TEST REPORT
19497T/15
PROTECTION AND MEASURING TRANSFORMERS

3 - RI REVISION : 4 - DATE: 5 - SECTOR: 6 - REF. RI : 7 - PAGE :


2 22 / 05 / 15 210 RI 042 4/4
CLIENT
SPEED
TRANSFORMER IDENTIFICATION
Type (Model) KR-974R Primary current (Ip) 3500A
Nominal frequency (F) in HZ 50/60 Secondary current (Is) 5A
Maximum voltage of the equipment (kV) 0,6 Class (Accuracy) 5 P10 50VA
Thermal factor. (FT) 1,2 Nominal ratio (Rn) 700:1
Insulation level (kV) 4/-/- Manufacturing Order 557564
RESULTS
CURRENT (A) Saturation curve S1-S2 VOLTAGE (VOLTS)
↓ 1814789 1814790 1814791 1814792 1814793 1814794 1814795 1814796 1814797
0 0 0 0 0 0 0 0 0 0
1 285 285 285 285 285 285 285 285 285
2 285 285 285 285 285 285 285 285 285
3 285 285 285 285 285 285 285 285 285
4 290 290 290 290 290 290 290 290 290
5 290 290 290 290 290 290 290 290 290

350

300
1814789
Tensão 250 1814790
1814791
200
1814792
150 1814793
1814794
100
1814795
50 1814796
1814797
0
0 1 2 3 4 5 6
Corrente

Precision -Class 0,2 Precision -Class 0,2 Precision -Class 0,2


5% In 20% In 100% In x FT
1814789 Error (%) Phase angle Error (%) Phase angle Error (%) Phase angle
-0,71 25,0 -0,30 12,0 -0,17 6,5
5% In 20% In 100% In x FT
1814790 Error (%) Phase angle Error (%) Phase angle Error (%) Phase angle
-0,71 24,5 -0,30 13,5 -0,17 8,1
5% In 20% In 100% In x FT
1814791 Error (%) Phase angle Error (%) Phase angle Error (%) Phase angle
-0,72 25,1 -0,30 13,1 -0,17 6,4
5% In 20% In 100% In x FT
1814792 Error (%) Phase angle Error (%) Phase angle Error (%) Phase angle
-0,73 25,2 -0,30 13,2 -0,17 6,6

5% In 20% In 100% In x FT
1814793 Error (%) Phase angle Error (%) Phase angle Error (%) Phase angle

-0,70 24,8 -0,30 13,4 -0,17 8,2

5% In 20% In 100% In x FT
1814794 Error (%) Phase angle Error (%) Phase angle Error (%) Phase angle

-0,70 24,6 -0,30 12,5 -0,17 7,9

5% In 20% In 100% In x FT
1814795 Error (%) Phase angle Error (%) Phase angle Error (%) Phase angle

-0,72 24,5 -0,30 12,8 -0,17 8,1

5% In 20% In 100% In x FT

1814796 Error (%) Phase angle Error (%) Phase angle Error (%) Phase angle

-0,72 24,6 -0,30 12,4 -0,17 7,8

5% In 20% In 100% In x FT
1814797 Error (%) Phase angle Error (%) Phase angle Error (%) Phase angle

-0,71 24,5 -0,30 13,1 -0,17 7,5

THE MAIN POINTS WERE VERIFIED AS STANDARD IEC/EM 60044-1

APPLIED VOLTAGE: 4kV APPLIED BETWEEN PRIM.XSEC. EARTH AND 60S - APPLIED 3kV SEC. X GROUND 60S. (OK)

INDUCED VOLTAGE: VOLTAGE WAS APPLIED SECONDARY TERMINAL SIDE (FREQUENCY 240Hz)

UNTIL 6A CIRCULATION DURING 30S (OK)


SUBTRACTIVE POLARITY TEST AND RELATION: HELD IN CONJUNCTION WITH THE ACCURACY TEST (OK)
INSULATION RESISTANCE TEST: APPLIED 500VDC ≥ 2 MΩ 60S (OK)
EQUIPMENT USED AND CERTIFICATES
CALIBRATION BRIDGE "TETTEX". CERTIFICATE: 0270 STANDARD TRANSFORMER "TETTEX". CERTIFICATE: 0326

SET OF CHARGE "TETTEX" CERTIFICATE: 1405 HIPOT "AVO ENGLAND" CERTIFICATE: 1754

DIGITAL VOLTAGE INDICATOR (DG 48) CERTIFICATE: 984 DIGITAL POWER INDICATOR (DG 48) CERTIFICATE:985

DIGITAL FREQUENCY INDICATOR (DG 48) CERTIFICATE: 986 MEGOHMMETER 1000R DIGITAL CERTIFICATE: 48132

APPROVAL: CLAUDINEY CHECK: