ACE PROJECT

CONTRACT NO
ACE-C-013
REV. NO PAGE / OF
EQUIPMENT INSPECTION REPORT
0 1/2
CONTRACTOR’S DOC No.:
REPORT No.: EL-004
QAF-032
DESCRIPTION: MARINE RADAR SCANNER TAG No: 6A-REWS86350
VENDOR: PO No: P6ALQTE01AF02A
AC
ACTIVITY DESCRIPTION ACC. REJ. ACTION
T N
Tick boxes for Accept or for
Reject & Action
1 Instead of ss coated cable ties there are used uncoated cable ties .
2 There is no nylon pad between SS EI 001 junction box and carbon steel
support
3 IP washers were missed EI 001 Junction box for glands (in all probability glands
are uncertified and need to be verified)
4 Used plastic gland for the outlet power socket (Tag N SC-001)
5 Junction box encloser earthing missing (EI-001, EI-002)
6 All tags for junction boxes are glued, self-tapping screw shall be used instead
of glue
7 Inside the EI 001 junction box three earth cable connected to one earthing
point. (To one earthing point max 2 earth cable can be connected)
8 Inside the cable tray there is no segregation plate between control and
instruments cables
9 Termination of box (EI-002) completed with a long supply of cable cores
10 Used SS bolt for the earth boss, earth boss to be completed with bronze bolt,
washer and nut
Note: The above equipment has been visually inspected in accordance with AF-6ATSZZ-MM-PRO-0026-000 for external damage and
deficiencies whilst every endeavour has been made to identify all deficiencies. AZFEN accepts no responsibility for deficiencies not
immediately apparent, and therefore not covered within this report.

Reference Documents / Drawings P.O.No. P6ALQTE01AF02A MMT No. P6AA0067

Proposed Actions: (to be completed by BP)

No Further Action BP to Advise Issue Site Instruction

Damaged on Site

Comments:

Inspected By:
Name: Famil Bayramov Signature: Date: 05.03.2020

Close-out
Action by: OS&D / SI No OS&D / SI Raised
AZFEN / Signature: Date: