You are on page 1of 83

ASCE7‐10

Components & Cladding
Wind Load Provisions

John Hutton, P.E., S.E.
Michael Stenstrom, P.E., S.E.
ASCE 7‐10 Wind 
Webinar Series
1. Basics of Wind Load Provisions & MWFRS’s

2. Components & Cladding Wind Load Provisions –
Roofs & Walls

3. Wind Loads for Signs, Other Structures, Roof –Top 
Structures, Equipment & Other Special Conditions

4. Wind Tunnel Applications for Buildings

5. Wind Loads on Non‐Standard Buildings
Changes in ASCE7‐10
• Complete reorganization of wind provisions
• Basic Wind Speed Based on Strength Design
– 1.0W for LRFD load combinations
– 0.6W for ASD load combinations
• Separate Maps for Risk Categories – No 
Importance Factors
• Surface Roughness D again applies along 
hurricane coastline
• New simplified methods for h<160 ft
Outline – C&C Loads
• A.  Important Limitations & Definitions

• B.  Building Types and the Organization of 
Chapter 30

• C.  Example Problems
Part 1 ‐ Low‐Rise Buildings
Part 2 ‐ Low‐Rise Buildings (Simplified)
Part 3 – Buildings with h > 60 ft
Part 4 – Buildings with h <= 160 ft (Simplified) ‐ New
ASCE 7 ‐ 10
Components & Cladding
Wind Loads

Important Limitations and 
Definitions
Important Limitations
• To use the C&C design procedures of ASCE 
7‐10, the building must meet the following 
conditions
• The building must be a regular‐shaped 
building, a building having no unusual 
geometrical irregularity in spatial form
• The building must not be subject to 
across wind loading, vortex shedding, 
galloping, or flutter
Important Limitations

• The site must not be subject to 
channeling effects or buffeting in the 
wake of upwind obstructions
• The wind loads for buildings failing to 
meet these limitations must be 
determined using wind tunnel 
procedures or using recognized literature 
documenting such wind load effects.
Important Definitions
What are Components and Cladding? 

Section 26.2 Definitions:
C&C: Elements of the building envelope that 
do not qualify as part of the MWFRS.
MWFRS: An assemblage of structural 
elements assigned to provide support and 
stability to the overall structure, generally 
receives wind loading from more than one 
surface.
Important Definitions
Commentary: Components and Cladding: 
Cladding receives wind loads directly. 
Components receive wind loads directly or 
from cladding and transfer the load to the 
MWFRS. Examples of components include 
fasteners, purlins, girts, studs, roof decking, 
and roof trusses. Components can be part of 
the MWFRS when they act as shear walls or 
roof diaphragms, but they may also be loaded 
as individual components. 
Important Definitions
Certain components may receive more than 
one type of wind loading, for example, long‐
span roof trusses should be designed for loads 
associated with MWFRSs (or C&C based on  
overall tributary area), and individual 
members of trusses should also be designed 
for C&C loads (based on member effective 
areas). Examples of cladding include wall 
coverings, curtain walls, roof coverings, 
exterior windows (fixed and operable) and 
doors, and overhead doors. 
Important Definitions
• Effective Wind Area – the area used to 
determine GCp
• C&C Elements – the effective wind area is 
the span length of the element times the 
spacing to the next element.  If the 
spacing is less than span length/3 one 
can use the span length/3 which will 
generate a larger effective area.
Important Definitions
• Tributary Area
• For C&C elements with tributary area of 
700 square feet or less, use the 
provisions of Chapter 30
• For C&C elements with tributary area 
greater than 700 square feet, the 
provisions for MWFRS may be used
Important Definitions
Cladding Fasteners – For cladding 
fasteners, the effective wind area shall not 
be greater than the area that is tributary to 
an individual fastener.
Important Definitions
• There are two primary procedures used for 
determining wind loads on buildings ‐
Directional Procedure and Envelope 
Procedure
• Directional Procedure – The pressure 
coefficients use in this procedure are 
based on past wind tunnel testing of 
prototypical building models for the 
corresponding direction of wind
Important Definitions

