CUADRO DE CARGAS - DIMENSIONAMIENTO DE CONDUCTORES

POT. INST. DEM. MAX. DEM. MAX. TENSION I = MD / (K * I DISEÑO SECCION ∆V = K" * I * ϕ * L / S < LLAVE
UBICACIÓN TABLERO CTO. DESCRIPCION CANT. C/U kW. F.D. kW. kW. * (V) V * COS φ) K (Amp) K" LONG ELEGIDA 1.5% TERMOM. CONDUCTOR ALIMENTADOR - TUBERIA
FS=0.50
CN-1 ALUMBRADO FLUORESCENTE LED 18W 14.00 18.00 0.25 80% 0.20 0.10
CN-2 ALUMBRADO FLUORESCENTE LED 36W 18.00 36.00 0.65 80% 0.52 0.26
CN-3 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-4 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
CN-5 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
TABLERO TD-01 380 4.00 1.73 5.00 1.73 265.36 25.00 1.61 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 20 mm ∅ PVC-SAP
CN-6 TOMACORRIENTES 14.00 200.00 2.80 60% 1.68 0.84
CN-7 TOMACORRIENTES 9.00 200.00 1.80 60% 1.08 0.54
CN-8 LUZ DE EMERGENCIA 8.00 36.00 0.29 60% 0.17 0.09
CN-9 LUZ DE EMERGENCIA 9.00 36.00 0.32 60% 0.19 0.10
CN-10 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
CN-1 ALUMBRADO FLUORESCENTE LED 18W 14.00 18.00 0.25 80% 0.20 0.10
CN-2 ALUMBRADO FLUORESCENTE LED 36W 18.00 36.00 0.65 80% 0.52 0.26
CN-3 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-4 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07

SUB TABLERO STD- CN-5 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
MODULO I 01.1 380 4.00 1.73 5.00 1.73 265.36 25.00 1.61 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-6 TOMACORRIENTES 14.00 200.00 2.80 60% 1.68 0.84
CN-7 TOMACORRIENTES 9.00 200.00 1.80 60% 1.08 0.54
CN-8 LUZ DE EMERGENCIA 8.00 36.00 0.29 60% 0.17 0.09
CN-9 LUZ DE EMERGENCIA 9.00 36.00 0.32 60% 0.19 0.10
CN-10 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
CN-1 ALUMBRADO FLUORESCENTE LED 18W 14.00 18.00 0.25 80% 0.20 0.10
CN-2 ALUMBRADO FLUORESCENTE LED 36W 18.00 36.00 0.65 80% 0.52 0.26
CN-3 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-4 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07

SUB TABLERO STD- CN-5 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
01.2 380 4.00 1.73 5.00 1.73 265.36 25.00 1.61 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-6 TOMACORRIENTES 14.00 200.00 2.80 60% 1.68 0.84
CN-7 TOMACORRIENTES 9.00 200.00 1.80 60% 1.08 0.54
CN-8 LUZ DE EMERGENCIA 8.00 36.00 0.29 60% 0.17 0.09
CN-9 LUZ DE EMERGENCIA 9.00 36.00 0.32 60% 0.19 0.10
CN-10 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
CN-1 ALUMBRADO FLUORESCENTE LED 18W 11.00 18.00 0.20 80% 0.16 0.08
CN-2 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-3 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
TABLERO TD-03 CN-4 TOMACORRIENTES 8.00 200.00 1.60 60% 0.96 0.48 380 2.95 1.73 3.69 1.73 150.91 25.00 0.67 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-5 TOMACORRIENTES 10.00 200.00 2.00 60% 1.20 0.60
CN-6 LUZ DE EMERGENCIA 11.00 36.00 0.40 60% 0.24 0.12
CN-7 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
CN-1 ALUMBRADO FLUORESCENTE LED 18W 11.00 18.00 0.20 80% 0.16 0.08
CN-2 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-3 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
SUB TABLERO STD-
03.1 CN-4 TOMACORRIENTES 8.00 200.00 1.60 60% 0.96 0.48 380 2.95 1.73 3.69 1.73 169.38 25.00 0.76 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-5 TOMACORRIENTES 10.00 200.00 2.00 60% 1.20 0.60
CN-6 LUZ DE EMERGENCIA 11.00 36.00 0.40 60% 0.24 0.12
CN-7 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
MODULO II
CN-1 ALUMBRADO FLUORESCENTE LED 18W 11.00 18.00 0.20 80% 0.16 0.08
CN-2 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-3 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
SUB TABLERO STD-
03.2 CN-4 TOMACORRIENTES 8.00 200.00 1.60 60% 0.96 0.48 380 2.95 1.73 3.69 1.73 169.38 25.00 0.76 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-5 TOMACORRIENTES 10.00 200.00 2.00 60% 1.20 0.60
CN-6 LUZ DE EMERGENCIA 11.00 36.00 0.40 60% 0.24 0.12
CN-7 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
CN-1 ALUMBRADO FLUORESCENTE LED 18W 11.00 18.00 0.20 80% 0.16 0.08
CN-2 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-3 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
SUB TABLERO STD- CN-4 TOMACORRIENTES 8.00 200.00 1.60 60% 0.96 0.48 380 2.95 1.73 3.69 1.73 169.38 25.00 0.76 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
03.3
CN-5 TOMACORRIENTES 10.00 200.00 2.00 60% 1.20 0.60
CN-6 LUZ DE EMERGENCIA 11.00 36.00 0.40 60% 0.24 0.12
CN-7 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
CN-1 ALUMBRADO FLUORESCENTE LED 18W 12.00 18.00 0.22 80% 0.17 0.09
CN-2 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-3 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-4 ALUMBRADO FLUORESCENTE LED 18W 5.00 18.00 0.09 80% 0.07 0.04
CN-5 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
TABLERO TD-04 380 3.99 1.73 4.99 1.73 305.68 25.00 1.85 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-6 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
CN-7 TOMACORRIENTES 14.00 200.00 2.80 60% 1.68 0.84
CN-8 TOMACORRIENTES 10.00 200.00 2.00 60% 1.20 0.60
CN-9 LUZ DE EMERGENCIA 14.00 36.00 0.50 60% 0.30 0.15
CN-10 PANEL DE ALARMAS ACI 5.00 100.00 0.50 60% 0.30 0.15
CN-1 ALUMBRADO FLUORESCENTE LED 18W 12.00 18.00 0.22 80% 0.17 0.09
CN-2 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-3 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-4 ALUMBRADO FLUORESCENTE LED 18W 5.00 18.00 0.09 80% 0.07 0.04

