he IEEE 14 bus system is shown in figure 3.1. The system data is taken
T from [9]. The data given in the following tables is on 100MVA base.
The minimum and maximum limits of voltage magnitude and phase angle are
considered to be 0.95p.u. to 1.05p.u. and -45◦ to +45◦ respectively.
126
Appendix A. IEEE 14 bus system 127
8 1 0 0 0 0 0 – –
9 1 0 0 0 29.5 16.6 – –
10 1 0 0 0 9.0 5.8 – –
11 1 0 0 0 3.5 1.8 – –
12 1 0 0 0 6.1 1.6 – –
13 1 0 0 0 13.8 5.8 – –
14 1 0 0 0 14.9 5.0 – –
he IEEE 30 bus system is shown in figure 3.3. The system data is taken
T from [47]. The data given in the following tables is on 100MVA base.
The minimum and maximum limits of voltage magnitude and phase angle are
considered to be 0.95p.u. to 1.05p.u. and -45◦ to +45◦ respectively.
129
Table B.1: Line data – IEEE 30 bus system
Line From To Line impedance (p.u.) Half line charging MVA Annual cost
number bus bus Resistance Reactance susceptance (p.u.) rating (×103 $/hr)
1 1 2 0.02 0.06 0.03 130 216.6125
2 1 3 0.05 0.20 0.02 130 307.2875
3 2 4 0.06 0.18 0.02 65 509.9500
4 2 5 0.05 0.02 0 130 721.5250
5 2 6 0.06 0.18 0.02 65 168.1750
6 3 4 0.01 0.04 0 130 700.000
7 4 6 0.01 0.04 0 90 474.3000
8 4 12 0 0.23 0 65 554.1250
9 5 7 0.05 0.12 0.01 70 62.2000
Appendix B. IEEE 30 bus system
8 1 0 30 30 0 0 0 0
9 1 0 0 0 0 0 0 0
10 1 0 5.919 2 0 0 0 0
11 1 0 0 0 0 0 0 0
12 1 0 11.2 7.5 0 0 0 0
13 1 0 0 0 37 13.949 -15 44.7
14 1 0 6.2 1.6 0 0 0 0
15 1 0 8.2 2.5 0 0 0 0
16 1 0 3.5 1.8 0 0 0 0
17 1 0 9 5.8 0 0 0 0
18 1 0 3.2 0.9 0 0 0 0
19 1 0 9.5 3.4 0 0 0 0
Continued on next page
132
Table B.2 – continued from previous page
Bus voltage Generation Load Reactive
Phase Real Reactive Real Reactive power
Bus Magnitude angle power power power power limits
number (p.u.) (degree) (MW ) (MVAR) (MW ) (MVAR) Qmin (MVAR) Qmax (MVAR)
20 1 0 2.2 0.7 0 0 0 0
21 1 0 19.669 11.20 0 0 0 0
22 1 0 0 0 31.59 40.34 -15 62.5
23 1 0 3.2 1.6 22.2 8.13 -10 40
24 1 0 15 6.70 0 0 0 0
25 1 0 1.00 0.00 0 0 0 0
26 1 0 3.50 2.30 0 0 0 0
27 1 0 0 0 28.91 10.97 -15 48.7
Appendix B. IEEE 30 bus system
28 1 0 0 0 0 0 0 0
29 1 0 3.659 0.90 0 0 0 0
30 1 0 12.00 1.90 0 0 0 0
133
Appendix B. IEEE 30 bus system 134
ndian utility 62 bus system is shown in figure 6.1. The system data is
I taken from [154]. The data given in the following tables is on 100MVA
base. The minimum and maximum limits of voltage magnitude and phase
angle are considered to be 0.95p.u. to 1.1p.u. and -45◦ to +45◦ respectively.