• Envelope Procedure – The pressure 
coefficients used in this procedure are 
based on past wind tunnel testing of 
prototypical building models successively 
rotated through 360 degrees under the 
wind loading.  The key structural actions 
(uplift, shear, overturning) are monitored 
and the maximum effects of all wind 
directions are used to create an envelope 
of pseudo‐pressure cases.
General Requirements
• Minimum Design Wind Pressures – the 
design wind pressure for C&C shall not be 
less than a net pressure (including internal 
pressures) of 16 psf acting in either 
direction normal to the surface

• (i.e. 10 psf ASD)
Wind Load Parameters
• Wind Load Parameters – specified in 
Chapter 26, General Requirements
• V = basic wind speed from one of the three Risk 
Category wind speed maps, Fig 26.5‐1A, B or C, 
three second gust speed at 33 feet Exposure 
Category C
• Kd = wind directionality factor from Table 26.6
Wind Load Parameters
• Exposure Category ‐ Category B, C, or D 
selected from 26.7.3 based on surface 
roughness  for the exposure resulting in the 
highest wind loads for any direction  on the site
(Exposure D now applicable to hurricane‐prone 
coastal areas)
• Kzt = topographic factor defined in section 26.8 
to account for wind speed‐up effect over hills, 
ridges, and escarpments
• G = Gust effect factor as determined by section 
26.9.  For the typical rigid building can be taken 
as 0.85
Wind Load Parameters
• Enclosure Classification ‐ used in determining 
internal pressure coefficient – either enclosed, 
partially enclosed, or open
• GCpi = internal pressure coefficient including 
gust factor as determined using Table 26.11‐1
Velocity Pressure
• qz = 0.00256 Kz Kzt Kd V2
• qz = velocity pressure evaluated at any height z
• qh = velocity pressure evaluated at the mean roof height, 
h
• Kz = velocity pressure exposure coefficient defined in 
Section 30.3.1 and given in Table 30.3‐1 evaluated at any 
height z (only used for Part 3, h> 60’ windward pressures 
and positive internal pressures for partially enclosed 
buildings)
• Kh = velocity pressure exposure coefficient evaluated at 
the mean roof height, h (used for low‐rise, roof, leeward 
and simplified pressures, and can be used for all cases)
Building Types
Building Types
Low Rise Buildings, h < 60’
Part 1 – Analytical
• ASEC 7‐05: Method 2 Low‐Rise
• Calculated
• Envelope Procedure
• Enclosed or Partially Enclosed
• Lowest Pressures

Part 2 – Simplified
• ASEC 7‐05: Method 1 Low‐Rise
• Tabulated
• Based on Part 1
• Enclosed Buildings Only
• Flat, Single Gable or Hip Roofs Only
Building Types
Buildings > 60’
Part 3 – Analytical
• ASCE 7‐05: Method 2 All‐Heights
• > 60’
• Calculated
• Directional Procedure
• Enclosed or Partially Enclosed

Part 4 – Simplified
• NEW: Based on Part 3
• < 160’
• Tabulated
• Enclosed Buildings Only
• Flat, Monoslope, Gable, Mansard or 
Hip Roofs & Parapets Only
Building Types
Special Types
Part 5 – Open Buildings
• All Heights
• Calculated
• Directional Procedure
• Monoslope, Pitched or Troughed 
Roofs
Part 6 – Appurtenances, etc
• Calculated
• Directional Procedure
• Parapets & Roof Overhangs (All 
Heights)
• Rooftop Structures & Equipment (h 
< 60’)
Building Types
Format
• Building Type 
Description

• Conditions

• Design Wind Pressure

• Notes

• Step‐by‐step Outline
Part 1:  Low‐Rise 
Buildings 
Component and 
Cladding 
Part 1: Low‐Rise 
Buildings
• Part 1:  Low Rise Buildings Component and Cladding 

• Per Table 30.4‐1   

• Steps to determine C & C Wind Loads

• For this exercise we will assume the following:  

• 2 Story Office Building 

• Wood Framed, Hip Roof 

• 30 Feet Mean Roof Height      

• Suburban Location, Flat Ground 
Part 1: Low‐Rise 
Buildings
30 ft

100 ft

34 ft
Mean roof height 30 ft

26 ft

15 ft
Part 1: Low‐Rise 
Buildings

• Wall studs are 15 feet tall and 16 inches on center (20 square feet tributary) 

• ‐‐ use 5 feet wide x 15 feet tall = 75 sq ft for Effective Area for GCp  

• Refer to page 243 Definition of Effective Area – Tributary width need not be 
less than 1/3 span length   

