Complete rehabilitation is not possible because it's
an old model and the spare parts are not available.
Damages is about 70%. It is recommended to be
replaced. CAPACITOR BANK
currently is out of the service and has suffered
major damage, so its maintenance is expensive compared to if supplied.
So we suggest replacing it with a new capacitor
bank device. TRANSFORMERS
The substation is containe two transformer
1000 KVA, 11/0.4 KV, 50 HZ. Currently both the transformers in service and working without any problem but its needs only to cleaning, testing and a little maintenance. High Tension Switch Gear
The H.T.S.G 11KV is consist from four cubic, one
No. incomer type, one No. outgoing type and two No. for transformer feeder. After a visual inspection and inquiries from the station official, it was found that the switchgear are in the service and there is no problem, just need some cleaning work and add meters (for current, voltage, kilo watt, kilo volt-ampere) to all the boards. The relays for all the boards needs to cleaning, re- adjustable and some of it is out of work and needs to change. -