Professional Documents
Culture Documents
qpEE2401 Power System Operation Control PDF
qpEE2401 Power System Operation Control PDF
Secondary loop is used to maintain the fine adjustment of the frequency, and also
by reset action maintains proper MW interchange with other pool members. This loop is
insensitive to rapid load and frequency changes but focuses instead on drift like changes
which take place over periods of minutes.
The advantage of AVR loop over ALFC is very fast and therefore there is a
tendency, for the AVR dynamics to settle down before they can make themselves felt in
the slower load frequency control channel.
The difference between large and small signal analysis is given below. Large
signal analysis is used where voltage and power may undergo sudden changes of
magnitude that may approach 100 percent of operating values. Usually this type of
analysis leads to differential equations of non-linear type. Small signal analysis is used
when variable excursions are relatively small, typically at most a few percent of normal
operating values.
The exciter is the main component in AVR loop. It delivers the DC power to the
generator field. It must have adequate power capacity and sufficient speed of response
(rise time less than 0.1 sec).
The function of the AVR is to provide constancy of the generator terminal voltage
during normal, small and slow changes in the load.
In a static AVR loop, the execution power is obtained directly from the generator
terminals or from the station service bus. The AC power is rectified by thyristor bridges
and fed into the main generator field via slip rings. Static exciters are very fast and
contribute to improved transient stability.
Static performance of AVR loop is to regulate the terminal |V| to within required
static accuracy limit, have sufficient speed of response and be stable.
9. What is the disadvantage of high loop gain? How it is to be eliminated?
The disadvantage of high loop gain is that it causes undesirable dynamic response,
possibly instability. By adding series AND/OR feedback stability compensation to the
AVR loop, this conflicting situation can be resolved.
Effects of generator loading in AVR loop is given below. Added load does not
change the basic features of the AVR loop; it will however affect the values of both gain
factor Kf and the field constant. High loading will make the generator work at higher
magnetic saturation levels. This means smaller changes in |E| for incremental increases in
if, translating into the reduction of KF. The field time constant will likewise decrease as
generator loading closing the armature current paths. This circumstance permits the
formation of transient stator currents the existence of which yields a lower effective field
induction.
The disadvantage of ALFC loop is that it will control only during normal changes
in load and frequency. It is unable to provide adequate control during emergency
situations, when large MW imbalances occur.
The real power in a power system is being controlled by controlling the driving
torque of the individual turbines of the system.
14. What is the need for large mechanical forces in speed-governing system?
Very large mechanical forces are needed to position the main valve against the
high stream pressure and these forces are obtained via several stages of hydraulic
amplifiers.
13. Define control area.
It is possible to divide an extended power system into subareas in which the
generators are tightly coupled together so as to form a coherent group. Such a coherent
group is called a control area in which the frequency is assumed to be the same
throughout in static as well as dynamic conditions.
14. What do you understand by coherent group of generators?
A control area is defined as a system to which a common generation control scheme is
applied. The electrical interconnection within each control area is very strong as compared to
the lies with the neighboring areas. All the generators in a control area swing in coherently or
it is characterized by a single frequency. It is necessary to be considered as many control area
as number of coherent group.
15. What is meant by AFRC?
∆fstat = (1/B ∆PD)/(1 + 1/BR) = M/(B + 1/R) = M/β where β = B + 1/R
16. Define electric stiffness of the interconnected system.
0 0
T12 = [|V1||V2|cos(δ 1 – δ 2)]/Pr1X12
= Synchronizing power coefficient or electric stiffness.
i.e., slope of the power angle curve at the initial operating angle δ120.
It is defined as the differential power increase obtained per differential power angle
increase.
17. Define Area Control Error.
Area Control error is the change in area frequency which when used in integral
control loop forced the steady state frequency error to zero.
18. What is AGC?
19. State the advantages of integral controller.
(i) For integral controller gain in the subcritical range i.e.,K1< Ki critical, system
is over damped and zero steady state error is achieved , after long time.
(ii) From the response characteristics, observe that initial response with integral
controller is just the same as without integral controller. After a small period only the
controller becomes effective and depending on the value of integral controller gain
frequency error is minimized. Higher the gain, quicker the actions after initial drop in
frequency.
20. List the advantages of Multi area operation.
1. Under normal operating condition each control area should have the capacity to meet
its own load from its own spinning Generator, plus the scheduled interchange between
the neighboring areas.
2. Under emergency conditions, the energy can be drawn from the spinning reserve of all
the neighboring areas immediately due to the sudden loss of generating unit.
21. Draw the dynamic response of change in frequency for a step load change.
22. Differentiate static and dynamic response of an ALFC loop.
Static response of an ALFC loop will inform about frequency accuracy.
The dynamic response of an ALFC loop will inform about the stability of the loop.
23. What is the function of load frequency control?
The function of load frequency control on a power system is to change the control
valve of the prime movers as a function of load variations in order to hold system
frequency constant.
24. How is the real power in a power system controlled?
By controlling the driving torque of the individual turbines of the system.
1. Develop the block diagram model of uncontrolled two area load frequency control
system and explain the salient features under dynamic conditions.