• Roof trusses span 30 feet, 2 feet on center (60 square feet tributary area) 

• – use 10 feet wide x 30 feet = 300 sq feet for Effective Area for GCp
Part 1: Low‐Rise 
Buildings
• Step 1:  Determine Risk Category 

• Office Building ……  Category II 

• (Table 1.5‐1 Chapter 1, page 2)

• Step 2:  Determine Basic Wind Speed

• ( Figure 26.5‐1A  page 247a ) 

• Wind Speed = 115 mph 
Part 1: Low‐Rise 
Buildings
• Step 3:  Determine Wind Load Parameters  

• Kd = 0.85  (Table 26.6 page 250)

• Exposure Category = B   (suburban page 251) 

Kzt Topo Category = 1  (flat per 26.8.2 last paragraph) 

Enclosure Class = Enclosed   (office building) 

• GCpi = + 0.18  (Table 26.11‐1 page 258)  
Part 1: Low‐Rise 
Buildings
• Step 4:  Determine Velocity Pressure Exposure 

• Kh 

• Kh = 0.70 per table 30.3‐1 page 317

• Step 5:  Determine Velocity Pressure qh  

• qh = 0.00256 Kz Kzt Kd (V)2 per equation 30.3‐1 page 316

• qh=0.00256 (0.70)(1)(.85)(115)2

• qh=20.1 psf 


Part 1: Low‐Rise 
Buildings
• Step 6:  Determine External Pressure 
Coefficient   GCp

• Walls  Per figure 30.4‐1 page 335

• Gcp  Zone 4  Zone 5

+ 0.85        + 0.85

• ‐ 0.95         ‐ 1.1 
Part 1: Low‐Rise 
Buildings
• Step 7:  Calculate Wind pressures per EQ 30.4‐1 

• p=qh((GCp)± (GCpi)) 

• Walls    

• p=20.1((+0.85) ‐ (± 0.18)) =  +13.4 psf, +20.7 psf  zone 4 & 5

p=20.1((‐0.95) ‐ (± 0.18)) =  ‐ 15.4 psf, ‐22.7 psf  zone 4  

• p=20.1((‐1.1) ‐ (± 0.18)) =  ‐ 18.5 psf, ‐25.7 psf  zone 5 


Part 1: Low‐Rise 
Buildings
 

                                                   

                    100 ft    
                                       30 ft     a = 10% of least dimension   

                                             30x 0.10 = 3 ft         Or  .4h     0.4 x 30 = 12 ft  

                          Or 4% of largest horizontal dimension  

                          0.04 x 100 = 4 ft  controls for ‘a’ dimension  
Part 1: Low‐Rise 
Buildings
• Hip Roof   Per figure 30.4‐2B  page 337 

• Zone 1    Zone 2    Zone 3 

• +0.3          +0.3        +0.3 

• ‐0.8          ‐1.2         ‐1.2 *   

• * Note:  per footnote 7,  Zone 3 = Zone 2 
for roof slopes less than 25o
Part 1: Low‐Rise 
Buildings
• Overhangs Per figure 30.4‐2B   (Assume 10 s f ) 

• Zone 2       Zone 3 

• Roof Truss “Tail” ‐2.2            ‐2.5                                        
Use tributary area of affected piece

• Roof Deck  ‐2.2 ‐2.2 for 10 sf 


Part 1: Low‐Rise 
Buildings
• Step 7:  Calculate Wind pressures per EQ 30.4‐1 (Continued) 

• Hip Roof ‐ Roof Trusses

• Zone 1, 2 & 3

• p=20.1((+0.3) ‐ (±0.18)) =  +4.4 psf, +9.7 psf 16 psf minimum governs 

• Zone 1

• p=20.1((‐0.8) ‐ (±0.18)) =  ‐ 12.4 psf, ‐19.7 psf 

• Zone 2 need to apply at discontinuities only 

• p=20.1((‐1.2) ‐ (±0.18)) =  ‐20.5 psf, ‐27.7 psf 

• Zone 3

• p=20.1((‐2.0) ‐ (±0.18)) =  ‐36.4 psf, ‐43.8 psf 
Part 1: Low‐Rise 
Buildings
• Step 7:  Calculate Wind pressures per EQ 30.4‐1 (Continued) 