135
Table C.1: Line data – Indian utility 62 bus system
Line From To Line impedance (p.u.) Half line charging MVA Annual cost
number bus bus Resistance Reactance susceptance (p.u.) rating (×105 |/yr)
1 1 2 0.00305 0.01565 0.01445 150 541
2 1 4 0.00716 0.03678 0.03397 100 522
3 1 6 0.00411 0.02113 0.01951 150 321
4 1 9 0.00229 0.01174 0.01084 150 812
5 1 10 0.01569 0.08061 0.07443 180 489
6 1 14 0.00548 0.02813 0.10392 300 256
7 2 3 0.00289 0.01487 0.01373 180 375
8 2 6 0.00168 0.00861 0.00795 150 584
9 3 4 0.00381 0.01957 0.01807 150 489
10 4 5 0.00716 0.03678 0.03397 180 494
11 4 14 0.00411 0.02113 0.01951 180 201
12 4 15 0.00411 0.02113 0.01951 180 628
13 5 6 0.00575 0.01478 0.00309 180 478
Appendix C. Indian utility 62 bus system
26 1 0 116 52 0 0 0 0 0
27 1 0 85 35 0 0 0 0 0
28 1 0 63 8 0 0 0 0 0
29 1 0 0 0 0 0 0 0 0
30 1 0 77 41 0 0 0 0 0
31 1 0 51 25 0 0 0 0 0
32 1.05 0 0 0 106.624 0 -100 400 0
33 1.05 0 46 25 62.380 0 0 30 0
Continued on next page
141
Table C.2 – continued from previous page
Bus voltage Generation Load Reactive Shunt
Phase Real Reactive Real Reactive power capacitor
Bus Magnitude angle power power power power limits (MVAR) data (MVAR)
number (p.u.) (degree) (MW ) (MVAR) (MW ) (MVAR) Qmin Qmax Susceptance
34 1 0 100 70 134.508 41 0 41 0
35 1 0 107 33 0 0 0 0 0
36 1 0 20 5 0 0 0 0 0
37 1.05 0 0 0 78.533 0 0 87 0
38 1 0 166 22 0 0 0 0 0
39 1 0 30 5 0 0 0 0 0
40 1 0 25 5 0 0 0 0 0
41 1 0 92 91 0 0 0 0 0
42 1 0 35 25 0 0 0 0 0
43 1 0 20 5 0 0 0 0 0
44 1 0 109 17 0 0 0 0 0
45 1 0 20 4 0 0 0 0 0
Appendix C. Indian utility 62 bus system
46 1 0 0 0 0 0 0 0 0
47 1 0 0 0 0 0 0 0 0
48 1 0 0 0 0 0 0 0 0
49 1.05 0 0 0 213.957 0 0 80 0
50 1.05 0 0 0 92.784 0 0 200 0
51 1.05 0 0 0 82.957 41.542 0 245 0
52 1.05 0 0 0 24.608 35 0 35 0
53 1 0 248 78 0 0 0.0 0 0
Continued on next page
142
Table C.2 – continued from previous page
Bus voltage Generation Load Reactive Shunt
Phase Real Reactive Real Reactive power capacitor
Bus Magnitude angle power power power power limits (MVAR) data (MVAR)
number (p.u.) (degree) (MW ) (MVAR) (MW ) (MVAR) Qmin Qmax Susceptance
54 1.05 0 0 0 72.633 0 0 100 0
55 1 0 94 29 0 0 0 0 0
56 1.05 0 0 0 0 0 0 0 0
57 1.05 0 0 0 219.441 0 0 20 0
58 1.05 0 0 0 339.708 100 100 420 0
59 1 0 0 0 0 0 0 0 0
60 1 0 0 0 0 0 0 0 0
61 1 0 0 0 0 0 0 0 0
62 1 0 93 23 0 0 0 0 0
Appendix C. Indian utility 62 bus system
143
Appendix C. Indian utility 62 bus system 144
Table C.3: Capacity and cost coefficients – Indian utility 62 bus system
Table C.4: Transformer tap setting data – Indian utility 62 bus system