You are on page 1of 4

LEGEND

410 Backwell St., Suite 10


Durham NC 27701
SYMBOL DESCRIPTION SYMBOL ABBREV. DESCRIPTION SYMBOL ABBREV. DESCRIPTION T: 919.474.2500 F: 919.474.2545

ROUND RECTANGULAR OVAL CHWS CHWS CHILLED WATER SUPPLY www.littleonline.com


12x10 RECTANGULAR DUCT
SUPPLY AIR DUCT TURNING UP CHWR CHWR CHILLED WATER RETURN
F SA
12ø ROUND DUCT This drawing and the design shown are the property
HHWS HHWS HEATING WATER SUPPLY
SUPPLY AIR DUCT TURNING DOWN of Little Diversified Architectural Consulting. The
HHWR HHWR HEATING WATER RETURN reproduction, copying or other use of this drawing
12/10 OVAL DUCT
without their written consent is prohibited and any
ROUND RECTANGULAR OVAL CDWS CDWS CONDENSER WATER SUPPLY infringement will be subject to legal action.
RETURN AIR DUCT TURNING UP CDWR CDWR CONDENSER WATER RETURN
MITERED ELBOW WITH TURNING VANES. RA c Little 2014
RETURN AIR DUCT TURNING DOWN CD CD COOLING COIL CONDENSATE DRAIN
MITERED ELBOW WITHOUT TURNING VANES
AND WITH LINER. DIMENSIONS ON PLANS ARE ROUND RECTANGULAR OVAL LPS LPS LOW PRESSURE STEAM (0-15 PSIG)
INTERIOR CLEAR DIMENSIONS. MECHANICAL LPC
CONTRACTOR IS RESPONSIBLE FOR UPSIZING EXHAUST AIR DUCT TURNING UP LPC LOW PRESSURE STEAM CONDENSATE
EA
DUCT TO ACCOUNT FOR LINER. MPS MPS MEDIUM PRESSURE STEAM (16-165 PSIG)
EXHAUST AIR DUCT TURNING DOWN MPC MPC MEDIUM PRESSURE STEAM CONDENSATE

RADIUS DUCT ELBOW. RADIUS ELBOWS CLASS 1 COMBINATION FIRE & SMOKE DAMPER HPS HPS HIGH PRESSURE STEAM (166+ PSIG)
SHALL BE 1.5W/1.5D ELBOWS UNLESS WITH DUCT ACCESS DOOR AND DUCT HPC HPC HIGH PRESSURE STEAM CONDENSATE
FSD MOUNTED ACTUATOR. REFER TO ELECTRICAL
OTHERWISE NOTED.
PLANS FOR POWER REQUIREMENTS.
RS/RL RS/RL REFRIGERANT SUCTION & LIQUID PIPING
S CLASS 1 SMOKE DAMPER WITH DUCT ACCESS
GORED ELBOW (OVAL DUCT)
DOOR AND DUCT MOUNTED ACTUATOR.
SD REFER TO ELECTRICAL PLANS FOR POWER
REQUIREMENTS.

PROVIDE LOCKING MANUAL


FLEXIBLE DUCT. MAXIMUM LENGTH 6'-0". DYNAMIC TYPE B FIRE DAMPER WITH DUCT DAMPERS AT ALL RUNOUTS
FD ACCESS DOOR. COORDINATE DAMPER RATING UNLESS OTHERWISE
WITH ARCHITECTURAL WALL SCHEDULE. BRANCH DUCT SIZE SAME
NOTED.
E AS NECK UNLESS
OTHERWISE NOTED.

DUCT MAIN
DEMOLITION WORK
M CLASS 1 MOTORIZED DAMPER. REFER
MD TO ELECTRICAL PLANS FOR POWER AIR TERMINAL TYPE.
REQUIREMENTS.
S1A
EXISTING CONDITIONS CARBON MONOXIDE DETECTOR . DUCT 500
CO CO CO MOUNTED (LEFT) ROOM MOUNTED (RIGHT)
AIR FLOW RATE (CFM)
NEW CONSTRUCTION CARBON DIOXIDE DETECTOR . DUCT
CO2 CO2 CO2 MOUNTED (LEFT) ROOM MOUNTED (RIGHT) THROW PATTERN (3-WAY SHOWN). 4-WAY
THROW UNLESS OTHERWISE NOTED.
TEMPORARY WORK STATIC PRESSURE TRANSMITTER. DUCT
SP SP SP MOUNTED (LEFT) ROOM MOUNTED (RIGHT)

CONNECT TO EXISTING DIFFERENTIAL PRESSURE TRANSMITTER.


DP DP DP DUCT MOUNTED (LEFT) ROOM MOUNTED
(RIGHT)
LIMIT OF DEMOLITION
SD SD DUCT MOUNTED SMOKE DETECTOR

T THERMOSTAT

FLOW DIRECTION

Mechanical Systems, Service Systems and Equipment


METHOD OF COMPLIANCE: No Change to Existing Systems
Prescriptive
Performance
Energy Cost Budget
Climate Zone: 3A GENERAL HVAC NOTES
Exterior Design Conditions:
summer dry bulb: 93 °F summer wet bulb: 79 °F 1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE
MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE.
winter dry bulb: 23 °F 2. CONTRACT DOCUMENT DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY.
Interior Design Conditions: 3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURERS’ RECOMMENDATIONS,
summer dry bulb: 75 °F CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
winter dry bulb: 70 °F 4. PROVIDE VIBRATION ISOLATION FOR ALL MECHANICAL EQUIPMENT TO PREVENT TRANSMISSION OF VIBRATION TO BUILDING
STRUCTURE. PROVIDE VIBRATION ISOLATORS FOR ALL SUPPORTS CONNECTED TO AND WITHIN 50 FEET OF ISOLATED
relative humidity: 40-60% EQUIPMENT (EXCEPT AT BASE ELBOW SUPPORTS AND ANCHOR POINTS) THROUGHOUT MECHANICAL EQUIPMENT ROOMS.
5. THE LOCATION OF EXISTING CONDITIONS IS APPROXIMATE. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF
ALL EXISTING CONDITIONS BEFORE COMMENCING WORK OR ORDERING EQUIPMENT. THE CONTRACTOR SHALL PAY FOR
Building Cooling Load: 0.0 Btu/h AND REPAIR ALL DAMAGES CAUSED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL EXISTING CONDITIONS
UNLESS OTHERWISE INDICATED.
6. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL WORK,
C ETC., SHOWN ON OTHER CONTRACT DOCUMENT DRAWINGS.
Building Heating Load: 0.0 Btu/h 7. MAINTAIN A MINIMUM OF 6′-8″ CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED EQUIPMENT, ETC.,
THROUGHOUT ACCESS ROUTES IN MECHANICAL ROOMS.
8. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED.
Mechanical Spacing Conditioning System: 9. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH STRAIGHT
SECTION OF PIPE OR DUCT UP AND DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER FOR GOOD ACCURACY.
Unitary: AIR CONDITIONERS, AIR COOLED 10. TESTING, ADJUSTING, AND BALANCING AGENCY SHALL BE A MEMBER OF THE ASSOCIATED AIR BALANCE COUNCIL (AABC) OR
description of unit: SPLIT SYSTEMS THE NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB). TESTING, ADJUSTING, AND BALANCING SHALL BE PERFORMED
cooling output: REFER TO MECHANICAL SCHEDULES IN ACCORDANCE WITH THE AABC STANDARDS.
ISSUE FOR
11. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE PRODUCT OF ONE MANUFACTURER
cooling efficiency: REFER TO MECHANICAL SCHEDULES SHALL BE USED. CONSTRUCTION
heating output: REFER TO MECHANICAL SCHEDULES 12. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS’ CERTIFIED DRAWINGS. COORDINATE AND PROVIDE DOCUMENTS
heating efficiency: REFER TO MECHANICAL SCHEDULES ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD
VERIFY AND COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION.
ISSUE DATE
13. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE AND DIVISION 16 OF THE
Chiller: N/A SPECIFICATION. 04/01/2016
Chiller output: REFER TO MECHANICAL SCHEDULES 14. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT SHALL BE SIZED AND LOCATED BY THE MECHANICAL
REVISIONS
CONTRACTOR. MINIMUM CONCRETE PAD THICKNESS SHALL BE 6 INCHES. PAD SHALL EXTEND BEYOND THE EQUIPMENT A
Oversizing reason: N/A NO. REASON DATE
MINIMUM OF 6 INCHES ON EACH SIDE. CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED BY THE GENERAL
CONTRACTOR. IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO COORDINATE SIZE AND LOCATION
Boiler: N/A OF CONCRETE HOUSEKEEPING PADS WITH GENERAL CONTRACTOR.
Boiler output: REFER TO MECHANICAL SCHEDULES 15. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS, WHERE REQUIRED, TO SERVICE DAMPERS, VALVES,
SMOKE DETECTORS, AND OTHER CONCEALED MECHANICAL EQUIPMENT. ACCESS PANELS SHALL BE TURNED OVER TO
Oversizing reason: N/A GENERAL CONTRACTOR FOR INSTALLATION. PROVIDE RATED ACCESS PANELS AS REQUIRED TO MAINTAIN ASSEMBLY
FIRE/SMOKE RATING.
16. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER TRADES
List equipment efficiencies: INVOLVED.
17. ALL OPENINGS IN RATED ASSEMBLIES DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE PROTECTED WITH AN
Cooling Efficiency: REFER TO MECHANICAL SCHEDULES
APPROVED U.L. DETAIL.
Heating Efficiency: REFER TO MECHANICAL SCHEDULES 18. ALL AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AIR HANDLING UNIT SHALL BE PIPED FULL SIZE OF THE UNIT
DRAIN OUTLET, WITH “P” TRAP, AND PIPED TO NEAREST DRAIN, SLOPED AT 1/8" PER LINEAR FOOT TOWARDS THE DRAIN.
SEE DETAILS SHOWN ON THE DRAWINGS OR THE CONTRACT SPECIFICATIONS FOR DEPTH OF AIR CONDITIONING
CONDENSATE TRAP.
B Mechanical system motors: 19. REFRIGERANT PIPING SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
Motor horsepower: REFER TO MECHANICAL SCHEDULES PROVIDE FILTER DRYERS, EXPANSION VALVES, STRAINERS, AND OTHER ACCESSORIES AS REQUIRED FOR PROPER
OPERATION
Number of phases: REFER TO MECHANICAL SCHEDULES 20. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME DAMPERS, ETC., ARE INDICATED ON
Minimum efficiency: REFER TO MECHANICAL SCHEDULES THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE
Motor type: REFER TO MECHANICAL SCHEDULES INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS.
21. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS, HUMIDISTATS, AND OTHER DEVICES 4′-0″ (CENTERLINE)
Number of poles: REFER TO MECHANICAL SCHEDULES ABOVE FINISHED FLOOR.
22. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS.
23. PROVIDE ALL 90 DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES UNLESS OTHERWISE INDICATED.
24. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, PROJECT TEAM
AND OTHER CEILING ITEMS AND MAKE MINOR DUCT MODIFICATIONS TO SUIT.
PRINCIPAL IN CHARGE
25. AIR HANDLING UNIT COILS SHALL BE ARRANGED FOR REMOVAL FROM THE UPSTREAM SIDE WITHOUT DISMANTLING
SUPPORTS. CHARLES J. TODD
26. LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, CONTROLS AND VALVING. PROJECT MANAGER
27. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER TIM McAULIFFE
EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE POINT OF
DESIGN TEAM
CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE INDICATED.
28. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF THE STRUCTURE, WITH SPACE LITTLE
FOR INSULATION IF REQUIRED. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS, PROJECT NAME

INCLUDING DIVIDED DUCTS AND TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT NO ADDITIONAL COST TO
THE OWNER. PENDER HIGH SCHOOL
29. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE DETECTORS, DAMPERS, HUMIDIFIERS,
COILS, AND OTHER ITEMS LOCATED IN THE DUCTWORK WHICH REQUIRE SERVICE AND/OR INSPECTION. PROVIDE ACCESS
DOORS IN DUCTWORK FOR OPERATION, ADJUSTMENT, AND MAINTENANCE OF ALL FANS, VALVES, AND MECHANICAL
EQUIPMENT.
30. SMOKE DETECTORS SHALL BE FURNISHED AND WIRED BY THE ELECTRICAL CONTRACTOR. THE MECHANICAL CONTRACTOR
SHALL BE RESPONSIBLE FOR MOUNTING THE SMOKE DETECTOR IN DUCTWORK AS SHOWN ON THE DRAWINGS AND IN
ACCORDANCE WITH MANUFACTURER’S PRINTED INSTRUCTIONS.
31. TERMINATE GAS VENTS FOR GAS APPLIANCES A MINIMUM OF 3′-0″ ABOVE ROOF WITH RAIN CAP
32. EXTERIOR LOUVERS ARE INDICATED FOR COORDINATION ONLY. DETAILED DESCRIPTIONS ARE PROVIDED IN THE PROJECT NO.

ARCHITECTURAL DRAWINGS AND SPECIFICATIONS. LOUVER SIZES, LOCATIONS, AND DETAILS SHALL BE COORDINATED WITH

A
ALL TRADES INVOLVED. 514.3969.00
SHEET TITLE

MECHANICAL COVER
SHEET

SHEET NUMBER

M001
1 2 3 4 5 6 7
8 9 10
GENERAL NOTES
MECHANICAL CONTRACTOR SHALL COORDINATE ALL DUCTWORK ROUTING AND
EQUIPMENT LOCATIONS WITH FRAMING CONTRACTOR PRIOR TO ORDERING
EQUIPMENT OR FABRICATION OF DUCTWORK/TRUSSES.

C1 PROVIDE MANUAL BALANCING DAMPERS AT ALL DUCT BRANCH RUNOUTS.

BRANCH DUCT RUNOUTS AND FLEX DUCTWORK SHALL BE SIZED TO MATCH THE
NECK SIZE OF THE DIFFUSER. 410 Backwell St., Suite 10
Durham NC 27701
T: 919.474.2500 F: 919.474.2545

www.littleonline.com

F
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
HP-1 2 c Little 2014

C
KEY NOTES
1 COORDINATE EXACT ROUTING OF DUCTWORK AND
SIDEWALL GRILLE WITH PENETRATIONS THROUGH
STRUCTURAL MEMBER.

2 MAINTAIN MANUFACTURER'S CLEARANCES ON ALL


SIDES AND ABOVE CONDENSING UNIT.

3 8" ROUND INTAKE UP TO GRAVITY VENTILATOR.


VENTILATOR SHALL BE GREENHECK MODEL GRSI-10
OR SIMILAR WITH MANUFACTURER'S ROOF CURB AND
INSECT SCREEN.

E 4 8" ROUND EXHAUST UP TO GRAVITY VENTILATOR.


VENTILATOR SHALL BE GREENHECK MODEL GRSR-08
OR SIMILAR WITH MANUFACTURER'S ROOF CURB AND
INSECT SCREEN.

5 RELOCATE EXISTING DIFFUSERS AND GRILLES IN


5 HATCHED AREA BASED ON NEW CEILING GRID.

B 6 EXHAUST AIR RELIEF LOUVER. LOUVER SHALL HAVE A


MINIMUM AREA OF 4 SQUARE FEET WITH 50% FREE
AREA. LOUVER SHALL BE PROVIDED WITH BIRD
H SCREEN AND MANUFACTURER'S POWDER COAT.
S1B
S1B 150 S1A
STORAGE 150 S1C S1B STORAGE 50 7 INTAKE AIR RELIEF LOUVER. LOUVER SHALL HAVE A
S1C
159
S1A 400 150 400
152 MINIMUM AREA OF 4 SQUARE FEET WITH 50% FREE
E2B S1A1
50
125 50
AREA. LOUVER SHALL BE PROVIDED WITH BIRD
SCREEN AND MANUFACTURER'S POWDER COAT.

FD
E2C CONCESSIONS
STAFF RESTROOM
136
375 E2C 105
E2C E1A1
E2C E2C 400 E1A1
400
375 375 UH-2
75
50
OFFICE 8 ENERGY RECOVERY VENTILATOR LOCATED ABOVE
104
HARD CEILING. MECHANICAL CONTRACTOR SHALL
H.C.

MECH HOME SHOWER MEN WOMEN VISITOR SHOWER JAN


12"x12" . E1A1
161 162 148 139 155 149
EF-1 4 WORKROOM
COORDINATE LOCATION OF ACCESS PANELS WITH
16"x16"

75 102
UH-1 12"x12" HP-4 OTHER TRADES.
S1A 8"ø HEALTH ROOM 8"ø
D 50 8"ø
10"x10"

106 OFFICE
RESTROOM

10"x10"
S1A 103
107 6"ø
14"x14"

50 HP-2 S1A

14"x14"
STORAGE STORAGE S1A1
IDU-4 ELEC STORAGE 125 8"ø 3

16"x16"
138 143
157 137 S1C S1A 50
8"ø
400 50
16"x16" T
E2B S1A IDU-1 16"x16"
S1A HP-3

16"x16"
175 100
100 E2A IDU-3 E2B 6 R1E S1B
6 IDU-2
100 S1A OFFICE 2
175 800 150 S1B
OFFICE 1 TRAINING R1E
100 146
S1B 20"x14" 125
16"x16"

147 145 800


8 8 125 RECEPTION
E2A
101
16"x16" 100 16"x16"
16"x16" E2A 16"x16"DRESSING ROOM A A
HOME DRESSING ROOM ERV-1 ERV-2 VISITORS

150
100 142
14"x12"
S1B S1B S1B S1B S1B S1B 10"x12"
7 7 150 150 150
150 150 150

8"x8"

8"x8"

8"x8"
16"x16" 16"x16"

AA S1B S1B AA
150 150
D2 1 1 1
BB S2A S2A BB
275 275
S2A
LOBBY
275
100

CC
C 26 27

1C FIELD HOUSE PLAN


M101 1/8" = 1'-0"

ISSUE FOR

WALL RATING LEGEND CONSTRUCTION


DOCUMENTS
ISSUE DATE
4B LOBBY PLAN 7.9
8.1
8 8.5 9 9.9
10
10.1 REFER TO ARCHITECTURAL SHEETS FOR MORE 04/01/2016
M101 1/8" = 1'-0" INFORMATION ON RATINGS.
REVISIONS

SMOKE PARTITION NO. REASON DATE

SMOKE BARRIER
FIRE PARTITION
30 MIN. FIRE PARTITION
1 HOUR BARRIER
2 HOUR BARRIER
3 HOUR FIRE WALL
4 HOUR FIRE WALL

PROJECT TEAM
PRINCIPAL IN CHARGE

CHARLES J. TODD
PROJECT MANAGER

TIM McAULIFFE
DESIGN TEAM
LITTLE
PROJECT NAME

PENDER HIGH SCHOOL

PROJECT NO.

A
514.3969.00
SHEET TITLE

MECHANICAL
DUCTWORK PLAN

SHEET NUMBER

M101
1 2 3 4 5 6 7
UNION
RECTANGULAR MAIN LOW RECTANGULAR MAIN LOW
PRESSURE AIR DUCT PRESSURE AIR DUCT
REMOVABLE CAP

SUPPORT STRAPS FROM CEILING SUPPLY DUCT


TO PREVENT KINKING OR LAYING COLLAR
ON CEILING.
DRAIN PAN
FLEX DUCT MAX. 6'-0"
FLEX DUCT SIZE SHALL
MATCH DIFFUSER NECK SIZE 410 Backwell St., Suite 10
FULL SIZE Durham NC 27701
OF DRAIN T: 919.474.2500 F: 919.474.2545
EACH DIMENSION IS CONNECTION
45° * 45° *
EQUAL TO FAN NEGATIVE www.littleonline.com
STATIC PRESSURE HIGH EFFICIENCY HIGH EFFICIENCY
F BRANCH DUCT RECTANGULAR LOW BRANCH DUCT
ROUND LOW LAY-IN T-BAR
TAKE-OFF FITTING PRESSURE BRANCH TAKE-OFF FITTING PRESSURE BRANCH This drawing and the design shown are the property
DUCT OR GWB
DUCT CEILING MANUAL VOLUME DAMPER WITH LOCKING of Little Diversified Architectural Consulting. The
QUADRANT. PROVIDE ACCESS DOOR OR reproduction, copying or other use of this drawing
OPPOSED BLADE FACE ACCESSED DAMPER WHEN WHEN without their written consent is prohibited and any
APPROVED MANUAL VOLUME MANUAL VOLUME DAMPER (WHEN LOCATED ABOVE GWB CEILING OR OTHER
AIR CAP
infringement will be subject to legal action.
DAMPER WITH DAMPER WITH SCHEDULED) INACCESSIBLE LOCATION
HEIGHT LOCKING QUADRANT LOCKING QUADRANT
LOCAL ROOF DRAIN DRAW BAND WITH SILICONE SEALER c Little 2014
FLOOR DRAIN, OR
FLOOR SINK. * - EQUALS WIDTH OF BRANCH DUCT UP TO 12". * - EQUALS WIDTH OF BRANCH DUCT UP TO 12".
12" FOR ALL BRANCH DUCTS LARGER THAN 12". 12" FOR ALL BRANCH DUCTS LARGER THAN 12". CEILING DIFFUSER

2E CONDENSATE DRAIN TO TERMINATION DETAIL 4E TYPICAL LOW PRESSURE BRANCH DUCT TAKE OFF 6E TYPICAL SUPPLY AIR DIFFUSER CONNECTION
M501 1/4" = 1'-0" M501 1/4" = 1'-0" M501 1/4" = 1'-0"

POWDER ACTUATED
PIN(F ALLOWED
BY CODE)

CONCRETE SLAB EXPANSION SHIELD WASHER STEEL BEAM


BEAM
CLAMP
BOTTOM CHORD OF STEEL JOIST RIGID AIR DUCT

USE THIS METHOD WHENEVER DUCTS FASTEN MOUNTING ANGLES


CAN BE GROUPED TOGETHER 1/2" ALL THREAD 16 GAUGE HOUSING (TYP.), FIRE DAMPER
1" X 16 GA. ROD FOR DAMPER SLEEVE ONLY. MIN 16 GAUGE
1/2" ALL THREAD 1-1/2" X 1-1/2")
STRAPS SEE PROJECT DRAWINGS FOR
SHEET METAL ROD FASTEN MOUNTING ANGLES
NUMBER & SIZE
SCREWS
E
FLOOR
DUCT DUCT DUCT OR WALL
DUCT

DUCT-SEE PROJECT
PLAN FOR SIZE

SINGLE RECTANGULAR DUCT MULTIPLE DUCT RUNS ON TRAPEZE HANGERS


CONNECT DUCT TO FIRE
NOTE: DUCTS SHALL BE SUPPORTED AT DAMPER WITH SLIP "S"
2"X2" X 3/16" ANGLE (WHERE NOT LESS THAN 10FT. O.C ACCESS DOOR CONNECTION
LENGTH OF ANGLE EXCEEDS
6FT. USE INTERMEDIATE
SUPPORT)

WOOD BEAM

DUCT RISER-SEE
PROJECT PLANS
FOR SIZE
1-1/2" X 1-1/2" X 1/8" NOTES:
ANGLE BOTH SIDES SHEET METAL SCREWS
1. DAMPER ASSEMBLY INSTALLED IN AND FASTENED TO THE SLEEVE.
OF DUCT 1-1/2" X 1-1/2" X 1/8"
ANGLE BOTH SIDES 2. MAINTAIN FULL DUCT SIZE. DAMPER HOUSING SHALL NOT
SECURE STRAP OF DUCT OBSTRUCT AIR FLOW, (TYPE "B")
HANGERS TO FLOOR
CURB
STRUCTURE 3. MOUNTING SHOWN IS VERTICAL INSTALLATION, HORIZONTAL
INSTALLATION IS SIMILAR
TURN STRAP
3" MIN.
D 1"X18 GAGE STRAP
HANGERS UP THRU SHEET METAL
6D FIRE DAMPER INSTALLATION DETAILS
30" 0 1"X 1/8" SCREWS M501 1/4" = 1'-0"
30" 0 AT 10' O.C HOLE IN STRUCTURAL
SEAL HOLE AFTER FLOOR
DUCT INSTALLATION
DUCT-SEE PROJECT WITH RED LEAD DUCT RISER
PLANS FOR SIZE AND OAKUM

RISER SUPPORT INDOOR UNIT


ROUND DUCT
WALL MOUNTING BRACKET
FURNISHED BY MFGR.
4D HANGERS AND SUPPORT FOR LOW PRESSURE DUCTWORK WALL SLEEVE WITH CAPS
M501 1/4" = 1'-0" FURNISHED BY FCU MFGR.
1/2" DRAIN
LINE SEE
PLANS FOR
ROUTING.
8
GENERAL NOTES:
MOTOR
PANELBOARD/ CONTROL 7 8 1. ALL POWER WIRING ASSOCIATED WITH DIVISION 22/23 (PLUMBING/MECHANICAL) SHALL BE PERFORMED
SWITCHBOARD CENTER UNDER THE SCOPE OF WORK OF THE CONTRACTOR SUPPLYING THE EQUIPMENT AND SHALL BE MOUNT FAN FROM STRUCTURE SA
COORDINATED WITH THE DIVISION 26 (ELECTRICAL) CONTRACTOR. ABOVE WITH THREADED RODS.
PROVIDE NEOPRENE ISOLATOR THERMISTOR
1 6 PADS. CABLE
2. ALL POWER DISCONNECT SWITCHES, VFDS, AND SINGLE SPEED MANUAL STARTING SWITCHES ASSOCIATED
WITH DIVISION 22/23 SHALL BE PROVIDED UNDER THE SCOPE OF WORK OF THE CONTRACTOR SUPPLYING THE
EQUIPMENT JB EQUIPMENT AND SHALL BE COORDINATED WITH THE DIVISION 26 CONTRACTOR. CONNECTION CABLE
WITH TO THERMOSTAT
BUILT-IN ACOUSTICAL LINING
5 5 3. EXCEPT AS MAY BE INDICATED ON THE DRAWINGS AND/OR HEREINAFTER NOTED, ALL LOW VOLTAGE CONTROL
SWITCH INSULATED RS, RL
C 2 WIRING, (INCLUDING ALL TEMPERATURE CONTROL WIRING, INTERLOCKING, START-STOP WIRING, TOGETHER REFGRIGERANT LINES, SIZE PER
WITH CONDUIT FOR SAME) SHALL BE PROVIDED UNDER DIVISION 22/23 BY THE CONTRACTOR SUPPLYING THE MFGR. RECOMMENDATIONS.
EQUIPMENT. THIS INCLUDES, BUT IS NOT LIMITED TO, WIRING TO LOW VOLTAGE THERMOSTATS, DAMPER
EXTEND 4' FROM
MOTORS, AQUASTATS, FIRESTATS, PUSH BUTTONS, SELECTOR SWITCHES, AND CONTROL PANELS. ALL
5 FAN DISCHARGE
DISCONNECT SWITCHES FOR CONTROL WIRING SHALL BE PROVIDED UNDER DIVISION 22/23 BY THE PROVIDE BDD
AIRFLOW
CONTRACTOR SUPPLYING THE EQUIPMENT.

1
4. WORK OF DIVISION 22/23 SHALL INCLUDE FURNISHING AND SETTING MOTORS.
3 ISSUE FOR

5. ALL MAGNETIC STARTERS AND OVERLOAD ELEMENTS WILL BE PROVIDED UNDER DIVISION 22/23 BY THE CONSTRUCTION
CONTRACTOR SUPPLYING THE EQUIPMENT AND SHALL BE COORDINATED WITH THE DIVISION 26 DOCUMENTS
CONTRACTOR. OVERLOAD ELEMENTS IN ALL STARTERS SHALL BE SELECTED ACCORDING TO ACTUAL
4 MOTOR NAMEPLATE FULL LOAD CURRENT. RESPONSIBILITY FOR THIS COORDINATION SHALL LIE WITH THE
ISSUE DATE
DIVISION UNDER WHICH THE PARTICULAR STARTER WAS FURNISHED. POWER & HIGH
2 2 2 VOLTAGE 04/01/2016
GASKETED AIRFLOW CONTROL TO
6. FIRESTATS AND WALL MOUNTED THERMOSTATS WHICH INTERRUPT LINE VOLTAGE POWER CIRCUITS TO MOTORS TO SIDEWALL ACCESS REVISIONS
FLEXIBLE CONNECTION INDOOR UNIT
SHALL BE PROVIDED UNDER DIVISION 23, AND ELECTRICALLY CONNECTED IN THE BRANCH CIRCUIT WIRING AS DISCHARGE CAP PANEL NO. REASON DATE
1 1 STARTER WORK OF DIVISION 26. W/ SCREEN OUTDOOR UNIT SECURE
OR VFD TO CONCRETE PAD
INDOOR 3 OUTDOOR
3 KEYED NOTES:
UNIT UNIT IN-LINE INSTALLATION 4" THICK CONCRETE PAD,
EXTEND MIN. 4" ALL SIDES.
1 DIVISION 22/23 EQUIPMENT
3

2
2 CONDUIT & WIRING OR CABLE BY MECHANICAL CONTRACTOR, CONTROLS CONTRACTOR, OR OTHER
TRADES. IN ALL CASES THE EQUIPMENT CONTRACTOR (DIV. 22/23) SHALL MAKE FINAL CONNECTIONS, START
5B INLINE CEILING EXHAUST FAN DETAIL 6B DUCTLESS SPLIT SYSTEM DETAIL
UP EQUIPMENT AND TEST EQUIPMENT. COORDINATE CONNECTIONS WITH DIV 26. M501 1/4" = 1'-0" M501 12" = 1'-0"

