Professional Documents
Culture Documents
DEP 31.76.10.10-Gen.
February 2014
DEM1
PREFACE
DEP (Design and Engineering Practice) publications reflect the views, at the time of publication, of Shell Global Solutions
International B.V. (Shell GSI) and, in some cases, of other Shell Companies.
These views are based on the experience acquired during involvement with the design, construction, operation and
maintenance of processing units and facilities. Where deemed appropriate DEPs are based on, or reference international,
regional, national and industry standards.
The objective is to set the standard for good design and engineering practice to be applied by Shell companies in oil and
gas production, oil refining, gas handling, gasification, chemical processing, or any other such facility, and thereby to help
achieve maximum technical and economic benefit from standardization.
The information set forth in these publications is provided to Shell companies for their consideration and decision to
implement. This is of particular importance where DEPs may not cover every requirement or diversity of condition at each
locality. The system of DEPs is expected to be sufficiently flexible to allow individual Operating Units to adapt the
information set forth in DEPs to their own environment and requirements.
When Contractors or Manufacturers/Suppliers use DEPs, they shall be solely responsible for such use, including the
quality of their work and the attainment of the required design and engineering standards. In particular, for those
requirements not specifically covered, the Principal will typically expect them to follow those design and engineering
practices that will achieve at least the same level of integrity as reflected in the DEPs. If in doubt, the Contractor or
Manufacturer/Supplier shall, without detracting from his own respons bility, consult the Principal.
The right to obtain and to use DEPs is restricted, and is typically granted by Shell GSI (and in some cases by other Shell
Companies) under a Service Agreement or a License Agreement. This right is granted primarily to Shell companies and
other companies receiving technical advice and services from Shell GSI or another Shell Company. Consequently, three
categories of users of DEPs can be distinguished:
1) Operating Units having a Service Agreement with Shell GSI or another Shell Company. The use of DEPs by these
Operating Units is subject in all respects to the terms and conditions of the relevant Service Agreement.
2) Other parties who are authorised to use DEPs subject to appropriate contractual arrangements (whether as part of
a Service Agreement or otherwise).
3) Contractors/subcontractors and Manufacturers/Suppliers under a contract with users referred to under 1) or 2)
which requires that tenders for projects, materials supplied or - generally - work performed on behalf of the said
users comply with the relevant standards.
Subject to any particular terms and conditions as may be set forth in specific agreements with users, Shell GSI disclaims
any liability of whatsoever nature for any damage (including injury or death) suffered by any company or person
whomsoever as a result of or in connection with the use, application or implementation of any DEP, combination of DEPs
or any part thereof, even if it is wholly or partly caused by negligence on the part of Shell GSI or other Shell Company. The
benefit of this disclaimer shall inure in all respects to Shell GSI and/or any Shell Company, or companies affiliated to these
companies, that may issue DEPs or advise or require the use of DEPs.
Without prejudice to any specific terms in respect of confidentiality under relevant contractual arrangements, DEPs shall
not, without the prior written consent of Shell GSI, be disclosed by users to any company or person whomsoever and the
DEPs shall be used exclusively for the purpose for which they have been provided to the user. They shall be returned after
use, including any copies which shall only be made by users with the express prior written consent of Shell GSI. The
copyright of DEPs vests in Shell Group of companies. Users shall arrange for DEPs to be held in safe custody and Shell
GSI may at any time require information satisfactory to them in order to ascertain how users implement this requirement.
All administrative queries should be directed to the DEP Administrator in Shell GSI.
TABLE OF CONTENTS
1. INTRODUCTION ........................................................................................................ 5
1.1 SCOPE........................................................................................................................ 5
1.2 DISTRIBUTION, INTENDED USE AND REGULATORY CONSIDERATIONS ......... 5
1.3 DEFINITIONS ............................................................................................................. 5
1.4 CROSS-REFERENCES ............................................................................................. 7
1.5 SUMMARY OF MAIN CHANGES ............................................................................... 7
1.6 COMMENTS ON THIS DEP ....................................................................................... 8
1.7 DUAL UNITS ............................................................................................................... 8
2. GENERAL................................................................................................................... 9
3. HVAC PHILOSOPHY ................................................................................................. 9
3.1 HVAC FUNCTIONS .................................................................................................... 9
3.2 DISCIPLINE INTERFACES ...................................................................................... 11
3.3 LIFECYCLE............................................................................................................... 12
4. DESIGN CONSIDERATIONS................................................................................... 12
4.1 INTERNAL DESIGN CONDITIONS .......................................................................... 12
4.2 EXTERNAL DESIGN CONDITIONS ........................................................................ 12
4.3 AIR QUALITY ............................................................................................................ 13
4.4 CALCULATIONS ...................................................................................................... 14
4.5 DESIGN AIR-CHANGE RATES................................................................................ 14
4.6 BUIDING LEAKAGE ................................................................................................. 15
4.7 AREA SEGREGATION ............................................................................................. 15
4.8 ENERGY EFFICIENCY ............................................................................................ 15
4.9 SOUND AND VIBRATION ........................................................................................ 15
4.10 ABNORMAL OPERATIONAL SITUATIONS ............................................................ 15
4.11 SERVICE LIFE .......................................................................................................... 16
5. HVAC SYSTEM DESIGN - GENERAL .................................................................... 16
5.1 AIR INTAKES AND OUTLETS ................................................................................. 16
5.2 PROTECTIVE DAMPERS ........................................................................................ 17
5.3 EQUIPMENT DUTY ARRANGEMENT ..................................................................... 18
5.4 HUMIDITY CONTROL .............................................................................................. 19
5.5 AIRFLOW PATTERNS AND DISTRIBUTION .......................................................... 19
5.6 PRESSURISATION .................................................................................................. 19
5.7 HEATING .................................................................................................................. 20
5.8 COOLING.................................................................................................................. 20
5.9 BATTERY ROOMS ................................................................................................... 21
5.10 HVAC EQUIPMENT ACCESS AND MAINTAINABILITY ......................................... 22
6. HVAC SYSTEM DESIGN ......................................................................................... 23
6.1 HVAC DETAIL DESIGN ............................................................................................ 23
6.2 CONTROL BUILDING .............................................................................................. 23
6.3 FIELD AUXILIARY ROOMS ..................................................................................... 24
6.4 ELECTRICAL SUBSTATIONS ................................................................................. 25
6.5 OTHER NON-HAZARDOUS BUILDING TYPES...................................................... 25
6.6 ANALYSER SHELTERS ........................................................................................... 26
6.7 HAZARDOUS CLASSIFIED BUILDINGS AND ENCLOSED FACILITIES ............... 26
7. HVAC EQUIPMENT DETAILS ................................................................................. 27
8. CONTROLS AND ALARMS..................................................................................... 27
8.1 GENERAL ................................................................................................................. 27
8.2 CONTROLS .............................................................................................................. 27
8.3 CONTROL FUNCTIONS .......................................................................................... 28
8.4 ALARMS AND MONITORING .................................................................................. 28
8.5 EQUIPMENT POWER SOURCE.............................................................................. 28
8.6 INSTRUMENT AIR SUPPLY .................................................................................... 28
9. ELECTRICAL POWER SUPPLY AND ELECTRICAL SAFETY ............................. 28
APPENDICES
APPENDIX 1 CLIMATIC CONDITIONS FOR VARIOUS PLANT FACILITIES .................... 38
APPENDIX 2 HVAC OPERATION IN ABNORMAL SITUATIONS ...................................... 39
APPENDIX 3 TYPICAL SINGLE LINE DIAGRAM FOR (HVAC) ELECTRICAL
SYSTEM .......................................................................................................... 40
APPENDIX 4 HVAC EQUIPMENT SPECIFICATIONS ......................................................... 41
1. INTRODUCTION
1.1 SCOPE
This DEP specifies requirements and gives recommendations for the indoor climate of
onshore plant buildings and for the design and engineering of HVAC systems. It takes into
account the requirements for safety, operations and personnel. Buildings that are not part
of the process plant might have to comply with local planning and building regulations. The
principles of this document may be applied to such buildings where relevant but local
regulations will take precedence.
This DEP is applicable only to onshore installations. HVAC systems for offshore
installations are covered by DEP 37.76.10.10-Gen.
This DEP contains mandatory requirements to mitigate process safety risks in accordance
with Design Engineering Manual DEM 1 – Application of Technical Standards.
This is a revision of the DEP of the same number dated February 2013; see (1.5) regarding
the changes.
1.3 DEFINITIONS
1.3.1 General definitions
The Contractor is the party that carries out all or part of the design, engineering,
procurement, construction, commissioning or management of a project or operation of a
facility. The Principal may undertake all or part of the duties of the Contractor.
The Manufacturer/Supplier is the party that manufactures or supplies equipment and
services to perform the duties specified by the Contractor.
The Principal is the party that initiates the project and ultimately pays for it. The Principal
may also include an agent or consultant authorised to act for, and on behalf of, the
Principal.
The word shall indicates a requirement.
The capitalised term SHALL [PS] indicates a process safety requirement.
The word should indicates a recommendation.
Term Definition
Air handling HVAC equipment that moves air and transforms it by means of filtration,
unit (AHU) control of temperature and control of moisture content. It typically
comprises filters, fan(s), dampers, heating coil, cooling coil (thermal
cooling and/or dehumidification). Humidifiers may be included in large
AHUs or separately.
Note that AHU sizes and configurations can vary widely. The internally
located section of a split air-conditioning system is included as an AHU.
A ‘system’ AHU serves multiple areas and is part of a system with
distribution ductwork. A ‘room’ AHU serves only the room in which it is
located.
An AHU may be designed to work with 100 % fresh air, 100 %
recirculation, or a mixture of both fresh and recirculated air.
Chiller A packaged unit that provides chilled water for use as a cooling medium
in AHUs and/or fan-coil units. The water is cooled by refrigerant in a
vapour-compression system and heat, thus removed, is rejected via a
condenser.
Condenser The heat-rejection part of a refrigerant vapour-compression cooling
system. It is normally located externally in the form of a heat exchanger
that is cooled by means of fans blowing ambient cooling air over it. If
liquid cooling medium is available, a condenser may take the form of a
shell and tube heat exchanger provided that operability criteria are
fulfilled.
DCS Distributed control system.
Direct- A refrigerant vapour-compression cooling system where the refrigerant
expansion directly cools a heat-exchanger (also referred to as evaporator) that has
(DX) cooling room or system air passing through it. The refrigerant is cooled by an
external condenser.
(Dry-bulb) The temperature of the air indicated by an accurate thermometer.
Temperature
Electronic/ Indoor electronic and electrical equipment, including microprocessor
Electrical based control, safeguarding, telecommunication, computer, power
equipment supply and switchgear systems.
Fan-coil unit HVAC equipment through which air is re-circulated from the space in
which it is located. The purpose of this re-circulation is to cool or heat
this air to the conditions required for the space. This unit is normally
connected to the chilled water system.
