Product Specification

36111

EGS 01
Control
• Fuel metering and
speed/load control
for stationary gas
engines
• Lean burn control
without the use of
a lean oxygen
sensor
EGS 01 CONTROL EGS System Types
• Adaptive
Efficiency, performance, and emissions The EGS control is available in different stoichiometric
system types, with or without speed/load
are factors that play a key role in gas control
engine development. As engine control:
performance improves, the need for a • Open loop system in mono or stereo • Integrated Pastor
more accurate and flexible metering control*. An open loop system has a misfire detection
system such as an electronic control pre-programmed fuel quantity which system
system is a logical step. depends on the load and speed of the
The EGS 01 is a state-of-the-art control engine. In this system, there is no • Optional FireFly™
module for stationary gas engines. It can feedback on the actual gas flow. detonation
be used to control the gas flow in relation • Lean burn closed loop system in detection system
to the air flow of an engine, at any load mono or stereo control. For this
and speed condition. • RS-232 plant
system type, an oxygen sensor is
installed in the exhaust, which takes communication
The EGS 01 control is capable of keeping
care of feedback on the actual gas
gas engine emissions constant over a • PC programmable
longer period of time. flow. All inaccurate influences of

And the EGS control is not sensitive to the


sensors, engine parameters, and • Temperature
TecJet™ control (see product spec protection
quality of the gas or the gas pressure and 36116) are eliminated by this system.
temperature. This is accomplished by the
patented gas quality closed loop (lean • Lambda=1 closed loop system in • Overspeed
burn) algorithm and lambda sensor after- mono or stereo control. This system protection
catalyst (lambda=1). can be used for stoichiometric gas
• Overload
engines with three way catalyst to
The EGS 01 control can be applied on keep the A/F (air/fuel) ratio within a protection
in-line and V-type engines of any power narrow band. In this band, the three-
output, naturally aspirated or way catalyst reaches its optimum in
turbocharged. oxidizing and reducing the CO, HC,
The control can be easily programmed and Nox emissions. A sensor after-
with the EGS monitoring program, and it catalyst will optimize the long term
covers the wide range of gas qualities, performance significantly.
from landfill gas to propane. *—Mono control means one gas flow
Even a significant change in gas quality calculation per engine. Stereo control
during normal operation of the engine will means two gas flow calculations, one for
be compensated for by the control. each separate bank of a V-engine.
• Gas quality closed loop system only in mono
• Control range unlimited because the TecJet unit
control. This system has mainly been designed to
controls the total gas flow. Naturally there is a limit
be applied on generator sets where a kW-signal
to the maximum possible gas flow.
normally is available. However, a torque-signal
also can be applied. Without a torque sensor, a
gas-engine-driven compressor cannot be APPLICATION
controlled by the system in the Gas Quality Closed
Loop mode. The EGS 01 control is applicable for stationary gas
engines which operate in island mode or in parallel
• Dual fuel system only in mono control. The dual with the utility. The EGS control always works in
fuel system is meant for applications where an combination with one or more TecJet controls. In
engine has to run on a variable mix of two gasses. general, the EGS calculates the desired gas flow from
(This function is not available in version 3.00.) the different engine and gas parameters. This gas flow
• Woodward will configure the EGS control to one of is transmitted through a CAN link to the TecJet
these system types which is suitable for your control(s). The TecJet control ensures that proper gas
application. flow is maintained, regardless of gas pressure and
temperature.
For EGS systems produced with speed control, an
extra hardware print has to be implemented in the EGS The EGS 01 control can be used for:
control. • Single speed and variable speed engines
• Mono fuel, dual fuel, and variable fuel
• Mono control or stereo control on V-engines
BENEFITS OF THE EGS
• Engine protection, emissions control, and
speed/load control
• Improves engine stability, performance, and
efficiency. • ‘V’ and/or inline, 4-cylinder engine types

• Gas quality closed loop system with EGS/TecJet™ ADJUSTMENTS


applicable on every generator set, resulting in low
emissions without the use of oxygen sensors. All monitoring and adjustments can be made quickly
• Reduction of costs due to user friendly system for and easily via a laptop or PC connected to the EGS
commissioning, diagnostics, and monitoring. control. With EGS monitoring software installed, seven
menus are available. Through these menus the user
• Reduced number of parts. One venturi fits all can perform all settings, authorization, commissioning,
applications and gas compositions. logging, overview of malfunctions, and so on.
• Control software, sensors, and the control module
will always be the same. Only the size of the
actuator is related to the engine output.