LEGEND: IF ANY ADDITIONAL DISCONNECTS ARE REQUIRED BY NEC, IT SHALL BE PROVIDED AND INSTALLED
3
BY THE EQUIPMENT CONTRACTOR (DIV. 22/23).
BY ELECTRICAL (DIV. 26) 2
B 4 A COMBINATION STARTER OR VFD MAY BE USED IN LIEU OF A SEPARATE DISCONNECT SWITCH AND STARTER. MECHANICAL CONTRACTOR SHALL COORDINATE EXACT LOCATION OF INDOOR
BY MECHANICAL (DIV. 22/23) FACTORY MOUNT OR LOCATE ADJACENT TO EQUIPMENT AND PROVIDED BY EQUIPMENT CONTRACTOR. UNIT WITH DUCTWORK, PLUMBING AND ELECTRICAL AND OTHER DISCIPLINES
1 1 TO MAINTAIN FILTER AND MAINTENANCE ACCESS CLEARANCES.
5 FEEDER CIRCUIT WIRING AND CONDUIT BY ELECTRICAL CONTRACTOR. FIELD FABRICATED FILTER BOX GALVANIZED ALL THREADED
WITH HINGED ACCESS DOOR ROD WITH SPRING
A JUNCTION BOX MAY BE SHOWN ON THE ELECTRICAL PLANS FOR SOME EQUIPMENT. IF NO STARTER OR FOR FILTER. VIBRATION ISOLATORS TO
6 STRUCTURE, WITH SEISMIC
DISCONNECT IS SUPPLIED, A JUNCTION BOX SHALL BE INSTALLED ADJACENT TO EQUIPMENT. THE OUTSIDE AIR DUCT TRANSITION
ELECTRICAL CONTRACTOR SHALL PROVIDE LINE SIDE WIRING TO JUNCTION BOX. LOAD SIDE WIRING WITH MANUAL VOLUME AS REQUIRED RESTRAINTS WHERE
WILL BE PROVIDED BY MECHANICAL CONTRACTOR OR OTHER TRADES. DAMPER. SEE PLANS TO UNIT REQUIRED (TYPICAL)
FOR ROUTING. INLET SIZE. REFRIGERANT PIPING
FOR PROJECTS UTILIZING MOTOR CONTROL CENTERS (MCC), THE STARTER, CB, OR VFD IN THE MCC ARE FAN GUARD PROJECT TEAM
7 AS RECOMMENDED PRINCIPAL IN CHARGE
PROVIDED BY THE ELECTRICAL CONTRACTOR. BY MANUFACTURER.
CONDENSING UNIT CHARLES J. TODD
DIVISION 26 EQUIPMENT SMOKE
8 DETECTOR PROJECT MANAGER

TIM McAULIFFE
DESIGN TEAM
1A EQUIPMENT CONNECTION DETAIL LITTLE
REFRIGERANT GAUGE PROJECT NAME
M501 1/8" = 1'-0" S
CONNECTION - PROVIDE WHEN
NOT INTEGRAL TO UNIT PENDER HIGH SCHOOL
SUPPLY DUCT 4"
2"
CONDENSATE
PUMP
BACK-SEATED REFRIGERANT
FLEXIBLE VALVE- PROVIDE WHEN NOT
LINED SHEET METAL INTEGRAL TO UNIT
RETURN PLENUM, FULL CONNECTION (TYP)
SIZE OF UNIT RETURN FULL SIZE DRAIN WITH PROJECT NO.

UNLESS NOTED. PROVIDE TRAP, SEE PLANS FOR 6" THICK CON. PAD - EXTEND

A
FLEXIBLE CONNECTION AT
CONNECTION OF RETURN
ROUTING. 3" TO 6" BEYOND UNIT ALL AROUND REFRIGERANT SUCTION LINE
WITH INSULATION
514.3969.00
EMERGENCY DRAIN PAIN WITH LIQUID
SHEET TITLE
DUCT TO PLENUM. DETECTOR FLOAT SWITCH WIRED TO SIGHT GLASS WITH MOISTURE REFRIGERANT LIQUID LINE
SHUT DOWN UNIT WHEN ACTIVATED. INDICATOR MECHANICAL DETAILS
NOTE:
PROVIDE UNIT WITH AN IONIZATION TYPE SMOKE DETECTOR INSTALLED IN THE RETURN CONDUIT- POWER AND
DUCT WIRED TO SHUT DOWN THE UNIT UPON ACTIVATION. ACTIVATION OF DUCT FILTER-DRYER CONTROL
DETECTOR SHALL ACTIVATE AN AUDIO VISUAL ALARM IN AN APPROVED LOCATION AND
SHALL BE IDENTIFIED AS "AIR DETECTOR TROUBLE". SMOKE DETECTOR AND ALARM
SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR.
6A AIR COOLED CONDENSING UNIT SLAB MOUNTED AT GRADE
M501 1/4" = 1'-0"
4A HORIZONTAL AIR HANDLING UNIT DX WITH OUTSIDE AIR DETAIL
M501 1/8" = 1'-0" SHEET NUMBER

M501
1 2 3 4 5 6 7
ENERGY RECOVERY UNIT SCHEDULE
SUPPLY FAN RELIEF FAN ENERGY RECOVERY WHEEL ELECTRICAL DATA SELECTION BASED ON
EXTERNAL DESSICANT SUMMER OPERATION WINTER OPERATION
STATIC SUPPLY FAN EXTERNAL WHEEL
PRESSURE DRIVE STATIC MOTOR 410 Backwell St., Suite 10
Designation AIR FLOW FAN MOTOR AIR FLOW FAN MOTOR FAN DRIVE INTAKE db INTAKE wb SUPPLY db SUPPLY wb RETURN db RETURN wb EXHAUST db EXHAUST wb INTAKE db INTAKE wb SUPPLY db SUPPLY wb RETURN db RETURN wb EXHAUST db EXHAUST wb VOLTAGE PHASE FREQUENCY MANUFACTURER MODEL REMARKS
Durham NC 27701
ERV-1 1625 CFM 0.75 in-wg 0.75 hp DIRECT 1550 CFM 0.75 in-wg 0.75 hp DIRECT 0.05 hp 93.3 °F 80.3 °F 80.2 °F 68.3 °F 75.0 °F 63.0 °F 88.7 °F 76.5 °F 24.0 °F 20.1 °F 56.8 °F 46.2 °F 70.0 °F 54.3 °F 35.5 °F 30.2 °F 208 V 3 60 Hz GREENHECK ERV-20 T: 919.474.2500 F: 919.474.2545
ERV-2 1625 CFM 0.75 in-wg 0.75 hp DIRECT 1550 CFM 0.75 in-wg 0.75 hp DIRECT 0.05 hp 93.3 °F 80.3 °F 80.2 °F 68.3 °F 75.0 °F 63.0 °F 88.7 °F 76.5 °F 24.0 °F 20.1 °F 56.8 °F 46.2 °F 70.0 °F 54.3 °F 35.5 °F 30.2 °F 208 V 3 60 Hz GREENHECK ERV-20
www.littleonline.com
NOTES:
F 1. PROVIDE FANS THAT OPERATE IN THE STABLE RANGE FROM MINIMUM TO MAXIMUM FLOW.
2. ALL FANS SHALL BE DIRECT DRIVE FANS. This drawing and the design shown are the property
3. PROVIDE VFD'S ON ALL FANS, EACH FAN SHALL HAVE A DEDICATED DRIVE. ALL VFD'S SHALL BE FACTORY INSTALLED. of Little Diversified Architectural Consulting. The
4. TOTAL AND SENSIBLE CAPACITY ARE PROVIDED FOR REFERENCE ONLY; SELECT WHEEL FOR SCHEDULED LEAVING CONDITIONS. reproduction, copying or other use of this drawing
5. PROVIDE MERV 8 PREFILTERS AND MERV 13 FINAL FILTERS PRIOR TO AIR ENTERING ENERGY RECOVERY WHEEL, ON BOTH RETURN AIR AND FRESH AIR CONNECTIONS.
without their written consent is prohibited and any
6. PROVIDE ENERGY OPTIMIZATION CONTROLS.
7. PROVIDE 5 YEAR EXTENDED WARRANTY-COMPLETE INCLUDING PARTS AND LABOR. infringement will be subject to legal action.
8. UNIT SHALL HAVE FACTORY MOUNTED OUTSIDE AIR MEASURING STATIONS.
9. AIR HANDLING UNIT CASING SHALL BE OF THE “NO-THROUGH-METAL” DESIGN. PROVIDE NECESSARY SUPPORT TO LIMIT CASING DEFLECTION TO L/200 OF THE NARROWEST PANEL DIMENSION. UNITS SHALL ENTIRELY BE MADE OF c Little 2014
DOUBLE WALL CONSTRUCTION. EXPOSED INSULATION EDGES IN THE AIRSTREAM ARE NOT ACCEPTABLE. UNIT WALL AND ROOF PANELS SHALL BE INSULATED WITH R-13 NON-COMPRESSED MINERAL WOOL INSULATION. UNIT INTERNAL
PARTITION SHALL BE INSULATED WITH R-9 NON-COMPRESSED MINERAL WOOL INSULATION. DX HEAT PUMP CONDENSING UNIT SCHEDULE
BO - FAN START/STOP COOLING HEATING ELECTRICAL DATA SELECTION BASED ON
ASSOCIATED TOTAL TOTAL
AO - RELIEF FAN VFD SPEED UNIT INDOOR UNIT COMPRESSOR COOLING HEATING
NUMBER NUMBER QUANTITY CAPACITY SEER CAPACITY HSPF VOLTAGE PHASE MANUFACTURER MODEL REMARKS
BI - RELIEF FAN VFD FAULT
HP-1 IDU-1 1 47,000.0 Btu/h 16 47,000.0 Btu/h 9 208 V 3 CARRIER 25HCB
AI - RA HUMIDITY HP-2 IDU-2 1 56,500.0 Btu/h 16 58,000.0 Btu/h 9 208 V 3 CARRIER 25HCB
HP-3 IDU-3 1 56,500.0 Btu/h 16 58,000.0 Btu/h 9 208 V 3 CARRIER 25HCB
AI - RA TEMP
VFD HP-4 IDU-4 1 24,000.0 Btu/h 17 26,000.0 Btu/h 10.8 208 V 3 MITSUBISHI PUZ-A24
BI - FAN STATUS
CT REMARKS
1. PROVIDE WITH MANUFACTURER'S LOW AMBIENT KIT.
H T 2. PROVIDE WITH MANUFACTURER'S LONG LINE APPLICATION KIT AS REQUIRED FOR FIELD ROUTING OF REFRIGERANT LINES.
3. PROVIDE WITH SINGLE POINT POWER CONNECTION.
4. MAINTAIN MANUFACTURER'S CLEARANCES AROUND UNIT.
EA RA

E BO - WHEEL START/STOP EXHAUST FAN SCHEDULE


AO - WHEEL VFD SPEED FAN DATA FAN MOTOR DATA SELECTION BASED ON
BI - WHEEL VFD FAULT EXTERNAL
UNIT MAXIMUM STATIC BLADE DRIVE WHEEL MOTOR
NUMBER DESCRIPTION AIRFLOW PRESSURE RPM TYPE TYPE SONES POWER RPM VOLTAGE PHASE MANUFACTURER MODEL REMARKS
EF-1 INLINE 200 CFM 0.50 in-wg 1000 DIRECT FC 3 83.0 W 1000 120 V 1 GREENHECK CSP-A250
VFD M
NOTES:
1. PROVIDE FACTORY MOUNTED SPEED CONTROLLER, SINGLE POINT ELECTRICAL CONNECTION, AND WIRED DISCONNECT.
2. PROVIDE MANUFACTURER'S GRAVITY BACKDRAFT DAMPER, EC MOTOR WITH FACTORY CONTROLS, AND SPRING AND MOUNTING KIT.
3. MECHANICAL CONTRACTOR TO PROVIDE ALL DRIVES AND STARTERS, ELECTRICAL CONTRACTOR TO INSTALL.
AI - SA HUMIDITY
4. FAN TO OPERATE CONTINUOUSLY DURING OCCUPIED HOURS.
AI - SA TEMP

H T
SINGLE ZONE CONSTANT VOLUME INDOOR UNIT SCHEDULE
OA SA ASSOCIATED SUPPLY FAN COOLING DATA HEATING DATA ELECTRICAL DATA SELECTION BASED ON
UNIT OUTDOOR SUPPLY FAN SENSIBLE HEAT PUMP AUX ELECTRIC
NUMBER UNIT NUMBER AIR FLOW ESP MOTOR LAT db LAT wb TOTAL CAPACITY CAPACITY LAT db CAPACITY HEAT (kW) VOLTAGE PHASE FREQUENCY MANUFACTURER MODEL REMARKS
BI - FAN STATUS IDU-1 HP-1 1600 CFM 0.75 in-wg 0.5 hp 55.0 °F 54.5 °F 47,000.0 Btu/h 35,500.0 Btu/h 90.0 °F 45,500.0 Btu/h 3.6 208 V 1 60 Hz CARRIER FV4B
CT IDU-2 HP-2 1800 CFM 0.75 in-wg 1.0 hp 55.0 °F 54.5 °F 57,500.0 Btu/h 44,400.0 Btu/h 90.0 °F 56,500.0 Btu/h 3.6 208 V 1 60 Hz CARRIER FV4B
IDU-3 HP-3 1800 CFM 0.75 in-wg 1.0 hp 55.0 °F 54.5 °F 57,500.0 Btu/h 44,400.0 Btu/h 90.0 °F 56,500.0 Btu/h 3.6 208 V 1 60 Hz CARRIER FV4B
VFD