Human Defined by the environmental parameters of temperature, radiation,
comfort humidity and air movement necessary for thermal comfort and depends
on the individual’s clothing and activity level.
Humidity The ratio of the weight fraction of water vapour present in the air to the
(Relative) weight fraction of water vapour present in saturated air at the same
temperature and barometric pressure.
HVAC system A heating, ventilation and air-conditioning system which maintains
required environmental conditions within rooms or buildings and also
fulfils any safety-critical functions such as over-pressure, minimum flow
rates and shutdown.
Term Definition
Interruptible, A source of electrical power which is backed up by a second
maintained (emergency) source of power to provide a supply of electricity that may
electrical be interrupted for no more than 15 s.
supply
Local Extract Dedicated extract system to contain and remove fumes that are
Ventilation potentially injurious to health, such as welding fumes extract and fume
(LEV) cupboard extract.
MCC Motor control centre.
Plant buildings Buildings such as control buildings, field auxiliary rooms (FARs),
analyser houses, electrical substations and others (e.g., dedicated flow
metering buildings). Such buildings may contain different types of rooms.
PAS Process automation system.
Process- Equipment or systems are process-critical if their failure could cause the
critical process to shut down in a safe manner.
Safety-critical Equipment or systems are safety-critical if they can cause or contribute
to the occurrence of a major accident hazard (MAH).
Uninterruptible A source of electrical power, which is backed up by a second
maintained (emergency) source of power to provide a supply of electricity that may
electrical be interrupted for no more than 0.5 ms.
supply
Vital A service which, if it fails in operation or when called upon, can cause an
equipment unsafe condition of the process and/or electrical installation, jeopardise
life, or cause major damage to the installation. Vital equipment generally
covers both process-critical and safety-critical equipment and is used for
consistency with other DEPs.
VSD Variable speed drive for an electric motor.
1.4 CROSS-REFERENCES
Where cross-references to other parts of this DEP are made, the referenced section
number is shown in brackets ( ). Other documents referenced by this DEP are listed in (13).
Section/Clause Change
1.1 Scope has been revised to clarify that this DEP does not apply to
offshore facilities.
Feedback that has been registered in the DEP Feedback System by using one of the above
options will be reviewed by the DEP Custodian for potential improvements to the DEP.
2. GENERAL
Plant buildings and facilities may require HVAC systems to fulfil the following functions:
a) Safety-critical functions: compliance with area classification requirements or to
reduce risk levels
b) Process-critical functions: to maintain suitable conditions for equipment operation.
c) Human comfort: to maintain conditions suitable for personnel to work in
d) Human welfare: to prevent personnel from being exposed to potentially hazardous
substances.
3. HVAC PHILOSOPHY
2. Safety-critical functions
The design and function of HVAC systems shall comply with the governing area
classification standard. Refer also to DEP 80.00.10.10-Gen. and
DEP 80.00.10.13-Gen.
Safety-critical functions shall be determined in conjunction with Safety discipline and
shall include consideration of the following:
a) Pressurisation of non-hazardous areas.
b) Segregation of hazardous and non-hazardous areas by means of imperforate
structure.
c) Gas detection at HVAC air intakes.
d) Fire/gas dampers to close the air intakes and outlets of a building. This is
required as a minimum for buildings that remain occupied and have
control/monitoring functions following a major release.
e) Classification of HVAC equipment that could be exposed to flammable gas,
including classification requirements for externally-located HVAC equipment
to prevent it from acting as an ignition point even if located in a non-
hazardous area.
f) Site gas detection and tripping philosophy, e.g., the likelihood of detection
systems to detect a major release and trip potential ignition sources before
the release can reach potential points of ignition.
g) The leak-tightness of buildings containing equipment that will remain live and
could be affected by a gas cloud following a major release event.
h) Ventilation rates of hazardous areas in relation to area classification
requirement.
i) Availability of power in situations when safety-critical functions are required.
j) Ignition risk posed by external HVAC equipment and HVAC systems for non-
hazardous buildings located outside hazardous areas. Area classification is
usually based on normal plant operation, but there may be possibility of larger
hydrocarbon release events spreading beyond the normal hazardous area
classification zones, such as major accident hazard events. If the risk of such
an event poses a threat to the installation, it is necessary to consider a
hierarchy of safety measures that include those mentioned above.
k) Requirements for a Safe-Haven or Temporary Refuge
Note that the design of plant layout will often enable areas of different classification
to be suitably segregated by distance, but it is necessary to assess the areas of risk
and eliminate or address them as appropriate.
The design philosophy shall state whether safety-critical functions are applicable or
non-applicable and which facilities they apply to.
Management of HVAC systems during the operations phase shall include testing to
demonstrate the continuing suitability of HVAC safety-critical elements.
3. Process-critical functions
Process-critical functions shall include consideration of the following:
• Adequate equipment ratings to provide a suitable operating environment
during normal operation;
• Equipment sparing to allow for reliability and maintenance issues;
• Availability of electrical power and the sources of power supplies used for
HVAC systems;
3.3 LIFECYCLE
HVAC systems shall be designed for longevity and ease of maintenance commensurate
with the whole life of the installation.
4. DESIGN CONSIDERATIONS
4. Cold climates
Special measures shall be taken to prevent filters from freezing in very cold climates,
such as:
• Recirculating a quantity of warmed air from the discharge side of the fan(s) to
the upstream side of the filter
• Using a pre-heater
4.4 CALCULATIONS
Calculations shall be undertaken to establish required airflows, equipment sizes and duties.
