AS OF JULY 31, 2019

RSLF EXTERNAL WORKS (FIRE,SEWERAND WATER)


S/N Area Drawing ID Description REQUEST FOR INFORMATION REMARKS/COMMENTS

AS PER GENERAL NOTE ALL FIRE


FIRE PROTECTION MAIN
NEAR BRIGADE DETAIL FOR MAIN LINE SIZE PROTECTION LINES ARE 400mm BUT FROM
1
HEAD QUARTERS CU-106 LINE AND MAIN LINE
VALVE
AND SIZE OF GATE VALVE, THE PUMP ROOM PIPE REDUCES FROM
400mm TO 250mm

AS PER GENERAL NOTE ALL FIRE


FIRE PROTECTION MAIN
BRIGADE HEAD DETAIL FOR MAIN LINE SIZE PROTECTION LINES ARE 400mm BUT FROM
2
QUARTERS CU-107 LINE AND MAIN LINE
VALVE
AND SIZE OF GATE VALVE, THE PUMP ROOM PIPE REDUCES FROM
400mm TO 250mm

DETAIL FOR BRANCH LINE SIZE


BRIGADE HEAD FIRE PROTECTION AS PER GENERAL NOTE ALL FIRE
3
QUARTERS CU-107 BRANCH LINE
AND GATE VALVE IZE GOING
TO BRIGADE HEAD QUARTERS
PROTECTION LINES ARE 400mm

BRIGADE HEAD DETAIL FOR SEWER MANHOLE


4
QUARTERS CU-107 SEWER LINE
3 (SMH-3)
NO DETAIL IN SEWER MANHOLE 3

BRIGADE HEAD DETAIL FOR SEWER MANHOLE


5
QUARTERS CU-107 SEWER LINE
8 (SMH-8)
NO DETAIL IN SEWER MANHOLE 8

DETAIL FOR DOMESTIC WATER AS PER GENERAL NOTE ALL DOMESTIC


BRIGADE HEAD DOMESTIC WATER MAIN
6
QUARTERS CU-107 LINE
MAIN LINE PIPE SIZES AND
DIRECT BURRIED VALVE SIZE
WATER MAIN LINE ARE 200mm TO
CLARIFY

AS PER GENERAL NOTE ALL FIRE


FIRE PROTECTION MAIN
BETWEEN BRIGADE DETAIL FOR MAIN LINE SIZE PROTECTION LINES ARE 400mm BUT FROM
7
HEAD QUARTERS CU-108 LINE AND MAIN LINE
VALVE
AND SIZE OF GATE VALVE, THE PUMP ROOM PIPE REDUCES FROM
400mm TO 250mm

AS OF 7/31/19 EXTERNAL MECHANICAL


AS OF JULY 31, 2019

RSLF EXTERNAL WORKS (FIRE,SEWERAND WATER)


S/N Area Drawing ID Description REQUEST FOR INFORMATION REMARKS/COMMENTS

BETWEEN BRIGADE DETAIL FOR SEWER MANHOLE


8
HEAD QUARTERS CU-108 SEWER LINE
10 (SMH-10)
NO DETAIL IN SEWER MANHOLE 10

DETAIL FOR DOMESTIC WATER AS PER GENERAL NOTE ALL DOMESTIC


BETWEEN BRIGADE DOMESTIC WATER MAIN
9
HEAD QUARTERS CU-108 LINE
MAIN LINE PIPE SIZES AND
DIRECT BURRIED VALVE SIZE
WATER MAIN LINE ARE 200mm TO
CLARIFY

BRIGADE HEAD AS PER GENERAL NOTE ALL FIRE


FIRE PROTECTION MAIN
QUARTERS AND DETAIL FOR MAIN LINE SIZE PROTECTION LINES ARE 400mm BUT FROM
10
COMPANY HEAD CU-109 LINE AND MAIN LINE
VALVE
AND SIZE OF GATE VALVE, THE PUMP ROOM PIPE REDUCES FROM
QUARTERS 400mm TO 250mm

BRIGADE HEAD
QUARTERS AND DETAIL FOR SEWER MANHOLE
11
COMPANY HEAD CU-109 SEWER LINE
10 (SMH-17)
NO DETAIL IN SEWER MANHOLE 10
QUARTERS
BRIGADE HEAD
DETAIL FOR DOMESTIC WATER AS PER GENERAL NOTE ALL DOMESTIC
QUARTERS AND DOMESTIC WATER MAIN
12
COMPANY HEAD CU-109 LINE
MAIN LINE PIPE SIZES AND
DIRECT BURRIED VALVE SIZE
WATER MAIN LINE ARE 200mm TO
CLARIFY
QUARTERS