MODULO III Y SUB TABLERO STD- CN-5 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
380 3.99 1.73 4.99 1.73 305.68 25.00 1.85 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
IV 04.1 CN-6 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
CN-7 TOMACORRIENTES 14.00 200.00 2.80 60% 1.68 0.84
CN-8 TOMACORRIENTES 10.00 200.00 2.00 60% 1.20 0.60
CN-9 LUZ DE EMERGENCIA 14.00 36.00 0.50 60% 0.30 0.15
CN-10 PANEL DE ALARMAS ACI 5.00 100.00 0.50 60% 0.30 0.15
CN-1 ALUMBRADO FLUORESCENTE LED 18W 12.00 18.00 0.22 80% 0.17 0.09
CN-2 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17

SUB TABLERO STD- 380 3.99 1.73 4.99 1.73 305.68 25.00 1.85 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
04.2
MODULO III Y
IV

CN-3 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
CN-4 ALUMBRADO FLUORESCENTE LED 18W 5.00 18.00 0.09 80% 0.07 0.04

SUB TABLERO STD- CN-5 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
380 3.99 1.73 4.99 1.73 305.68 25.00 1.85 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
04.2 CN-6 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
CN-7 TOMACORRIENTES 14.00 200.00 2.80 60% 1.68 0.84
CN-8 TOMACORRIENTES 10.00 200.00 2.00 60% 1.20 0.60
CN-9 LUZ DE EMERGENCIA 14.00 36.00 0.50 60% 0.30 0.15
CN-10 PANEL DE ALARMAS ACI 5.00 100.00 0.50 60% 0.30 0.15
CN-1 ALUMBRADO FLUORESCENTE LED 18W 16.00 18.00 0.29 80% 0.23 0.12
CN-2 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
CN-3 ALUMBRADO SPOT LIGTH DE 17W 11.00 17.00 0.19 80% 0.15 0.07
CN-4 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
TABLERO TD-08 380 2.88 1.73 3.60 1.73 211.64 25.00 0.92 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-5 TOMACORRIENTES 9.00 200.00 1.80 60% 1.08 0.54
CN-6 TOMACORRIENTES 9.00 200.00 1.80 60% 1.08 0.54
CN-7 LUZ DE EMERGENCIA 9.00 36.00 0.32 60% 0.19 0.10
CN-8 PANEL DE ALARMAS ACI 3.00 100.00 0.30 60% 0.18 0.09
CN-1 ALUMBRADO FLUORESCENTE LED 18W 16.00 18.00 0.29 80% 0.23 0.12
CN-2 ALUMBRADO FLUORESCENTE LED 36W 15.00 36.00 0.54 80% 0.43 0.22
CN-3 ALUMBRADO FLUORESCENTE LED 36W 8.00 36.00 0.29 80% 0.23 0.12

SUB TABLERO STD- CN-4 ALUMBRADO FLUORESCENTE LED 36W 8.00 36.00 0.29 80% 0.23 0.12
MODULO V 08.1
380 3.09 1.73 3.86 1.73 196.15 25.00 0.92 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-5 TOMACORRIENTES 9.00 200.00 1.80 60% 1.08 0.54
CN-6 TOMACORRIENTES 9.00 200.00 1.80 60% 1.08 0.54
CN-7 LUZ DE EMERGENCIA 9.00 36.00 0.32 60% 0.19 0.10
CN-8 PANEL DE ALARMAS ACI 3.00 100.00 0.30 60% 0.18 0.09
CN-1 ALUMBRADO FLUORESCENTE LED 18W 16.00 18.00 0.29 80% 0.23 0.12
CN-2 ALUMBRADO FLUORESCENTE LED 36W 15.00 17.00 0.26 80% 0.20 0.10
CN-3 ALUMBRADO FLUORESCENTE LED 36W 8.00 17.00 0.14 80% 0.11 0.05

