a r ticles (oxida tion prod ucts) of t he oil
a nd p a per in sula tion. These p a rticles exten d across t he wa te r/oil in t erface line
a nd wea ken t he te nsion betwee n t he two liquids. The more pa r ticles, t he wea ke r
t he in terfacial t ension a n d t he lowe r t he IFT n u mbe r. The IF T a nd acid n u m be rs
toget he r a re a n excelle n t indica tion of when t he oil needs to be reclaimed. It is
recom me nded t he oil be reclaim ed when t he IFT n u mber falls to 25 dynes per
cen time ter. At t his level, t he oil is very con t a min a ted a n d m us t be reclaim ed to
preven t sludging, which begins a rou nd 22 dynes pe r ce n tim ete r. See F IST 3-5
[20].
If oil is not reclaimed, sludge will se t tle on win dings, insula tion, etc., a nd ca use
loa ding a nd cooling problem s discussed in a n e a rlier section. This will gre a tly
shor te n t ra nsfor mer life.
There is a definite
rela tionship be tween t he acid
n u mber, t he IFT, a nd t he
n u mber of yea rs in se rvice.
The accom pa nying cu rve
(figu re 24) s hows t he
rela tionship a n d is fou nd in
m a ny p ublica tions. (It wa s
origin ally publis hed in t he
AIE E t ra ns actions in 1955.)
Notice t h a t t he cu rve shows
t he nor m al service limits bot h
for t he IFT a n d t he acid
n u mber.
Fi g u r e 24.—In t e rfa c i al T e n s i o n, Ac i d
4.6.3 Ac i d N u m b e r. Acid
N u m b e r, Ye a r s i n S e r vi c e .
n u mber (acidity) is t he
a mou n t of pot assiu m hydroxide (KOH) in milligra m s (mg) t h a t it t a kes to
ne u t r alize t he acid in 1 gr a m (gm) of t ra nsfor mer oil. The highe r t he acid n u mber,
t he more acid is in t he oil. New t r a n sfor me r oils con t ain p ractically no acid.
Oxida tion of t he ins ula tion a n d oils for ms acids a s t he t r a nsform er ages. The
oxida tion products for m sludge a nd precipit a te ou t inside t he t r a n sfor me r. The
acids a t t ack me t als inside t he t a n k a nd for m soa ps (more sludge). Acid also
a t t acks cellulose a nd accele r a tes ins ula tion degr a da tion. Sludging h a s been fou nd
to begin whe n t he acid n u m be r re aches 0.40; it is obvious t h a t t he oil should be
reclaimed before it re aches 0.40. It i s r e c o m m e n d e d t h a t t h e oil b e r e c l a i m e d
w h e n it r e a c h e s 0.20 m g KOH/g m [20]. As wit h all ot hers, t his decision m u st
not be based on one DGA tes t, bu t wa tch for rising t re nd in t he acid n u m be r each
ye a r. Pla n a hea d a nd begin budge t pla n ning before t he acid n u mber re aches 0.20.
4.6.4 T e s t fo r Ox y g e n I n h ib i to r E v e r y 3 to 5 Ye ar s w i t h t h e An n u a l
DGA T e s t. In p revious section s, t he need to keep t he t ra nsfor mer dry a nd O 2 free
wa s e m ph a sized. Mois t u re is dest r uctive to cellulose a nd eve n more so in t he
62
prese nce of oxyge n. Som e publica tion s st a te t h a t each tim e you double t he
mois t u re (pp m), you h alve t he life of t he t r a nsform er. As wa s discu ssed, acids a re
for m ed t h a t a t t ack t he insula tion a nd m et als which for m more acids, ca using a
viscous cycle. Oxygen in hibitor is a key to exten ding t he life of t r a n sfor me rs. The
in hibitor cu r re n tly used is Dite r tia ry B u tyl P a r acresol (DBPC). This wor ks sor t of
like a sacrificial a node in grou nding circuits. The oxygen a t t acks t he in hibitor
in ste a d of t he cellulose insula tion. As t his occu rs a n d t he t ra n sfor me r ages, t he
in hibitor is u sed up a nd needs to be replaced. The ide al a mou n t of DB PC is 0.3%
by tot al weigh t of t he oil (ASTM D-3487).
Ca u ti o n: Do not a t tem pt t his u nless you h ave h a d expe rie nce. Con t act a n
experienced con t r actor or experienced Recla m a tion people if you need help.
In eit her ca se, do not neglect t his im por t a n t m ain t en a nce fu nction; it is critical to
t ra n sfor me r insula tion to h ave t he p roper a mou n t of oxyge n in hibitor.
