LOW TENSION SWITCH GEAR 400 V

Includes two inputs from transformer, bus coupler


between them and other outputs.

Complete rehabilitation is not possible because it's


an old model and the spare parts are not available.

Damages is about 70%. It is recommended to be


replaced.
CAPACITOR BANK

currently is out of the service and has suffered


major damage, so its maintenance is expensive
compared to if supplied.

So we suggest replacing it with a new capacitor


bank device.
TRANSFORMERS

The substation is containe two transformer


1000 KVA, 11/0.4 KV, 50 HZ. Currently both the
transformers in service and working without any
problem but its needs only to cleaning, testing and
a little maintenance.
High Tension Switch Gear

The H.T.S.G 11KV is consist from four cubic, one


No. incomer type, one No. outgoing type and two
No. for transformer feeder. After a visual
inspection and inquiries from the station official,
it was found that the switchgear are in the service
and there is no problem, just need some cleaning
work and add meters (for current, voltage, kilo
watt, kilo volt-ampere) to all the boards. The
relays for all the boards needs to cleaning, re-
adjustable and some of it is out of work and
needs to change.
-