Recognised design software packages shall be used to establish building heating and
cooling requirements, and the proposed software shall be submitted to the Principal for
acceptance. Calculations shall include the following:
a) Thermal properties of building fabric,
b) Heat losses at winter design conditions,
c) Heat gains and cooling duty, including lighting, solar gains and equipment gains,
d) Airflows required to provide heating and cooling without excessive temperature
differentials,
e) Flow rate for fresh air, airflow required for pressurisation,
f) Duct flow and resistance calculations,
g) HVAC sound level calculations,
h) Clear statements of required equipment duties,
i) Calculations shall be subject to acceptance by the Principal.
Calculations of heating requirement shall include an allowance for heat gains from lighting
and equipment in cases where the heat gains will usually be present. But consideration
shall be given to situations where the heat gains are not present, such as plant black-out or
during construction.
Heat emissions data for use in calculating cooling requirements shall be based on
equipment Manufacturer’s heat emission data.
NOTE: Under all stated climatic conditions (3.3.1), condensation on air ducting and chilled water piping shall
be prevented. Insulation shall be installed where necessary to achieve this.
3. Blast events
If externally-located HVAC equipment is required to continue to operate after a blast, it
shall be located either within the building or where it will be exposed to the least blast
overpressure (e.g., shaded from the blast by the building) and able to withstand the
blast forces to which it will be exposed.
In order to ensure protection in the above cases, the blast protection device must operate
quickly enough to prevent the shock wave pulse from passing through. Therefore, it is
necessary to establish the required closure time (usually expressed as milliseconds) versus
applied over- or under-pressure. Note that shock waves can have positive and negative
pressure pulses. Blast dampers/valves shall self-reset after the shock wave has expired.
Blast protection devices tend to have high resistance to normal airflow velocities. They
usually have to be selected with substantially larger cross-sectional area to reduce airflow
resistance to a tolerable value. Their locations at or within building structure require
consideration of access for both the blast-protection device and fire/gas dampers. The
following factors shall be considered in assessing the need for blast protection devices:
- Locate HVAC penetrations in sides of the building that face away from the blast
origin
- HVAC penetrations below a certain size do not require blast dampers, if the
overpressure is below certain levels. Refer to DEP 34.17.10.30-Gen.
- High integrity fire/gas dampers, such as those used offshore, may withstand blast
pressures of up to 36 kPa (5 psi) and would not require protection for overpressures
within this capability. It is essential to consult Manufacturers regarding the capability
of their products.
Equipment can be selected as 2 × ‘n’ units with ‘n’ being less than 100 % only for
applications that are not safety- or process- critical and where the absence of full cooling
capacity can be tolerated for extended time periods.
It is acceptable to use a single AHU with duty/standby fans because this reduces space
requirements and provides standby fan capacity, but standby capacity for cooling or heating
shall also be considered and included where necessary. Complete standby air-handling
units offer greatest availability but carry the penalties of space and cost.
The determining factors for equipment arrangement are operational criticality, repair times
and risk of single point failures.
Standby equipment shall always be energised and available for auto-changeover on failure
of the duty package unless it has failed or is undergoing maintenance.
5.3.2 Future capacity allowance
For the control room and field auxiliary room, system cooling capacities shall include a
margin of 15 % to 20 % over and above the basic design cooling requirement to allow for
engineering design growth in heat emissions of equipment.
Other future capacity allowances may be included, if required by the Principal.
5.6 PRESSURISATION
All buildings with fresh air supplies shall be pressurised to prevent ingress of dust. Where
required, pressurisation shall be obtained by either:
- The differential between gross quantities of air supplied and extracted (taking
account of the building leakage rate).
- Providing only supply air and allowing it to escape to outside via pressure-relief
damper(s).
Buildings shall include air locks at entrances as indicated in the buildings specifications
documents.
If pressurisation is monitored or controlled by instruments, the outside air terminal of any
differential pressure instruments shall be located at roof level and face vertically
downwards. It is not acceptable for the outside air terminal to be located at an external wall
where it will be affected by zones of high static pressure caused by wind acting against a
vertical surface.
5.7 HEATING
Heating shall be provided where required by climatic conditions in order to maintain
adequate conditions for personnel and equipment. The minimum heat emissions of room
equipment during normal operation can be allowed for to reduce or eliminate room heating
requirements, provided that the equipment is normally in operation and there will be no
adverse consequences if the heat emissions cease during abnormal operation.
The method of heating shall be selected so that there is no risk of water leakage to vital
equipment and heating shall normally be provided by means of warming the air in air
handling systems. Hot water convectors/radiators may be used in rooms/buildings that do
not contain vital equipment.
Low-pressure steam or hot water may be considered as a heating medium for air heating
coils, provided that the coils are not located near vital equipment and the risks of leakage
are allowed for. If steam heating is used, ensure that provisions are made to avoid freezing
of condensate lines and drains.
Electric heating shall be used for rooms containing vital equipment or where the risks of
water leakage are unacceptable.
Heat pump systems may be employed where DX cooling is required and where suitable for
the climatic conditions.
Ground-sourced heating (e.g., using pumped water) may be used where feasible.
5.8 COOLING
Cooling shall be provided where required for personnel comfort, for dehumidification and to
keep the temperature of rooms that contain heat-emitting equipment within acceptable limits.
The main types of cooling are refrigerated chilled water and direct-expansion refrigeration.
Ground-sourced cooling may also be used where suitable conditions exist and reliable
performance is assured. Fresh air cooling may be used where feasible, but factors on which
this depends include climate, requirement for gas detection and closing air inlets and outlets,
and requirements for maintaining cooling after an incident when smoke or gas may be present.