SUB TABLERO STD- CN-4 ALUMBRADO FLUORESCENTE LED 36W 8.00 36.00 0.29 80% 0.23 0.12
380 2.80 1.73 3.50 1.73 196.15 25.00 0.83 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
08.2 CN-5 TOMACORRIENTES 9.00 200.00 1.80 60% 1.08 0.54
CN-6 TOMACORRIENTES 9.00 200.00 1.80 60% 1.08 0.54
CN-7 LUZ DE EMERGENCIA 9.00 36.00 0.32 60% 0.19 0.10
CN-8 PANEL DE ALARMAS ACI 3.00 100.00 0.30 60% 0.18 0.09
CN-1 ALUMBRADO SPOT LIGTH DE 17W 5.00 17.00 0.09 80% 0.07 0.03
ALUMBRADO FLUORESCENTE LED 36W 6.00 36.00 0.22 80% 0.17 0.09
CN-2
ALUMBRADO FLUORESCENTE LED 18W 4.00 18.00 0.07 80% 0.06 0.03
TABLERO TD-09 380 1.51 1.73 1.89 1.73 63.95 25.00 0.15 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-3 TOMACORRIENTES 10.00 200.00 2.00 60% 1.20 0.60
CN-5 LUZ DE EMERGENCIA 8.00 36.00 0.29 60% 0.17 0.09
CN-6 PANEL DE ALARMAS ACI 2.00 100.00 0.20 60% 0.12 0.06
CN-1 ALUMBRADO SPOT LIGTH DE 17W 6.00 17.00 0.10 80% 0.08 0.04
ALUMBRADO FLUORESCENTE LED 36W 6.00 36.00 0.22 80% 0.17 0.09
CN-2
MODULO VI ALUMBRADO FLUORESCENTE LED 18W 5.00 18.00 0.09 80% 0.07 0.04
SUB TABLERO STD- CN-3 ALUMBRADO FLUORESCENTE LED 36W 16.00 36.00 0.58 80% 0.46 0.23 380 1.57 1.73 1.96 1.73 123.22 25.00 0.29 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
09.1
CN-4 TOMACORRIENTES 7.00 200.00 1.40 60% 0.84 0.42
CN-5 LUZ DE EMERGENCIA 5.00 36.00 0.18 60% 0.11 0.05
CN-6 PANEL DE ALARMAS ACI 2.00 100.00 0.20 60% 0.12 0.06
CN-1 ALUMBRADO SPOT LIGTH DE 17W 7.00 17.00 0.12 80% 0.10 0.05

SUB TABLERO STD- CN-2 TOMACORRIENTES 1.00 200.00 0.20 60% 0.12 0.06
09.2 380 0.27 1.73 0.34 1.73 63.95 25.00 0.03 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-3 LUZ DE EMERGENCIA 2.00 36.00 0.07 60% 0.04 0.02
CN-4 PANEL DE ALARMAS ACI 1.00 100.00 0.10 60% 0.06 0.03
CN-1 ALUMBRADO FLUORESCENTE LED 36W 16.00 36.00 0.58 80% 0.46 0.23
CN-2 ALUMBRADO FLUORESCENTE LED 18W 14.00 18.00 0.25 80% 0.20 0.10
CN-3 ALUMBRADO FLUORESCENTE LED 36W 16.00 36.00 0.58 80% 0.46 0.23
CN-4 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17
TABLERO TD-07 380 4.12 1.73 5.15 1.73 267.03 25.00 1.67 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-5 TOMACORRIENTES 11.00 200.00 2.20 60% 1.32 0.66
CN-6 TOMACORRIENTES 13.00 200.00 2.60 60% 1.56 0.78
CN-7 LUZ DE EMERGENCIA 13.00 36.00 0.47 60% 0.28 0.14
CN-8 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
MODULO VII CN-1 ALUMBRADO FLUORESCENTE LED 36W 16.00 36.00 0.58 80% 0.46 0.23
CN-2 ALUMBRADO FLUORESCENTE LED 18W 14.00 18.00 0.25 80% 0.20 0.10
CN-3 ALUMBRADO FLUORESCENTE LED 36W 15.00 36.00 0.54 80% 0.43 0.22
CN-4 ALUMBRADO FLUORESCENTE LED 36W 3.00 36.00 0.11 80% 0.09 0.04
SUB TABLERO STD- CN-5 ALUMBRADO FLUORESCENTE LED 36W 15.00 36.00 0.54 80% 0.43 0.22 380 4.34 1.73 5.43 1.73 290.99 25.00 1.91 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
07.1
CN-6 TOMACORRIENTES 14.00 200.00 2.80 60% 1.68 0.84
CN-7 TOMACORRIENTES 11.00 200.00 2.20 60% 1.32 0.66
CN-8 LUZ DE EMERGENCIA 13.00 36.00 0.47 60% 0.28 0.14
CN-9 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
CN-1 ALUMBRADO FLUORESCENTE LED 36W 11.00 36.00 0.40 80% 0.32 0.16
CN-2 ALUMBRADO FLUORESCENTE LED 36W 7.00 36.00 0.25 80% 0.20 0.10
SUB TABLERO STD-
MODULO VIII 01.3
CN-3 TOMACORRIENTES 18.00 200.00 3.60 60% 2.16 1.08 380 2.65 1.73 3.31 1.73 99.48 25.00 0.40 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-4 LUZ DE EMERGENCIA 10.00 36.00 0.36 60% 0.22 0.11
CN-5 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
CN-1 ALUMBRADO TIPO HIGH BAY DE 36W 15.00 36.00 0.54 80% 0.43 0.22
CN-2 ALUMBRADO TIPO HIGH BAY DE 36W 15.00 36.00 0.54 80% 0.43 0.22
CN-3 TOMACORRIENTES 12.00 200.00 2.40 60% 1.44 0.72
TABLERO TD-05 380 3.64 1.73 4.55 1.73 79.44 25.00 0.44 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-4 TOMACORRIENTES 14.00 200.00 2.80 60% 1.68 0.84
CN-5 LUZ DE EMERGENCIA 4.00 36.00 0.14 60% 0.09 0.04
CN-6 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
CN-1 ALUMBRADO TIPO HIGH BAY DE 36W 9.00 36.00 0.32 80% 0.26 0.13
CN-2 ALUMBRADO TIPO HIGH BAY DE 36W 9.00 36.00 0.32 80% 0.26 0.13
CN-3 ALUMBRADO TIPO HIGH BAY DE 36W 9.00 36.00 0.32 80% 0.26 0.13
CN-4 ALUMBRADO TIPO HIGH BAY DE 36W 9.00 36.00 0.32 80% 0.26 0.13
SUB TABLERO STD- CN-5 ALUMBRADO TIPO HIGH BAY DE 36W 9.00 36.00 0.32 80% 0.26 0.13 380 3.94 1.73 4.93 1.73 170.08 25.00 1.01 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
05.1
MODULO IX CN-6 TOMACORRIENTES 13.00 200.00 2.60 60% 1.56 0.78
CN-7 TOMACORRIENTES 12.00 200.00 2.40 60% 1.44 0.72
SUB TABLERO STD-
05.1 380 3.94 1.73 4.93 1.73 170.08 25.00 1.01 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
MODULO IX

CN-8 LUZ DE EMERGENCIA 6.00 36.00 0.22 60% 0.13 0.06


CN-9 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
CN-1 ALUMBRADO SPOT LIGTH DE 17W 12.00 17.00 0.20 80% 0.16 0.08
CN-2 ALUMBRADO SPOT LIGTH DE 17W 15.00 17.00 0.26 80% 0.20 0.10
CN-3 ALUMBRADO SPOT LIGTH DE 17W 8.00 17.00 0.14 80% 0.11 0.05
CN-4 ALUMBRADO SPOT LIGTH DE 17W 15.00 17.00 0.26 80% 0.20 0.10
TABLERO TD-06 380 3.11 1.73 3.89 1.73 141.49 25.00 0.67 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-5 ALUMBRADO SPOT LIGTH DE 17W 8.00 17.00 0.14 80% 0.11 0.05
CN-6 TOMACORRIENTES 10.00 200.00 2.00 60% 1.20 0.60
CN-7 TOMACORRIENTES 13.00 200.00 2.60 60% 1.56 0.78
CN-8 LUZ DE EMERGENCIA 6.00 36.00 0.22 60% 0.13 0.06
CN-1 ALUMBRADO FLUORESCENTE LED 18W 10.00 18.00 0.18 80% 0.14 0.07
CN-2 ALUMBRADO SPOT LIGTH DE 17W 6.00 17.00 0.10 80% 0.08 0.04
CN-3 ALUMBRADO FLUORESCENTE LED 36W 9.00 36.00 0.32 80% 0.26 0.13
SUB TABLERO STD-
MODULO X 01.4
CN-4 ALUMBRADO FLUORESCENTE LED 36W 12.00 36.00 0.43 80% 0.35 0.17 380 2.41 1.73 3.01 1.73 184.67 25.00 0.67 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-5 TOMACORRIENTES 13.00 200.00 2.60 60% 1.56 0.78
CN-6 LUZ DE EMERGENCIA 10.00 36.00 0.36 60% 0.22 0.11
CN-7 PANEL DE ALARMAS ACI 4.00 100.00 0.40 60% 0.24 0.12
CN-1 ALUMBRADO FLUORESCENTE LED 18W 5.00 18.00 0.09 80% 0.07 0.04
CN-2 TOMACORRIENTES 4.00 200.00 0.80 60% 0.48 0.24
TABLERO TD-02 380 0.54 1.73 0.68 1.73 12.93 25.00 0.01 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-3 LUZ DE EMERGENCIA 1.00 36.00 0.04 60% 0.02 0.01
CN-4 PANEL DE ALARMAS ACI 1.00 100.00 0.10 60% 0.06 0.03
MODULO XI
CN-1 ALUMBRADO FLUORESCENTE LED 18W 2.00 18.00 0.04 80% 0.03 0.01

SUB TABLERO STD- CN-2 TOMACORRIENTES 4.00 200.00 0.80 60% 0.48 0.24
02.1 380 0.50 1.73 0.63 1.73 7.62 25.00 0.01 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
CN-3 LUZ DE EMERGENCIA 1.00 36.00 0.04 60% 0.02 0.01
CN-4 PANEL DE ALARMAS ACI 1.00 100.00 0.10 60% 0.06 0.03
CN-1 ALUMBRADO FLUORESCENTE LED 18W 10.00 18.00 0.18 80% 0.14 0.07

COMPLEMEN TABLERO TD-10


CN-2 TOMACORRIENTES 9.00 200.00 1.80 60% 1.08 0.54
380 1.24 1.73 1.55 1.73 29.45 25.00 0.06 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 50 mm ∅ PVC-SAP
TARIO CN-3 LUZ DE EMERGENCIA 3.00 36.00 0.11 60% 0.06 0.03
CN-4 PANEL DE ALARMAS ACI 3.00 100.00 0.30 60% 0.18 0.09
CN-1 ALUMBRADO FLUORESCENTE LED 18W 4.00 18.00 0.07 80% 0.06 0.03
CN-2 TOMACORRIENTES 3.00 200.00 0.60 60% 0.36 0.18
TABLERO BOMBA CN-3 LUZ DE EMERGENCIA 1.00 36.00 0.04 60% 0.02 0.01
380 2.44 1.73 3.05 1.73 9.40 25.00 0.03 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 35 mm ∅ PVC-SAP
TDB-01 CN-4 PANEL DE ALARMAS ACI 1.00 100.00 0.10 60% 0.06 0.03
CN-5 ALIMENTADOR AGUA 1.00 746.00 0.75 80% 0.60 0.30
CN-6 AGUA POTABLE 1HP 2.00 1,492.00 2.98 60% 1.79 0.90
CN-1 ALUMBRADO FLUORESCENTE LED 18W 4.00 18.00 0.07 80% 0.06 0.03
CN-2 TOMACORRIENTES 3.00 200.00 0.60 60% 0.36 0.18
TABLERO BOMBA CN-3 LUZ DE EMERGENCIA 1.00 36.00 0.04 60% 0.02 0.01
380 8.49 1.73 10.61 1.73 9.40 25.00 0.12 < 2.5% -.- OK 3x70 AMP. (3-1x25 RST + 1x25 N + 1x25-T)mm2 N2XOH - 35 mm ∅ PVC-SAP
TDB-02 CN-4 PANEL DE ALARMAS ACI 1.00 100.00 0.10 60% 0.06 0.03
CN-5 ALIMENTADOR AGUA 1.00 746.00 0.75 80% 0.60 0.30
CN-6 AGUA CONTRA INCENDIO 15HP 1.00 11,190.00 11.19 80% 8.95 4.48
V 220 V
K 1 Ø
K" 2
CosØ 0.9
Id 1.25
ϕ 0.0175
Seccion (mm) 2.5
%ΔV 1.5