2. Develop the block diagram model of uncontrolled two area load frequency control
system and explain the salient features under static conditions.
3. Draw the block diagram of LFC control of single area and derive the dynamic response.
4. Draw the block diagram of LFC control of single area and derive the steady state
frequency error.
5. Obtain a block diagram for the representation of single control area without integral
control.
6. What are the components of speed governor system of an alternator? Derive a transfer
function and sketch a block diagram.
Rotating amplifier
Feedback stability compensation is used to resolve the effect of high loop gain in
AVR. High loop gain is needed for static accuracy but this causes undesirable dynamic
response, possibly instability.
Static VAR switches or systems are Static VAR compensators which use
switching for VAR control. It means that terminology wise SVC=SVS.
Tap changing transformers are the power transformers and many distribution
transformers which have taps in one or more windings for changing the turn’s ratio.
15. Write the types of tap changing transformers.
The off- load tap changers are used when it is expected that the ratio will need to
be changed only infrequently, because of load growth or some seasonal change. TCUL is
used when changes in ratio may be frequent or when it is undesirably to de-energize the
transformer to change the tap.
17. Compare shunt and series capacitors.
1. The voltage boost due to a shunt capacitor is evenly distributed over the transmission
line whereas the change in voltage between the two ends of a series capacitor where it
is connected in sudden. The voltage drop along the line is unaffected.
2. For the same voltage, the reactive power capacity of a shunt capacitor is greater than
that of a series capacitor.
3. The shunt capacitor improves the power factor of the load whereas the series
capacitor has little effect on the power factor.
4. For long transmission lines where the total reactance is high, series capacitor are
effective for improvement of system stability.
18. State the functions of AVR.
The function of AVR excitation control is to regulate generator voltage and relative
power output. As the terminal voltage varies the excitation control, it maintains the terminal
voltage to the required standard and the demand of the reactive power is also met by the
excitation control unit.
19. What are the various functions of excitation system and also mention the types.
The basic function of an excitation system is to provide direct current to the synchronous
machine. In addition, the excitation system performs control and protective functions essentially to
the satisfactory performance of the power system by cooling the field voltage, thereby the field
current.
20. List the various components in AVR loop.
Exciter, comparator, amplifier, rectifier, synchronous generator.
21. What is the significance of stability compensation in AVR loop?
Stability compensation improves the dynamic response characteristics without
affecting the static loop again.
High loop gain is needed for static accuracy, but this causes undesirable dynamic
response i.e., possibility instability.
This conflict situation can be avoided by adding series and/or feedback stability
compensation to the AVR loop.
22. What is the need for compensator in the AVR loop?
Stability compensation improves the dynamic response characteristics without affecting
the static loop gain.
23. Distinguish between onload and offload tap changing.
offload tap changing
The offload tap changing transformer which requires the disconnection of
transformer when the tap settings is to be changed.
onload tap changing
In this type, the voltage is a maximum value and since the current are divided
equally and flow in opposition through the coils, the resultant flux is zero and hence the
minimum
impedance.
24. What is SVC? Mention the different types of SVC.
Static VAR compensators use switching for var control. These are also called static
VAR switches or systems. It means that terminology wise SVC=SVS. And we will use
these interchangeably.
25
25. What is a synchronous condenser and also state the merits
It is a synchronous motor running at noload and having excitation adjustable over
a wide range. It feeds positive VARs into the line under overexcited conditions and
negative VARs when under excited.
16-Mark Questions
1. Draw the circuit diagram for a typical excitation system and derive the transfer
function model and draw the block diagram.
2. Discuss generation and absorption of reactive power.
3. Explain different types of static VAR compensators with a phasor diagram.
4. Discuss about the various methods of voltage control.
5. Derive the relations between voltage, power and reactive power at a node for
applications in power system control
6. Explain stability compensation and effects of generator loading.
7. Explain the dynamic performance of AVR loop.
8. Explain typical brushless automatic voltage regulator.
UNIT-IV UNIT COMMITMENT AND ECONOMIC DISPATCH
Incremental cost is defined as the rate of change of fuel cost with active power
generation.
Spinning Reserve is defined as the term that describes the total amount of
generation availability from all units synchronized on the system.
The two approaches to treat a thermal unit to operating temperature are given
below.
a. Allows the unit boiler to cool down and then heat backup to operating
temperature in time for a scheduled turn on.
b. Requires that sufficient energy be input to the boiler to just maintain operating
temperature.
12. What are the techniques for the solution of the unit commitment problem?
The techniques for the solution of the unit commitment problem are
i. Priority list method
ii. Dynamic programming
iii. Lagrange relation
i. A state consists of an array of units with specified units operating and the rest of
the time.
ii. The startup cost of a unit is independent of the time it has been offline.
Long range hydro scheduling problem is defined as the problem involves the long
range of water availability and scheduling of reservoir water releases. For an interval of
time that depends on the reservoir capacities.
15. What are the optimization techniques for long range hydro scheduling problem?
The optimization techniques for long range hydro scheduling problem are
a. Dynamic programming
b. Composite hydraulic simulation methods
c. Statistical production cost
Short range hydro scheduling problem is defined as the hour by hour scheduling
of all generators on a system to achieve minimum production condition for the given time
period.
