PLATE ANALYSIS (PCA) REINFORCEMENT CALCULATIONS

Vs Negative Vs Positive
q 61.0 KN/m2 q 61.0 KN/m2 CALCULATION FOR 'Ru' CALCULATION FOR 'Ru'
q 1281 Psf Mu 18.51 k-ft. Mu 9.51 k-ft.
height/width ratio (a/b) 4.13 b 12.00 in. b 12.00 in.
Support Conditions: h 20.00 in. h 20.00 in.
Top hinged a 2.8 9.1868 d 17.00 in. d 17.00 in.
Bottom fixed m. ft. Ru 0.0640 ksi. Ru 0.0329 ksi.
Left fixed
Right fixed y CALCULATION FOR 'Rho' CALCULATION FOR 'Rho'
design strip widht (b) 12 in. fc' 3.00 ksi. fc' 3.60 ksi.
thickness (h) 20 in. fy 60.00 ksi. fy 72.00 ksi.
Load Factor 2 x Ru 0.0640 ksi. Ru 0.0329 ksi.
clr. Cover 3 in. phi 0.90 phi 0.90
b 11.55 37.89555 beta 0.85 beta 0.85
Working Formulae: m ft. rho 0.001203 rho 0.000511

CALCULATION FOR 'As' CALCULATION FOR 'As'


b 12.00 in. b 12.00 in.
d 17.00 in. d 17.00 in.
rho 0.001203 rho 0.000511
As 0.245 in2. As 0.104 in2.

CALCULATION FOR 'SPACING IN SLAB' CALCULATION FOR 'SPACING IN SLAB'


As 0.245 in2. As 0.104 in2.
Ab 0.310 in2. Ab 0.175 in2.
spacing 15.16 in. spacing 20.14 in.
BENDING MOMENT
VERTICAL (Mx) hs Negative hs Positive
Max. positive 55 5946.2 lb-ft/ft CALCULATION FOR 'Ru' CALCULATION FOR 'Ru'
Max.negative 107 11568.1 lb-ft/ft Mu 13.84 k-ft. Mu 4.32 k-ft.
HORIZONTAL (My) b 12.00 in. b 12.00 in.
Max. positive 25 2702.8 lb-ft/ft h 20.00 in. h 20.00 in.
Max.negative 80 8649.0 lb-ft/ft d 17.00 in. d 17.00 in.
Ru 0.0479 ksi. Ru 0.0150 ksi.
Mx negative
Flexural Capacity for 16@200 c/c CALCULATION FOR 'Rho' CALCULATION FOR 'Rho'
bw 12
dia. 16 0.312 fc' 3.00 ksi. fc' 3.60 ksi.
spacing 200 7.874 fy 60.00 ksi. fy 72.00 ksi.
depth 500 19.69 Ru 0.0479 ksi. Ru 0.0150 ksi.
deff. 425 16.73 phi 0.90 phi 0.90
f'c 21 3.0 beta 0.85 beta 0.85
fy 414 60.0 rho 0.000896 rho 0.000232
As 0.474949441
c 1.079964126 CALCULATION FOR 'As' CALCULATION FOR 'As'
phiMn 417574.3652 lb-in/ft b 12.00 in. b 12.00 in.
34797.86377 lb-ft/ft OK d 17.00 in. d 17.00 in.
FOS 1.50 rho 0.000896 rho 0.000232
My negative As 0.183 in2. As 0.047 in2.
Flexural Capacity for 16@200 c/c
bw 12 CALCULATION FOR 'SPACING IN SLAB' CALCULATION FOR 'SPACING IN SLAB'
dia. 16 0.312 As 0.183 in2. As 0.047 in2.
spacing 200 7.874 Ab 0.175 in2. Ab 0.175 in2.
depth 425 16.73228346 spacing 11.49 in. spacing 44.46 in.
f'c 21 3.0
fy 414 60.0
As 0.474949441
c 1.079964126
phiMn 417574.3652 lb-in/ft
34797.86377 lb-ft/ft OK
FOS 2.01

Max. of
Flexural Capacity for 16@200 c/c
bw 12
dia. 16 0.312
spacing 200 3.94
depth 425 16.73228346
f'c 21 3.0
fy 414 60.0
As 0.949898881
c 2.159928252
phiMn 811593.5472 lb-in/ft
67632.7956 lb-ft/ft OK
FOS 5.69

SHEAR (AT. MAX DEPTH)


1.6*V 0.4 7531.71 lb/ft 1.6*V
phi Vc 16619.63 lb/ft. phi Vc