Chilled water cooling shall be used in preference to direct-expansion cooling in the following
situations:
- for whole-building systems with multiple cooling coils
- for large capacity cooling systems
- where feasible to reduce refrigerant inventories and reduce likelihood of leakage from
multiple DX systems
- where the system can be arranged so that there is no chilled water pipework in rooms
that contain vital equipment
- where feasible for groups of buildings located close together (but whole-site systems
with central chillers and extensive distribution pipework shall not be used).
Chiller plant shall include standby capacity as described elsewhere in this document.
Chilled water pipework shall:
- be arranged to minimise risks of leakage and pipework within buildings and be run at
low-level. It is not acceptable for chilled water pipework to run above electronic
equipment.
- be insulated complete with continuous vapour barrier
- be pressure-tested on completion of construction.
unless the level of heat emissions from equipment requires air distribution via a floor
plenum.
Human factors engineering shall be applied to designs for the control room and sound
levels from any locally-installed HVAC equipment shall be unobtrusive.
6.2.4 Other rooms
Other rooms shall be provided with fresh air where required for occupancy and/or
pressurisation. Cooling shall be provided by individual fan coil units or by means of the
central re-circulation air handling unit if this would be feasible and more economic.
6.2.5 Heating
Heating shall be provided in accordance with (5.7) for rooms where heat emissions during
normal operation would not be adequate to reach minimum temperature. In cold climates a
pre-heater shall be included in the fresh-air AHU and terminal re-heaters provided as
required.
6.2.6 Room conditions monitoring
Instruments shall be provided to measure and transmit temperature and humidity in rooms
containing vital equipment. The output signals of the instruments shall be conveyed to a
monitored panel to provide alarms. The set points for alarms shall be based on the design
or operational limits of equipment within the rooms.
6.2.7 HVAC plant room
The HVAC plant room shall be located as close and centrally as possible to those rooms
which it serves in order to minimise the lengths of distribution ducts.
The HVAC plant room shall contain the main items of HVAC equipment such as the fresh
air/recirculation AHU, hot water calorifier, and relevant control panels/cabinets. Dedicated
extract systems shall be located in the plant room where feasible, but may be located local
to the rooms served if they are not close to the plant room.
temperature, humidity.
- Safety philosophies, e.g., if it is necessary to be able to seal the building/facility in
the event of a leak inside, or to prevent an external gas cloud entering.
- The intensity of heat emissions inside the building/facility.
A secondary (scouring) ventilation system may be used in congested areas in order to
prevent stagnant areas.
Where mechanical ventilation is required, the HVAC system shall be based on mechanical
supply ventilation because the ‘throw’ of supply grilles produces better air movement in
relation to the objective of preventing stagnant areas. Air shall exit by means of low-
resistance outlets located at high and low level to deal with different gas densities.
Mechanical extract shall be included for the following situations:
a) if it is necessary to prevent positive pressurisation (e.g., in relation to adjacent non-
hazardous areas)
b) for buildings or enclosures where there is risk of toxic gas release. These facilities
shall be maintained at negative pressurisation to prevent any gas releases escaping
from the building/enclosure in an uncontrolled manner.
Gas detection, fire/gas dampers shall be provided in accordance with Safety philosophies.
HVAC operation and shut-down shall comply with Safety philosophy, Fire & Gas
philosophy, and cause-and-effect diagrams.
In extremely cold climates, the heating of large quantities of fresh air may require large
amounts of energy/heating medium. Consideration can be given to using lower design
airflow during normal operation and increasing the flow rate if gas is detected.
8.1 GENERAL
1. The general principle is for controls systems to be as simple as possible and based
on Manufacturers’ standard arrangements.
2. Controls and alarms can be arranged in various ways to suit the type of HVAC
system and the installation as a whole. The HVAC Contractor shall liaise with the
Principal’s Control and Automation engineers to agree requirements and the
design/supply responsibilities.
8.2 CONTROLS
1. Simple controls, such as on/off switching, relays and thermostat temperature control
shall be used where possible.
2. Manufacturer’s standard control panels shall be provided for packaged equipment
such as stand-alone DX cooling systems and chiller units. Where this type of
equipment is part of a larger HVAC system, the Manufacturer’s standard controls
shall be used and shall interface with the main HVAC control system.
3. Control systems for more complex HVAC systems may be based on programmable
logic controllers (PLCs) where the HVAC systems are extensive and require logic
control, interlocks, and temperature/humidity control loops. The PLC shall be from a
recognised Manufacturer with a record of high reliability and which can be fully
supported during operational life. Proposals for PLC-based controls shall be
interruption is sufficiently short that the vital equipment will not overheat. Otherwise, the
essential functions of the HVAC systems shall be connected to an uninterruptible power
supply.
Refer to (Appendix 3) for a typical single-line diagram of HVAC electrical power supply
system. Particular project requirements shall take precedence.
11.1 CONSTRUCTION
The Contractor shall install the equipment and materials in compliance with:
• This document
• relevant ASHRAE, NFPA 90A and SMACNA standards and guidelines.
• DEP 33.64.10.10-Gen. for electrical facilities
The Contractor shall complete Shell Construction check sheets.
11.9 POST-COMMISSIONING
When commissioning work has been completed, the Contractor shall fit new air filter
elements and provide an additional set (identified by tag number) for the first operational
change-out.
13. REFERENCES
In this DEP, reference is made to the following publications:
NOTES: 1. Unless specifically designated by date, the latest edition of each publication shall be used,
together with any amendments/supplements/revisions thereto.
