Professional Documents
Culture Documents
Revised Record
Catalogue
Foreword .....................................................................................................................................6
Chapter 1 Summary................................................................................................................7
1.4 Types.......................................................................................................................................... 8
Diagram Catalogue
Foreword
This manual introduces the technical parameters, specification, capacity calculation,
installation and maintenance of AGM battery. It mainly contains four chapters:
Chapter 1: Product application, technical parameters, specification and working principle.
Chapter 2: Technical characteristic of AGM battery.
Chapter 3: Installation of AGM battery.
Chapter 4: Maintenance of AGM battery.
Abbreviation:
Chapter 1 Summary
ŶOther backups
l Safety: The valve can automatically regulate the internal pressure of the battery, and
the one way valve can prevent the outer air into the battery. The special filter prevents
l Easy installation: The battery can be installed vertically or horizontally. Only normal
ventilation is required.
l High nominal voltage: The nominal voltage is the highest except lithium cell, fewer
l Low cost.
l Low resistance: About several milliohm, can adapt to discharge with heavy current.
l Low self-discharge rate: Self-discharge rate less than 2% per month at 25ć.
1.4 Types
The electrochemical reaction of the lead acid battery involves lead, lead dioxide and an
The following formula shows the main chemical reactions for discharge and charge:
Disch arg e
PbO 2 + 2H 2SO 4 + Pb ® 2PbSO 4 + 2H 2O
Charge
2PbSO 4 + 2H 2O ® PbO 2 + 2H 2SO 4 + Pb
2H2O ® 2H 2 - + O 2 -
This side reaction leads to water loss gradually, therefore, pure water have to be added
AGM battery adopts the design of barren-liquor, and there are a mass of paths in the separator
which is made up of micro porous glass fiber. Also special alloy grid is chosen to increase the
hydrogen. Therefore, the oxygen generated from positive pole diffuses through separator to the
negative pole, then reacts quickly there and recombined into water. The reactions are as
follows:
The float current passing through cell then reduces, instead of evolving hydrogen, on the
negative electrode, the formed lead sulfate back to lead and sulfuric acid so that a closed cycle
(oxygen recombination cycle) is obtained.
Ł Floating charge
The floating charge voltage of the battery is set as 2.23V/cell (at 25ć), the initial charge
current is not more than 0.15C10A. When the ambient temperature deviates from 25ć, the
U f = 2.230 - (t - 25 ) ´ 0.003
Uf —Floating charge voltage after setting-up; t —Ambient temperature
ł Equalizing charge
The equalizing charge voltage is usually set as 2.35V/cell (25ć), and the maximum
immediately. The limited current is 0.15C10A (battery used outdoor) and 0.10C10A (battery
used indoor). The charge time depends on the discharged capacity and the initial charge
current. Figure 2 shows that the charge performance of the AGM battery with a depth of
50%C10 and 100%C10, at a limited charge current of 0.1C10A and constant voltage of
2.23v/cell at 25ć.
Conventionally, the rated capacity of a battery in the communication industry is defined as the
ten-hour-rate discharge capacity (I=0.1C10A) at 25ć, i.e., a fully charged battery is discharged
at 25ć with 0.1CA current until the operation voltage declines to 1.80V/cell, The unit of
For the same battery at the same condition, there is an inverse ratio between discharged
2008-11-3 Public Page 11 of 23
VRLA AGM BATTERY OPERATION MANUAL˄AGM˅ PUBLIC
capacity and discharge current. Less the discharged capacity, heavier the discharge current
increases.
W ´ t ´ 1.04 ´ 1.25
C=
Vr ´ h
Ș 0.4 0.55 0.63 0.7 0.75 0.8 0.85 0.9 0.92 0.95 0.98 1 1.01 1.03
2.3.2 Example
E.g.: The load power of 48V system is 3000W; standby time is 6 h, Please figure out the
battery capacity.
Solution : W˙3000ˈVr ˙48ˈt˙6ˈ n˙2ˈ IURPWKHWDEOHNQRZȘ˙0.9
Thus, battery capacity calculate˖
Battery capacity select˖The battery capacity select is 300Ah with two strings parallel
connection or 600Ah with one string.
2. The installation environment should be dry, clean and ventilating, free of organic solvent
3. Direct sunlight should be avoided, and keep away from heater or electric power switch
4. The foundation of installation should meet the weight bearing requirement of the battery
block.
1. Please check the outer package before unpacking. Once there are breakages on the
package, check the appearance of each battery to make sure that everyone is in fine
condition.
2. Check the number of batteries and accessories according to the packing list and read the
3. Check the open circuit voltage (OCV) of each battery before installation: OCV should be
1. Check the ambient temperature to make sure it meets the requirement mentioned above.
2. Please program the position of battery string first according to the practical installing
status.
4. The space between two batteries in the same string should be more than 15 mm.
5. Please read the attached installation drawing before installing and DO NOT modified it
7. DO NOT open the regulating valve and put anything else into the battery.
10. Please clean the surface of the connection cable, copper bar and battery terminal before
connection
12. Terminal screw connections must be tightened, the torque of different screws are shown
in table.4
13. Check-up the total voltage of the battery string before operation.
M6 8
M8 11-15
M10 22
1. Please read the attached connection drawing before installing the batteries into the racks.
7. Install the batteries, install the 2V batteries of each side at the bottom, and then the four in
the middle.
10. Install the output terminal, fixed the output terminal with M8 hexagon-headed bolts.
11. In the end, install the connector and insulation cover, install the connector according to
1. Please read the attached connection drawing before installing the batteries into the cabinet.
2. Connect the cabinet to the ground at the installation site with the ground bolts.
4. Move the cabinet to the point and tighten expansion bolts up(with the front gate’s
accessories removed).
5. The connection position of positive and negative pole should be preplanned before battery
installation, as well as the battery rank order and the orientation of positive and negative
polarity.
6. Remove the front blocked sides, and then install batteries from the bottom to upper (with
8. Install the front blocked sides, connect connecting barsǃsoft cable and terminal safety
1. All the tools must be insulated. Never place the metal tools on the bareness terminal of a
battery.
3. DO NOT open the safety valve or put anything else into the battery.
Periodic inspections and maintenance are very necessary. Good habit to record the details of
battery maintenance is helpful to deal with any problem about battery operation.
n Physical conditions about the battery, such as leakage, distention, distortion, break or
damage.
n And other conditions relevant to safety issues and battery’s service life (battery room
n If more than two cells’ voltages are less than 2.18V after temperature adjustment, the
n Make a discharge test to check with exact load every year, discharging 30%-40% of rated
capacity.
n Make a capacity test every three years and annually after six years’ operation.
n If the capacity of the battery decreases to lower than 80% of rated capacity, the battery
should be replaced.