Design Calculation of Blast Wall

Project: Design, Supply, Installation, Testing and Commissioning of 230 KV Indoor GIS Substation with 132 kV AIS at Faridpur and
GIS Bay Ex-tension of existing 230/132 kV Barisal (North) AIS Substation on turnkey basis

Blast wall Data


Hight of wall above pile cap = H 10.65 m
length of wall = L 8.70 m
Wind pressure at top 2.25 kn/m2
Wall Thickness bottom = b 0.55 m
Wall Thickness top = a 0.20 m
Footing width = p 1.05 m
Footing Depth = d 0.50 m
f'c 20.40 Mpa
fy 500.00 Mpa

Pull out on pile


Over turning moment for wind pressure 792.20 kn.m
Resisting moment for self weight at A point 505.67 kn.m
Remaining over turning moment 286.54 kn.m
Total pull out on pile 545.78 Kn

Total weight of wall 963.17 Kn

Deflection check
E 21538.11 N/mm2
I 4394531250.00 mm4
H 10650.00 mm
w 2.25 N/mm
Deflection (11wL^4)/120 28.03 mm
Allowable (L/360) 29.44 mm
OK

Wall reinforcement at bottom


Moment for wind pressure = M 740.08 kn.m
6549.72 kip.in
Shear 104.24 kn
depth = 22.00 in
Effective depth = 20.00 in
width = 348.00 in
f'c = 2.96 ksi
fy = 72.50 ksi
Mu = 6549.72 kip-in
Let, a= 0.4
use 12.00 mm
As = 5.07 in2
Minimum As 12.53 in2
new a = 0.42 in
Total reabar 69.27 nos
Spacing 125.60 mm

Rainforcement of pile cap


Distributed load w 132.85125 Kn/m
Cantilever portion of the footing 1.088 m
Moment = M (wl^2/2) 78.63 kn.m
695.88 kip.in
depth = 20.00 in
effective = 18.00 in
width = 42.00 in
f'c = 2.96 ksi
fy = 72.50 ksi
Mu = 695.88 kip-in
Let, a= 0.4
use 16.00 mm
As = 0.60 in2
Minimun As 1.36 in2
new a = 0.41 in
Total reabar 5.00 nos