2. The DEPs and most referenced external standards are available to Shell staff on the SWW (Shell
Wide Web) at http://sww.shell.com/standards/.
SHELL STANDARDS
Global technical standards index DEP 00.00.05.05-Gen.
DEP feedback form DEP 00.00.05.80-Gen.
Noise control (amendments/supplements to ISO 15664) DEP 31.10.00.31-Gen.
Instrument air supply DEP 31.37.00.11-Gen.
Fire, gas and smoke detection systems DEP 32.30.20.11-Gen.
Analyser housing DEP 32.31.50.13-Gen.
Electrical engineering design DEP 33.64.10.10-Gen.
Synchronous AC machines (amendments/supplements to DEP 33.65.11.31-Gen.
IEC 60034-1 and IEC 60034-14)
Design and engineering of buildings DEP 34.17.00.32-Gen.
Inspection and functional testing of instruments DEP 62.10.08.11-Gen.
HVAC for offshore installations (amendments/supplements to
DEP 37.76.10.10-Gen.
ISO 15138)
Inspection and functional testing of instruments DEP 62.10.08.11-Gen.
Field commissioning and maintenance of electrical installations and
DEP 63.10.08.11-Gen.
equipment
Area classification (amendments/supplements to IP 15) DEP 80.00.10.10-Gen.
Area classification and electrical equipment spacing for North
DEP 80.00.10.13-Gen.
American application
Shell HSSE & SP Control Framework, Design Engineering Manual DEM1
(DEM) 1 – Application of Technical Standards.
http://sww.manuals.shell.com/HSSE/
AMERICAN STANDARDS
ASHRAE Handbook: Fundamentals ASHRAE
ASHRAE Handbook: ‘HVAC Applications’ Sound and Vibration
ASHRAE
Control
Method of testing air-cleaning devices used in general ventilation for
ASHRAE 52.1
removing particulate matter
Thermal environmental conditions for human occupancy ASHRAE 55
Ventilation for Acceptable Indoor Quality ASHRAE 62
HVAC&R Technical Requirements for the Commissioning Process ASHRAE Guideline 1
Preparation of operating and maintenance documentation for building
ASHRAE Guideline 4
systems
Guideline to commissioning smoke management systems
Issued by: American Society of Heating, Refrigeration and Air-Conditioning Engineers ASHRAE Guideline 5
Incorporated
EUROPEAN STANDARDS
Refrigerating Systems and Heat Pumps – Safety and Environmental
EN 378, 2008 (all parts)
Requirements
Particulate air filters for general ventilation – Determination of
EN 779, 2002
filtration performance
Ventilation for Buildings - Air Terminal Devices - Aerodynamic
EN 1751
Testing of Dampers and Valves
Ventilation for buildings — Air handling units — Mechanical
EN 1886
performance
Continuously hot-dip coated steel flat products - Technical delivery
EN 10346
conditions
Pressure equipment for refrigerating systems and heat pumps —
EN 14276-2
Part 2: Piping — General requirements -
Design of fans working in potentially explosive atmospheres EN 14986
Safety requirements for secondary batteries and battery installations
EN 50272
Part 1: General safety information
INTERNATIONAL STANDARDS
Explosive atmospheres – Part 14: Electrical installations design,
IEC 60079-14
selection and erection -
Industrial-process measurement and control equipment; operating
IEC 60654-1
conditions, Part 1: Climatic conditions
Operating conditions for industrial-process measurement and control
IEC 60654-4
equipment. Part 4: Corrosive and erosive influences
Environmental Conditions for Process Measurement and Control
Systems: Airborne Contaminants ISA S71.04:1985
Issued by: International Society of Automation
FAR
Instr. eqt. Room 5 27 20 80 (6) (6) F5 G4
Electr. eqt. Room 5 27 20 80 (6) (6) F5 G4
Battery Room 15 25 20 80 (10) - - -
NOTES: (1) The set point shall be adjustable within the 'normal' temperature range stated. Set point tolerance shall not
exceed +/- 1 °C.
(2) The set point shall normally be set in the range 40-50% relative humidity as appropriate for climate. Set
point tolerance shall not exceed +/- 5 % RH.
(3) Control of over-pressure is not required unless pressurisation is required for compliance with area
classification code.
(4) Filtration grade in accordance with EN 779.
(5) Deleted
(6) Rooms may not require a fresh air supply directly, but pressurisation can be obtained by transfer from
adjacent areas. A defined pressurisation level is not required unless necessary under application of area
classification code.
(9) Fresh air to make-up for air extracted via fume cupboards and to provide pressurisation.
(10) Fresh air to make-up for air extracted via battery extract system. Battery room pressurisation should be
negative relative to adjacent rooms.
(11) Refer to DEP 32.31.50.13-Gen.
(12) 100 % fresh air, to comply with classification code requirements
(13) Principal to confirm.
(14) Temperature and humidity determined if applicable by control (electronic) equipment.
(15) Minimum temperature applies to heating capacity calculation (at minimum outdoor temperature).
Maximum temperature applies to cooling capacity calculation (at maximum outdoor temperature).
(16) Hazardous facilities should normally be negatively pressurised to ensure containment of any gas releases.
Fresh air supply Run Close inlet Stop (1) Run (1) Stop & Run if
and outlet close redundant
dampers (1) dampers fan available
Air Handling Units Run Run Stop (1) Run Run or Redundant
(re-circulation or self- Stop (2) unit(s) run
contained)
Cooling systems Run Run Run Run Run or Redundant
Stop (2) unit(s) run
Heating System Run Stop Stop Run Stop No
redundancy
HVAC Control System Run Run Run Run Run (3) Run
NOTES: 1. Actions to be determined in conjunction with Safety and Fire & Gas philosophies. Special consideration
may be required for battery rooms.