4.6.5 P o w e r F a c to r. Powe r factor indica tes t he dielect ric loss (le a k age cu r re n t)
of t he oil. This test m ay be done by t he DGA la bor a tories. It m ay also be done by
Doble tes ting. A high power factor in dica tes de terior a tion a nd/or con t a min a tion
by-products s uch a s wa te r, ca rbon, or ot he r cond ucting pa rticles; me t al soa ps
ca used by acids (form ed a s me n tioned above); a t t acking t r a nsfor m er m et als; a nd
product s of oxid a tion. The DGA labs nor m ally test t he power factor a t 25 °C a nd
100 °C. Doble infor m a tion [23] indica tes t he in-se rvice limit for power factor is
less t h a n 0.5% a t 25 °C. If t he powe r factor is gre a te r t h a n 0.5% a nd less t h a n
1.0%, fu r t he r inves tiga tion is required; t he oil m ay require replace me n t or fullers
e a r t h filtering. If th e p o w e r fa c t or i s g r e a t e r t h a n 1.0% a t 25 °C, th e o il m a y
c a u s e fail u r e of th e tr a n sfor m e r; r e pl a c e m e n t or r e c la i m i n g i s r e q u i r e d.
Above 2%, t he oil s hould be re moved from service a nd reclaimed or replaced
beca use equipme n t fa ilu re is a high probability.
63
a nd for m fu r a nic compou n ds. C h a nges in fu ra ns betwee n DGA test s a re more
im port a n t t h a n in dividu al n u mbe rs. The sa me is t r ue for dissolved ga ses.
Tr a nsfor me rs wit h grea ter t h a n 250 pa r ts pe r billion (ppb) should be inves tiga ted
beca use p a per in sula tion is being degr a ded. Also look a t t he IFT a nd acid
n u mber.
Doble in-service limit s a re reprod uced below to su ppor t t he a bove recom m ended
guidelines.
Ta ble 12 below is excerp ted from Doble E nginee ring Comp a ny’s Reference Book on
Insulating Liquids an d Gases [23]. These Doble Oil Limit t a bles su ppor t
inform a tion give n in prior sections in t his F IST m a n u al a n d a re shown here as
su m m a ry t a bles.
Voltage Class
2 2 2
Water Content, D 1533, ppm, max. 35 25 20
3 3 3
Soluble Sludge ND ND ND
1
D 877 test is not as sensitive to dissolved water as the D 1816 test and should not be used with oils for extra high voltage
(EHV) equipment. Dielectric breakdown tests do not replace specific tests for water content.
2
The use of absolute values of water-in-oil (ppm) do not always guarantee safe conditions in electrical apparatus. The percent
by dry weight should be determined from the curves provided. See the information in section. “4.5 Moisture Problems.”
3
ND = None detectable.
These recommended limits for in-service oils are not intended to be used as absolute requirements for removing oil from
service but to provide guidelines to aid in determining when remedial action is most beneficial. Remedial action will vary
depending upon the test results. Reconditioning of oil, that is, particulate removal (filtration) and drying, may be required if the
dielectric breakdown voltage or water content do not meet these limits. Reclamation (clay filtration) or replacement of the oil may
be required if test values for power factor, interfacial tension, neutralization number, or soluble sludge do not meet recommended
limits.
64
4.6.7 Ta k i n g Oil S a m p l e s for DGA. S a m pling procedu res a nd lab h a ndling a re
u su ally a rea s t h a t ca u se t he most problem s in ge t ting a n accu r a te DGA. There
a re times whe n a t mosphe ric ga ses, mois t u re, or hydrogen t a ke a su dde n le a p from
one DGA to t he next. As h a s bee n me n tioned, a t t hese times, one s hould
im media tely t a ke a not he r s a m ple to confir m DGA values. It is, of cou rse, possible
t h a t t he t ra n sfor me r h a s developed a n a t mosp heric lea k, or t h a t a fa ult h a s
suddenly occu r red inside. More often, t he sa m ple h a s not bee n t a ken prope rly, or
it h a s been con t a min a t ed wit h a t mosphe ric ga ses or mis h a ndled in ot her ways.
The sa m ple m u st be p rotected from all con t a min a tion, including a t mosp heric
expos u re.
Do not t a ke sa m ples from t he s m all sa m ple por t s loca ted on t he side of t he la rge
sa mple (d r ain) valves. These por ts a re too sm all to a dequ a tely flush t he la rge
valve a n d pipe nipple con nected to t he t a n k; in a ddition, air ca n be dr awn pa st t he
t h re a ds a nd con t a min a te t he sa m ple. F luid in t he valve a nd pipe nipple re m ain
dor m a n t d u ring oper a tion a n d ca n be con t a min a ted wit h moist u re, microscopic
ste m packing p a rticles, a nd ot he r p a r ticles. The volu me of oil in t his loca tion ca n
also be con t a min a ted wit h ga ses, especially hydrogen. Hydrogen is one of t he
e a sies t ga sses to for m. Wit h hot s u n on t he side of t he t r a n sfor me r t a n k whe re
t he sa m ple va lve is loca t ed, high a mbien t te mpe r a t u re, high oil te mpe r a t u re, a n d
ca pt u red oil in t he s a m ple valve a nd exte nsion, hydroge n for med will st ay in t his
a rea u n til a sa m ple is dr a wn.
The la rge sa m ple (dr ain) valve ca n also be con t a min a ted wit h hydrogen by
galva nic action of dissimila r m et als. S a mple valves a re us u ally br a ss, a nd a br a ss
pipe plug s hould be inst alled whe n t he valve is not being used. If a galva nized or
black iron pipe is inst alled in a br a ss valve, t he dissimila r me t als produce a
t her mocouple effect, a nd circula ting cu rren ts a re p roduced. As a res ult, hyd roge n
is gene r a t ed in t he void be tween t he plug a n d valve ga te. If t he valve is not
flu shed v e r y t horoughly t he DGA will s how high hyd roge n.
Oil should not be s a m pled for DGA pu rposes whe n t he t ra nsfor mer is a t or below
freezing te m per a t u re. Tes t values which a re affected by wa ter (such as dielect ric
st rengt h, power factor, a n d dissolved moist u re con te n t) will be in accu r a te.
Ca u ti o n: Tr a n s for m e r s m u s t n ot b e s a m p l e d if t h e r e i s a n e g a ti v e
p r e s s u r e (v a c u u m) a t t h e s a m p l e v al v e.
This is typically not a problem wit h conse rva tor t r a nsform ers. If t he t r a nsform er
is nit rogen bla n ke ted, look a t t he pressu re/vacu u m gage. If t he pressu re is
positive, go a he a d a nd t a ke t he s a mple. If t he pressu re is nega tive, a vacu u m
exist s a t t he top of t he t r a nsform er. If t here is a vacu u m a t t he bot tom, air will be
pulled in whe n t he sa m ple valve is ope ned. W ait u n til t he p ress u re gage re ads
positive before s a m pling. P u lli n g i n a v ol u m e of a ir c o u l d b e d i s a s tr o u s if
t h e tr a n sfo r m e r i s e n e r g iz e d.
If nega tive pressu re (vacu u m) is not too high, t he weigh t of oil (he ad) will m a ke
positive pressu re a t t he sa mple valve, a nd it will be s afe to t a ke a sa m ple. Oil
66
he a d is a bou t 2.9 fee t (2 feet 10.8 inches) of oil per pou n ds pe r squ a re inch (psi). If
it is im por t a n t to t a ke t he s a m ple eve n wit h a vacu u m showing a t t he top, proceed
a s described below.
For t hese rea sons, gla ss syringes a re recom me nded, a nd t he ins t r uction s below
inclu de only t his s a m pling me t hod.
Obt ain a br a ss pipe plug (nor m ally 2 inches) t h a t will t h rea d in to t he s a m ple
valve a t t he bot tom of t he t ra n sfor me r. Drill a nd t a p t he pipe plug for -inch
N PT a nd in ser t a -inch pipe nipple (br a ss if possible) a nd a t t ach a sm all -inch
valve for con t rolling t he sa m ple flow. At t ach a -inch tygon t ubing a da ptor to t he
sm all valve ou tle t. Sizes of t he piping a nd t h rea ds above do not m a t ter; a ny
a r r a nge men t wit h a s m all s a mple valve a n d a d ap tor to -inch tygon t ubing will
suffice. See figu re 25.
67
T a k i n g t h e S a m p l e.
• Ins t all t he br a ss pipe plug (described a bove) a n d a ssocia ted -inch pipe a n d
sm all valve, a n d a short piece of new -inch tygon t ubing to t he ou tlet of t he
-inch valve.
• Neve r use t he s a m e sa m ple t ubing on diffe re n t t r a n sfor me rs. This is one way
a s a m ple ca n be con t a min a ted a n d give false re a dings.
• Ope n bot h t he la rge valve a nd s m all sa mple valve a n d a llow a not her qu a r t to
flush t h rough t he s a mpling a ppa r a t us. Close bot h valves. Do t his before
a t t aching t he gla ss sa m ple syringe. Ma ke s u re t he shor t piece of tygon t ubing
t h a t will a t t ach to t he s a mple syringe is in st alled on t he -inch valve before
you do t his.
68
• Open t he la rge s a m ple valve a s m a ll a mou n t a nd a dju st t he -inch valve so
t h a t a gen tle flow goes t h rough t he flushing por t of t he gla ss syringe in to t he
was te bucket.
• Allow a sm all a mou n t, abou t 10 cubic ce n tim ete rs (cc), to flow in to t he syringe
a nd t u r n t he stopcock h a ndle again so t h a t it poin ts to t he syringe. This will
again allow oil to com e ou t of t he flus hing por t in to t he was te bucket.
• Rea t t ach t he tygon t ubing. This will again allow oil to flow ou t of t he flus hing
port. Slowly t u rn t he s topcock h a ndle towa rd t he flus hing por t which again
will allow oil to fill t he syringe. The syringe piston will again back slowly ou t
of t he syringe. Allow t he syringe to fill abou t 80% full. Hold t he pis ton so you
ca n s top its movem en t a t a bou t 80% filled.
69
• Close t he stopcock by t u r ning t he h a ndle towa rd t he syringe. Oil a gain will
flow in to t he wa ste con t aine r. S h u t off bot h valves, re move t he s a mpling
a pp a r a t u s, a n d reinst all t he origin al pipe plug.
4.6.8 S ili c o n e Oil-F ill e d Tr a n sfor m e r s. Silicone oils beca me more com mon
when PCBs we re discon tin ued. They a re m ainly u sed in t r a nsfor me rs inside
buildings a nd t h a t a re sm alle r t h a n gener a tor step-up t r a nsfor mers. Silicone oils
h ave a higher fire poin t t h a n miner al oils a nd, t herefore, a re u sed where fire
conce rn s a re more critical. As of t his writing, t here a re no definitive published
st a nd a rds. IE E E h as a guide a n d Doble h a s som e service limits, bu t t here a re no
st a nd a rds. Infor m a tion below is t a ke n from t he IE E E p ublica tion, from Doble,
from a r ticles, from IEC 60599 concep ts, a nd from Delt a X Rese a rch’s/Tr a nsfor m er
Oil An alyst rules. Silicone oil dissolved ga s a n alysis is in t he begin ning s t ages,
a nd t he s ugges ted m et hods a nd limits below a re s ubject to ch a nge a s we gain
more experience. However, in t he a bse nce of a ny ot he r me t hods a nd limit s, use
t he ones below a s a begin ning.
As wit h mine r al oil-filled t r a nsform ers, t h ree principal ca uses of ga s ge ner a tion
a re a ging, t he rm al fa ults, a n d/or elect rical fa ults res ulting in de terior a tion of solid
in sula tion a nd de terior a tion of silicone fluid. These fa ults h ave bee n discussed a t
le ngt h in p rior sections a nd will not be discu ssed in grea t de t ail here.
Over hea ting of silicone oils ca u ses degr a da tion of fluid a nd gene r a tion of ga ses.
Ga ses ge ner a ted depe nd on t he a mou n t of dissolved oxyge n in t he fluid,
te m per a t u re, a nd how close ba re coppe r conductors a re to t he hea ting. Whe n a
t ra n sfor me r is new, silicone oil will typically con t ain a lot of oxyge n. Silicone
t ra n sfor me rs a re typically se aled a n d pressu rized wit h nit roge n. New silicone oil
is not dega ssed; a n d, a s a rule, oxyge n concen t r a tion will be equivalen t to oxyge n
solubility (m axim u m) in silicone. The silicone h a s been exposed to a t mosphe re for
70
som e time du ring m a n ufact u re of t he t r a nsfor mer a n d m a n ufact u re r a nd stor age
of silicone oil itself. Therefore, ca rbon monoxide a nd ca rbon dioxide a re e a sily
for m ed a nd dissolved in t he silicone due to t he a bu nd a nce of oxyge n in t he oil
resulting from t his a t mosphe ric exposu re. In nor m al new silicone t r a n sfor me rs
(no fa ults), bot h ca rbon monoxide a nd ca rbon dioxide will be gene ra ted in t he
initial yea rs of oper a tion. As t he t r a n sfor me r ages a nd oxyge n is deple ted,
gene r a tion of t hese ga ses slows a nd conce n t r a tion s level off [25]. See figu re 29
below for t he rela tion ship of decrea sing oxygen a n d increa sing ca rbon monoxide
a nd ca rbon dioxide a s a t r a n sfor me r ages. This cu rve is for ge ner al infor m a tion
only a nd should not be t a ken to represen t a ny p a r ticula r t ra nsfor mer. A re al
t ra n sfor me r wit h ch a nges in loa ding, a mbien t te m per a t u res, a n d va rious d u ty
cycles would m a ke t hese cu rves look tot ally diffe re n t.
Afte r t he
t ra n sfor me r is
older (a ssu ming no
fa ult s h ave
occu r red), oxygen
conce n t r a tion will
reach equilibriu m
(figu re 29).
