You are on page 1of 4

UNILLANOS

ID-INS-HD-001

ESP INSTRUM Y CTRL IND


HOJA DE DATOS INGENIERÍA DE DETALLE
MOD INSTRUMENTACION
ELABORÓ: JOHNP
REV. 1

HOJA DE DATOS TRANSMISORES DE TEMPERATURA

REV. DESCRIPCIÓN FECHA ELABORÓ REVISÓ APROBÓ


AREA DE DISTRIBUCIÓN DISTRIBUIDO POR: ARCHIVO
MAGNÉTICO
UNILLANOS

ID-INS-HD-001

ESP INSTRUM Y CTRL IND


HOJA DE DATOS INGENIERÍA DE DETALLE
MOD INSTRUMENTACION

HOJA DE DATOS TRANSMISORES DE TEMPERATURA ELABORÓ: JOHNP


REV. 1

1 Tag Nº: TIT-203 Service: medición de temperatura TK-201

2 Function Indicate ✘ Control Transm. ✘ Other:

3 Case MFR STD ✘ Nom. Size: Color: MFR STD Other:

4 Mounting Direct Mounting ✘ 2 in. pipe Other:

GENERAL 5 Enclousure Class General purpose Weather proof ✘ Explosion proof Class:

For use Intrin. Safe system Other:

6 Power Supply AC ✘ DC 18-32 Volts

7 Type SMART Protocol: IO-LINK

8 Indicator Type: LCD Scale: ENG. UNITS Mounting: Integral Remote ✘

9 Output 4-20 mA ✘ 21-103 kPa(3-15 psig) Other:

TRANSMITTER 10 Electrical Connection ½ in. NPT ¾ in. NPT ✘ Power: 18-32 VDC Wire Connec:

11 Accuracy ±𝟎,𝟑 𝐎𝐅 𝐒𝐏𝐀𝐍

12 Control Modes P=Prop(Gain) I=Integral(Auto-Reset) D=Derivative(Rate)

Subindex; s=Slow f=Fast

P PI PD PID If Df Is Ds

Other:

CONTROLLER 13 Action On Meas. Increase Output: Increases Decreases

14 Auto-Man Switch None MFR STD Other:

15 Set point Adj. Manual External Remote Other:

16 Manual Reg. None MFR STD Other:

17 Controller Output 4-20 mA 3-15 psig Other:

18 Element Type: pt-100(3 wire) type A Input Range: -50 to 200 ºF ✘ ºC

SENSOR Location: Integral to Transmitter ✘ Remote Note:

19 Connection to Thermowell ¼ in.NPT ½ in. NPT Other:

20 Dimensions Nipple Size: Lenght: Union

Insertion lenght "U" Element lenght "S"


THERMOWELL
Lag extension "T"

21 Process Connection & Rating ¾ in.NPT 1 in. NPT Other:

22 Fluid Solución acuosa

PROCESS DATA 23 Temperature Min: 65 Normal: 70 Max: 75

24 Press Min: N/A Normal: N/A Max: N/A

25 Alarm Switches Quantity: Form: Rating:

26 Transient Protection Yes ✘


No
OPTIONS
27 Fail Safe Level Loss Input, Indication goes: Upscale Downscale

Other:

28 Manufacturer IFM EFECTOR

29 Model TA2511

NOTES:
1. Instrument shall have a permanently attached nameplate in 304 S.S stamped with following information: P.O. Number, Identification TAG
2. Vendor shall include Factory Calibration and Vendor Configuration on transmitter.
3. Transmitter Zero and Span shall be continuously adjustable.
4. Transmitter shall have Foundation Fieldbus protocol.
5. It shall be H1 Full ITK Compliance, FoundationTM Fieldbus check marked. Additionally, Vendor shall specify: DEV revision, DD revision level, CF revision and information such as Channel number and
Description, and Function Blocks Available, if so. Vendor shall provide with the instrument its proper device descriptors: .sym, .ffo, cff

Página 2 de 3
UNILLANOS

ID-INS-HD-001

ESP INSTRUM Y CTRL IND


HOJA DE DATOS INGENIERÍA DE DETALLE
MOD INSTRUMENTACION

HOJA DE DATOS TRANSMISORES DE TEMPERATURA ELABORÓ: JOHNP


REV. 1

Threaded ✘ Flanged

Temp. Press. Well Dim. Element


Well Single or
Tag No. P&ID Norm/Max Norm/Max Connection
Lenght
Dual
Service Notes
(ºF) (psig) U T S

TIT-203 P&ID proceso margarinas 158/167 N/A 0,73" single TK-201 temperature measurement 1 to 4

TT-205 P&ID proceso margarinas 176/194 N/A 0,73" single TK-202 temperature measurement 1 to 4

TT-209 P&ID proceso margarinas N/A N/A 0,73" single TK-203 temperature measurement 1 to 4

NOTES:
1. Instrument shall have a permanently attached nameplate in 304 S.S stamped with following information: P.O. Number, Identification TAG
2. Vendor shall include Factory Calibration and Vendor Configuration on transmitter.
3. Transmitter Zero and Span shall be continuously adjustable.
4. Transmitter shall have Foundation Fieldbus protocol.
5. It shall be H1 Full ITK Compliance, FoundationTM Fieldbus check marked. Additionally, Vendor shall specify: DEV revision, DD revision level, CF revision and information such as Channel number and
Description, and Function Blocks Available, if so. Vendor shall provide with the instrument its proper device descriptors: .sym, .ffo, cff

Página 3 de 3