You are on page 1of 1

IBD Instalación de Anillo Periférico de

ERSA010-DSM-001 PROJECT
Refrigeración de Manto de Estanques
SPRAY NOZZLE DATA SHEET
CLIENT Enap Refinerías S.A., Planta Linares
REV. DATE BY APPROVED DESCRIPTION
A 30-sep-16 ITG CTM / OFV Se emite para comentarios
0 11-abr-17 ITG CTM / OFV Emisión Final

1. Tag Number
Kerosene Tank Gasoline 97 Tank Diesel Tank Gasoline 93 Tank
2. Service
protection protection protection protection
GENERAL

3. Quantity / Spare / Total 28 / 6 / 34 36 / 6 / 42 48 / 6 / 54 48 / 6 / 54

4. Type Spray Nozzle Spray Nozzle Spray Nozzle Spray Nozzle


For shell of vertical For shell of vertical For shell of vertical For shell of vertical
5. Orientation
tank tank tank tank
6. Rings number 1 1 1 1
7. Fluid Water Water Water Water
8. minimum - - - -
9. Temp. Internal average 15 ºC 15 ºC 15 ºC 15 ºC
FLUID DATA

10. maximun 25 ºC 25 ºC 25 ºC 25 ºC
11. Min. Inlet Pressure 8,7 barg 8,7 barg 8,7 barg 8,7 barg
183 psig 183 psig 183 psig 183 psig
12. Design Pressure
(12 barg) (12 barg) (12 barg) (12 barg)
13. Density @TP 999 kg/m3 999 kg/m3 999 kg/m3 999 kg/m3
14. Viscosity @TP 1,14 cP 1,14 cP 1,14 cP 1,14 cP
15. Location Outdoor Outdoor Outdoor Outdoor
16. Humidity, % 54 - 87% 54 - 87% 54 - 87% 54 - 87%
SITE DATA

17. Wind speed 3-4 m/s 3-4 m/s 3-4 m/s 3-4 m/s
18. minimum -5 ºC -5 ºC -5 ºC -5 ºC
19. Site Temperature average 14 ºC 14 ºC 14 ºC 14 ºC
20. maximun 38 ºC 38 ºC 38 ºC 38 ºC
21. Manufacter Viking or similar Viking or similar Viking or similar Viking or similar
22. Model number VK814 or similar VK814 or similar VK814 or similar VK814 or similar
23. Size (gpm/psi0,5) 3,2 3,2 3,2 3,2
24. Connection 1/2 NPT 1/2 NPT 1/2 NPT 1/2 NPT
25. Material By vendor By vendor By vendor By vendor
SERVICE DATA

Minimum required discharge flow by


26. 5,4 m3/h 5,9 m3/h 6,4 m3/h 6,4 m3/h
each nozzle
27. Distance between nozzle and surface 0,6 m 0,6 m 0,6 m 0,6 m

28. Spray angle 125° 125° 125° 125°


29. Classification temperature - - - -
30. Temperature rating - - - -
31. Maximum ceiling temperature - - - -
32. Code - - - -

Notes:
1. Vendor shall design the water spray nozzles for the correct working
2. Vendor shall consider NFPA 15 recommendations in the system design
3. Spray nozzles shall be listed UL/FM for fire protection in accordance with NFPA 15
4.
5.

You might also like