Re aching
equilibriu m m ay
t a ke a few ye a rs
depe nding on t he
size of t he
t ra n sfor me r,
loa ding, a m bien t
te m per a t u res, e tc.
Afte r t his time,
oxyge n, ca rbon
monoxide, a nd Fi g u r e 29.—R e l ati o n s h i p of O x y g e n to Carb o n
ca rbon dioxide D i o xi d e a n d Car b o n Mo n o x i d e a s Tr a n sfo r m e r Ag e s.
level off a nd t he
r a te of p roduction of t hese ga ses from nor m al aging should be rela tively cons t a n t.
If ge ner a tion r a tes of t hese ga ses ch a nge gre a tly (seen from t he DGA), a fa ult h a s
occu r red, eit her t her m al or elect rical. Ra te of gene r a tion of t hese ga ses a nd
a mou n t s ca n be used to roughly dete rmine wh a t t he fa ult is. Once you notice a n
significa n t increa se in r a te of ge ner a tion of a ny ga s, it is a good idea to s ubt r act
t he a mou n t of ga s t h a t wa s alrea dy in t he t ra nsfor mer before t his increa se. This
e nsu res t h a t ga ses used in t he diagnosis a re only ga ses t h a t we re gene ra ted afte r
t he fa ult bega n.
71
occu r ring a nd is p roducing CO a n d sm all a mou n ts of m et h a ne a nd hyd roge n, t he
fa ult m ay be m a sked by t he norm al p roduction of CO from t he silicone oil itself. If
t he CO ge ner a tion r a te h a s gre a tly increa sed, along wit h ot her ga ses, it becomes
obviou s t h a t a fa ult h a s occu r red. The fu r a n a n alysis ca n only tell you if t he pa pe r
is involved (being hea ted) in t he fa ult.
Some ge ner al conclu sion s ca n be dr a wn by com pa ring silicone oil a nd mine r al oil
t ra nsfor me rs.
1. All silicone oil filled t r a nsfor m ers will h ave a grea t deal more CO t h a n nor m al
miner al oil filled t r a nsform ers. CO ca n come from two sou rces, t he oil it self a nd
from degr ad a tion of p a per in sula tion. If t he DGA s hows lit tle ot he r fa ult in ga s
gene r a tion besides CO, t he only way to tell for ce r t ain if CO is coming from p a per
degr a da tion (a fa ult) is to r u n a fu ra n a n alysis wit h t he DGA. If ot her fa ult gases
a re a lso being gener a ted in significa n t a mou n ts, in a ddition to CO, obviou sly t here
is a fa ult, a nd CO is coming from pa pe r degr ad a tion.
2. There will ge ner ally be more hydrogen presen t t h a n in a mine ral oil-filled
t ra nsfor me r.
3. Due to “fa ult m a sking,” men tioned above, it is almost impossible to diagnose
wh a t is going on inside a silicone filled t r a n sfor me r based solely on DGA. One
exception is if acetyle ne is being ge ner a ted, t here is a n active a rc. You m u st also
look a t ga s ge ner a tion r a tes a nd ope ra ting his tory. Look a t loa ding history,
t h rough fa ult s, a nd ot he r incide n ts. It is impe r a tive t h a t de t ailed records of
silicone oil filled t r a n sfor me rs be ca refully kep t u p-to-d a te. These a re invalu able
when a p roble m is e ncou n te red.
In t a ble 14 below a re IE E E limit s [26], com pa red wit h Doble [25] in a st udy of
299 oper a ting t ra nsfor mers. The t able of ga ses from t he Doble st udy see ms more
realis tic. They s how ga s level ave rage of 95% of t ra nsfor me rs in t he s t udy. Note,
wit h t he la st fou r ga ses, limits given by t he IE E E (t rial use guide) r u n ove r 70%
highe r t h a n t he Doble 95% nor m s. B u t wit h t he first t h ree ga ses, hydroge n,
m et h a ne, a n d e t h a ne, t he IE E E limits a re well below t he a mou n t of ga s fou n d in
95% norm s in t he Doble st udy. We ob vi o u sl y c a n n ot h a v e li m i ts th at a r e
b e lo w t h e a m o u n t of g a s fo u n d i n n o r m a l o p e ra ti n g tr a n sfor m e r s.
72
Therefore, it is s uggested t h a t we use t he Doble (95% nor m) limits. The
95% norm limit mea n s t h a t 95% of t he silicone oil t r a nsfor m ers st udied h a d ga s
levels below t hese limits. Obviously, 5% h a d ga ses higher t h a n t hese limits.
These a re problem t ra nsfor mers t h a t we s hould pay more a t te n tion to.