2. Cooling may be stopped if the electronic equipment can withstand the resultant temperature and humidity
for a period of 30 minutes (safe shut-down period of the plant). Calculations shall cover the worst case
scenario (scenarios with partly running equipment may be taken into account). If power is required, it
should be obtained from an interruptible power supply (e.g., the available diesel generator).
If the electronic equipment cannot withstand these conditions the HVAC system shall continue to run.
3. The HVAC control system shall have a stand-alone back-up battery or shall be connected to the UPS
system.
2. ANALYSER HOUSES
ABNORMAL SITUATIONS
Normal Flammable Toxic Gas External Mains HVAC
Gas Detected Detected in Explosion Power Redundancy
in Fresh Air Fresh Air Failure if QMI is vital
Intake Intake (3)
Fresh air supply system Run Run (4) Stop (4) Run Stop Yes
NOTES: 1. Actions to be taken shall be subject to the safety measures defined in DEP 32.31.50.13-Gen.
2. Inside the analyser house, electrical apparatus which is required to run in case of a ventilation failure shall
have a type of protection in compliance with IEC 60079-14 (zone 1).
Outside the analyser house, electrical apparatus shall have a type of protection in compliance with
IEC 60079-14 suitable for the particular area classification (typically zone 2).
3. Actions to be taken if gas is detected inside the analyser houses are specified in DEP 32.31.50.13-Gen.
Hot surfaces shall comply with the appropriate temperature class.
4. If both toxic and flammable gas are detected in the fresh air intake, the fresh air supply system shall stop
for a ‘pressurised’ analyser shelter and shall continue to run for a ‘closed’ analyser shelter.
DX cooling coils shall be sized to minimise moisture carry-over and shall also be provided
with droplet eliminators having blades manufactured from stainless steel UNS S31603.
On completion of satisfactory testing, DX coils shall be dehydrated, charged with an inert
gas and sealed.
A.4.3.3 AHU coils
Coils in AHUs shall be designed for side-withdrawal to facilitate possible future
replacement.
A.4.5 FANS
A.4.5.1 Applicability
This section covers centrifugal fans, mixed-flow fans and cased axial fans. Fans for
hazardous areas or which may be exposed to flammable gas shall comply with the
applicable parts of DEP 37.76.10.10-Gen.
A.4.5.2 Fan general requirements
The type of fan to be used shall include consideration of functional requirements, efficiency,
space requirements, maintainability and life-cycle. Fans shall be non-stall and non-
overloading.
For all fan types, selections shall be based on:
- Steep performance curves to minimise airflow change with changes in static
pressures, e.g., due to adverse wind conditions (fresh air fans) or dirty filters.
- Allowance for dirty filter condition: fan selections shall be based on filter ‘dirty’
resistance.
- Fan duty point shall be at least 15 % below the fan’s maximum static pressure.
Where feasible, fans shall be direct-drive to eliminate belt maintenance requirements. Use
of direct-drive fans may require suitable capacity adjusting devices and allowances in
system design to ensure that minimum duty requirement can be obtained. Inlet guide vane
dampers may be used if located within an AHU.
Fans to be located externally in corrosive environments (e.g., coastal) or handling moist or
corrosive air shall have casings manufactured from stainless steel UNS S31603 unless
located within an enclosure. Fans in other locations and not subject to moist or corrosive air
shall be manufactured from galvanised mild steel or with epoxy paint coating. For belt-drive
fans the frame shall incorporate facilities for drive belt tensioning and alignment of pulleys.
Fans for use in extract systems where there is a possibility of fouling by particulate matter
shall have motors outside the airstream and be designed to resist build-up of contaminants
and to facilitate cleaning.
Fans should not be selected to have excessive velocities and rotational speeds because
this creates excessive noise and may reduce operational life. This situation should be
avoided by improving system design to reduce fan duties. Discharge velocities should not
exceed 15 m/s.
Fan shafts shall be of high-tensile steel and designed to withstand fatigue. The shaft’s first
critical speed should be at least 20 % in excess of the recommended maximum fan
operating speed.
Fan impellers shall be keyed on to shafts and shall be dynamically balanced in accordance
with recognised standards such as ISO 1940-1 and ISO 14694. Fans with driver power
equal to or less than 37 kW (BV-3) should meet Balance Quality Grade G 6.3, while fans
with driver power higher than 37 kW (BV-4) should meet Balance Quality Grade G 2.5. All
rotating parts of the fan and motor shall be protected with suitable guards in accordance
with ISO 12499.
Fans shall have anti-vibration mountings that provide isolation efficiency of at least 95%.
Connections to adjacent ductwork or components shall be by means of 150 mm long
flexible connections having flanges at both ends that are clamped by metal backing flanges.
Fan installations shall be provided with appropriate instruments for control and monitoring
purposes. Belt-driven fans shall have speed sensors or differential pressure switches to
warn of fan failure. Where speed sensors are used, failure indication or changeover shall
be initiated at 80% of normal speed. Direct-drive fans can be monitored by means of motor
operation or differential pressure switch.
Belt drives, if used, shall be rated for continuous duty, and when used on single fans they
shall be arranged to have spare capacity so that in the event of one belt breaking the
remainder will be capable of transmitting the full drive load.
Fan bearings shall be rated for a design life of at least 40,000 hours and have lubrication
points extended as required so that they are accessible from outside the fan casing. The
fan nameplate shall state the required frequency and quantity of Shell lubricant.
