Module Data:

ILC 131 ETH

Inline Controller for Ethernet Networks With 8 Digital Inputs and 4


Digital Outputs
General Data/Programming Data
Function/Features
Pin Assignment
PCP Services
System Variables
Module Interfaces
Technical Data
The detailed data sheet for the relevant product can be downloaded at
www.phoenixcontact.net/catalog.

▲General Data

General Product
Information
Manufacturer: Phoenix
Contact
Device type: PLC
Product ILC1xx
range:
Order No.: 2700973
Version: 00/4.10

Fig. 1: ILC 131 ETH

▲Function
The ILC 131 is a Remote Field Controller with IB local bus interface for the Inline installation system with
programming options according to IEC 61131-3 and a universal Ethernet gateway with TCP/IP transport
protocol.

▲Features
l Automation and control functions according to IEC 61131-3

file:///C:/Users/Public/Documents/FDCML10/ETHERNET/Phoenix%20Contact/Sho... 15/04/2019
Page 2 of 7

▲Pin Assignment
terminal signal/
plug
point description
1 1.1 PWR US
1 1.2 PWR UL
1 1.3 GND UL
1 1.4 Functional
earth
ground
(FE)
1 2.1 PWR UM
1 2.2 PWR UM
1 2.3 GND UM,
US
1 2.4 Functional Fig. 2: Terminal assignment
earth
ground
(FE)
2 1.1 Output 1
2 1.2 GND
2 1.3 FE
2 1.4 Output 3
2 2.1 Output 2
2 2.2 GND
2 2.3 FE
2 2.4 Output 4
3 1.1 Input 1
3 1.2 PWR UM
3 1.3 GND
3 1.4 Input 3
3 2.1 Input 2
3 2.2 PWR UM
3 2.3 GND
3 2.4 Input 4
4 3.1 Input 5
4 3.2 PWR UM
4 3.3 GND
4 3.4 Input 7
4 4.1 Input 6
4 4.2 PWR UM
4 4.3 GND
4 4.4 Input 8
ETH RJ45 RJ45

file:///C:/Users/Public/Documents/FDCML10/ETHERNET/Phoenix%20Contact/Sho... 15/04/2019
Page 3 of 7

▲PCP Services
Service
PCP read supported (client) True
PCP write supported (client) True
PCP get OD long supported (client) True
PCP program invocation supported (client) True
PCP download supported (client) True
PCP upload supported (client) True
PCP request domain upload supported (client) True
PCP information report supported (client) True
PCP read and write with name supported (client) True
Number of parallel PCP services (client) 1
PCP read supported (server) True
PCP write supported (server) True
PCP get OD long supported (server) False
PCP program invocation supported (server) False
PCP download supported (server) False
PCP upload supported (server) False
PCP request domain upload supported (server) False
PCP information report supported (server) True
PCP read and write with name supported (server) False
Number of parallel PCP services (server) 1
PCP PDU length (transmit direction) 246 byte
PCP PDU length (receive direction) 246 byte
PCP PNM7 PDU length (transmit direction) 246 byte
PCP PNM7 PDU length (receive direction) 246 byte

▲System Variables
Data
Name Description
Type
PLCMODE_ON PLC status ON BOOL
PLCMODE_LOADING PLC status LOADING BOOL
PLCMODE_RUN PLC status RUN BOOL
PLCMODE_STOP PLC status STOP BOOL
PLCMODE_HALT PLC status HALT BOOL
PLCDEBUG_BPSET Breakpoint set BOOL
PLCDEBUG_FORCE Variable(s) forced BOOL
PLCDEBUG_POWERFLOW Address status enabled BOOL
PLC_TICKS_PER_SEC System ticks per second INT
PLC_SYS_TICK_CNT Number of system ticks DINT
PLC_TASK_AVAILABLE Number of available PLC INT
tasks

file:///C:/Users/Public/Documents/FDCML10/ETHERNET/Phoenix%20Contact/Sho... 15/04/2019
Page 4 of 7

PLC_SYSTASK_AVAILABLE Number of available INT


system tasks
PLC_MAX_ERRORS DINT
PLC_ERRORS DINT
PLC_TASK_DEFINED Number of tasks used INT
PLC_TASK_1 Task 1 information Record,
elements
= 30
PLC_TASK_2 Task 2 information Record,
elements
= 30
PLC_TASK_3 Task 3 information Record,
elements
= 30
PLC_TASK_4 Task 4 information Record,
elements
= 30
PLC_TASK_5 Task 5 information Record,
elements
= 30
PLC_TASK_6 Task 6 information Record,
elements
= 30
PLC_TASK_7 Task 7 information Record,
elements
= 30
PLC_TASK_8 Task 8 information Record,
elements
= 30
LICENSE License information DWORD
MASTER_DIAG_STATUS_REG_HI Master diagnostic status BYTE
register high byte
MASTER_DIAG_STATUS_REG_LOW Master diagnostic status BYTE
register low byte
MASTER_DIAG_STATUS_REG_BSA Bus segment BOOL
disconnected
MASTER_DIAG_STATUS_REG_SYSFAIL System failure BOOL
MASTER_DIAG_STATUS_REG_RES Standard function BOOL
processed negatively
MASTER_DIAG_STATUS_REG_SYNCRES Synchronization error BOOL
MASTER_DIAG_STATUS_REG_DCR Faulty data cycles BOOL
MASTER_DIAG_STATUS_REG_WARN Defined warning time BOOL
exceeded
MASTER_DIAG_STATUS_REG_QUAL Defined error density BOOL
exceeded
MASTER_DIAG_STATUS_REG_SSINFO Pending message BOOL
MASTER_DIAG_STATUS_REG_USER User BOOL
error/parameterization
MASTER_DIAG_STATUS_REG_PF Peripheral fault BOOL

file:///C:/Users/Public/Documents/FDCML10/ETHERNET/Phoenix%20Contact/Sho... 15/04/2019
Page 5 of 7

MASTER_DIAG_STATUS_REG_BUS Bus error BOOL


MASTER_DIAG_STATUS_REG_CTRL Fault on the controller BOOL
board/hardware
MASTER_DIAG_STATUS_REG_DTC Diagnostic routine active BOOL
MASTER_DIAG_STATUS_REG_RUN Data transmission active BOOL
MASTER_DIAG_STATUS_REG_ACT Selected configuration BOOL
ready to operate
MASTER_DIAG_STATUS_REG_RDY Controller board ready to BOOL
operate
MASTER_DIAG_PARAM_REG_HI Master diagnostic BYTE
parameter register high
byte
MASTER_DIAG_PARAM_REG_LOW Master diagnostic BYTE
parameter register low
byte
MASTER_DIAG_PARAM_2_REG_HI Extended master BYTE
diagnostic parameter
register 2 high byte
MASTER_DIAG_PARAM_2_REG_LOW Extended master BYTE
diagnostic parameter
register 2 low byte
COP_DIAG_STATUS_REG_RT_ERR Runtime error (control BOOL
processor)
COP_DIAG_STATUS_REG_FAT_ERR Fatal error (control BOOL
processor)
COP_DIAG_STATUS_REG_WARN Warning (control BOOL
processor)
COP_DIAG_STATUS_REG_PON Power on (control BOOL
processor)
COP_DIAG_STATUS_REG_FC_RUN Runtime system RUN BOOL
COP_DIAG_STATUS_REG_FC_STOP Runtime system STOP BOOL
COP_DIAG_STATUS_REG_FC_HALT Runtime system HALT BOOL
COP_DIAG_STATUS_REG_FC_LDG Runtime system BOOL
LOADING
COP_DIAG_STATUS_REG_FC_DBG Runtime system DEBUG BOOL
COP_DIAG_STATUS_REG_FC_RDO Runtime system BOOL
READONLY
COP_DIAG_PARAM_REG Diagnostic parameter WORD
register of the control
processor
COP_DIAG_PARAM_2_REG Extended diagnostic WORD
parameter register of the
control processor
COP_CPU_LOAD_WARNING The controller is BOOL
approaching its
processor capacity limit
ONBOARD_INPUT Local inputs WORD
ONBOARD_INPUT_BIT0 Local input IN1 BOOL
ONBOARD_INPUT_BIT1 Local input IN2 BOOL

file:///C:/Users/Public/Documents/FDCML10/ETHERNET/Phoenix%20Contact/Sho... 15/04/2019
Page 6 of 7