Ethane 26 30
Ethylene 17 30
Acetylene 0.6 1
CO 1,749 3,000
In t a ble 15, t he IE E E limit s for L1 were chose n. For L2 limit s, a s t a tis tical
a n alysis wa s a pplied, a nd two st a n da rd devia tion s were a dded to L1 to obt ain L2.
For L3 limits, t he L1 limits were doubled.
L1 L2 L3 G1 G2
Gas (ppm) (ppm) (ppm) (ppm per month) (ppm per month)
Ethane 30 40 60 3 15
Ethylene 30 25 60 3 15
Acetylene 1 2 3 1 1
73
due to abse nce of a ny ot her criteria. As ou r experience grows in silicone DGA,
t hese m ay h ave to be ch a nged, bu t t hey will be used in t he begin ning.
Except for ace tylene, gene ra tion r a te levels G1 a nd G2 were t a ken from IEC 60599
reference [12] which is used wit h miner al oil t r a n sfor me rs. An y a m o u n t of
o n g o i n g a c e t yl e n e g e n e r ati o n m e a n s a c ti v e ar c i n g i n s i d e t h e
tra n sfor m e r. In t h i s c a s e, th e tr a n s for m e r s h o u l d b e r e m o v e d fro m
s e r v i c e. These criteria were chose n beca use of a n absence of a ny ot her criteria.
As dissolved ga s a n alysis criteria for silicone oils becomes be t te r k nown a nd
qu a n tified t able 15 will ch a nge to reflect new infor m a tion.
As w i t h m i n e r al o il-fill e d tr a n sfor m e r s, g a s g e n e r a ti o n r a t e s ar e m u c h
m o r e i m p or ta n t t h a t t h e a m o u n t of g a s p r e s e n t. Tot al accu m ula ted ga s
depe nds a lot on a ge (a n olde r t r a nsform er h as more ga s). If t he r a t e of ge ner a tion
of a ny combu stible ga s shows a s udden incre a se in t he DGA, t a ke a not her oil
sa mple im media tely to confir m t he gas gene r a tion r a te incre a se. If t he second
DGA confir m s a ge ner a tion ra te increa se, get some ou tside a dvice. Be ca reful; ga s
gene r a tion ra tes incre ase som ewh a t wit h tem pe ra t u re va ria tions ca u sed by
increa sed loa ding a nd su m me r a mbien t te mpe r a t u res. Howeve r, highe r oper a ting
te m per a t u res a re also t he mos t likely con ditions for a fa ult to occu r. The re al
question is h a s t he increa sed gas gene r a tion r a te been ca u sed by a fa ult or
increa sed tem pe ra t u re from gre a t er loa ding or higher a mbien t te m per a t u re?
If gas gene r a tion r a tes a re fairly con st a n t (no big increa ses a nd less t h a n G1
limits a bove), wh a t do we do if a t r a nsfor me r exceeds t he L1 limit s? We begin to
pay more a t te n tion to t h a t t r a nsfor m er, just a s we do wit h a mine r al oil
t ra n sfor me r. We m ay s hor te n t he DGA s a m pling in te rval, reduce loa ding, check
t ra n sfor me r cooling, ge t som e ou t side a dvice, etc. As wit h miner al oil
t ra n sfor me rs, age exer t s a big influe nce in accu m ula ted ga s. We s hould be m uch
more conce rned if a 3-ye a r old t r a nsfor m er which h a s exceeded t he L1 limits t h a n
if a 30-yea r old t r a nsfor mer exceeds t he limit s. However, if G1 ge ner a tion r a t es
a re exceeded in eit her a n old or new t r a n sfor me r, we should step up ou r level of
conce rn.
74
If bot h L1 limits a nd G1 limit s a re exceeded, we should becom e m o r e c o n c e r n e d.
Reduce sa m pling in tervals, get ou t side advice, reduce loa ding, check t r a n sfor me r
cooling a nd oil levels, e tc. If G2 g e n e r ati o n li m i ts ar e e x c e e d e d, w e s h o u ld
b e e x tr e m e l y c o n c e r n e d. It will not be long before L3 limit s a re exceeded, a nd
con sider a tion m u st be given to removing t he t r a nsfor me r from se rvice, for testing,
repair, or replace me n t.
If a c e t yl e n e i s b e i n g g e n e ra t e d, t h e tr a n sfor m e r s h o u ld b e ta k e n o u t of
s e r v i c e. However a s wit h miner al oil t r a nsform ers, a one-tim e ne a rby ligh t ning
st rike or t h rough fa ult ca n ca use a “one-tim e” ge ner a tion of acetylene. If you
notice acetyle ne in t he DGA, im media tely t a ke a not he r sa m ple. If t h e a m o u n t of
a c e t yl e n e is i n c r e a s i n g, a n a c ti v e e l e c tr i c a l ar c i s p r e s e n t w it h i n t h e
tra n sfor m e r. It s h o u l d b e ta k e n o u t of s e r vi c e .
