You are on page 1of 8

Water

Serial number Plot Land Use Built-up Area (m2) Staff Visitor Prayer Demand
(m3/day)

Unit Rate Consumption (l/capita/day) 50 10 40


1 A Building A 33,000 2,000 1,650 116.5
2 B Building B 33,000 2,000 1,650 116.5
3 C Building C 30,000 2,000 1,500 115
4 D Building D 15,000 1,626 750 88.8
4 Ladies Sport Club 7,800 390 1,170 31.2
4 Men Sport Club 8,775 439 1,316 35.11
5 E All Plot E Buildings 20,000 
5 Community Center 9,000 450 1,350 36
5 Government Office 800 40 40 2.4
5 Foot Court Travel Offices 2,000 100 100 6
5 Retail Beauty center ATM 5,000 250 750 20
5 Virtual hall, guest house 3,000 150 450 12
5 STC Academy 7,500 375 1,125 30
6 Existing Building 11,12 30,068 2,000 1,503 115.03
7 1 Service Building 1, Coffee Shop, Retail & Staff Plaza 2,500
7 Coffee shop, retail 3,000 150 450 12
7 Staff Plaza 1,250 63 188 5.03
8 2 Service Building 2, Coffee Shop, Retail & Staff Plaza 2,500
8 Coffee shop, retail 3,000 150 450 12
8 Staff Plaza 1,250 63 188 5.03
9 HQ Building Headquarter 70,000 3,500 3,500
10 Existing NOC Building - (Network Operation Center)  - 2,300 2,000 135
11 Data Center 972 150 7.5
12 Existing Multi Story Parking 1250cars  - 10
13 SCECO Existing
14 Security, Safety & STC Fire Station 2,500 125 - 6.25
15 Future expansion
16 Existing Utility  -
17 Existing Care Building (building 45) 15,000 1,143 750 64.65
18 Open Spaces
19 Temporary Surface Parking 150cars & Future use  -
20 Temporary Surface Parking 110cars & Future use  -
21 Multi Story Parking Future -  0
22 Catering Building 700 35 - 5
23 Existing Water Tank
24 Contractors Area & General Stores 700 35 - 5
25 Open Spaces
26 Cafeteria 325 10 2,000 20
27 Multi Story Parking HQ  - 0
28 Existing Board & Personnel Building (Building no. 41) 26,000 1,821 1,300 104.05
29 SCECO Existing
30 Future Expansion 17000+ Emergency Building 15,000 750 750 45
31 Water Tank  -
32 Future Expansion 4000+ Emergency Building 2,000 100 100 6
33 Museum 3,000 45 1,000 13
34 Mosque 2,700 2700 108
35 Multi Story Parking A 72,000 20
36 Multi Story Parking B 72,000 20
37 Existing Building 1 19,433 1,000 1,000 60
38 Existing Building 2 15,374 750 750 45
39 Existing Mosque 2,154 2150 86
40 Existing Building 5 14,097 1,000 750 57.5
532,398 25,010 28,530 4850 1576.55
36.49421296
Flushing toilet
Availability of Graywater demand
demand WD-FW
GrayWater System (m3/day)
(m3/day)

Gray Water 25.63 34.95 81.55


Gray Water 25.63 34.95 81.55
Gray Water 25.3 34.5 80.5
Gray Water 19.536 26.64 62.16
Gray Water 6.864 9.36 21.84
Gray Water 7.7242 10.533 24.577
Gray Water 0
Gray Water 7.92 10.8 25.2
Gray Water 0.528 0.72 1.68
Gray Water 1.32 1.8 4.2
Gray Water 4.4 6 14
Gray Water 2.64 3.6 8.4
Gray Water 6.6 9 21
Gray Water 25.3066 34.509 80.521
Gray Water
Gray Water 2.64 3.6 8.4
Gray Water 1.1066 1.509 3.521
Gray Water
Gray Water 2.64 3.6 8.4
Gray Water 1.1066 1.509 3.521

Gray Water 29.7 40.5 94.5


N/A 7.5
N/A 10

N/A 6.25

N/A
Gray Water 14.223 19.395 45.255

N/A
N/A
N/A
N/A 5

N/A 5
N/A
N/A 20
N/A
Gray Water 22.891 31.215 72.835
 N/A
 N/A 45
N/A
6
Gray Water 2.86 3.9 9.1
Gray Water 71.28 6.48 101.52
N/A 20
N/A 20
N/A 60
N/A 45
N/A 86
N/A 57.5
307.846 329.07
FLUSH WATER

Serial number Plot Land Use Peak Flow(m3/hr) Required Pressure(bar)


Unit Rate Consumption (l/capita/day)
1 A Building A
2 B Building B
3 C Building C
4 D Building D
4 Ladies Sport Club
4 Men Sport Club
5 E All Plot E Buildings
5 Community Center
5 Government Office
5 Foot Court Travel Offices
5 Retail Beauty center ATM
5 Virtual hall, guest house
5 STC Academy
6 Existing Building 11,12
7 1 Service Building 1, Coffee Shop, Retail & Staff Plaza
7 Coffee shop, retail
7 Staff Plaza
8 2 Service Building 2, Coffee Shop, Retail & Staff Plaza
8 Coffee shop, retail
8 Staff Plaza
9 HQ Building Headquarter 80 11
10 Existing NOC Building - (Network Operation Center)
11 Data Center
12 Existing Multi Story Parking 1250cars
13 SCECO Existing
14 Security, Safety & STC Fire Station
15 Future expansion
16 Existing Utility
17 Existing Care Building (building 45)
18 Open Spaces
19 Temporary Surface Parking 150cars & Future use
20 Temporary Surface Parking 110cars & Future use
21 Multi Story Parking Future
22 Catering Building
23 Existing Water Tank
24 Contractors Area & General Stores
25 Open Spaces
26 Cafeteria
27 Multi Story Parking HQ
28 Existing Board & Personnel Building (Building no. 41)
29 SCECO Existing
30 Future Expansion 17000+ Emergency Building
31 Water Tank
32 Future Expansion 4000+ Emergency Building
33 Museum
34 Mosque
35 Multi Story Parking A
36 Multi Story Parking B
37 Existing Building 1
38 Existing Building 2
39 Existing Mosque
40 Existing Building 5
DOMESTIC WATER FIRE

Peak Flow(m3/hr) Required Pressure(bar) Peak Flow(m3/hr) Required Pressure(bar)

50 9 227 15