• Overhangs  Roof Truss “Tails”

• Zone 2                          p=20.1(‐2.2)  =  ‐ 44.2 psf   use trib area of tail 

• Zone 3  p=20.1(‐2.5) =  ‐ 50.3 psf 

• Roof Deck at Overhangs 

• Zone 2  p=20.1(‐2.2) =   ‐ 44.2 psf 

• Zone 3  p=20.1(‐3.7) =   ‐ 74.4 psf 


Part 1: Low‐Rise 
Buildings  

  

Zone 2 occurs when 
wind blows from 
right 
 

   

   

      WIND  

            

                   Higher wind uplift ( zone 2 and 3 ) occurs  
                               when wind crosses roof edge  
 
            
 
 
Part 1: Low‐Rise 
Buildings

Roof truss at 2’‐0” on    
center  

Code Zone Diagram 

WIND  

                          Load Application Diagram  
Part 1: Low‐Rise 
Buildings
30 ft

Roof truss at 2’-0”


on center

100 ft

                 Positive Pressure (Downward)  

                     Negative Pressure (upward)
Zone 2 can be applied 
on both sides for 
simplifying of  load 
cases                          
  Truss Loading Diagrams  
Part 1: Low‐Rise 
Buildings
       Shallow Sloped Roofs (Monosloped or Gable)  
Gable Roofs 0 < 70 (~ 1-3/4:12 )
And Monoslope Roofs 0 < 30 (~ 3/4:12 )
Refer to figure 30.4-5A Footnote #5

Zone 3 Zone 2

Roof Joist @ 5’-0”

WIND

Zone Zzzzzz Zone 1

Positive Pressure (Downward)  
                                 

                     Negative Pressure (upward)                     
Zone 2 can be applied 
on both sides for 
simplifying load cases 

                                     Truss Loading Diagrams  
Part 1: Low‐Rise 
Buildings
Stepped Roofs  
Figure 30.4‐3   page 339 

Zone 2  

Zone 3 Zone 1 h1 Zone 3 (treat as zone 2 for ‐ GCp)


                

Zone 2 (treat as zone 1 for ‐ GCp) 
Zone 1 (treat as zone 1 for –GCp )  

        When h1 ≥ 10 ft        b = 1.5 h1   & b < 100 ft  
 
 (Note b is way out of scale on figure 30.4‐3, it looks like .5 h1 
instead of 1.5h1) 
For area within b distance on low roof, refer to Figure                  
30.4‐3) use wall values in figure 30.4‐1 for positive values of 
GCp 
Part 1: Low‐Rise 
Buildings
• Keys to Remember for Part 1:  
• Roof Zones 2 & 3 can be applied immediately adjacent to roof 
discontinuities based on the direction of the wind force

• Refer to Figure 30.4‐5A for “flat” roofs.  Footnote #5 directs user 
back to Figure 30.4‐2A for monoslopes less than 30

• Do not mix positive and negative wind forces on component loading 

• Recommend using wall pressures for roof slopes greater than 450

• Part 1 method may be used for h<90 ft. if the height/width ratio < 1

• This method generally yields the lowest wind pressures
Part 2:  Low‐Rise 
Buildings, h<60 ft
(Simplified)
Components and 
Cladding 
Part 2: Low‐Rise 
Buildings (Simplified)
• Part 2:  Low Rise Buildings ( Simplified)  

• Component and Cladding 

• Per Table 30.5‐1   

• For this exercise we will assume the following:  

• 2 Story Office Building 

• Wood Framed, Hip Roof 

• 30 Feet Mean Roof Height      

• Suburban Location, Flat Ground 

• Roof Slope is 250
Part 2: Low‐Rise 
Buildings (Simplified)

• Wall studs are 15 feet tall and 16 inches on center (20 square feet tributary) 

• ‐‐ use 5 feet wide x 15 feet tall = 75 sq ft for Effective Area for GCp  

• Refer to page 243 Definition of Effective Area – Tributary width need not be 
less than 1/3 span length   

• Roof trusses span 30 feet, 2 feet on center (60 square feet tributary area) 

• – use 10 feet wide x 30 feet = 300 sq feet for Effective Area for GCp
Part 2: Low‐Rise 
Buildings (Simplified)
• Part 2:  Buildings with h ≤ 60 ft Components and Cladding 

