You are on page 1of 4

TECHNICAL SPECIFICATION:

1) Filter Feed Pump with motor 1 Nos


Make : Kirloskar/Equivalent
Type : Monobloc, Self Priming
Flow : 2m3/hr
MOC : CI
Head : 35 MWC
Rating : 0.5HP

2) Pressure Sand Filter 1 Nos


Flow : 1.2m3/hr
Make : Pentair
Tank Type : FRP
Medias : Various Graded Pebbles
Graded Sand
Size : Diameter – 250 MM
Height - 1350 MM
Op Pressure : 3 kg/cm2
Valve Type : TMF
Valve Make : Solo
Mode : Manual

3) Activated Carbon Filter 1 Nos


Flow : 1.2m3/hr
Make : Pentair
Tank Type : FRP
Medias : Various Graded Pebbles
Graded Sand
Size : Diameter – 250 MM
Height - 1350 MM
Op Pressure : 3 kg/cm2
Valve Type : TMF
Valve Make : Solo
Mode : Manual
4) Cartridge Filter with Housing 1 Set
Flow : 1.2m3/hr
Cartridge : 2.5” Dia x 20” Length
Type : Wound
Micron : 5 Micron
MOC : PP

5) Dosing Pump 1 Nos


Make : I-Dose/Equivalent
Range : 0-6 LPH
MOC : PP
Op Press : 5 kg/cm2
Power : 200 watts

6) High Pressure Pump with motor 1 Nos


Make : CRI/Equivalent
Type : Vertical centrifugal pump
Model : 2-15
Pressure : 15 kg/cm2
Head : 150 M
Rating : 2 HP
MOC : SS304/CI

7) Membrane 2 Nos
Make : LG/Equivalent
Model No : 40 - 40
Type : Spiral Wound
Size : 4”

8) Pressure Vessel 2 Nos


Make : Alfa/Equivalent
Size : 4 Inch
Pressure : 300 PSI
9) Accessories

1. Flow meter (Rota meter)


M.O.C : PC
Range : 0-1200 LPH
Qty : 2 Nos
2. Pressure Gauges
Type : Panel Mountable
Size : 2.5” SS Glycerin filled
Qty : 2 Nos
3. Internal pipe and valve (Inside RO Plant)
Moc : UPVC
Valve sizes : 15NB and 25NB
Valve Qty : As Required

CONTROL PANEL SYSTEM:

The RO skid shall be supplied with a control panel with the following features :
1. Starter switch for high pressure pumps motor.
2. On/Off switch with indication for high pressure pump.
3. Low Pressure Switch.
4. Feed, Reject Pressure Gauge.
5. Reject Control Valve.
6. Permeate, reject flow meter.
7. Relays and required electrical components.
8. Powder coated panel board.

Note: The above all systems required following


1. Anti scalant should be silica or Phosphate based depends on raw water quality.
2. permeate flush @ before shut down the system
3. If possible coagulant can be added in Raw water
4. Without anti scalant system should not Run
5. Rejection flow should be as per system design
6. This Design applicable only if the TDS<1500ppm, SDI<3,Hardness<300ppm,System
recovery 40 – 50%
CLIENT SCOPE:
 All Civil Works like Pump Foundations, Raw water storage tank, Product
water storage tank, Reject water storage tank.
 Adequate Room for RO Plant with Electricity.
 Pipeline from raw water area to plant area & from Plant to end point, Waste
Water Pipeline.
 EB supply point at plant area.
 All Plumbing Materials for pipeline work.
 Food, Accommodation & Transport Charges for our E&C Team.

BASIC PRICE, COMMERCIAL TERMS & CONDITIONS

Basic Price : Rs.90, 000/- (Ninety Thousand Only)

Price Quoted : Ex-Chennai

GST : 18% Extra

Packing & Forwarding: Rs.8000/- for Wooden Box Pacing Extra

Freight : On – To Pay Basis

Erection &
Commissioning : Rs.6000/- Will be charged extra……
Charges

Payment Terms : 60% Advance along with Purchase Order & 40% before dispatch

Delivery :Within 3 – 4 Days of placement of order with advance.

Validity : 30 Days