Industrial fans shall be designed to comply with ISO-5801:2007.
A.4.5.3 Centrifugal fans (further requirements)
Centrifugal fan casings shall be stiffened to prevent flexing and shall allow for impeller
removal.
The casing shall be provided with a removable bolt-fixed access door and a plugged casing
drain.
Impellers shall be backward-curved with single-skin or aerofoil section blades and shall be
fabricated from mild or low carbon steel and finished with epoxy paint. Welds shall be
tested by dye-penetration.
A.4.5.4 Mixed flow fans (further requirements)
Mixed-flow fan impellers shall be of the type where the air enters axially through an inlet
cone and the discharge has both axial and radial components. The casing shall include
welded supports for the fan shaft bearings (or motor for direct-drive type). All welds shall be
tested by dye-penetration.
Casings shall be flanged at each end. Bolted access doors shall be provided for fans over
400 mm diameter.
A.4.5.5 Axial fans (further requirements)
Axial fans have limited pressure capability and must be selected so that the required
performance in adverse conditions is within their capacity and they will not stall.
Casings shall be fully welded with rolled flanges at each end and bolted access doors
provided for fans over 400 mm diameter.
Where possible, axial fans shall be of the long case type with guide vanes welded to the
inside of the casing to improve performance and efficiency.
A.4.5.6 Fan motors
Electric motors shall comply with DEP 33.65.11.31-Gen. and shall be selected so that the
design loading, including transmission allowance, does not exceed 90 % of the motor
nameplate rating. Fan power requirement at the lowest design air temperature shall be
checked to ensure that the motor is adequate.
Small packaged HVAC equipment may not be available with motors that meet the Shell
specification. In such instances, the details shall be submitted to the Principal for approval.
For actuated fire dampers, a thermal device shall be provided to close the fire damper in
the event of excessive temperature in the duct. For pneumatically operated dampers, the
thermal device shall be a liquid-filled glass bulb designed to break at a given temperature
and interrupt the actuator’s air supply. For electrically operated dampers, the thermal
device shall be a fail-safe detector that interrupts the actuator’s power supply.
All duct-mounted actuated fire/gas dampers shall be provided with an adjacent access door
to enable internal inspection of the damper.
A.4.10 HUMIDIFIERS
Humidifiers shall be electrically powered and generate fresh, odourless, sterile steam from
the installation’s potable water supply system. Steam shall be introduced to the ducted
airstream by means of dispersion tubes that will ensure even steam distribution and rapid
absorption to minimise water particle drop-out. The improved moisture absorption will
enable more compact installations.
Humidifiers shall meet the following requirements:
a) Be designed for industrial use and continuous operation at full output.
b) Electrical equipment shall be in compartments that are segregated from water or
steam carrying components to prevent them from being exposed to water or vapour
during either normal operation or maintenance. Such compartments and any stand-
alone electrical or instruments equipment shall have a suitable moisture ingress
protection rating.
c) The main electrical connections shall be capable of accepting the types of cable
terminations specified in applicable electrical standards.
d) There shall be no exposed hot surfaces that are normally accessible. All
components shall be enclosed in a sheet steel casing and insulation shall be used
where required to prevent surface temperatures from exceeding safe levels.
e) The package shall include all necessary safety devices and the controls shall be
capable of operating in conjunction with the HVAC control system for permissive
signals, transmitting alarm signals and receiving trip signals.
f) Heater elements shall be the resistive type.
g) Steam chambers shall be of stainless steel and easily accessible for maintenance.
h) Float valve for water level control.
i) Humidifiers shall have water skimming/flushing systems to prevent accumulations
of solids.
j) Humidifiers shall operate only when system airflow has been established.
A.4.13 DUCTS
The material and type of construction for ductwork shall be selected to be suitable for the
operating conditions and design life of the installation.
Stainless steel UNS S31603 with angle flanges shall be used for external ductwork and any
ductwork exposed to moisture.
Refer to DEP 37.76.10.10-Gen. for details and classes of ductwork. Table A.3 provides
further details of minimum duct construction standards for classes A, C and E. For duct of
non-welded construction, further details shall be in accordance with recognised standards
such as SMACNA or HVCA Specification for Sheet Metal Ductwork DW144.
Flange details for external/heavy construction ductwork are included in Appendix E of
DEP 37.76.10.10-Gen.
Duct nominal sizes are based on internal dimensions for fabricated rectangular and circular
ducts. Refer to Manufacturer’s information for factory-made spiral-wound ductwork.
Rectangular duct bends shall be medium- or short-radius type with one or more internal
splitter vanes where necessary to obtain suitably low pressure loss. Mitred bends with
short-chord turning vanes shall not be used.
Circular duct bends shall have minimum throat radius of half-diameter and be constructed
in accordance with DW144 Figure 127 or Figure 128.
Supports for external ducts shall be arranged in conjunction with Civil/Structural discipline
to ensure adequacy of the support design, support spacing and their attachment to
structure. External duct supports shall be sufficiently strong and rigid to provide both
vertical and lateral support to deal with duct weight, wind loading, and may also have to
consider blast loading. Proprietary channel systems with bolted/clamped connections may
be used where adequate for smaller duct sizes.
Table A.3 indicates minimum requirements for the duct types referenced in Table A.2.
Stainless steel shall be type UNS S31603, pre-galvanised mild steel sheet shall be in
accordance with BS EN 10346 or equivalent with galvanised coating 275 g/m².
Duct penetrations at fire barriers shall be in accordance with the Certifying Authority or third
party verification body.