• Per Table 30.5‐1   Steps to determine C & C Wind Loads

• The first two steps are exactly the same as in Part 1:
• Step 1:  Determine Risk Category
– Office Building ……  Category II
• Step 2:  Determine Basic Wind Speed
– Wind Speed = 115 mph
• Step 3: Determine Wind Load Parameters (Exp. Cat only)
– Exposure Category = B 
– (GCPi = +/‐0.18 & Kd = 0.85 already incorporated into tables)
• Step 4: Determine Topographic Factors
– Kzt Topo Category = 1  (flat per 26.8.2 last paragraph)
Part 2: Low‐Rise 
Buildings (Simplified)
• Use same building as used in Part 1 
30 ft

100 ft

34 ft
Mean roof height 30 ft

26 ft

15 ft
Part 2: Low‐Rise 
Buildings (Simplified)
• Step 5 & 6 :  Enter figure 30.5‐1 to determine pressure on walls and roof, p. 
346

• pnet = λ Kzt pnet 30  (Eq. 30.5‐1)

λ = 1.0, adjustment factor for bldg height and exposure from fig.30.5‐1

pnet 30  = net design wind pressure for Exposure B, at h = 30 ft. 

Kzt = 1.0, topographic factor as defined in Section 26.8 evaluated at 
0.33 mean roof height, 0.33h 

Note:  Figure 30.5‐1 is on page 345, 346 and 347  All figures for this method 
are called 30.5‐1 
Part 2: Low‐Rise 
Bldgs (Simplified)
Step 5 & 6 :  Enter figure 30.5‐1

to determine pressure on walls

and roof, p. 346


Part 2: Low‐Rise 
Buildings (Simplified)
• Step 5:  Enter Figure 30.5‐1 to determine pressure on walls and roof, p

• p = pnet30 for h = 30 ft, Hip Roof  Exposure B    
Zone
• 1 2 3 4 5

‐19.8 ‐27.8 ‐44.0 ‐22.8 ‐25.8


+16 +16 +16 +20.8 +20.8
•p from Part 1  

Zone
1 2 3 4 5
‐19.7 ‐27.7 ‐43.8 ‐22.7 ‐25.7
+16 +16 +16 +20.7 +20.7
Part 3:  Buildings with 
h>60 ft 
Component and 
Cladding 
Part 3: Buildings 
with h> 60 ft
• Part 3:  Buildings with h>60 ft Component and Cladding 

• Determine C & C Wind Loads per Table 30.6‐1 Steps

• For this exercise we will assume the following:  
• 6 Story Office Building with 13 ft floor to floor 
• Glass Curtain Wall system with vertical mullions at 4 ft on center
• Flat  Roof framed with bar joists spanning 50 ft at  6’‐8” on center.
• 78 Feet Mean Roof Height      
• Suburban Location, Flat Ground 
Part 3: Buildings 
with h> 60 ft
This image cannot currently be display ed.
Part 3: Buildings 
with h> 60 ft

• Curtain Wall mullions are 13 feet tall and 48 inches on center (52 square feet 
tributary) 

• Refer to page 243 Definition of Effective Area – Tributary width need not be 
less than 1/3 span length   

• ‐‐ use 4’‐4” wide x 13 feet tall = 56 sq ft for Effective Area for GCp  

• Roof joists span 50 feet at 6’‐8” on center (333 square feet tributary area) 

• – use 16’‐8” wide x 50 feet = 833 sq feet for Effective Area for GCp
Part 3: Buildings 
with h> 60 ft
• Step 1:  Determine Risk Category 

• Office Building ……  Category II 

• (Table 1.5‐1 Chapter 1, page 2)

• Step 2:  Determine Basic Wind Speed

• ( Figure 26.5‐1A  page 247b ) 

• Wind Speed = 115 mph 
Part 3: Buildings 
with h> 60 ft
• Step 3:  Determine Wind Load Parameters  

• Kd = 0.85  (Table 26.6 page 250)

• Exposure Category = B   (suburban page 251) 

Kzt Topo Category = 1  (flat per 26.8.2 last paragraph) 

Enclosure Class = Enclosed   (office building) 

• GCpi = +/‐ 0.18  (Table 26.11‐1 page 258)  
Part 3: Buildings 
with h> 60 ft
• Step 4:  Determine Velocity Pressure Exposure 