If you h ave a critical silicone (or miner al oil-filled t ra nsfor mer), such a s a single
st a tion service t r a nsform er, or excit a tion t r a nsfor mer, you should find ou t if a
sp a re is availa ble a t a not her facility or from Weste rn Area Power Ad minist r a tion
or Bon neville Power. If t here a re no ot her possible spa res consider begin ning t he
bu dget process for get ting a spa re t r a n sfor me r.
Ta ble 16 lis ts test limit s for se rvice-aged silicone filled t ra n sfor me r oil. If a ny of
t hese limits a re exceeded, it is sugges ted t h a t t he oil be t re a ted in wh a teve r
m a n ner is a pprop ria te to ret u rn t he oil to servicea ble con dition.
Table 16.—Doble and IEEE Physical Test Limits for Service-Aged Silicone Fluid
Note: If only one number appears, both Doble and IEEE have the same limit.
75
If t he above limits a re exceeded in t he DGA, t he silicone oil should be
filtered, dried or t rea ted to cor r ect t he specific p roblem.
4.7 Tr a n sfor m e r T e s ti n g
Wh e n t h e tr a n sfo r m e r i s n e w b e fo r e e n e r gi z i n g a n d e v e ry 3 t o 5 y e ar s, t h e
tra n sfor m e r a n d b u s h i n g s s h o u ld b e D o bl e te st e d. Tr a nsfor me r testing falls in to
t h ree broa d ca tegories: F actory tes ting when t he t r a nsfor mer is new or h a s been
refu rbished, accept a nce testing upon delivery, a n d field t es ting for m ain te n a nce a nd
diagnos tic p u rposes. Some test s a t t he factory a re com mon to most powe r
t ra n sfor me rs, bu t m a ny of t he factory t es ts a re t r a nsform er- specific. Table 17 list s
sever al test s. This test ch a rt h a s been a da pted from IE E E 62-1995 reference [19]. Not
all of t he lis ted test s a re done a t t he factory, a nd not all of t hem a re done in t he field.
E ach t r a n sfor me r a nd e ach sit u a tion is differen t, requiring its own u nique a pproach
a nd test s.
Det ails of how to r u n specific tes ts will not be addressed in t his F IST. It would be
im pr actical to repe a t how to do Doble tes ting of a t ra nsfor mer whe n t he inform a tion is
rea dily availa ble in Doble p ublica tions. Wit h some exception s, t his is t r ue for mos t of
t he t es ts. Specific infor m a tion is re a dily available wit hin t he t es t in st r u m en t
m a n ufact u re rs liter a t u re. Anot he r exa mple is t he t ra nsfor me r t u r ns r a tio t es t (TTR);
specific t es t inform a tion is availa ble wit h t he ins t r u me n t. Howeve r, infor m a tion on
som e tes ts m ay not be ava ila ble a nd will be cove red briefly.
Ts Tk
Rs Rm
Tm Tk
Rs = Resist a nce a t t he factory reference te mpe r a t u re (fou n d in t he t r a nsform er
m a n u al)
Rm = Resist a nce you act u ally mea s u red
Ts = F actory reference tem pe ra t u re (us u ally 75 °C)
Tm = Tem pe ra t u re a t which you took t he me as u reme n t s
Tk = a con st a n t for t he p a r ticula r m et al t he win ding is m a de from:
234.5 °C for copper 225 °C for alu min u m
76
sufficie n t to ca use des t r uctive circula ting cu rren ts a nd m u st be fu r t he r
investiga ted [19]. A solid core grou nd m ay rea d ze ro oh m s; t his, of cou rse, ca uses
des t r uctive circula ting cu rren t s also.
Some limited success h a s been obt ained in “bu r ning off” u nin te n tion al core
grou n ds using a dc or ac cu r ren t sou rce. This is a risky ope r a tion, a nd t he cu rren t
m ay ca u se a ddition al da m age. The cu rren t sou rce is nor m ally limited to 40 to
50 a m ps m axim u m a nd should be increa sed slowly so a s to u se a s lit tle cu rren t a s
possible to accom plis h t he t a sk. This should only be used a s a la s t resor t a n d t hen
only wit h consult a tion from t he m a n ufact u rer, if possible, a n d wit h ot he rs
experienced in t his t a sk.
78
Table 17.—Transformer Test Summary Chart
79
RE F E RE NCE S
3. Powe r Tr a nsfor mer Ma in te n a nce a n d Tes ting, Ge ner al P hysics Corpor a tion. 1990.
4. Guidelines for t he Life Exte nsion of S ubst a tions E P RI, TR-105070. Ap ril 1995.
5. Tra nsfor mer M ain t en a nce Guide, by J .J Kelly, S.D. Myers, R.H. P a r rish,
S.D. Meyers Co. 1981.