P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 P13 P14 P15 P16 P17 P18 P19 P20 P21 P22 P23 P24 P25 P26 P27 P28 P29 P30
Potencia (W) 72 72 72 72 72 72 72 72 72 72 72 72 72 72 72 - - - - - - - - - - - - - - -
I=P/(K*V*CosØ) 0.36 0.36 0.36 0.36 0.36 0.36 0.36 0.36 0.36 0.36 0.36 0.36 0.36 0.36 0.36
Id (A) 0.45 0.45 0.45 0.45 0.45 0.45 0.45 0.45 0.45 0.45 0.45 0.45 0.45 0.45 0.45
∑ Id
L (m) 1 1.23 0.8 0.6 1.3 0.6 0.7 1.3 2.3 2.13 2.5 3.65 2.2 1 0.9
∆V = K"*Id*ϕ*L / S*% 0.42 0.52 0.34 0.25 0.55 0.25 0.30 0.55 0.98 0.90 1.06 1.55 0.93 0.42 0.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
∆V 0.001928
CUADRO DE
UBICACIÓN TABLERO CTO. DESCRIPCION CANT.

CE-1 ALUMBRADO TIPO FAROLA DE 120W 12.00


MODULO III TABLERO TE-01
CE-2 ALUMBRADO TIPO FAROLA DE 120W 7.00
TABLERO TE-02 CE-1 ALUMBRADO EXTERIORES DE 200W 12.00
CE-1 ALUMBRADO TIPO FAROLA DE 120W 8.00
MODULO IX TABLERO TE-03
CE-2 ALUMBRA DOLVD DOWNLIGHT L840 L60 20.00
WT DE 70W
MODULO X TABLERO TE-04 CE-1 ALUMBRADO EXTERIORES DE 200W 4.00
TABLERO TE-05 CE-1 ALUMBRADO TIPO FAROLA DE 120W 12.00
MODULO XI TABLERO TE-06 CE-1 ALUMBRADO TIPO FAROLA DE 120W 12.00
ADRO DE CARGAS - DIMENSIONAMIENTO DE C
POT. INST. DEM. MAX. DEM. MAX. TENSION I = MD / (K * I DISEÑO
C/U kW. F.D. kW. kW. * (V) V * COS φ) K (Amp)
FS=0.50
120.00 1.44 80% 1.15 0.58
380 1.54 1.73 1.93
120.00 0.84 80% 0.67 0.34
200.00 2.40 80% 1.92 0.96 380 1.62 1.73 2.03
200.00 1.60 80% 1.28 0.64
380 2.03 1.73 2.54
70.00 1.40 80% 1.12 0.56

200.00 0.80 80% 0.64 0.32 380 0.54 1.73 0.68


120.00 1.44 80% 1.15 0.58 380 0.97 1.73 1.21
120.00 1.44 80% 1.15 0.58 380 0.97 1.73 1.21
NAMIENTO DE CONDUCTORES
SECCION ∆V = K" * I * ϕ * L / S < LLAVE
K" LONG ELEGIDA 1.5% TERMOM.

1.73 174.41 10.00 1.02 < 2.5% -.- OK 3x40 AMP.

1.73 96.61 10.00 0.59 < 2.5% -.- OK 3x40 AMP.

1.73 114.13 10.00 0.88 < 2.5% -.- OK 3x40 AMP.

1.73 59.57 10.00 0.12 < 2.5% -.- OK 3x40 AMP.


1.73 79.69 10.00 0.29 < 2.5% -.- OK 3x40 AMP.
1.73 92.01 10.00 0.34 < 2.5% -.- OK 3x40 AMP.
ORES
CONDUCTOR ALIMENTADOR - TUBERIA

(3-1x10 RST + 1x10 N + 1x10-T)mm2 N2XOH - 35 mm ∅ PVC-SAP

(3-1x10 RST + 1x10 N + 1x10-T)mm2 N2XOH - 35 mm ∅ PVC-SAP

(3-1x10 RST + 1x10 N + 1x10-T)mm2 N2XOH - 35 mm ∅ PVC-SAP

(3-1x10 RST + 1x10 N + 1x10-T)mm2 N2XOH - 35 mm ∅ PVC-SAP


(3-1x10 RST + 1x10 N + 1x10-T)mm2 N2XOH - 35 mm ∅ PVC-SAP
(3-1x10 RST + 1x10 N + 1x10-T)mm2 N2XOH - 35 mm ∅ PVC-SAP
CUADRO DE CARGAS ELECTRICAS - SUB TABLEROS DE DISTRIBUCION ESTABILIZADOS
DEM. MAX.
UBICACIÓN TABLERO CTO. DESCRIPCION CANT. C/U POT. INST. F.D. DEM. MAX. kW. * I = MD / (K * K I diseño K" LONG SECCION ∆V = K" * I * ϕ * L / S < LLAVE CONDUCTOR ALIMENTADOR - CABLE
kW. kW. FS=0.50 V * COS φ) (Amp) ELEGIDA 1.5% TERMOM.