• Kz or Kh 

• Kh = 0.92 per table 30.3‐1 page 317

• Kz = varies with height from 0.70 to 0.92 
per table 30.3‐1 page 317


Part 3: Buildings 
with h> 60 ft
• Step 5:  Determine Velocity Pressure qh and qz

• qh is determined at the mean roof height  

• qh = 0.00256 Kh Kzt Kd (V)2 per equation 30.3‐1 page 316

• qh=0.00256 (0.92)(1)(.85)(115)2

• qh=26.5 psf 

• qz is determined at the height of the element being considered

• qz = 0.00256 Kz Kzt Kd (V)2 per equation 30.3‐1 page 316

• qz=0.00256 (Kz)(1)(.85)(115)2  = (Kz)28.8 psf

• qh=varies from 20.1 psf  in the lower 15 ft to 26.5 psf at the top


Part 3: Buildings 
with h> 60 ft
• Step 6:  Determine External Pressure 
Coefficient   GCp

• Per figure 30.6‐1 page 348

• Roof Walls 
Joists Mullions

• 833 sq ft 56 sq ft

Zone 1   Zone 2   Zone 3   Zone 4   Zone 5

+ 0.8        + 0.8

‐ 0.9        ‐ 1.6      ‐ 2.3      ‐ 0.85       ‐ 1.55 


Part 3: Buildings 
with h> 60 ft
• Step 7:  Calculate Wall Mullion Wind pressures per EQ 30.6‐1 

• p=q(GCp)‐qi (GCpi) 

• Windward Walls    q=qz which varies from bottom to top

• p=qz(+0.8) – 26.5(± 0.18)  zone 4 & 5

for the following selected heights (40’, 60’, 78’)

@40’ p=21.9(+0.8) – 26.5(± 0.18) = 22.3 psf

@60’ p=24.5(+0.8) – 26.5(± 0.18) = 24.4 psf

@78’ p=26.5(+0.8) – 26.5(± 0.18) = 26.0 psf


Part 3: Buildings 
with h> 60 ft
• Step 7:  Calculate Wall Mullion Wind pressures per EQ 30.6‐1 

• p=q(GCp)‐qi (GCpi) 

• Leeward Walls    q=qh   which is constant from bottom to top

• p=qh(GCp) – 26.5(± 0.18)  zone 4 & 5

p=26.5(‐0.85) – 26.5(± 0.18) =  ‐ 27.3 psf zone 4  

• p=26.5(‐1.55) – 26.5(± 0.18) =  ‐ 45.8 psf zone 5 


Part 3: Buildings 
with h> 60 ft
Part 3: Buildings 
with h> 60 ft
• Step 7:  Calculate Roof Joist Wind pressures per EQ 30.6‐1 

• p=q(GCp)‐qi (GCpi) 

• Roof    q=qh   evaluated at mean roof height

• p=26.5(GCp) – 26.5(± 0.18)  zone 1, 2, & 3

p=26.5(‐0.9) – 26.5(± 0.18) =  ‐ 28.6 psf  zone 1  

p=26.5 (‐1.6) – 26.5(± 0.18) =  ‐ 47.2 psf  zone 2

p=26.5 (‐2.3) – 26.5(± 0.18) =  ‐ 65.7 psf  zone 3

p=16 psf minimum positive pressure all zones
Part 3: Buildings 
with h> 60 ft
Part 3: Buildings 
with h> 60 ft
• Keys to Remember for Part 3:  
• Use Figure 30.6‐1 for walls & flat roofs, <10 degrees 
• For Roof slopes >10 degrees, use Part 1 Figures for GCp
• Use Fig 30.4‐7 for dome roofs
• See Fig 27.4‐3, footnote 4, for arched roofs
– At roof perimeter, use the external pressure coefficients in 
Fig. 30.42 A, B and C with θ based on spring‐line slope
– for remaining roof areas, use MWFRS external pressure 
coefficients multiplied by 0.87.
Part 4:  Buildings with 
h<160 ft
Components and 
Cladding 
Part 4:  Buildings 
with h<160 ft
• Assume the same building used in Part 3: Buildings >60ft
• 78 Feet Mean Roof Height, flat roof
Part 4:  Buildings 
with h<160 ft
• Part 4:  Buildings with h>160 ft Components and Cladding 