EGS Monitoring Program


SPECIFICATIONS
Analog Inputs
Lambda_1 thru Lambda_3 0–25 V / 0–5 V
Map_1 thru Map_2 0–5 V / 0–10 V / 0–20 mA
TPS 0–5 V / 0–10 V / 0–20 mA
Detonation_1/Detonation _2 0–5 V / 0–10 V / 0–20 mA
Power 0–5 V / 0–10 V / 0–20 mA
CH4 0–5 V / 0–10 V / 0–20 mA
Analog_1 thru Analog_2 0–5 V / 0–10 V / 0–20 mA
For all analog inputs: Accuracy 1% of full scale / Linearity 0.1% / Resolution 12 bit / Stability 1%
per year / Common mode voltage. Every input has an input range of –7 V
up to +14 V for the high and the low input.
PT-100 Inputs
Resolution 11 bit over 120 °C / Accuracy 0.5% of 100°
Thermocouple Inputs
Range –40 to +40 mV / Resolution 12 bit / Accuracy
Phase Inputs
Maximum Frequency 100 Hz
Block Signal Turn-over 0 V / Hysteresis 0.2 V / Min. amplitude 6 V / Max. amplitude 32
V. Common mode 10 V on the I/O input
AC Signal Turnover 0 V / Min. amplitude 6 V / Max. amplitude 60 V. Common mode
10 V on the I/O input
Ignition Coil Signal Turnover 100–150 V / Max. voltage 400 V
Speed Input
Accuracy 0.01% / Maximum frequency 9 kHz
Block signal Turnover 2.5 V / Hysteresis 0.2 V / Min. amplitude 5 V / Max. amplitude 32
V. Common mode 10 V on the I/O input
AC signal Turnover 0 V / Min. amplitude 6 V / Max. amplitude 60 V. Common mode
10 V on the I/O input
Digital Inputs
Logic 0 -> 0 – 6 V /Logic 1 -> 4 – 32 V
Relays
Current 1A
TecJet™ Power Supply
Maximum current peak 10 A during 1 second continuous 6 A
TecJet On/Off Maximum current 10 mA
Heater Outputs
Duty Cycle 0–100% / frequency f = 25 Hz / Accuracy 1% / Resolution 8 bit
Peak Current 20 A during 1 second (one single peak) / Nominal current 5 A
PWM Output
Current 1.5 A / Frequency 1000 Hz / Resolution 12 bit / Accuracy 0.1% Push-pull
5 V Reference Output
Accuracy 0.5% / Current 70 mA
RS-232
Plant Communication Port Maximum 9600 baud / Monitoring connection
Certification
Incorporation (DOI) for CE approval
Weight 2.9 kg (6.33 lb)
Power Supply 10–32 Vdc nominal (10 V minimum)
Woodward
Industrial Controls Climatics
PO Box 1519 Temperature, Ambient 0 to 70 °C
Fort Collins CO, USA
80522-1519 Humidity 85%
1000 East Drake Road Enclosure Protection, Water IEC 529 Class IP56
Fort Collins CO 80525
Ph: +1 (970) 482-5811 Dynamics
Fax: +1 (970) 498-3058 Vibration, Swept Sine 4 G, 5 mm, 5–2000 Hz, 3 h min./axis, 90 min
dwells
Distributors & Service Vibration, Random 0.04 G²/Hz, 10–2000 Hz, 90 min/axis, 8.2
Woodward has an Grms
international network of Shock 40 G, 11 ms Sawtooth Pulse
distributors and service
facilities. For your nearest
representative, call the
EMC
Fort Collins plant or see EMC Immunity EC Generic Immunity, EN50082-2
the Worldwide Directory EMC Emissions EC Generic Emissions, EN50081-2
on our website.

Corporate Headquarters
Rockford IL, USA
Ph: +1 (815) 877-7441

www.woodward.com

EGS 01 Control Outline Drawing

This document is distributed


for informational purposes
only. It is not to be construed
as creating or becoming part
of any Woodward Governor For more information contact:
Company contractual or
warranty obligation unless
expressly stated in a written
sales contract.

© Woodward Governor
Company, 1999
All Rights Reserved