NOTES:
BO - FAN START/STOP 1. PROVIDE MERV 8 FILTERS
AO - SUPPLY FAN VFD SPEED 2. PROVIDE ENERGY OPTIMIZATION CONTROLS.
D 3. PROVIDE 5 YEAR EXTENDED WARRANTY-COMPLETE INCLUDING PARTS AND LABOR
BI - SUPPLY FAN VFD FAULT

6 TOTAL ENERGY RECOVERY UNIT SCHEMATIC


M601 12" = 1'-0"
DUCTLESS MINISPLIT SYSTEM HEAT PUMP - INDOOR UNIT SCHEDULE
ASSOCIATED COOLING DATA HEATING DATA ELECTRICAL DATA SELECTION BASED ON
UNIT OUTDOOR EAT - EAT - EAT - EAT - TOTAL
NUMBER UNIT NUMBER AIR FLOW OA -db db wb TOTAL CAPACITY OA -db db wb CAPACITY VOLTAGE PHASE MANUFACTURER MODEL REMARKS
IDU-4 HP-4 700 CFM 95 °F 80 °F 67 °F 24,000.0 Btu/h 47 °F 70 °F 60 °F 26,000.0 Btu/h 208 V 1 MITSUBISHI PKA-A24KA4

REMARKS
BI - ZONE OVERRIDE 1. MOUNT UNIT HIGH ON WALL. MAINTAIN MANUFACTURER'S CLEARANCE AROUND UNIT.
2. PROVIDE UNIT WITH MANUFACTURER'S WALL MOUNTING KIT, THERMOSTAT, AND INTEGRAL CONDENSATE PUMP.
RA SA AI - ZONE TEMP 3. MECHANICAL CONTRACTOR SHALL PROVIDE DISCONNECT AT INDOOR UNIT.
T

M AI - ZONE SETPOINT ADJUST

AIR DISTRIBUTION DEVICE SCHEDULE


BO - REVERSING VALVE
HP BASED ON
UNIT NUMBER SERVICE NECK SIZE TYPE SHAPE MATERIAL FRAME TYPE MODULE SIZE FINISH MANUFACTURER MODEL
BO - COMPRESSOR STAGE E1A1 EXHAUST AIR 6"ø SQUARE PLAQUE DIFFUSER SQUARE ALUMINUM LAY-IN 24''x24'' WHITE PRICE SPD
E2A EXHAUST AIR 6"ø SQUARE PLAQUE DIFFUSER SQUARE ALUMINUM SURFACE 24''x24'' WHITE PRICE SPD
E2B EXHAUST AIR 8"ø SQUARE PLAQUE DIFFUSER SQUARE ALUMINUM SURFACE 24''x24'' WHITE PRICE SPD
BI - FAN STATUS E2C EXHAUST AIR 10"ø SQUARE PLAQUE DIFFUSER SQUARE ALUMINUM SURFACE 24''x24'' WHITE PRICE SPD
CT R1E RETURN AIR 14"ø PLAQUE FACE DIFFUSER SQUARE ALUMINUM LAY-IN 24''x24'' WHITE PRICE ASPD
C BO - FAN START/STOP S1A SUPPLY 6"ø SQUARE PLAQUE DIFFUSER SQUARE ALUMINUM LAY-IN 24''x24'' WHITE PRICE ASPD
S1A1 SUPPLY 6"ø SQUARE PLAQUE DIFFUSER SQUARE ALUMINUM LAY-IN 12"x12" WHITE PRICE ASPD
S1B SUPPLY 8"ø SQUARE PLAQUE DIFFUSER SQUARE ALUMINUM LAY-IN 24''x24'' WHITE PRICE ASPD
7 AIR SOURCE HEAT PUMP SCHEMATIC S1C SUPPLY 10"ø SQUARE PLAQUE DIFFUSER SQUARE ALUMINUM LAY-IN 24''x24'' WHITE PRICE ASPD
M601 12" = 1'-0" S2A RETURN 12"x8" DOUBLE DEFLECTION GRILLE RECTANGLE STEEL SURFACE MOUNT 8x6 WHITE PRICE 520D

NOTES:
1. PROVIDE WITH FACTORY FACE ADJUSTABLE OPPOSED BLADE DAMPERS.
ISSUE FOR
2. COORDINATE FRAME TYPE WITH CEILING.
CONSTRUCTION
AI - DISCHARGE AIR TEMP
DOCUMENTS

T ISSUE DATE
BI - ZONE OVERRIDE
ELECTRIC UNIT HEATER SCHEDULE 04/01/2016
SA T AI - ZONE TEMP REVISIONS
HEATER INFO ELECTRICAL DATA BASED ON
AI - ZONE
NO. REASON DATE
EA UNIT LEAVING AIR HEATING
SETPOINT ADJUST NUMBER TEMPERATURE CAPACITY VOLTAGE PHASE FREQUENCY MANUFACTURER MODEL REMARKS
M UH-1 90 °F 1.0 kW 120 V 1 60 Hz QMARK CWH1101DSF
BI - FAN STATUS UH-2 90 °F 1.0 kW 120 V 1 60 Hz QMARK CWH1101DSF
CT

ELEC
BO - FAN START/STOP
BI - FAN STATUS
CT AO - HEATING OUTPUT
BO - FAN START/STOP BO - HEATING ENABLE

8 ELECTRIC RADIANT HEATER SCHEMATIC 9 CONTINUOUS EXHAUST FAN SCHEMATIC


B M601 12" = 1'-0" M601 12" = 1'-0"

PROJECT TEAM
PRINCIPAL IN CHARGE

CHARLES J. TODD
PROJECT MANAGER

TIM McAULIFFE
DESIGN TEAM
LITTLE
PROJECT NAME

PENDER HIGH SCHOOL

PROJECT NO.

A
514.3969.00
SHEET TITLE

MECHANICAL
SCHEDULES

SHEET NUMBER

M601
1 2 3 4 5 6 7