CE-1 TOMACORRIENTES ESTABILIZADOS 11.00 200.00 2.20 80% 1.76 0.88


CE-2 TOMACORRIENTES ESTABILIZADOS 10.00 200.00 2.00 80% 1.60 0.80
TABLERO STDE-11.1 17.37 1.00 21.71 2.00 3.23 6.00 0.41 < 1.5% -.- OK 2x30 AMP. 1_1x6.0mm2 NH-80(F) + 1x6.0mm2 NH-80(N) + 1x6.0mm2 NH-80(T)
CE-3 TOMACORRIENTES ESTABILIZADOS 10.00 200.00 2.00 80% 1.60 0.80
PRIMER CE-4 TOMACORRIENTES ESTABILIZADOS 12.00 200.00 2.40 80% 1.92 0.96
PISO CE-1 TOMACORRIENTES ESTABILIZADOS 5.00 200.00 1.00 80% 0.80 0.40
CE-2 TOMACORRIENTES ESTABILIZADOS 10.00 200.00 2.00 80% 1.60 0.80
TABLERO STDE-11.2 11.72 1.00 14.65 2.00 29.23 10.00 1.50 < 1.5% -.- OK 2x40 AMP. 1_1x10mm2 NH-80(F) + 1x10mm2 NH-80(N) + 1x10mm2 NH-80(T)
CE-3 TOMACORRIENTES ESTABILIZADOS 10.00 200.00 2.00 80% 1.60 0.80
CE-4 TOMACORRIENTES ESTABILIZADOS 4.00 200.00 0.80 80% 0.64 0.32
CE-1 TOMACORRIENTES ESTABILIZADOS 6.00 200.00 1.20 80% 0.96 0.48
CE-2 TOMACORRIENTES ESTABILIZADOS 8.00 200.00 1.60 80% 1.28 0.64
TABLERO STDE-21.1 CE-3 TOMACORRIENTES ESTABILIZADOS 8.00 200.00 1.60 80% 1.28 0.64 14.95 1.00 18.69 2.00 18.23 10.00 1.19 < 1.5% -.- OK 2x40 AMP. 1_1x10mm2 NH-80(F) + 1x10mm2 NH-80(N) + 1x10mm2 NH-80(T)
CE-4 TOMACORRIENTES ESTABILIZADOS 7.00 200.00 1.40 80% 1.12 0.56
CE-5 TOMACORRIENTES ESTABILIZADOS 8.00 200.00 1.60 80% 1.28 0.64
SEGUNDO CE-1 TOMACORRIENTES ESTABILIZADOS 11.00 200.00 2.20 80% 1.76 0.88
PISO CE-2 TOMACORRIENTES ESTABILIZADOS 10.00 200.00 2.00 80% 1.60 0.80
CE-3 TOMACORRIENTES ESTABILIZADOS 10.00 200.00 2.00 80% 1.60 0.80
TABLERO STDE-21.2 23.03 1.00 28.79 2.00 29.12 25.00 1.17 < 1.5% -.- OK 2x70 AMP. 1_1x25mm2 NH-80(F) + 1x25mm2 NH-80(N) + 1x16mm2NH-80(T)
CE-4 TOMACORRIENTES ESTABILIZADOS 9.00 200.00 1.80 80% 1.44 0.72
CE-5 TOMACORRIENTES ESTABILIZADOS 9.00 200.00 1.80 80% 1.44 0.72
CE-6 TOMACORRIENTES ESTABILIZADOS 8.00 200.00 1.60 80% 1.28 0.64

CUADRO DE CARGAS ELECTRICAS - TABLEROS DE DISTRIBUCION ESTABILIZADOS


DEM. MAX.
UBICACIÓN TABLERO CTO. DESCRIPCION CANT. C/U POT. INST. F.D. DEM. MAX. kW. * I = MD / (K * K I diseño K" LONG SECCION ∆V = K" * I * ϕ * L / S < LLAVE CONDUCTOR ALIMENTADOR - CABLE
kW. kW. FS=0.50 V * COS φ) (Amp) ELEGIDA 1.5% TERMOM.

PRIMER CE-1 TABLERO STDE-11.1 1.00 8,600.00 8.60 80% 6.88 3.44
TDE-11 29.09 1.00 36.36 2.00 5.56 16.00 0.44 < 1.5% -.- OK 2x50 AMP. 1_1x16mm2NH-80(F) + 1x16mm2NH-80(N) + 1x16mm2NH-80(T)
PISO CE-2 TABLERO STDE-11.2 1.00 5,800.00 5.80 80% 4.64 2.32
SEGUNDO CE-1 TABLERO STDE-21.1 1.00 7,400.00 7.40 80% 5.92 2.96
TDE-21 37.98 1.00 47.56 2.00 12.65 35.00 0.60 < 1.5% -.- OK 2x90 AMP. 1_1x35mm2NH-80(F) + 1x35mm2NH-80(N) + 1x16mm2NH-80(T)
PISO CE-2 TABLERO STDE-21.2 1.00 11,400.00 11.40 80% 9.12 4.56
CE-1 TOMACORRIENTES ESTABILIZADOS 9.00 200.00 1.80 80% 1.44 0.72
TERCER TDE-31 CE-2 TOMACORRIENTES ESTABILIZADOS 5.00 200.00 1.00 80% 0.80 0.40 8.08 1.00 10.10 2.00 14.23 6.00 0.84 < 1.5% -.- OK 2x30 AMP. 1_1x6.0mm2 NH-80(F) + 1x6.0mm2 NH-80(N) + 1x6.0mm2 NH-80(T)
PISO
CE-3 TOMACORRIENTES ESTABILIZADOS 6.00 200.00 1.20 80% 0.96 0.48
CE-1 RACK DE AMPLIFICADOR 1.00 4,000.00 4.00 80% 3.20 1.60
CE-2 PANEL DE INTRUSIÓN 1.00 2,000.00 2.00 80% 1.60 0.80
CE-3 PANEL DE INCENDIO 1.00 3,000.00 3.00 80% 2.40 1.20
CE-4 VIDEOWAL MONITOREO 1.00 3,000.00 3.00 80% 2.40 1.20
CE-5 VIDEOWAL SCADA 1.00 3,000.00 3.00 80% 2.40 1.20
CUARTO CE-6 COMPUTADORAS 1.00 4,500.00 4.50 80% 3.60 1.80
TDE-31 55.23 1.73 69.04 1.73 3.15 35.00 0.19 < 1.5% -.- OK 3x80 AMP. (3-1x35 RST + 1x35 N + 1x16-T)mm2 N2XOH
PISO CE-7 GDP-01 1.00 13,300.00 13.30 80% 10.64 5.32
CE-8 GDP02 1.00 4,800.00 4.80 80% 3.84 1.92
CE-9 GDP-03 1.00 13,000.00 13.00 80% 10.40 5.20
CE-10 GDP-04 1.00 13,300.00 13.30 80% 10.64 5.32
CE-11 GDP-05 1.00 4,800.00 4.80 80% 3.84 1.92
CE-12 GDP-06 1.00 13,000.00 13.00 80% 10.40 5.20
S - SUB TABLEROS DE DISTRIBUCION ESTABILIZADOS
TG-EST

TDE-11

TDE-21

CAS - TABLEROS DE DISTRIBUCION ESTABILIZADOS


TG

TG-EST
TG-EST
TG-EST

TG-EST
CUADRO DE CARGAS ELECTRICAS - TABLEROS DE DISTRIBUCION
DEM. MAX.
UBICACIÓN TABLERO CTO. DESCRIPCION CANT. C/U POT. INST. F.D. DEM. MAX. kW. * I = MD / (K * K I diseño K" LONG SECCION ∆V = K" * I * ϕ * L / S < LLAVE CONDUCTOR ALIMENTADOR - CABLE
kW. kW. FS=0.50 V * COS φ) (Amp) ELEGIDA 1.5% TERMOM.

C-1 ALUMBRADO FLUORESCENTE CON REJILLADE 2X36W 1.00 36.00 0.04 100% 0.04 0.02
ALUMBRADO LDV DOWNLIGHT DE 18W 1.00 18.00 0.02 100% 0.02 0.01
TABLERO TA-01 C-2 TOMACORRIENTES 2.00 200.00 0.40 80% 0.32 0.16 5.37 1.73 6.71 1.73 65.12 16.00 0.83 < 1.5% -.- OK 3x50 AMP. (3-1x16 RST + 1x16 N + 1x16-T)mm2 N2XOH
C-3 LUZ DE EMERGENCIA 1.00 20.00 0.02 80% 0.02 0.01
CUARTO C-4 MOTOR PARA ASCENSOR DE 10HP 1.00 7,460.00 7.46 80% 5.97 2.98
DE MAQUINA C-1 ALUMBRADO FLUORESCENTE CON REJILLADE 2X36W 1.00 36.00 0.04 100% 0.04 0.02
DE ASCENDOR ALUMBRADO LDV DOWNLIGHT DE 18W 1.00 18.00 0.02 100% 0.02 0.01
TABLERO TA-02 C-2 TOMACORRIENTES 2.00 200.00 0.40 80% 0.32 0.16 5.37 1.73 6.71 1.73 76.45 16.00 0.97 < 1.5% -.- OK 3x50 AMP. (3-1x16 RST + 1x16 N + 1x16-T)mm2 N2XOH
C-3 LUZ DE EMERGENCIA 1.00 20.00 0.02 80% 0.02 0.01
C-4 MOTOR PARA ASCENSOR DE 10HP 1.00 7,460.00 7.46 80% 5.97 2.98
C-1 ALUMBRADO FLUORESCENTE HERMETICO DE 2X36W 2.00 72.00 0.14 100% 0.14 0.07
CUARTO DE TABLERO TD-B C-2 TOMACORRIENTES 3.00 200.00 0.60 80% 0.48 0.24 11.12 1.73 13.90 1.73 19.98 10.00 0.84 < 1.5% -.- OK 3x40 AMP. (3-1x10 RST + 1x10 N + 1x16-T)mm2 N2XOH
BOMBAS C-3 TABLERO TC-B 1.00 15,666.00 15.67 80% 12.53 6.27
C-1 MOTOR ELECTROBOMBA B-1 DE 6HP 1.00 4,476.00 4.48 80% 3.58 1.79
C-2 MOTOR ELECTROBOMBA B-2 DE 6HP 1.00 4,476.00 4.48 80% 3.58 1.79
CUARTO DE TABLERO ST-B C-3 MOTOR ELECTROBOMBA B-3 DE 6HP 1.00 4,476.00 4.48 80% 3.58 1.79 10.59 1.73 13.24 1.73 5.36 6.00 0.36 < 1.5% -.- OK 3x30 AMP. (3-1x6 RST + 1x6 N + 1x10-T)mm2 N2XOH
BOMBAS C-4 MOTOR ELECTROBOMBA B-4 DE 1.5HP 1.00 1,119.00 1.12 80% 0.90 0.45
C-5 MOTOR ELECTROBOMBA B-5 DE 1.5HP 1.00 1,119.00 1.12 80% 0.90 0.45
CUARTO DE TABLERO TD-BACI
C-1 MOTOR ELECTROBOMBA B-6 DE 46HP 1.00 34,316.00 34.32 100% 34.32 17.16
31.52 1.73 39.40 1.73 19.98 16.00 1.49 < 1.5% -.- OK 3x50 AMP. (3-1x16 RST + 1x16 N + 1x16-T)mm2 N2XOH
BOMBAS C-2 MOTOR ELECTROBOMBA B-1 DE 5HP 1.00 3,730.00 3.73 80% 2.98 1.49
ELECTRICAS - TABLEROS DE DISTRIBUCION
TG

TG
CUADRO DE CARGAS - DIMENSIONAMIENTO DE CONDUCTORES
NOMBRE TABLERO POT. INST. kW. F.D. DEM. MAX. DEM. MAX. kW. TENSION I = MD / (K * V * I diseño (Amp) K K" LONG SECCION ∆V = K "* I * ϕ * L / S < 1.5%
∆V = 0.0175*I*L*100/(V*S) < LLAVE TERMOM.
kW. * FS=0.750 (V) COS φ) ELEGIDA 1.5%

TABLERO TD-01 31.09 80% 24.87 12.44 380.00 21.02 27.00 1.73 1.73 27.87 35.00 0.65 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TD-02 2.00 80% 1.60 0.80 380.00 1.35 2.00 1.73 1.73 37.07 35.00 0.06 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TD-03 24.12 80% 19.30 9.65 380.00 16.31 21.00 1.73 1.73 54.47 35.00 0.99 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TD-04 22.05 80% 17.64 8.82 380.00 14.91 19.00 1.73 1.73 54.47 35.00 0.90 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TD-05 14.06 80% 11.25 5.63 380.00 9.51 12.00 1.73 1.73 92.48 35.00 0.96 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TD-06 5.80 80% 4.64 2.32 380.00 3.92 5.00 1.73 1.73 114.05 35.00 0.49 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TD-07 15.38 80% 12.30 6.15 380.00 10.39 13.00 1.73 1.73 65.69 35.00 0.74 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TD-08 16.14 80% 12.91 6.46 380.00 10.91 14.00 1.73 1.73 70.74 35.00 0.86 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TD-09 6.11 80% 4.89 3.67 380.00 6.20 8.00 1.73 1.73 100.55 35.00 0.70 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TD-10 2.39 80% 1.91 0.96 380.00 1.61 3.00 1.73 1.73 29.45 35.00 0.08 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO BOMBA TDB-01 4.54 80% 3.63 1.82 380.00 3.07 4.00 1.73 1.73 9.40 35.00 0.03 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO BOMBA TDB-02 12.74 80% 10.20 5.10 380.00 8.62 11.00 1.73 1.73 9.40 35.00 0.09 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TE-01 2.28 80% 1.82 0.91 380.00 1.54 2.00 1.73 1.73 174.41 35.00 0.30 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TE-02 2.40 80% 1.92 0.96 380.00 1.62 3.00 1.73 1.73 96.61 35.00 0.25 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TE-03 3.00 80% 2.40 1.20 380.00 2.03 3.00 1.73 1.73 114.13 35.00 0.30 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TE-04 0.80 80% 0.64 0.32 380.00 0.54 1.00 1.73 1.73 59.57 35.00 0.05 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TE-05 1.44 80% 1.15 0.58 380.00 0.97 2.00 1.73 1.73 79.69 35.00 0.14 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

TABLERO TE-06 1.44 80% 1.15 0.58 380.00 0.97 2.00 1.73 1.73 92.01 35.00 0.16 < 2.5% …. OK < 2.5% .. OK 3x80 AMP.

DEM. MAX. DEM. MAX. kW. TENSION I = MD / (K * V *


NOMBRE TABLERO POT. INST. kW. F.D. kW. * FS=0.70 (V) COS φ) I diseño (Amp) K LONG SECCION ELEGIDA ∆V = K * I * ϕ * L / S < 2.5% ∆V = 0.0175*I*L*100/(V*S) < 2.5% LLAVE TERMOM.

< 2.50% ….
POTENCIA INSTALADA 156.42 75% 117.32 82.12 380.00 138.80 174.00 1.73 75.85 185.00 2.16 OK < 2.5% .. OK 3x300 AMP.

DEMANDA MAXIMA A CONTRATAR (KVA) 130.35 132.00


GRUPO ELECTROGENO (KVA) 21.30 25.00
SUBESTACION (KVA) 130 132.00
GAS - DIMENSIONAMIENTO DE CONDUCTORES
CONDUCTOR ALIMENTADOR

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

(3-1x35 RST + 1 X35N + 1x35-T) mm2 N2XOH - 50 mm PVC - SAP

CONDUCTOR ALIMENTADOR

(3-1x185 RST + 1 X185N + 1x185-T) mm2 N2XOH - 100 mm PVC -


SAP