• Per Table 30.7‐1   Steps to determine C & C Wind Loads

• The first two steps are exactly the same as in Part 3:
• Step 1:  Determine Risk Category
– Office Building ……  Category II
• Step 2:  Determine Basic Wind Speed
– Wind Speed = 115 mph
• Step 3: Determine Wind Load Parameters (Exp. Cat only)
– Exposure Category = B 
– (GCPi = +/‐0.18 & Kd = 0.85 already incorporated into tables)
• Step 5: Determine Topographic Factors
– Kzt Topo Category = 1  (flat per 26.8.2 last paragraph)
Part 4:  Buildings 
with h<160 ft
• Step 4:  Enter Table 30.7‐2 to determine pressure on walls and roof, p

• p = ptable (EAF)(RF)Kzt (Eq. 30.7‐1)

ptable = Tabulated Pressure for Exp C, 10 ft2 from Table 30.7‐2


RF     = Effective Area Reduction Factor from Table 30.7‐2
EAF   = Exposure Adjustment Factor from Table 30.7‐2
Kzt = 1


Part 4:  Buildings 
with h<160 ft
• Step 4:  Enter Table 30.7‐2 to determine pressure on walls and roof, p

• p = ptable for h = 78 ft, Flat Roof


Part 4:  Buildings 
with h<160 ft
• Step 4:  Enter Table 30.7‐2 to determine pressure on walls and roof, p

• p = ptable for h = 78 ft, Flat Roof

• Zone
1 2 3 4 5
‐54.6 ‐85.7 ‐116.8 ‐37.3 ‐68.4
NA NA NA 37.5 37.5
Part 4:  Buildings 
with h<160 ft
• Step 4:  Enter Table 30.7‐2 to determine pressure on walls and roof, p

• EAF = 0.766 (Exposure B, Mean Roof Ht. = 78’)
– Use linear interpolation as permitted for Kz
– Part 4 uses Kh for all pressures.  EAF values could be calculated 
for alternate heights for windward pressures, but since leeward 
pressures are larger anyway, this is not typically needed.


Part 4:  Buildings 
with h<160 ft
• Step 4:  Enter Table 30.7‐2 to determine pressure on walls and roof, p

Roof Joists Curtain 
Wall
Effective Area  Effective 
= 833 ft^2 Area = 
56 ft^2
Part 4:  Buildings 
with h<160 ft
• Step 4:  Enter Table 30.7‐2 to determine pressure on walls and roof, p

RF, Reduction Factors
For Effective Wind Areas
Roof Joists Curtain Wall
Effective Area = 833 ft^2 Effective Area = 56 
ft^2
Sign Zone
Pressure 1 2 3 4 5
Minus D D D C E
Plus NA NA NA D D
Minus .7 .7 .7 .91 .82
Plus .87 .87
Part 4:  Buildings 
with h<160 ft
• Step 4:  Enter Table 30.7‐2 to determine pressure on walls and roof, p

Part 4: p = ptable (EAF)(RF)Kzt (psf)


Roof Joists Curtain Wall
Zone
1 2 3 4 5
‐29.3 ‐46.0 ‐62.6 ‐26.0 ‐43.0
16.0* 16.0* 16.0* 24.9 24.9
Part 3, h>60 ft: p
‐28.6 ‐47.2 ‐65.7 ‐27.3 ‐45.8
16.0* 16.0* 16.0* 26.0 26.0

•Note that the simplified method 
is not always the most 
conservative.
Part 4:  Buildings 
with h<160 ft

a is not defined in Part 4, 
however, use zone 
dimensions as in Part 3:
Part 4:  Buildings 
with h<160 ft
Part 4:  Buildings 
with h<160 ft
Part 4:  Buildings 
with h<160 ft
• Keys to Remember for Part 4:
• Quick solution for Exposure C , 10 sf effective wind area
• Must be modified for Exposure B or D 
• Must be modified for effective wind areas > 10sf
• May be used for all heights < 160ft
• Not always the most conservative method – look for errata
• General Keys to Remember for Components & 
Cladding:
• ASCE 7‐10 wind loads are strength method  (0.6 W for ASD)
• Use effective  areas to establish GCp
• Recommend using wall pressures for roof slopes > 450
• May use 0.42W (=.6*.7) for IBC deflection limits (10 year winds)
Questions

You might also like