System blackout problem is defined as the event occurs on a system that leaves it
operating with limits violated; the event may be followed by a series of further actions
that switch other equipment out of service. If the process of cascading failures continues,
the entire system of it may completely collapse.
18. What is meant by cascading outages?
Cascading outages are the process if one of the remaining lines is now too heavily
loaded, it may open due to relay action, thereby causing even more load on the remaining
lines.
19. Mention the constraints in unit commitment problem.
1.Spinning reserve:
2.Thermal Constraints = Minimum up time
Minimum down time
Crew Constraint
3.Other Constraints = Hydro Constraint
Must run constraint
Fuel constraint.
20. What are basepoint and participation factors?
The present operating point of the system is called base point.
The change in generation required to meet power demand is called as participation factor.
21. List the various constraints in economic dispatch problem.
The equality constraint equation
PD = PG1 + PG2 + …….. + PGN = PGi …(1)
Where, PGi = Output of unit i, MW.
PD = Total power received by the plant bus and transferred to the load.
Since our system is a compact one and we neglect the losses in the transmission
line. We may write equation (1) as,
22. Explain penalty factor.
The exact coordination equation is given by
Lamda=(IC)i/1(ITL)i=(IC)iLi.
Li=1/1(ITL)i
Li is a penalty factor where ITLi incremental transmissions loss.
23. Define spinning reserve.
Spinning reserve is the total amount of generation available from all units
synchronized on the system minus the present load and losses being supplied.
Spinning reserve = Total amount of generation – (Present load + losses)
24. Compare economic dispatch and unit commitment.
Unit Commitment Economic load dispatch
Optimum allocation of number of units to be Optimum location of generation to each
operated (to determine the units of a plant station (at each generating station at various
that should operate for a given load is the load levels)
problem of unit commitment)
There are number of subsets of the complete The problem assumes that there are n units
set of n units that would satisfy the expected already connected to the systems
demand
Purpose of units commitment is to find the Purpose of economic dispatch problems is to
optimal subset among the subsets which find the optimum operating policy for these n
provide the minimum operating cost units
25. What are the factors affecting the cost of generation?
Equality constraint
Inequality constraints
Generator Constraints
Voltage Constraints
Running space capacity constraints
Transformers tap settings.
Transmission line constraints
26. What are the advantages of using participation factor?
a) Computer implementation of economic dispatch is straight forward
b) Execution time for economic dispatch is short
c) It will always give consistent answers when units reach limits.
1. Derive the coordination equation with losses neglected.
3. Derive the expression for base point and participation method.
4. State the unit commitment problem. With the help of flowchart explain forward
dynamic programming solution method.
5. Explain Priority list method using full Load average production cost. State the
merits and demerits.
6. Numerical problems in economic dispatch & unit commitment.
7. Explain about startup and shutdown costs?
8. Explain briefly bruteforce technique.
UNIT-V COMPUTER CONTROL OF POWER SYSTEM
SCADA stands for supervisory control and data acquisition system. It allows a
few operators to monitor the generation and high voltage transmission systems and to
take action to correct overloads.
Normal mode is defined as the mode of operation if the system is in secure even
the occurrence of all possible outages has been simulated the system remain secure.
Alert mode is defined as the mode of operation of the system that it does not
remain in the secure for the occurrence of all possible outages.
7. What are the distribution factors?
Must run constraint is defined as the condition that some units are given a must
run status during certain times of the year for reason of voltage support on the
transmission network.
Fuel constrain is defined as the condition if a system in which some units have
limited fuel or else have constraints that require them to burn a specified amount of fuel
in a given time.
14. What are the assumptions made in priority list method?
17. What are the known values in short term hydro scheduling problem?
19. What are the functions of security constrained optimal power flow?
The state of optimal dispatch is defined as the state that the power system is in
prior to any contingency. It is optimal with respect to economic operation but may not be
secure.
Post contingency is defined as the state of the power system after a contingency
has occurred.
Secure dispatch is defined as the state of the power system with no contingency
outages, but with correction to the operating parameters to account for security violations.
23. What are the priorities for operation of modern power system?
The priorities for operation of modern power system are
A. Operating the system in such a way that power is delivered reliably
B. Within the constraints placed on the system operation by reliability
considerations, the system will be operated most economically.
Linear sensitivity factor method is the easiest way to provide quick calculation of
possible overloads because many outages become very difficult to solve if it is desired to
present the results quickly.
Line distribution factor is used to apply to the testing for overloads when
transmission circuits are lost.
16-Mark Questions
1. Briefly discuss the various functions of energy control centre.
2. Explain the different operating states of power system with state transition diagram.
3. Explain the hardware components of SCADA with neat diagram and also mention
the functions of it.
4. Explain about power system security.
5. What is EMS? What are its major functions in power system operation and control?
6. Explain the various controls for secure operation.
7. Explain briefly how the system states are continuously monitored and controlled.
8. Explain the substation control functions arranged through SCADA system.