6. Tra nsfor mer Gene r al Ga sketing P rocedu res, by Ala n Cote, S.D. Meyers Co. 1987.
7. N F PA 70B-1998 Recom men ded P r actice for Elect rical Equip me n t Ma in te n a nce.
8. Bus hing Field Tes t Guide, Doble E nginee ring Com p a ny. 1966.
9. Testing a nd Main ten a nce of High-Volt age Bu shings, F IST 3-2, B u rea u of
Recla m a tion. 1991.
11. IE E E S t a nd a rd C57.104-1991 Guide for t he In terp re t a tion of Ga ses Gene ra ted in Oil-
Im m ersed Tr a nsfor mers.
12. In te rn a tion al Elect rotech nical Com mission (Dr aft IEC 60599 Edition 2), Miner al Oil-
Im pregn a ted Elect rical Equipme n t in Se rvice-In te rpret a tion of Dissolved a nd F ree
Ga s An a lysis. 1997.
13. Dissolved Ga s An alysis of Tr a n sfor me r Oil, by Joh n C. Drotos, Joh n W. Por te r, Ra ndy
S tebbins, publis hed by t he S.D. Meyers Co. 1996.
14. IE E E S t a nd a rd C57.94, 1982, Recom men ded P r actice for In st alla tion, Applica tion,
Oper a tion a nd M ain ten a nce of Dry-Type Ge ner al P u rpose Dis t ribu tion a nd Powe r
Tra nsfor mers.
15. Criteria for t he In terp re t a tion of Da t a for Dissolved Ga ses in Oil from Tr a nsfor mers
(A Review), by P a ul Griffin, Doble E nginee ring Co. 1996.
16. Main ten a nce of High Volt a ge Tr a nsform ers, by Ma r tin Hea t h Cote Associa tes,
London, E ngla nd. 1989.
17. The r m al Monitors a nd Loa ding, by H a rold Moore, from Tr a nsform er P erfor m a nce
Monitoring a nd Diagnostics E P RI. Septe mber 1997.
80
18. IE E E a n d IEC Codes to In terpret Incipien t F a ult s in Tr a n sfor me rs, Using Ga s in Oil
An alysis, by R.R. Roge rs C.E.G.B, Tr a n smission Division, Guilford, E ngla nd. Circa
1995.
19. IE E E S t a nd a rd 62-1995, IE E E Guide for Diagnostic Field Testing of Elect rical Power
Appa r a t us, P a rt 1: Oil Filled Power Tr a nsform ers, Regula tors, a nd Reactors.
20. F IST 3-5 Main te n a nce of Liquid In sula tion: Miner al Oils a n d Ask a rels. 1992.
21. ANSI/ASTM D 971-91, S t a nd a rd Tes t Me t hod for In terfacial Ten sion of Oil Again st
W a te r by t he Ring Me t hod.
22. E PRI S ubs t a tion Equip men t Diagnos tics Conference VII, Expe rie nce wit h In-Field
W a te r Con t a min a tion of La rge Power Tr a n sfor me rs, by Victor V. Sokolov a n d Boris V.
Va nin, Scie n tific a nd E ngineering Ce n ter “ZTZ Se rvice Co.,” U kr aine. 1999
23. Doble E nginee ring Comp a ny “Refe re nce Book on In sula ting Liquids a nd Ga ses”
RBILG-391. 1993.
24. ANSI/IE E E C57.92-1981, Guide for Loa ding Mine r al Oil Im m ersed Tr a nsform ers.
25. Doble E nginee ring Comp a ny Clien t Confe re nce Min u tes 1998 Insula ting Fluids
No. 65PAIC98.
26. IE E E P 1258, Trial-Use Guide for t he In t erpret a tion of Gases Ge ner a ted in Silicone-
Im m ersed Tr a nsfor mers. 1999.
27. ASTM D-1933-97. St a nda rd Specifica tion of Nit roge n Ga s a s a n Elect rical Ins ula ting
Ma terial.
28. ASTM D-3487-88, St a nda rd Specifica tion for Miner al In sula ting Oil Used in
Elect rical Appa r a t us.
29. ASTM D-5837-96, St a nda rd Test Met hod for F u r a nic Com pou n ds in Elect rical
Ins ula ting Liquids by High P erfor m a nce Liquid Ch rom a togr a phy.
30. ASTM F-36-99, S t a nd a rd Tes t Me t hod for Com pressibility a n d Recove ry of Ga ske t
Ma terials.
31. ASTM D-2240-97, St a nda rd Test Met hod for Rubbe r P rope rty – Du rome ter H a rdness.
81