AS PER GENERAL NOTE ALL FIRE


FIRE PROTECTION MAIN
NEAR COMPANY DETAIL FOR MAIN LINE SIZE PROTECTION LINES ARE 400mm BUT FROM
13
HEAD QUARTERS CU-110 LINE AND MAIN LINE
VALVE
AND SIZE OF GATE VALVE, THE PUMP ROOM PIPE REDUCES FROM
400mm TO 250mm

AS OF 7/31/19 EXTERNAL MECHANICAL


AS OF JULY 31, 2019

RSLF EXTERNAL WORKS (FIRE,SEWERAND WATER)


S/N Area Drawing ID Description REQUEST FOR INFORMATION REMARKS/COMMENTS

DETAIL FOR DOMESTIC WATER AS PER GENERAL NOTE ALL DOMESTIC


NEAR COMPANY DOMESTIC WATER MAIN
14
HEAD QUARTERS CU-110 LINE
MAIN LINE PIPE SIZES AND
DIRECT BURRIED VALVE SIZE
WATER MAIN LINE ARE 200mm TO
CLARIFY

AS PER GENERAL NOTE ALL FIRE


PUMP ROOM AND FIRE PROTECTION MAIN
DETAIL FOR MAIN LINE SIZE PROTECTION LINES ARE 400mm BUT FROM
15 STORAGE TANK
AREA
CU-111 LINE AND MAIN LINE
VALVE
AND SIZE OF GATE VALVE, THE PUMP ROOM PIPE REDUCES FROM
400mm TO 250mm

PUMP ROOM AND DETAIL FOR DOMESTIC WATER AS PER GENERAL NOTE ALL DOMESTIC
DOMESTIC WATER MAIN
16 STORAGE TANK
AREA
CU-111 LINE
MAIN LINE PIPE SIZES AND
DIRECT BURRIED VALVE SIZE
WATER MAIN LINE ARE 200mm TO
CLARIFY

AS PER GENERAL NOTE ALL FIRE


ENTERSECTION OF FIRE PROTECTION MAIN
DETAIL FOR MAIN LINE SIZE PROTECTION LINES ARE 400mm BUT FROM
17 MAIN ROAD AND
PUMP ROOM AREA
CU-112 LINE AND MAIN LINE
VALVE
AND SIZE OF GATE VALVE, THE PUMP ROOM PIPE REDUCES FROM
400mm TO 250mm

ENTERSECTION OF DETAIL FOR DOMESTIC WATER AS PER GENERAL NOTE ALL DOMESTIC
DOMESTIC WATER MAIN
18 MAIN ROAD AND
PUMP ROOM AREA
CU-112 LINE
MAIN LINE PIPE SIZES AND
DIRECT BURRIED VALVE SIZE
WATER MAIN LINE ARE 200mm TO
CLARIFY

AS PER GENERAL NOTE ALL FIRE


FIRE PROTECTION MAIN
GUARD HOUSE DETAIL FOR MAIN LINE SIZE PROTECTION LINES ARE 400mm BUT FROM
19
AREA CU-117 LINE AND MAIN LINE
VALVE
AND SIZE OF GATE VALVE, THE PUMP ROOM PIPE REDUCES FROM
400mm TO 250mm

AS OF 7/31/19 EXTERNAL MECHANICAL


AS OF JULY 31, 2019

RSLF EXTERNAL WORKS (FIRE,SEWERAND WATER)


S/N Area Drawing ID Description REQUEST FOR INFORMATION REMARKS/COMMENTS

DETAIL FOR DOMESTIC WATER AS PER GENERAL NOTE ALL DOMESTIC


GUARD HOUSE DOMESTIC WATER MAIN
20
AREA CU-117 LINE
MAIN LINE PIPE SIZES AND
DIRECT BURRIED VALVE SIZE
WATER MAIN LINE ARE 200mm TO
CLARIFY

DETAIL FOR DOMESTIC WATER AS PER GENERAL NOTE ALL DOMESTIC


DOMESTIC WATER MAIN
21 ENTRANCE ROAD CU-122 LINE
MAIN LINE PIPE SIZES AND
DIRECT BURRIED VALVE SIZE
WATER MAIN LINE ARE 200mm TO
CLARIFY

DETAIL FOR DOMESTIC WATER AS PER GENERAL NOTE ALL DOMESTIC


DOMESTIC WATER MAIN
22 ENTRANCE ROAD CU-127 LINE
MAIN LINE PIPE SIZES AND
DIRECT BURRIED VALVE SIZE
WATER MAIN LINE ARE 200mm TO
CLARIFY

DETAIL OF D.I PIPE 300mm AS PER FIRE PUMP PIPING AT PUMP ROOM
DIA. FIRE WATER RETURN TO GOING TO FIRE WATER TANK (DWG. CU-
23 FIRE WATER TANK CU-525 FIRE WATER TANK
CONNECT INTO THE FIRE 111) FIRE WATER RETURN CONNECTED TO
WATER TANK FIRE WATER TANK.

AS OF 7/31/19 EXTERNAL MECHANICAL