ONBOARD_INPUT_BIT2 Local input IN3 BOOL


ONBOARD_INPUT_BIT3 Local input IN4 BOOL
ONBOARD_INPUT_BIT4 Local input IN5 BOOL
ONBOARD_INPUT_BIT5 Local input IN6 BOOL
ONBOARD_INPUT_BIT6 Local input IN7 BOOL
ONBOARD_INPUT_BIT7 Local input IN8 BOOL
ONBOARD_OUTPUT_BIT0 Local output OUT1 BOOL
ONBOARD_OUTPUT_BIT1 Local output OUT2 BOOL
ONBOARD_OUTPUT_BIT2 Local output OUT3 BOOL
ONBOARD_OUTPUT_BIT3 Local output OUT4 BOOL
RTC_BATTERY_LOW Realtime clock battery BOOL
capacity low
RTC_DATA_INVALID Realtime clock data BOOL
invalid
FLASHCARD_PRESENT Phoenix Contact SD card BOOL
inserted
ONBOARD_OUTPUT_OVERLOAD_0_3 Local I/O overload BOOL
POWER_SUPPLY_MAIN_OK 24 V main supply voltage BOOL
OK
POWER_SUPPLY_INPUTS_OK 24 V local input supply BOOL
OK
POWER_SUPPLY_OUTPUTS_0_3_OK 24 V local output supply BOOL
OK (bits 0...3)
KEY_SWITCH_RESET Start/stop switch in BOOL
MRESET position
KEY_SWITCH_STOP Start/stop switch in BOOL
STOP position
KEY_SWITCH_RUN_PROG Start/stop switch in BOOL
RUN/PROG position
RTC_HOURS System time (hours) INT
RTC_MINUTES System time (minutes) INT
RTC_SECONDS System time (seconds) INT
RTC_DAY System time (day) INT
RTC_MONTH System time (month) INT
RTC_YEAR System time (year) INT
PND_S1_PLC_RUN Status of the higher-level BOOL
control system
PND_S1_VALID_DATA_CYCLE IO Controller has BOOL
established the
connection
PND_S1_OUTPUT_STATUS_GOOD IOP status of the higher- BOOL
level control system
PND_S1_DATA_LENGTH Process data length WORD
PND_S1_OUTPUTS Output process data Record,
elements
= 256
PND_S1_INPUTS Input process data Record,

file:///C:/Users/Public/Documents/FDCML10/ETHERNET/Phoenix%20Contact/Sho... 15/04/2019
Page 7 of 7

elements
= 256
PND_IO_DRIVEN_BY_PLC Number of the PLC INT
currently connected with
the PNIO Device
PND_RESET_FACTORY_SETTINGS shows the bits of the kind WORD
of a reset to factory
service
IB_DEVICE_PARAM_ACTIVATED Interbus device BOOL
configuration activated
IB_DEVICE_PARAM_READY Interbus device BOOL
configuration completed
IB_DEVICE_PARAM_ERROR Interbus device BOOL
configuration error
APPMGR_APPLICATION_ID STRING
APPMGR_TEMPLATE_ID STRING
APPMGR_APPLICATION_NAME STRING

▲Module Interfaces
Description
Ethernet
Internal interface
Internal interface
Internal interface
Internal interface
MODBUS
Outgoing IL local bus
Serial interface
Internal interface

▲Technical Data
General data
Order designation ILC 131 ETH