You are on page 1of 4

Para L=400 ft

h pump ,u =18.41+ 3.8114 x 10−5 x Q 2

Q h pump ,u

600 32.13

800 42.79

1200 73.29

1600 115.48

2000 170.87

2400 237.41

Q= 1220 GPM

h= 75 ft

η = 75%
ρg v̇ h pump ,u
w pump, shaff =
η pump

ft 3
lbm ft
w pump, shaff =62.4 3 x 32.2 2
ft
1 lbf
s 32.2 lbm ft
2 ( ()
x 1220 GPMx
1
s
448,8 GPM
)
x 75 ft ÷ 0.75

lbf −ft 1 HP
10962.57 x =30.84 HP
s lbf −ft
550
s
Para L=300 ft

h pump ,u =18.41+ 3.0116 x 10−5 x Q2

Q h pump ,u

600 29.25

800 37.08

1200 61.78

1600 95.51

2000 138.87

2400 191.88

Q= 1330 GPM

h= 72 ft

η = 80.5%
ρg v̇ h pump ,u
w pump, shaff =
η pump

ft 3
lbm ft
w pump, shaff =62.4 3 x 32.2 2
ft
1 lbf
s 32.2 lbm ft
2 ( ()
x 133 0 GPMx
1
s
448,8 GPM
)
x 72 ft ÷ 0.805

lbf −ft 1 HP
16539.41 x =30.07 HP
s lbf −ft
550
s
Para L=200 ft

h pump ,u =18.41+ 2.2116 x 10−5 x Q2

Q h pump ,u

600 26.37

800 32.56

1200 50.26

1600 75.03

2000 106.87

2400 145.79

Q= 1488 GPM

h= 68 ft

η = 86%
ρg v̇ h pump ,u
w pump, shaff =
η pump

ft 3
lbm ft
w pump, shaff =62.4 3 x 32.2 2
ft
1 lbf
s 32.2 lbm ft
2 ( ()
x 1488 GPMx
1
s
448,8 GPM
)
x 68 ft ÷ 0.86

lbf −ft 1 HP
16358 x =29.74 HP
s lbf −ft
550
s
Para L=200 ft

h pump ,u =18.41+1.4117 x 10−5 x Q2

Q h pump ,u

600 23.49

800 27.44

1200 38.74

1600 54.75

2000 74.38

2400 99.72

Q= 1740 GPM

h= 61.5 ft

η = 82%
ρg v̇ h pump ,u
w pump, shaff =
η pump

ft 3
lbm ft
w pump, shaff =62.4 3 x 32.2 2
ft
1 lbf
s 32.2 lbm ft
2 ( ()
x 1740 GPMx
1
s
448,8 GPM
)
x 61.5 ft ÷ 0.82

lbf −ft 1 HP
18144.4 x =32.99 HP
s lbf −ft
550
s

You might also like